SPC Modulo User manual

Modulo Thermostat
Installation and operating instructions
Read carefully before installation,commissioning and operation

2IOM 81, Issue 2 - Modulo Thermostat
Contents Page
1|Safety Instructions 3
1.1 |EG-Conformity 3
1.2 |General Instructions 3
1.3 |Changes to the Unit 4
1.4 |Warranty and Liability 4
1.5 |Disposal and Pollutants 4
2|Description SPC Modulo Thermostat 5
2.1 | Specifi cations 5
2.2 |Scope of Supply 6
3|Installation 7
3.1 |SPC Modulo Installation 7
3.2 |Sample Wiring 9
4|Setup 9
4.1 |Setup Procedure 9
5|Operation 10
5.1 |Overview of Temperatures & Humidity 10
5.2 |Operating Mode 10
5.3 |Menu 11
5.4 |Set Operation Hours 11
5.5 |Expert Menu 13
5.6 |Expert Menu Settings 13
5.7 |Settings Functions 14
6|Fault Finding 15
6.1 |Factory Reset 15
6.2 |Hard Reset 15
7|Appendix 1 16
7.1 |Setting Up Menu Lock 16
7. 2 |Setting Up Interface Lock 17
3IOM 81, Issue 2 - Modulo Thermostat
1. Safety instructions
1.1 EC-Conformity
By affi xing the CE mark to the unit the manufacturer declares that SPC Modulo Thermostat conforms to
the following relevant safety regulations:
• EU low voltage directive 2014/35/EU • EU electromagnetic compatibility directive
2014/30/EU
Conformity has been verifi ed and the corresponding documentation and the EU declaration of
conformity are kept on fi le by the manufacturer.
1.2 General Instructions
Please read carefully!
These installation and operating instructions
contain basic instructions and important
information regarding safety, installation,
commissioning, maintenance and the optimal
use of the unit. Therefore these instructions
must be read and understood completely by the
installation technician/specialist and by the system
user before installation, commissioning and
operation of the unit.
This unit is an automatic, electronic room
thermostat. Install the device only in dry rooms
and under environmental conditions as described
under “Technical Data”.
In addition, observe the applicable accident
prevention regulations, the regulations of the
Institute of Electrical Engineering, the local power
supply utility, the applicable BS-EN standards and
the installation and operating instructions for
the additional system components. Installation,
electrical connection, commissioning and
maintenance of the unit may only be carried
out by specialists who possess the appropriate
training.
Users: Make sure that the specialist gives
you detailed information on the function
and operation of the unit. Always keep these
instructions in the vicinity of the unit.
The manufacturer does not take over any liability
for damage caused through improper usage or
non-compliance of this manual!

2IOM 81, Issue 2 - Modulo Thermostat
Contents Page
1|Safety Instructions 3
1.1 |EG-Conformity 3
1.2 |General Instructions 3
1.3 |Changes to the Unit 4
1.4 |Warranty and Liability 4
1.5 |Disposal and Pollutants 4
2|Description SPC Modulo Thermostat 5
2.1 | Specifi cations 5
2.2 |Scope of Supply 6
3|Installation 7
3.1 |SPC Modulo Installation 7
3.2 |Sample Wiring 9
4|Setup 9
4.1 |Setup Procedure 9
5|Operation 10
5.1 |Overview of Temperatures & Humidity 10
5.2 |Operating Mode 10
5.3 |Menu 11
5.4 |Set Operation Hours 11
5.5 |Expert Menu 13
5.6 |Expert Menu Settings 13
5.7 |Settings Functions 14
6|Fault Finding 15
6.1 |Factory Reset 15
6.2 |Hard Reset 15
7|Appendix 1 16
7.1 |Setting Up Menu Lock 16
7. 2 |Setting Up Interface Lock 17
3IOM 81, Issue 2 - Modulo Thermostat
1. Safety instructions
1.1 EC-Conformity
By affi xing the CE mark to the unit the manufacturer declares that SPC Modulo Thermostat conforms to
the following relevant safety regulations:
• EU low voltage directive 2014/35/EU • EU electromagnetic compatibility directive
2014/30/EU
Conformity has been verifi ed and the corresponding documentation and the EU declaration of
conformity are kept on fi le by the manufacturer.
1.2 General Instructions
Please read carefully!
These installation and operating instructions
contain basic instructions and important
information regarding safety, installation,
commissioning, maintenance and the optimal
use of the unit. Therefore these instructions
must be read and understood completely by the
installation technician/specialist and by the system
user before installation, commissioning and
operation of the unit.
This unit is an automatic, electronic room
thermostat. Install the device only in dry rooms
and under environmental conditions as described
under “Technical Data”.
In addition, observe the applicable accident
prevention regulations, the regulations of the
Institute of Electrical Engineering, the local power
supply utility, the applicable BS-EN standards and
the installation and operating instructions for
the additional system components. Installation,
electrical connection, commissioning and
maintenance of the unit may only be carried
out by specialists who possess the appropriate
training.
Users: Make sure that the specialist gives
you detailed information on the function
and operation of the unit. Always keep these
instructions in the vicinity of the unit.
The manufacturer does not take over any liability
for damage caused through improper usage or
non-compliance of this manual!

