socomec NET-VISION Specification sheet

NET-VISION
Version 7
GB
www.socomec.com
OPERATING
AND
INSTALLATION
MANUAL

2GB NET-VISION 7 - SOCOMEC
1. ELECTRONIC EMISSION NOTICE ....................................................5
1.1. FEDERAL COMMUNICATIONS COMMISSION (FCC) ..............................5
2. SAFETY INFORMATION ............................................................5
2.1. FOR NET VISION CARD .....................................................5
2.2. FOR NET VISION BOX ......................................................5
3. GENERAL DESCRIPTION ...........................................................6
3.1. NET VISION PRESENTATION .................................................6
3.2. SOCOMEC UPS COMPATIBILITY ..............................................6
3.3. NET VISION 7 FEATURES ....................................................7
4. REQUIREMENTS..................................................................8
4.1. WEB BROWSER ...........................................................8
4.2. NET VISION Explorer........................................................8
5. NET VISION INSTALLATION .........................................................8
6. UPS SERIAL LINK SETTINGS .......................................................8
7. NET VISION 7 BOOT SEQUENCE ....................................................9
7.1. EMD LIGHTS SEQUENCE....................................................9
7.2. MODBUS POLLING.........................................................9
7.3. UPS DATA BASE ..........................................................10
7.4. UPS ARCHITECTURE:......................................................10
8. NET VISION EXPLORER PRESENTATION .............................................11
8.1. IP SETTINGS (only for NV 7) ................................................11
8.2. BROWSE ................................................................11
8.3. FW UPGRADE ............................................................12
8.4. NET VISION SETTINGS FILE DOWNLOAD (only for NV 7)..........................12
8.5. BATCH OPERATION .......................................................12
8.6. SUPGRADE.EXE TOOL ....................................................12
9. IP ADDRESS CONFIGURATION .....................................................13
9.1. PREPARING NET VISION ...................................................13
9.2. DEFAULT IP ADDRESS .....................................................13
9.3. NET VISION ACCESS ......................................................13
9.4. IP SETTINGS USING NETWORK IF DHCP NOT PRESENT ........................13
9.5. IP SETTINGS USING A TERMINAL AND RS232 CONNECTION for NET VISION 5 and 6 .13
9.6. IP SETTINGS USING A TERMINAL AND USB for NET VISION 7 ....................13
10. NET VISION 6 FUNCTIONS .......................................................14
11. RESET NET VISION WITH FACTORY SETTINGS ......................................14
12. NET VISION 7 USER INTERFACE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
12.1. NET VISION HOME PAGE ..................................................15
12.2. NET VISION MENU .......................................................16
12.3. UPS ARCHITECTURE TREE-VIEW ...........................................19
12.4. UPS SYNOPTIC..........................................................19
12.5. USER LOGIN ............................................................20
GB CONTENTS

3
GB
NET-VISION 7 - SOCOMEC
13. UPS MONITORING ..............................................................21
13.1. UNIT SYNOPTIC .........................................................21
13.2. SYSTEM SYNOPTIC ......................................................26
13.3. ALARM TABLE ...........................................................27
14. UPS DASHBOARD ..............................................................28
15. REAL TIME GRAPH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
16. CLIENT TABLE .................................................................29
17. UPS MANAGEMENT .............................................................30
17.1. UPS CONTROL ..........................................................30
17.2. BATTERY TEST ..........................................................31
17.3. BATTERY TEST SCHEDULE ................................................31
17.4. eco mode SCHEDULE.....................................................32
17.5. WEEKLY SHUTDOWN SCHEDULE...........................................32
17.6. SPECIAL DAY SHUTDOWN SCHEDULE ......................................32
17.7. POWER SHARE..........................................................33
17.8. SHUTDOWN MANAGEMENT ...............................................34
18. EMD DEVICE MANAGEMENT .....................................................37
19. NET VISION MANAGEMENT ......................................................38
19.1. DATE and TIME ..........................................................38
19.2. NET VISION CONFIGURATION ..............................................39
19.3. NET VISION CONTROL ....................................................40
19.4. MULTI-USER TABLE ......................................................41
19.5. REMOTE VIEW PRO CONFIGURATION .......................................41
19.6. REMOTE VIEW PRO Server Configuration .....................................42
19.7. SNMP v3 USM TABLE CONFIGURATION......................................43
19.8. SNMP TRAP RECEIVERS CONFIGURATION ...................................43
19.9. EMAIL NOTIFICATION .....................................................45
19.10. AUTHENTICATION CONFIGURATION........................................46
19.11. WOL TARGETS .........................................................47
19.12. MODBUS TCP CONFIGURATION ...........................................47
19.13. SYSLOG SETUP ........................................................48
19.14. DDNS SETUP ..........................................................48
19.15. FIREWALL SETUP .......................................................49
19.16. UPnP PROTOCOL .......................................................49
20. EXTERNAL LINK SETUP..........................................................50
21. HISTORY LOG ..................................................................51
21.1. HISTORY LOG ...........................................................51
21.2. UPS EXTENDED HISTORY LOG .............................................53
21.3. UPS EVENTS LOG .......................................................55
21.4. NET VISION EVENTS LOG .................................................56
21.5. CLEAR & SAVE LOG DATA .................................................58

