SolarEast BLN-006TB1 User manual

BLN-006TB1/BLN-010TB1/BLN-014TB1/BLN-018TB1
BLN-010TB3/BLN-014TB3/BLN-018TB3/BLN-024TB3
Please read this manual carefully before using it and keep it in a safe place
Heat Pump for Heating & Cooling & DHW
Air Source Heat Pump
R32

1. Please read the instruction manual carefully before installation or operation.
2. The heat pump must be installed by a professional installer.
3. Please follow the instruction manual strictly when installing the heat pump
4. If any update on the product, this instruction manual is subject to change without notice
5. If the heat pump is installed where is vulnerable to lightning strikes, it is necessary to take lightning
protection measures; if the heat pump is turned off in the winter, please be sure to drain the water
in the system to prevent cold water from swelling and causing system damage.
User Instruction-------------------------------------------------------------------1
Operation Instructions----------------------------------------------------------8
Dimension-------------------------------------------------------------------------15
Installation------------------------------------------------------------------------17
Commissioning and Maintenance ---------------------------------------28
Trouble Analysis-----------------------------------------------------------------30
Specification----------------------------------------------------------------------34
After-sale Service----------------------------------------------------------------36
Controller Supplement--------------------------------------------------------37
Note
Content

1
1. Precautions
Please make sure that you have read this manual before using our air source heat pump. In the
“User Information” chapter, “User Information” provides essential safety information. Please be
sure to follow the instruction strictly.
User Instructions
1.
Please use an electrical leakage switch,
otherwise, there may be electric shock, fire, etc.
Test Button
2. Make sure that the leakage protection switch
is securely connected. If the wiring is not secure,
it may cause electric shock, heat, or fire.
3. Do not operate with a wet hand,
otherwise, there may cause electric
shock.
4. Do not insert your fingers or any stick into
the
inside of the ventilation area, otherwise,
harm
will
be
caused.
Dange
r
Warning
Wrong operations are likely to cause serious consequences such as death, serious
injury, or major accidents
Improper operation may result in a safety accident, damage to the machine, or affect
the function of the machine.
Note

2
1) This Machine is not allowed to be installed by the user. A professional installer must install it,
Otherwise cause safety accidents or affects the machine’s performance.
2) Without professional guidance, non-professionals are not allowed to disassemble the machine.
Otherwise, accidents or damage may be caused to the device.
3) Do not use or store flammable materials such as hair spray, paint, gasoline, alcohol, etc., around
the machine. Otherwise, fire may be caused.
4) The machine’s main power switch should be placed where that child cannot reach to prevent
children from playing with the power switch.
5) Do not spray water or other liquids on the machine. Otherwise, danger may occur.
6) Do not touch the machine with wet hands. Otherwise, it may cause an electric shock.
7) In thunderstorms, please disconnect the main power switch off the machine. Otherwise, lightning
may cause danger or damage to the device.
8) The machine needs to use a separate power switch to avoid sharing the same circuit with other
electrical appliances, supply the power to the machine vice the specified power cable, and use
the proper breaker with the electric leakage protection required.
9) The machine must be installed with a specified grounding wire. Do not connect the grounding
wire to the gas pipe, water pipe, lightning conductor, or telephone, and the machine must be
grounded reliably to avoid any electric shock.
10) Do not disconnect the power supply when the machine is running.
11) When the machine is not used for a long time, please disconnect the main power switch to avoid
accidents.
12) If the ambient temperature is below 0 ℃, it is forbidden to cut off the power supply. If the power
is turned off unexpectedly under these conditions, drain the water inside the pipeline.
1) Do not put your hands or other objects into the air outlet of the machine. Otherwise, the fan
running at high speed may cause harm.
2) Do not remove the fan cover. Otherwise, the fan running at high speed may cause injury to you
or others.
3) Lightning and other sources of electromagnetic radiation may have a remarkable effect on the
machine. Turn off the power and then restart the device if it does affect it.
4) Make sure the water supply is frequent. Otherwise, the machine may be damaged.
5) Do not restart the machine frequently. Otherwise, the device may be damaged.
6) The operating parameters of the machine and the set value of the protection device have been
selected by the manufacturer. Users should not change the set value arbitrarily and do not short
the wire of the protection device. Otherwise, the machine may be damaged due to improper
protection.
7) To avoid the freezing of the water system pipeline when the machine is deactivated in an
environment below 0 ℃, please keep the machine standby state. If the device is out of service
Please read the labels on the machine carefully. If abnormal conditions such as abnormal noise, odor, smoke,
temperature rise, electric leakage, fire, etc. are found during use, please cut off the power immediately and
contact our local customer service center or dealer in time to repair it. Contact the local fire and emergency
department immediately if necessary.
Warning
Note