4IOM 81, Issue 2 - Modulo Thermostat
1.3 Changes to the Unit
• Changes, additions to or conversion of the unit
are not permitted without written permission
from the manufacturer.
• It is likewise forbidden to install additional
components that have not been tested
together with the unit.
• If it becomes clear that safe operation of
the unit is no longer possible, for example
because of damage to the housing, turn the
unit off immediately.
• Any parts of the unit or accessories that are
not in perfect condition must be exchanged
immediately.
• Use only original spare parts and accessories
from the manufacturer.
• Markings made on the unit at the factory must
not be altered, removed or made illegible.
• Only the settings described in these
instructions may be set using the Unit.
Changes to the unit can compromise the safety and function of the unit or the entire system.
1.4 Warranty and Liability
The Unit has been manufactured and tested with regard to high quality and safety requirements.
The warranty and liability shall not include, however, any injury to persons or material damage that is
attributable to one or more of the following causes:
• Failure to observe these installation and
operating instructions.
• Improper installation, commissioning,
maintenance and operation.
• Improperly executed repairs.
• Unauthorised structural changes to the unit.
• Use of the device for other than its intended
purpose.
• Operation above or below the limit values
listed in the ‚Specifi cations‘ section.
• Force majeure.
1.5 Disposal and Pollutants
The unit conforms to the European RoHS 2011/65/EU for 2011/65/EUthe restriction of the use of certain
hazardous substances in electrical and electronic equipment.
Under no circumstances may the device be disposed of with
the normal household waste. Dispose of the unit only at appropriate collection points
or ship it back to the seller or manufacturer system.
5IOM 81, Issue 2 - Modulo Thermostat
2. Description SPC Modulo
Thermostat
2.1 Specifi cations
Housing
2-part, ABS plastic
75 mm x 95 mm x 30 mm
Glass front
Display
Capacitive touch panel
Colour display with 240x320 dots
2.8 inches (7 cm) diagonal
123
Operation
Intuitive user guidance
30mm
95mm
75mm

4IOM 81, Issue 2 - Modulo Thermostat
1.3 Changes to the Unit
• Changes, additions to or conversion of the unit
are not permitted without written permission
from the manufacturer.
• It is likewise forbidden to install additional
components that have not been tested
together with the unit.
• If it becomes clear that safe operation of
the unit is no longer possible, for example
because of damage to the housing, turn the
unit off immediately.
• Any parts of the unit or accessories that are
not in perfect condition must be exchanged
immediately.
• Use only original spare parts and accessories
from the manufacturer.
• Markings made on the unit at the factory must
not be altered, removed or made illegible.
• Only the settings described in these
instructions may be set using the Unit.
Changes to the unit can compromise the safety and function of the unit or the entire system.
1.4 Warranty and Liability
The Unit has been manufactured and tested with regard to high quality and safety requirements.
The warranty and liability shall not include, however, any injury to persons or material damage that is
attributable to one or more of the following causes:
• Failure to observe these installation and
operating instructions.
• Improper installation, commissioning,
maintenance and operation.
• Improperly executed repairs.
• Unauthorised structural changes to the unit.
• Use of the device for other than its intended
purpose.
• Operation above or below the limit values
listed in the ‚Specifi cations‘ section.
• Force majeure.
1.5 Disposal and Pollutants
The unit conforms to the European RoHS 2011/65/EU for 2011/65/EUthe restriction of the use of certain
hazardous substances in electrical and electronic equipment.
Under no circumstances may the device be disposed of with
the normal household waste. Dispose of the unit only at appropriate collection points
or ship it back to the seller or manufacturer system.
5IOM 81, Issue 2 - Modulo Thermostat
2. Description SPC Modulo
Thermostat
2.1 Specifi cations
Housing
2-part, ABS plastic
75 mm x 95 mm x 30 mm
Glass front
Display
Capacitive touch panel
Colour display with 240x320 dots
2.8 inches (7 cm) diagonal
123
Operation
Intuitive user guidance
30mm
95mm
75mm