4GB NET-VISION 7 - SOCOMEC
CERTIFICATE AND CONDITIONS OF WARRANTY
Installing the software means full acceptance of all contractual terms. For this reason, please read
all the points listed below carefully. If you do not agree with one or more of the contractual terms,
do not install this software and/or return it immediately to SOCOMEC.
1. Copyright and intelleCtual property ownership rights
The user of the software acknowledges that all rights referred thereto and the copyright belong to
SOCOMEC, in relation to both the source code and the object code.
Anyone entering into possession of the software without prior authorization from SOCOMEC must
immediately uninstall it, if it has been installed and return it to SOCOMEC. If such persons fail to take
this action SOCOMEC will exercise its rights to the full extent permitted by civil and criminal law.
The software and documentation are protected by copyright. The unlawful use and/or copying par-
tially or totally of the software shall lead to claims for damages. It is permitted to create a backup
copy of the media supplied by SOCOMEC (CD Rom). This documentation and software are not
specications. SOCOMEC reserves the right to make any changes to data without prior notice.
SOCOMEC retains the full and exclusive ownership of all intellectual rights, such as, but not lim-
ited to the ones related to documentation, software, source code, object code, etc. Only a per-
sonal right to utilize the documentation and software for the application indicated by SOCOMEC is
granted to their recipients. All reproduction, modication, dissemination of this documentation and
software whether in part or whole and by any manner are expressly prohibited except upon SO-
COMEC’s express prior written consent.
2. liCense to use
The NET VISION. NET VISION Explorer and supporting documentation are freely installable for pri-
vate use solely.
The software contains condential information. This license does not authorize the user to modify,
adapt, decompile or disassemble the software in question or to reconstruct the source code using
any other method. SOCOMEC will protect its rights against any such unauthorized use to the full
extent permitted by civil and criminal law.
The software may not be hired out to third parties. The license of use of this software is issued ex-
clusively for the purposes laid down in the software documentation.
3. entry into forCe and duration of the liCense
This license enters into force on the day of installation of the software, whereby the user accepts
these conditions of use and liability. The license is open term and has no date of expiry. The licence
and the limited rights of use by the user of the software will be invalidated in case of a breach of
any of the points laid down in paragraphs “1. Copyright and Intellectual Property ownership rights”
and “2. License”.
4. warranty Conditions
SOCOMEC neither implicitly nor explicitly provides any warranty concerning the usability of the soft-
ware. Despite the extensive use of resources to develop the software, no guarantees are provided
concerning the absence of errors. SOCOMEC may provide the support needed to solve any errors
present in the software. Such support is limited to the correction of programming errors and is not
extended to the implementation of new functions that are not present in the version of the software
used by the user.
Should the user nd any manifest or hidden errors, they must be notied to SOCOMEC in writing.
5. software updates
This licence does not grant the right to receive software updates, or new versions.
6. limitations of liability
SOCOMEC shall not be held liable, under any circumstances, for damage of any kind, including
economic losses, directly or indirectly consequential to the use of, or inability to use the software.
7. severability
If any clause of this contract is found to be ineffective or become ineffective for any reason what-
soever, the remaining terms of the licence shall still apply. The unenforceable clause or ineffective
provisions will be replaced by a clause, also with retroactive effect, that addresses subsequently
identied requirements, within the scope of legal enforceability.
8. amendments to the liCenCe
Any amendment to this licence must be made in writing.
9. appliCable law
This contract is subject to French law.
The information contained herein, the software and documentation, are the exclusive property of SOCOMEC.