3
for a long time, it is recommended that the user drain the water out of the water system and
disconnect the power supply.
8) Please perform regular maintenance on the machine as required by the instructions to ensure the
device is in good operating condition.
2. Refrigerant Precaution
1) Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacturer.
2) The appliance shall be stored in a room without continuously operating ignition sources (for
example open flames, an operating gas appliance, or an operating electric heater)
3) Do not pierce or burn.
4) Be aware that refrigerants may not contain an odor.
5) Appliance shall be installed, operated, and stored in a room with a floor area larger than X
m2
6) The installation of pipe-work shall be kept to a minimum of X m2
7) Spaces where refrigerant pipes shall be in compliance with national gas regulations.
8) Servicing shall be performed only as recommended by the manufacturer.
9) The appliance shall be stored in a well-ventilated area where the room size corresponds
to the room area as specified for operation.
10) All working procedures that affect safety means shall only be carried out by competent
persons.
3. Requirement of Flammable Refrigerant
1) Transport of equipment containing flammable refrigerants: Compliance with the transport
regulations
2) Marking of equipment using signs: Compliance with local regulations
3) Disposal of equipment using flammable refrigerants: Compliance with national regulations
4) Storage of equipment/appliances: The storage of equipment should be in accordance with the
manufacturer’s instructions.
5) Storage of packed (unsold) equipment: Storage package protection should be constructed such
that mechanical damage to the equipment inside the package will not cause a leak of the
refrigerant charge. The maximum number of pieces of equipment permitted to be stored together
will be determined by local regulations.
6) Information on servicing:
i. Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are
necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system,
the following precautions shall be complied with prior to conducting work on the system.
ii. Work Procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of flammable
gas or vapor being present while the work is being performed.
iii. General Work Area
All maintenance staff and others working in the local area shall be instructed on the nature of
the work being carried out. Work in confined spaces shall be avoided. The area around the
workspace shall be sectioned off. Ensure that the conditions within the area have been made
safe by control of flammable material.
iv. Checking for the presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to

4
ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak
detection equipment being used is suitable for use with flammable refrigerants, i.e. non-
sparking, adequately sealed or intrinsically safe.
v. Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2
fire extinguisher adjacent to the charging area.
vi. No ignition sources
No person carrying out work in relation to a refrigeration system that involves exposing any
pipework that contains or has contained flammable refrigerant shall use any sources of ignition
in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources,
including cigarette smoking, should be kept sufficiently far away from the site of installation,
repairing, removal, and disposal, during which flammable refrigerant can possibly be released
to the surrounding space. Prior to work taking place, the area around the equipment is to be
surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking”
signs shall be displayed.
vii. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the
system or conducting any hot work. A degree of ventilation shall continue during the period
that the work is carried out. The ventilation should safely disperse any released refrigerant and
preferably expel it externally into the atmosphere.
viii. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification. At all times the manufacturer’s maintenance and service guidelines shall
be followed. If in doubt consult the manufacturer’s technical department for assistance. The
following checks shall be applied to installations using flammable refrigerants:
--The charge size is in accordance with the room size within which the refrigerant containing
parts are installed;
--The ventilation machinery and outlets are operating adequately and are not obstructed;
--If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the
presence of refrigerant;
--Marking of the equipment continues to be visible and legible. Markings and signs that are
illegible shall be corrected;
--Refrigeration pipes or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant-containing components unless the
components are constructed of materials that are inherently resistant to being corroded or are
suitably protected against being so corroded.
ix. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. If a fault exists that could compromise safety, then no
electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault
cannot be corrected immediately but it is necessary to continue operation, an adequate
temporary solution shall be used. This shall be reported to the owner of the equipment so all
parties are advised.
Initial safety checks shall include:
• That capacitor is discharged: this shall be done in a safe manner to avoid the possibility of
sparking;
• That there no live electrical components and wiring are exposed while charging, recovering,
or purging the system;
• That there is continuity of earth bonding.