6IOM 81, Issue 2 - Modulo Thermostat
Figure 1. Plasterboard hanging
Electrical specifi cations:
Power supply 24VAC or 24VDC +/- 10% SELV
Power consumption max. 2,5 W
Degree of protection IP20
Protection class III
Max. cable length
0-10V Signal < 30m
Permissible Ambient Conditions
during operation 0 °C - 50 °C, no moisture condensation permitted
for transport/storage 0 °C - 60 °C, no moisture condensation permitted
Measuring range Outside the measuring ranges there are larger deviations
Internal temperature sensor 0 °C - 60 °C Accuracy +/- 1 °C
Resolution 0,1 °C
Internal sensor for rel. humidity 0 % - 100 % Accuracy +/- 6 %
Resolution 0,1 %
Other Specifi cations
Installation methods Wall installation, with/without wall socket
Real Time Clock RTC with 24 hour power reserve
2.2 Scope of Supply
• SPC Modulo room thermostat
• 2 screws 3,5 x 35 mm and 2 plugs 6 mm for wall installation
• SPC Modulo installation guide
7IOM 81, Issue 2 - Modulo Thermostat
Pay attention to suitable
environmental conditions. Direct
sunlight, sources of heat and cold,
e.g. radiators and windows
must be avoided.
3. Installation
3.1 SPC Modulo Installation
Mount the unit at a suitable location.
Strip cables by 75 mm max.
and strip the last 7-10 mm of the wires.
Approx.
120cm - 160cm
75mm
7-10mm

6IOM 81, Issue 2 - Modulo Thermostat
Figure 1. Plasterboard hanging
Electrical specifi cations:
Power supply 24VAC or 24VDC +/- 10% SELV
Power consumption max. 2,5 W
Degree of protection IP20
Protection class III
Max. cable length
0-10V Signal < 30m
Permissible Ambient Conditions
during operation 0 °C - 50 °C, no moisture condensation permitted
for transport/storage 0 °C - 60 °C, no moisture condensation permitted
Measuring range Outside the measuring ranges there are larger deviations
Internal temperature sensor 0 °C - 60 °C Accuracy +/- 1 °C
Resolution 0,1 °C
Internal sensor for rel. humidity 0 % - 100 % Accuracy +/- 6 %
Resolution 0,1 %
Other Specifi cations
Installation methods Wall installation, with/without wall socket
Real Time Clock RTC with 24 hour power reserve
2.2 Scope of Supply
• SPC Modulo room thermostat
• 2 screws 3,5 x 35 mm and 2 plugs 6 mm for wall installation
• SPC Modulo installation guide
7IOM 81, Issue 2 - Modulo Thermostat
Pay attention to suitable
environmental conditions. Direct
sunlight, sources of heat and cold,
e.g. radiators and windows
must be avoided.
3. Installation
3.1 SPC Modulo Installation
Mount the unit at a suitable location.
Strip cables by 75 mm max.
and strip the last 7-10 mm of the wires.
Approx.
120cm - 160cm
75mm
7-10mm

8IOM 81, Issue 2 - Modulo Thermostat
Unscrew the screw, remove the cable cover and connect the electric as described.
Refi t the base and fasten with screw.
Switch on mains voltage and place
SPC Modulo in operation.
Never remove front cover while
Modulo is connected to power.
This will result in damage
to the thermostat.
9IOM 81, Issue 2 - Modulo Thermostat
3.2 Sample Wiring
4. Setup
4.1 Setup Procedure
Install device
Install the device as described (See “Sample wiring”).
A wiring diagram will be supplied with the heating unit that the Modulo is intended to control. This shows
the wiring required between the Modulo and the heater.
Set Functions
Assign a switching output to the respective function via the “Expert” menu in the “Settings” menu item
under “Functions” and parameterize it (See “Settings Functions”).
0-10V
0-10V
GND Fan GND
Fan 0-10V
Valve 24VAC L’ / 24VDC +’
Valve 24VA N’ / 24VDC -’
Supply 24VA L / 24VDC +
Supply 24VA N / 24VDC -
Relay
24V out
L’
AC
N’
+’
DC
-’
L’
AC
N’
+’
DC
-’
Fuse
24V in