5
GB
NET-VISION 7 - SOCOMEC
1. ELECTRONIC EMISSION NOTICE
1.1. FEDERAL COMMUNICATIONS COMMISSION (FCC)
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protec-
tion against harmful interference when the equipment is operated in a commercial environment.
1.1.1. CE Notice
This device complies with the EMC directive of the European Community and meets or exceeds
the following technical standard:
• EN 55022:1998 – “Limits and Methods of Measurement of Radio Interference Characteristics
of Information Technology Equipment.” This device complies with the CISPR Class B standard
• EN 55024:1998 – “Electromagnetic compatibility - Generic immunity standard Part1: Residen-
tial and light industry.”
2. SAFETY INFORMATION
2.1. FOR NET VISION CARD
• All servicing of this equipment must be performed by qualied service personnel. Remove
rings, watches, and other jewellery before servicing the unit.
• Before plugging in/pulling out the Net Vision card to/from the UPS, please make sure that the
power supplying the UPS has been switched off. Hot swap of the Net Vision in UPS is inhibited.
2.2. FOR NET VISION BOX
• To reduce the risk of re or electric shock, install the unit in a temperature-controlled indoor
area free of conductive objects. Do not place the unit near liquids or in an excessively humid
environment.
• Do not allow liquids or foreign objects to enter the unit
• The unit does not contain any user-serviceable parts. Do not open the unit.
• All servicing of this equipment must be performed by qualied service personnel. Remove
rings, watches, and other jewellery before servicing the unit.
• Before maintenance, repair or shipment, the unit must be switched off completely and un-
plugged and all connections removed.
• Before plugging in the Net Vision power adaptor, please make sure the power source rating
matches the Net Vision power adaptor rating.

6GB NET-VISION 7 - SOCOMEC
3. GENERAL DESCRIPTION
3.1. NET VISION PRESENTATION
NET VISION is a network adapter for the professional monitoring and remote control of a single
and modular UPS or parallel UPS system.
The NET VISION network adaptor allows a UPS to connect directly the Ethernet network allow-
ing secure management of the UPS over the network using a web browser or NMS application
via SNMP. The protocols used for connection are independent of the platform and operating
system, therefore Net Vision is extremely exible and suitable for all systems.
In addition to monitoring and control, the NET VISION interface provides a high level of protec-
tion for standalone servers or hosts managing virtual machines powered by the UPS.
In critical conditions, up to 250 devices powered by the UPS can be switched off in an orderly
sequence whilst ensuring data integrity.
The remote shutdown is provided by a client shutdown to be installed on all standalone servers
(JNC) or on a virtual machine (VIRTUAL-JNC) that require this automatic function.
JNC and VIRTUAL-JNC are shutdown agent software available for free on SOCOMEC’s web
site or on the NET VISION CD.
3.2. SOCOMEC UPS COMPATIBILITY
Net Vision is compatible with the following SOCOMEC UPS products:
• NETYS PR
• NETYS RT
• ITYS
• ITYS-PRO
• MODULYS
• MODULYS GP 2.0
• MASTERYS BC. IP+. EM and GP
• MASTERYS BC+ / GP4
• DELPHYS MP / MX
• DELPHYS BC. GP and Xtend
• And all new SOCOMEC UPS with standard COM-Slot.