5
7) Repairs sealed components:
a) During repairs to sealed components, all electrical supplies shall be disconnected from the
equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely
necessary to have an electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical point to warn of a
potentially hazardous situation.
b) Particular attention shall be paid to the following to ensure that by working on electrical
components, the casing is not altered in such a way that the level of protection is affected. This
shall include damage to cables, an excessive number of connections, terminals not made to
original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is
mounted securely. Ensure that seals or sealing materials have not degraded such that they no
longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement
parts shall be in accordance with the manufacturer’s specifications.
NOTE: The use of silicone sealant may inhibit the effectiveness of some types of the leak.
8) Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that
this will not exceed the permissible voltage and currently permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on whillivingve in the
presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace
components only with parts specified by the manufacturer. Other parts may result in the ignition
of refrigerant in the atmosphere from a leak.
9) Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental effects. The check shall also take into account the
effects of aging or continual vibration from sources such as compressors or fans.
10) Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not
be used.
11) Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable
refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may
not be adequate or may need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable
for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the
refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of
gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents
containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
12) Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose –
conventional procedures shall be used. However, it is important that best practice is followed
since flammability is a consideration. The following procedure shall be adhered to:
• Remove refrigerant;
• Purge the circuit with inert gas;
• Evacuate;
• Purge again with inert gas;
• Open the circuit by cutting or brazing.

6
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be
“flushed” with OFN to render the unit safe. This process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill
until the working pressure is achieved, then venting to the atmosphere, and finally pulling down
to a vacuum. This process shall be repeated until no refrigerant is within the system. When the
final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work
to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take
place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is
ventilation available.
13) Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.
--Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimize the amount of
refrigerant contained in them.
--Cylinders shall be kept upright.
--Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
--Label the system when charging is complete (if not already).
--Extreme care shall be taken not to overfill the refrigeration system.
--Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak
tested on completion of charging prior to commissioning. A follow-up leak test shall be carried
out prior to leaving the site.
14) Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with
the equipment and all its detail. It is recommended good practice that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken
in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical
power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
• Mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• All personal protective equipment is available and being used correctly;
• The recovery process is supervised at all times by a competent person;
• Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various
parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer's instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the
cylinders and the equipment are removed from the site promptly and all isolation valves on the
equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been
cleaned and checked.
15) Labelling
Equipment shall be labeled stating that it has been decommissioned and emptied of refrigerant.

7
The label shall be dated and signed. Ensure that there are labels on the equipment stating the
equipment contains flammable refrigerant.
16) Recovery
When removing refrigerants from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely. When transferring
refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are
employed. Ensure that the correct number of cylinders for holding the total system charge is
available. All cylinders to be used are designated for the recovered refrigerant and labeled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with
a pressure relief valve and associated shut-off valves in good working order. Empty recovery
cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment
shall be in good working order with a set of instructions concerning the equipment that is at hand
and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated
weighing scales shall be available and in good working order. Hoses shall be complete with leak-
free disconnect couplings and in good condition. Before using the recovery machine, check that
it is in satisfactory working order, has been properly maintained, and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant release. Consulting
manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units
and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that
they have been evacuated to an acceptable level to make certain that flammable refrigerant does
not remain within the lubricant. The evacuation process shall be carried out prior to returning the
compressor to the suppliers. Only electric heating to the compressor body shall be employed to
accelerate this process. When oil is drained from a system, it shall be carried out safely.
4. Other Safety
Thank you for choosing a heat pump. This is a heat pump capable of providing the ideal comfort for
your home, always with a suitable hydraulic installation. The unit is an air source heat pump for
space heating/cooling and a sanitary water heater for houses, apartment blocks, and small industrial
premises. Outdoor air is used as a heat source creating free energy to heat your home.
This manual forms an essential part of the product and it must be given to the user. Read the
warnings and recommendations in the manual carefully, as they contain important information on
the safety, use, and maintenance of the installation.
This heat pump must be installed by qualified personnel only, in accordance with the legislation in
force and following the manufacturer’s instructions.
The start-up of this heat pump and any maintenance operations must be carried only by qualified
personnel only.
Incorrect installation of this heat pump could result in damage to people, animals or property, and
the manufacturer will not be held liable in such cases.
The following safety precautions should always be taken into account:
1) Be sure to read the following WARNING before installing the unit.
2) Be sure to observe the cautions specified here as they include important items related to safety.
3) After reading these instructions, be sure to keep them in a handy place for future reference.
4) Equipment shall contain the following identification:
Inflammable “ ” Read Carefully “ ” Professional Recycling “ “