8IOM 81, Issue 2 - Modulo Thermostat
Unscrew the screw, remove the cable cover and connect the electric as described.
Refi t the base and fasten with screw.
Switch on mains voltage and place
SPC Modulo in operation.
Never remove front cover while
Modulo is connected to power.
This will result in damage
to the thermostat.
9IOM 81, Issue 2 - Modulo Thermostat
3.2 Sample Wiring
4. Setup
4.1 Setup Procedure
Install device
Install the device as described (See “Sample wiring”).
A wiring diagram will be supplied with the heating unit that the Modulo is intended to control. This shows
the wiring required between the Modulo and the heater.
Set Functions
Assign a switching output to the respective function via the “Expert” menu in the “Settings” menu item
under “Functions” and parameterize it (See “Settings Functions”).
0-10V
0-10V
GND Fan GND
Fan 0-10V
Valve 24VAC L’ / 24VDC +’
Valve 24VA N’ / 24VDC -’
Supply 24VA L / 24VDC +
Supply 24VA N / 24VDC -
Relay
24V out
L’
AC
N’
+’
DC
-’
L’
AC
N’
+’
DC
-’
Fuse
24V in

10 IOM 81, Issue 2 - Modulo Thermostat
5. Operation
5.1 Overview of Temperatures & Humidity
It displays room temperature and humidity, If there is no activity for 60 sec, the device is automatically
switched to the overview.
5.2 Operating Mode
Overview > Operating Mode
Room Icon
By selecting the room icon
you will be directed to the
room temperature settings.
Back / Forward
Navigation back to
the overview.
Menu
Navigation to the
main menu.
Operating Modes
The operating mode
shown in colour is
currently active and can
be changed by selecting a
diff erent mode. Manually
selected modes remain
active until the next change
of mode by the timer
program. A background
frost protection function
remains active in the
“off ’’ mode.
Reference Temperature
Setting the reference
temperature for the active
operating mode in the
displayed room.
Room Humidity
Relative humidity.
Room
Display of the selected room.
11IOM 81, Issue 2 - Modulo Thermostat
5.3 Menu
Overview > Operating Mode > Menu
5.4 Set Operation Hours
Overview > Operating Mode > Main Menu > Timer
Operating Modes
Selection of the operating
mode to select individual
heating or cooling sections.
Menu
Opens the copy function.
The function allows you
to copy the heating and
cooling times to the
following day,
to Monday - Friday or to
Monday - Sunday.
Back/Next Weekday:
Sellection of the day of
week which is to be set.
Clock
Time table for selecting the
time intervals in 30-minute
steps. Touch individual
segments, or drag your
fi nger over complete time
intervals to colour them
according to the selected
operation mode.
Timer
Setting of individual
heating and cooling times
for each day of the week
including a copy function
for following days.
Holiday
Sets the duration
and temperature for
a longer absence.
Expert
Advanced settings
for technicians.
Fan
Settings of the fan
operating mode.

10 IOM 81, Issue 2 - Modulo Thermostat
5. Operation
5.1 Overview of Temperatures & Humidity
It displays room temperature and humidity, If there is no activity for 60 sec, the device is automatically
switched to the overview.
5.2 Operating Mode
Overview > Operating Mode
Room Icon
By selecting the room icon
you will be directed to the
room temperature settings.
Back / Forward
Navigation back to
the overview.
Menu
Navigation to the
main menu.
Operating Modes
The operating mode
shown in colour is
currently active and can
be changed by selecting a
diff erent mode. Manually
selected modes remain
active until the next change
of mode by the timer
program. A background
frost protection function
remains active in the
“off ’’ mode.
Reference Temperature
Setting the reference
temperature for the active
operating mode in the
displayed room.
Room Humidity
Relative humidity.
Room
Display of the selected room.
11IOM 81, Issue 2 - Modulo Thermostat
5.3 Menu
Overview > Operating Mode > Menu
5.4 Set Operation Hours
Overview > Operating Mode > Main Menu > Timer
Operating Modes
Selection of the operating
mode to select individual
heating or cooling sections.
Menu
Opens the copy function.
The function allows you
to copy the heating and
cooling times to the
following day,
to Monday - Friday or to
Monday - Sunday.
Back/Next Weekday:
Sellection of the day of
week which is to be set.
Clock
Time table for selecting the
time intervals in 30-minute
steps. Touch individual
segments, or drag your
fi nger over complete time
intervals to colour them
according to the selected
operation mode.
Timer
Setting of individual
heating and cooling times
for each day of the week
including a copy function
for following days.
Holiday
Sets the duration
and temperature for
a longer absence.
Expert
Advanced settings
for technicians.
Fan
Settings of the fan
operating mode.