7
GB
NET-VISION 7 - SOCOMEC
3.3. NET VISION 7 FEATURES
3.3.1. UPS FUNCTIONS
• Real-time UPS health monitoring
• Comprehensive UPS management and exible conguration via Web Browser
• Automatic detection of UPS architecture: single, modular, or parallel system.
• Battery test management (if supported by UPS)
• UPS controls (If enabled by UPS)
• UPS date and time synchronisation (if enabled by UPS)
• Automatic UPS events notication via E-mail and SNMP Trap
• Complete shutdown procedure to protect up to 250 servers/workstations or HOSTS/VM from
data loss due to power outage
• Scheduling shutdown/start-up/reboot of UPS via remote control (only for single phase UPS)
• Regularly records UPS parameters for statistical analysis and event diagnostics
3.3.2. NETWORK SERVICES
• Assigned IP automatically via DHCP or BOOTP
• Standard RFC1628 UPS MIB and NET VISION proprietary MIB supported
• 10/100Mbps fast Ethernet auto-sense network environment
• Conguration utility simplies the rmware upgrade process
• Radius users account support
• IPv4 and IPv6 dual-stake
• Supports MODBUS TCP protocol to connect monitoring equipment
• Digital output to support relay control device (EMD)
• Firewall network access control avoiding non-authorized IP access
3.3.3. NETWORK PROTOCOLS
• IPv4 / v6
• HTTP / HTTPs with certicate
• DHCP / BOOTP
• SNMP v1 / v2c / v3 (MD5-SHA / DES-AES)
• SMTP over TLS
• SSH
• UPnP
• NTP / ICMP
• WOL
• RADIUS
• TFTP
• SYSLOG

8GB NET-VISION 7 - SOCOMEC
4. REQUIREMENTS
4.1. WEB BROWSER
NET VISION interacts with the end user through a web browser. All web browsers compliant
with HTML. js and XML technologies can access to NET VISION pages.
4.2. NET VISION Explorer
This tool must be installed in a Windows™ computer to congure IP settings, to upload the NET
VISION conguration, or to upgrade the FW. Please refer to the Appendix.
NET VISION Explorer detects all UPS connected on the same local network through NET VI-
SION. This tool helps to check the IP addresses of each NET VISION.
NET VISION Explorer is compliant with all NET VISION FW versions from V5 to V7.
5. NET VISION INSTALLATION
NET VISION CARD 5 & 6
NET VISION 7 Card
NET VISION Card is installed and screwed into one of the available COM-Slots. The metallic
front part can be adapted, to x the NET VISION to com-Slot depending on the UPS model.
NET VISION is powered by the UPS and communicates through serial link to the internal µC
board of the UPS.
The serial link COM port must be set on the UPS control panel to establish the communication with UPS.
6. UPS SERIAL LINK SETTINGS
• NETYS / MODULYS range: 9600bds, no parity, slave 1
• ITYS: 2400bds, no parity, slave 1
• MODULYS GP2.0 / ITYS PRO:
57600bds
, no parity, slave 1:
COM-Slot 1 or COM-Slot 2
• MASTERYS BC / GP / GP 2.0 / IP+ / EM:
9600bds, no parity, slave 1:
COM-Slot 1 or COM-Slot 2
• MASTERYS BC+ / GP4:
57600bds
, no parity, slave 1:
COM-Slot 1 or COM-Slot 2
• DELPHYS MP / MP elite + / EM / MX: 9600bds, no parity, slave 1: COM-Slot 5 only
• DELPHYS BC / GP / GP2.0 / Xtend: 9600bds, no parity, slave 1: COM-Slot 2 only

9
GB
NET-VISION 7 - SOCOMEC
7. NET VISION 7 BOOT SEQUENCE
During NET VISION’s starting phase, the Power EMD light is OFF and Status EMD light will ash
till communication is established.
NET VISION automatically detects the protocol and UPS type. Once the communication is es-
tablished, the Power EMD light is continuous; and the Status EMD light ashes when NET VI-
SION is sending MODBUS request to the UPS. At the end of the boot sequence, the MODBUS
polling starts and the NET VISION communicates with the UPS.
7.1. EMD LIGHTS SEQUENCE
POWER Green Power Light:
ON
OFF
STATUS Yellow Light:
ON
OFF
Baud rate detection Synchro OK Data base de-
tection
MODBUS polling
7.2. MODBUS POLLING
As NET VISION communicates with the UPS through the MODBUS serial link, the data refresh-
ing depends on the baud rate and the number of units for parallel systems.
At 9600 bauds, the polling time for 1 unit is around 3 seconds. This polling time is to be multiplied
by the number of units present in the system in order to have a global time of data refreshing.