8
1. Control Panel
2. Operation Instruction
Operation Instruction
Timer
Power ON/OFF
Power ON/OFF
Heating/Cooling/DHW
Change Mode
Water Temperature
Current Mode
Up
Down
Temperature Setting
Time or fault display area
Long press 2s to turn off
the heat pump
When the lock symbol is
displayed, press and
hold 5s to unlock the
screen
Long press 2s to turn on
the heat pump
Power On/Off
Press M to switch mode
Cooling/Heating/DHW
Mode Setting

9
Temperature Setting
Press the up button
to raise the temperature
If there is no operation or press the
on/off button within 5 seconds, the
setting temperature will be saved
automatically and return to the
homepage
Press the down button
to lower the temperature
使用操作说明
Time Setting
Press the
clock button for
1s to enter the current clock
setting
Press the clock key again,
the hour area flashes
Press
the up and down
keys to adjust the value
Press the clock button again to
enter the minute clock setting
Press the clock button
again, the minute
area flashes
Press the up and down
keys to adjust the value
If there is no operation or press the
on/off button within 5 seconds, the
setting temperature will be saved
automatically and return to the
homepage
Scheduled Power On
使用操作说明
Press and hold the clock
key for 5s to enter the
timer boot time setting
Press the clock key again,
the hour area flashes
Press the up and down
keys to adjust the value
Press the clock button again to
enter the minute clock setting
Press the clock button
again, the minute
area flashes
Press the up and down
keys to adjust the value
If there is no operation or press the
on/off button within 5 seconds, the
setting temperature will be saved
automatically and return to the
homepage.
Three timings can be set.

10
Long press the down
button for 5 s to enter
the status search page
Status Search
Enter the status search
page
Adjust the status parameter serial
number in combination with the up
and down keys
ECO Mode
.
Unlock the case while holding down the
up button + down button to enter ECO
energy-saving mode
ECO symbol lit
Pump forced evacuation mode
Press and hold the on/off button + up button
at the same time in the unlocked state to enter the
intelligent distribution mode
When the water pump symbol flashes
enter forced emptying mode

11
3. Temperature and Climate Curve Setting
When the climate temperature curve function is enabled, the user can select one of the eight curves in
the main interface; curve 4 is the default curve, and curve 6 is the ECO energy-saving curve.
4. Wi-Fi Setting
4.1 Software Download and Account Registration
4.1.1 Search for Smart Life in the app store on the mobile phone, and download and
install it.
4.1.2 Users who do not have an account can apply by clicking the "Create New User" function on
the login page.
4.1.3 Create a new account → Enter your cell phone number or email address, → get the verification
code → to enter the verification code → set the password → complete, in the following order.
4.1.4 After registration is complete, you need to create a family: create a family, → set the family
name → set the location → to add a room → ultimately, in the following order.
4.1.5 Click on the device name to enter the main interface of the device
1) Family name, which allows access to family management.
2) Adding devices.
3) Added room; click on it to view the devices added to that room.
4) Room management.
Press the key for 1s to
enter the temperature
setting interface
1
Setting Climate Temperature Curve
Set temperature
flashing
Press and hold the M
button again for 5s
Enter the temperature curve
setting status to enable or
disable the curve
Press the upper key
again for 1s
Curve set successfully

12
4.2 Connection (Intelligent Mode)
Step 1
Open the "Smart Life" APP, login to the main interface, click the "lift" icon in the upper right corner
to add devices or "Add Device" in the interface, enter the device type selection, and select "Smart
Heat Pump (Wi-Fi)" in the "Main Appliance" device, enter the add device interface.
Step 2
Select Smart Heat Pump (Wi-Fi) and enter into the Wi-Fi connection interface, enter the Wi-Fi
password that the phone has been connected to (must be the same as the Wi-Fi connection to the
phone), click Next, and confirm that the line controller has selected the intelligent distribution mode,
" " icon is fast-flashing, click "Confirm that the indicator is flashing, then start adding devices
directly, click the "lift" icon to add devices.
Note: The icon flashes slowly when the Wi-Fi module is connected to the Wi-Fi hotspot.
Step 3
The system prompts "Add Device Successfully" and then the network is successfully distributed.
Click on the icon in this interface to change the device name, select the device installation location
(living room, main bedroom), and click Finish to enter the main interface of device operation.
4.3 Connection (AP Mode)
Step 1 and Step 2: Be consistent with the Intelligent Mode
Step 3
Select innovative heat pump (Wi-Fi) after entering into the Wi-Fi connection interface, enter the
phone has been connected to the (Wi-Fi) password (must be consistent with the Wi-Fi connection
Manual Intelligent Distribution Network
In the unlocked state, press and hold the on/off button + up button
at the same time to enter the intelligent distribution mode
Wifi signal flashes
Enter distribution network status
In the unlocked state, press and hold the on/off button + down
button
at the same time to enter the intelligent distribution mode
Wifi signal flashes
Enter distribution network status
Manual AP Distribution Network

13
to the phone), click next, confirm that the line controller has selected AP distribution mode, an icon
in the slow flashing state “ ”, click "Confirm that the indicator is in slow flashing,” then connect
the phone Wi-Fi to the device hotspot (as shown below), confirm that the connection hotspot is
correct to continue to the next step then directly begin to connect the device interface, find the
device → registers to the cloud → device initialization is complete.
Note: When the wire Wi-Fi module is connected to the Wi-Fi hotspot, the icon “ ” slows flashing.
Step 4 The same as the Intelligent Mode
Note: If the connection fails, manually enter the AP network configuration mode again and repeat
the preceding steps to connect again.
4.4 Software Function Operation
4.4.1 A device is automatically bound to a virtual gateway. The "My Home Heat Pump" (device name,
which can be changed) operation page is displayed.
Buy a ticket to enter the device operation page of "My Home Heat Pump" by clicking on "My Home
Heat Pump" in the "All Devices" screen of smart Life.
4.4.2 Modify device name and modify device location information Click "Name" to rename the
device name and "Location" to alter the device location.
4.5 Device Sharing
Share bound devices in the following sequence:
1) After successful sharing, the list is added to display the shared person.
2) To delete the shared user, long-press the selected user, and the deletion interface will pop up,
click "Delete"
3) User interface operations are as follows:
4) Enter the account of the shared user and click "Finish" to display the newly shared history in the
list of successful sharing
5) The interface of the shared person is as follows. The shared device received is displayed. Click in
to operate and control the device.

14
Operation Parameter Query
Q
uery Code
D
escription
R
ange
1
C
ompressor Running Frequency
0
~
150
Hz
2
F
an
M
otor
R
unning
F
requency
0
~ 99
9
Hz
3
Electronic expansion valve steps
0
~ 480 P
4
EVI valve steps
0
~ 480 P
5
A
C
I
nput
V
oltage
0
~ 500 V
6
A
C
Input Current
0
~ 50 A
7
C
ompressor
Phase Current
0
~ 50 A
8
IPM temperature of the compressor
-
40
~
140
℃
9
High
-
pressure
saturation temperature
-
50 ~ 200
℃
1
0
Low
-
pressure
saturation temperature
-
50 ~ 200
℃
1
1
External ambient temperature T1
-
40 ~ 140
℃
1
2
Outer coil (fin) T2
-
40 ~ 140
℃
1
3
Internal coil (plate
heat exchanger
)
T3
-
40 ~ 140
℃
1
4
G
as
Suction Temperature
T4
-
40 ~ 140
℃
1
5
Gas
Exhaust Temperature
T5
0
~
150
℃
1
6
W
ater
Inlet Temperature
T6
-
40 ~ 140
℃
1
7
W
ater
Outlet Temperature
T7
-
40 ~ 140
℃
1
8
E
conomizer
Inlet
Temperature
T8
-
40 ~ 140
℃
1
9
E
conomizer
Outlet Temperature
T9
-
40 ~ 140
℃
2
0
Machine Tooling No.
0
~
1
20
2
1
Water tank temperature
-
40 ~ 140
℃
22 Fluorine plate heat exchanger out
temperature
-40 ~ 140 ℃
2
3
Drive
r
manufacturers
0
~
10
2
4
Water
pump speed PWM
0
~ 100%
2
5
Water flow
3
~ 100 L/min
2
6
R
eturn water temperature
-
40 ~ 140
℃
2
7
Unit input voltage
0
~ 500 V
2
8
Unit input current
0A
~
99.99A
2
9
Unit input power
0
~
99.99KW
30 Total electricity consumption of the
unit
0 ~ 9999 Kw.h
Display Fault: When the machine has a fault, the fault is flashing in the timing area and the fault code is
displayed cyclically; when the fault is eliminated, the standard display is restored.