10 GB NET-VISION 7 - SOCOMEC
7.3. UPS DATA BASE
NET VISION manages 2 types of UPS mapping:
• ‘JBUSP’ mapping for NETYS PR - RT / ITYS / MODULYS / MASTERYS MC-BC-GP-IP-EM /
DELPHYS BC-GP-Xtend
• ‘VU-MAP’ mapping for ITYS-PRO / MODULYS GP 2.0 / MASTERYS BC+ and GP4 ranges and
future SOCOMEC UPS range.
JBUSP TABLES
STATUS S00 – S63 0x1020 4 w
ALARMS A00 – A63 0x1040 4 w
MEASUREMENTS M00 – M47 0x1060 48 w
VU-MAP TABLES
STATUS S000 – S127 0x0030 8 w
ALARMS A000 – A127 0x0038 8 w
MEASUREMENTS M000 – M079 0x0040 80 w
MODBUS TCP access must follow the addresses according to the UPS mapping
Please refer to the Appendix: MODBUS TCP JBUSP and VU-MAP TABLE.
7.4. UPS ARCHITECTURE:
• Single Unit 1 phase and 3 phases
• Converter - without battery
• Module – without bypass
• Modular Unit up to 8 modules
• Parallel system, distributed bypass or centralized bypass, up to 6 Units (JBUSP) and 10 Units
(VU-MAP)
• Modular system up to 3 Units – 24 modules.

11
GB
NET-VISION 7 - SOCOMEC
8. NET VISION EXPLORER PRESENTATION
8.1. IP SETTINGS (only for NV 7)
Click on to open the IP settings window:
8.2. BROWSE
Click on to start the web browser and open the NET VISION home page.
Action buttons
D: DHCP
S: IP Static
Refresh/Preferences
Add or Remove device from the list
Batch
operation
Connected
Locked/unlocked
Pages
navigation
Connection must be unlocked to change IP settings

12 GB NET-VISION 7 - SOCOMEC
8.3. FW UPGRADE
Click on to open the FW upgrade window
If several NET VISION units have been selected, the FW bin le can be updated to all selected
NET VISION through batch function.
8.4. NET VISION SETTINGS FILE DOWNLOAD (only for NV 7)
Click on to open the conguration le download window
8.5. BATCH OPERATION
Click on to open the batch operation window
8.6. SUPGRADE.EXE TOOL
The Supgrade.exe tool used for NET VISION 6 does not recognize the NET VISION 7 Card.
Connection must be unlocked to change IP settings
File name selection
File name selection
Batch operation selection:
- FW update
- Cong le upload

13
GB
NET-VISION 7 - SOCOMEC
9. IP ADDRESS CONFIGURATION
9.1. PREPARING NET VISION
Once the UPS power is on and NET VISION has been installed in the COM-Slot and connected
to the Network, the Net Vision’s IP address must be programmed.
9.2. DEFAULT IP ADDRESS
If a DHCP server is available on the same Network as NET VISION, the NET VISION will request
a valid IP address from the server. If the DHCP server is not available, NET VISION switches to
the following default IP address: 192.168.7.18
IPv6 is not activated by default. The default IP address is set to IPv4 format
9.3. NET VISION ACCESS
When the Net Vision has a valid IP address, open the web browser and enter the IP address set
manually or given by the DHCP server. The IP address can be checked with the NET VISION
Explorer software utility (see NET VISION explorer §).
By default, NET VISION requests the admin account login and password to open web pages.
Login: admin
Password: public
9.4. IP SETTINGS USING NETWORK IF DHCP NOT PRESENT
For the case of NET VISION 5 and 6:
1. You need a computer with Terminal application connected to the same Network as Net Vision.
2. Check the IP address of your terminal
3. Run a terminal session (a DOS session for example)
4. Execute the following command: ROUTE ADD 192.168.7.18 computer.IP.address
5. Test the connection to Net Vision: Ping 192.168.7.18
6. If the NET VISION responds to the ping, open a web session to modify IP parameters.
For the case of NET VISION 7
Even if DHCP is not available, the IP address can be set through the Net Vision Explorer tool.
9.5. IP SETTINGS USING A TERMINAL AND RS232 CONNECTION for NET VISION 5 and 6
1. Connect the RS232/RJ45 PC cable from Net Vision to your computer
2. Open a Terminal session with the parameters assigned to the right COM port:
• 9600 bauds
• Parity none
• 8 bits data
• No control
3. Press ‘space’ to open the communication.
4. Enter the password: public (default password)
9.6. IP SETTINGS USING A TERMINAL AND USB for NET VISION 7
The USB Gadget Serial driver must be installed. Please refer to the APPENDIX.
Once the device is recognized, open an SSH terminal connection to modify IP settings.

14 GB NET-VISION 7 - SOCOMEC
10. NET VISION 6 FUNCTIONS
Please refer to the dedicated NET VISION 6 User manual, for all related functions.
The following chapters concern NET VISION 7
11. RESET NET VISION WITH FACTORY SETTINGS
When removing NET VISION from the network, make sure it does not affect your remote
monitoring system.
1. Remove Network cable and EMD if present
2. Unscrew and remove the board
3. Set SW1 and SW2 according to requirements
4. Replace the board in the Com-Slot
5. Wait for NET VISION to restart: Green/Yellow EMD LED xed ON
6. Remove the board again
7. Set SW1 and SW2 to OFF position – Normal mode
8. Replace the board in Com-Slot and tighten screw
9. Wait for NET VISION to restart for a new operation
DIP SWITCH functions SW1 SW2 SW3 SW4
NORMAL MODE OFF OFF X X
ADMIN PASSWORD RESET On OFF X X
RESET TO FACTORY DEFAULT OFF On X X
If functions have been set before this procedure (email, SNMP, Shutdown …) those
functions will need to be recongured.
The RESET button does not affect the Net Vision settings, it only restarts Net Vision.
Make sure that the IP given by the DHCP server remains the same as before the Net Vision RESET.

15
GB
NET-VISION 7 - SOCOMEC
12. NET VISION 7 USER INTERFACE
12.1. NET VISION HOME PAGE
NET VISION reference UPS Reference Shortcut access Login
NET VISION MENU UPS tree-view UPS SYNOPTIC Parameters table

16 GB NET-VISION 7 - SOCOMEC
12.2. NET VISION MENU
12.2.1. UPS Monitoring
UPS monitoring items Access to Shortcut access
“Comprehensive view” UPS synoptic
“UPS Dashboard” Synthesis page of UPS parameters displayed
by widgets
“UPS real-time Graph” Scan function of UPS parameters
“Client table” List of Servers connected to NET VISION asso-
ciated with shutdown client
12.2.2. UPS Management
UPS management items Access condition
“Shutdown management” Always
“Battery Test”
If Battery is present
The battery test can be applied only if remote
controls are enabled by UPS
Controls are available for
Read/Write user rights
and admin accounts
“Battery Schedule”
If Battery is present and remote controls are en-
abled by UPS. Available only for ‘VU_MAP’ UPS
“UPS control” If remote controls enabled by UPS
“eco mode schedule” If eco mode and remote controls are enabled
by UPS
“Weekly schedule” If “weekly schedule” is selected in shutdown
event
“Special day schedule” If “special day” is selected in shutdown event
“Power share” If “Power share” function is present and remote
controls are enabled by UPS
“EMD device” If the EMD device is connected to NET VISION

17
GB
NET-VISION 7 - SOCOMEC
12.2.3. NET VISION Management
NET VISION management items Access condition Remarks
“Date and Time” Update and synchronize NET VISION and UPS
date and time
“NET VISION Conguration” General settings
“NET VISION Control” Enable or disable network services / protocols
“Multi-User Table” Set the users access rights
“Remote View Pro Conguration” To activate the connection to Remote View Pro
supervision software RV Pro v2 only
“SNMP v3 Conguration” SNMP v3 USM table settings
“SNMP TRAP Receivers” NMS conguration
“Email Notication” SMTP server / emails addresses settings
“Authentication Conguration” RADIUS settings
Pages are present if
services or protocols
have been enabled in
NET VISION Control
page.
“WOL Targets”
Protocol pages settings
“Modbus TCP Cong”
“Syslog Setup”
“DDNS Setup”
“Firewall Setup”
“External Links Setup” To add hyperlink for network devices access