15
1. Dimension
Model Dimensions
L×W×H(mm)
BLN-006TB1
1100×445×850
BLN-010TB1
1100×445×850
BLN-010TB3
1100×445×850
BLN-014TB1
1110×480×850
BLN-014TB3
1110×480×850
Model Dimensions
L1×W1×H1(mm)
BLN-018TB1
1110×445×1450
BLN-018TB3
1110×445×1450
BLN-024TB1
1110×445×1450
Dimension

16
2. Explosive Diagram
N
umber
D
escription
N
umber
D
escription
1
F
ront
P
anel
Components
1
6
P
iping
C
omponents
2
L
eft
-
side
P
late
1
7
Gas
-
liquid
S
eparator
3
Evaporator
A
ssembly
1
8
Accumulator
4
Electric
R
eactor
1
9
C
ondenser
P
late
5
Electrical
C
omponents
2
0
Inverter
C
irculating
W
ater
P
ump
6
J
unction
P
late 1
2
1
C
ondenser
7
T
op
C
over
2
2
Mounting
P
late 2
8
I
ntermediate
H
eat
E
xchanger
2
3
U
nit
B
ase
P
late
9
Mounting
P
late
1
2
4
C
ompressor
1
0
R
ight
-
back
P
late
2
5
Mounting
P
late 3
1
1
P
robe
C
lamp
2
6
M
edium
S
eptum
1
2
Plastic
W
aterproof
J
oint
2
7
T
he
M
otor
B
racket
1
3
J
unction
P
late 2
2
8
T
he
M
otor
1
4
J
unction
P
late 3
2
9
F
an
B
lade
1
5
R
ight
-
side
P
late

17
1. Installation Preparation
1.1 Install The Required Tools (Self-Provided)
1.2 Connecting Wires, Insulation Materials, PP-R Pipe, And Connector
a) The material and thickness of the insulation pipe meet the specified requirements. Otherwise,
heat loss and condensation will be caused.
b) Please refer to this manual's “Electrical Installation” description section for wire size selection.
Model The water inlet/outlet size
BLN-006TB1 DN25 (1’’)
BLN-010TB1 DN25 (1’’)
BLN-010TB3 DN25 (1’’)
BLN-014TB1 DN32 (1-1/4’’)
BLN-018TB1 DN40 (1.5’’)
BLN-014TB3 DN32 (1-1/4’’)
BLN-018TB3 DN40 (1.5’’)
BLN-024TB3 DN40 (1.5’’)
1.3 Other Installation Materials
a) Fix the pipe bracket and pipe clamp of the connecting pipe
b) Wire threading pipe and pipe clamp
c) Insulting tape, raw tape
d) Expansion bolt
e) Mounting bracket
Number
Tool
Number
Tool
1
Level
10
Saw
2
Electric
H
ammer
11
Flat
B
lade
S
crewdriver
3
Adjustable
W
rench
12
Cross
S
crewdriver
4
Needle
-
nose
P
lier
13
Copper
T
ube
K
nife
5
Impulse
D
rill
14
PP
-
R
T
ube
K
nife
6
Ruler
15
PP
-
R
T
ube
H
eat
M
elting
D
evice
7
Torque
W
rench
16
Compound
G
auge
8
Hexagonal
W
rench
17
Vacuum
P
ump
9
Hammer
18
Electronic
B
alance
Installation

18
2. Heat Pump Installation
2.1 The machine installation space meets the following schematic requirements to ensure
regular air circulation and maintenance;
2.2 The location of the machine should be kept away from heat, steam, or flammable gases;
2.3 Do not install the machine in places with strong wind or dust;
2.4 Do not install the machine where it is often passed through the air suction side and air
exhaust side;
2.5 The installation position of the machine should be adequately drained to the nearby sewer.
Heat Pump Installation Space Diagram
Installation In The Following Locations May Cause The Machine To Malfunction:
1. A place with more oil;
2. Wet place
3. Seaside saline-alkali area;
4. Special environmental conditions;
5. High-frequency facilities such as wireless equipment, welding machines, and medical equipment.
3. Outdoor Unit Specific Installation Steps
3.1 Install the unit on a solid surface such as concrete, and the load-bearing cover or mounting
bracket must meet the strength requirements;
3.2 Fasten the outdoor unit to the mounting bracket with bolts and nuts and keep it level;
Note
Other manuals for BLN-006TB1
1
This manual suits for next models
7
Table of contents
Other SolarEast Heat Pump manuals