18 GB NET-VISION 7 - SOCOMEC
12.2.4. History Log menu
History Log items Remarks
“UPS History Log”
NET VISION stores the measurements ev-
ery 60s by default.
2048 is the maximum of records stored by
NET VISION.
Shortcut access in graphic mode
“UPS Extend History log”
NET VISION stores in this log the minimum,
average and maximum of UPS measurements
every 1 hour by default; up to 2048 records
Shortcut access in graphic mode
“UPS event Log” Store UPS alarms (add and remove)
“NET VISION Event Log” Store all actions done on NET VISION
“Clear and save Logs” Remove logs from NET VISION memory
Download logs to local computer (csv)
List of measurements stored by NET VISION in “History Log” and “Extend History Log”
Input voltage (V) Per phase
A measurement stored with a value of -1 means that
this measurement is not managed by the UPS
Input frequency (Hz * 10)
Output load rate (%) per phase
Output voltage (V) per phase
Battery capacity (%)
UPS temperature (°C) or (°F)
EMD temperature (°C) if EMD connected
EMD humidity (%) if EMD connected
12.2.5. External Link
An extra menu is present if devices have been activated. These links give direct access to other
devices. It automatically opens a new page in the web browser with the selected link.

19
GB
NET-VISION 7 - SOCOMEC
12.3. UPS ARCHITECTURE TREE-VIEW
NET VISION automatically recognizes the UPS topology and adapts the UPS tree-view and synoptic view.
UPS TOPOLOGIES
SINGLE UNIT UPS MODULAR UNIT UPS MODULAR SYSTEM
Up to 3 units in parallel
PARALLEL SYSTEM UPS
Up to 10 units in parallel
UPS reference UPS reference
Module number
Module number
SYSTEM reference
Unit number
• Module number
Unit number
• Module number
SYSTEM reference
Unit number
Unit number
Unit number
Unit number
Modules numbered from 1
to 8, according the physical
position in the unit’s cabinet
Modules numbered from 1
to 24, according the physical
position in the unit’s cabinet
In case of centralized bypass,
the Bypass Unit is not repre-
sented
Device status management:
STATUS SINGLE / MODULAR SYSTEM UNIT MODULE
On standby
Operating
Operating with alarm
Operating with critical alarm
Imminent stop ashing
Click for access to: UNIT SYNOPTIC
UNIT TABLE
SYSTEM
SYNOPTIC
UPS TABLE
UNIT
SYNOPTIC
UNIT TABLE
MODULE
TABLE
12.4. UPS SYNOPTIC
NET VISION manages 2 types of synoptic: SYSTEM VIEW and UNIT VIEW
SYSTEM VIEW FOR PARALLEL SYSTEMS
Overviews of units’ input and bypass input sup-
ply and the global output of the UPS.
The UPS output parameters table gives the glob-
al measurements of all units that are operating.
UNIT VIEW FOR SINGLE, MODULAR OR UNITS AS PART OF A PARALLEL SYSTEM
This view gives details of rectier and bypass
inputs supply, battery status and unit output pa-
rameters.

20 GB NET-VISION 7 - SOCOMEC
12.5. USER LOGIN
The login status is given by following icons:
Not logged Logged
Click on the button to open a session or to close the current session.
Login popup:
The admin session default credentials are:
Login: admin
Password: public
The web pages are opened in “Read Only” mode if the “HTTP Security Control” is disabled.
To access to all the congurations and UPS controls, it is necessary to open a session as admin
or with a “Read/Write” user access account.
It is possible to set a “Login Timeout (in Seconds)” in the NET VISION Conguration page. At the
end of the timeout, the current session is closed automatically and switches to “Read Only” ac-
cess mode.
NET VISION does not allow more than one admin session.
If an admin session is still open, a new session that is opened forces the logout of the
previous admin session.
Other manuals for NET-VISION
1
Table of contents
Popular Network Card manuals by other brands

Renesas
Renesas User System Interface Board HS1650ECN61H user manual

Vertiv
Vertiv LIEBERT RPC2 Installer/user guide

Barracuda Networks
Barracuda Networks Link Balance quick start guide

Aewin Technologies
Aewin Technologies SCB-6980 user manual

ADTRAN
ADTRAN ATLAS 800 Series Module QUAD E1 Specification sheet

Abocom
Abocom CWB1000 Quick installation guide

Cisco
Cisco WUSB100 user guide

Ziton
Ziton 2010-1-NB Installation sheet

Adaptec
Adaptec SAS/SATA/SCSI RAID Controllers Installation and user guide

Dialogic
Dialogic Digital Network Interface Board... installation guide

ZyXEL Communications
ZyXEL Communications GLC1320G-55 user guide

Supero
Supero AOC-USAS-S8i user guide