12 IOM 81, Issue 2 - Modulo Thermostat
Step 1
Use the arrow keys to select the desired day.
Step 2
Select the fi rst heating mode (normal) - move the
index fi nger over the desired length of time. The
selected period will be coloured after selecting the
colour of the operating mode (normal = orange).
Set the times of the other operating modes in the
same way.
Step 3
After completing the setting of the individual
heating and cooling times, you have the option
of copying the times via the main menu
to the following day, to Monday - Friday or to
Monday-Sunday or individually for each weekday.
13IOM 81, Issue 2 - Modulo Thermostat
5.5 Expert Menu
Overview > Operating Mode > Main Menu > Expert
5.6 Expert Menu Settings
Overview > Operating Mode > Main Menu > Expert > Settings
Select Language
Sets the device language.
Settings
Parameterisation of the
heating / cooling system.
Menu Lock
Activate menu lock to
protect settings with
a password.
Functions
Management of local control
functions - thermostat and
dehumidifi er.
Sensor calibration
Used to adapt the
temperature and humidity
of the said local sensor for
the selected area.
Location
Set where the device is
installed (selection of the
room icon).
Display Brightness
Adjustment of
display brightness.
Interface Mode
Switches between full and
restricted menu. Only the
reference temperature can
be set in the mode “Hide
menu” To return to “full”
mode, press and hold the
upper-right comer of the
display for 5 seconds.
Date & Time
Sets time and date and
automatic changeover
to local standard time
(summer/winter).
Service Values
Information about
the system.
Factory Settings
Resets the device to
factory settings.

12 IOM 81, Issue 2 - Modulo Thermostat
Step 1
Use the arrow keys to select the desired day.
Step 2
Select the fi rst heating mode (normal) - move the
index fi nger over the desired length of time. The
selected period will be coloured after selecting the
colour of the operating mode (normal = orange).
Set the times of the other operating modes in the
same way.
Step 3
After completing the setting of the individual
heating and cooling times, you have the option
of copying the times via the main menu
to the following day, to Monday - Friday or to
Monday-Sunday or individually for each weekday.
13IOM 81, Issue 2 - Modulo Thermostat
5.5 Expert Menu
Overview > Operating Mode > Main Menu > Expert
5.6 Expert Menu Settings
Overview > Operating Mode > Main Menu > Expert > Settings
Select Language
Sets the device language.
Settings
Parameterisation of the
heating / cooling system.
Menu Lock
Activate menu lock to
protect settings with
a password.
Functions
Management of local control
functions - thermostat and
dehumidifi er.
Sensor calibration
Used to adapt the
temperature and humidity
of the said local sensor for
the selected area.
Location
Set where the device is
installed (selection of the
room icon).
Display Brightness
Adjustment of
display brightness.
Interface Mode
Switches between full and
restricted menu. Only the
reference temperature can
be set in the mode “Hide
menu” To return to “full”
mode, press and hold the
upper-right comer of the
display for 5 seconds.
Date & Time
Sets time and date and
automatic changeover
to local standard time
(summer/winter).
Service Values
Information about
the system.
Factory Settings
Resets the device to
factory settings.

14 IOM 81, Issue 2 - Modulo Thermostat
5.7 Settings Functions
Overview > Operating Mode > Main Menu > Expert > Settings > Functions
Overview > Operating mode > Menu > Expert > Settings > Functions > Thermostat
Thermostat
Fan
Hysteresis
Heating hysteresis of the
thermostat function in
relation to the actual set
room temperature _
15IOM 81, Issue 2 - Modulo Thermostat
Overview > Operating mode > Main menu > Expert > Settings > Functions > Fan
Hysteresis
Fan Mode
Minimum Speed
Medium Speed
Maximum Speed
6. Fault Finding
Under certain circumstances the thermostat may need to be reset. This may be as a result of external
issues with equipment that the thermostat is connected to.
6.1 Factory Reset
If the screen remains illuminated but is displaying odd or unexpected data this can be resolved by
performing a factory reset. Enter expert mode and select ‘Factory Settings’ as described earlier.
6.2 Hard Reset
If the thermostat screen is blank and will not illuminate then a hard reset may resolve the issue. Firstly,
isolate the thermostat by isolating the heating unit which is powering it. Reconnect the power and check
if the thermostat is still blank, if it is proceed as below. Isolate the power again and then remove the front
from the Modulo thermostat, replace the front and then reconnect the power.
Under no circumstances remove the front cover while the thermostat is powered - this may cause
irrecoverable damage.

14 IOM 81, Issue 2 - Modulo Thermostat
5.7 Settings Functions
Overview > Operating Mode > Main Menu > Expert > Settings > Functions
Overview > Operating mode > Menu > Expert > Settings > Functions > Thermostat
Thermostat
Fan
Hysteresis
Heating hysteresis of the
thermostat function in
relation to the actual set
room temperature _
15IOM 81, Issue 2 - Modulo Thermostat
Overview > Operating mode > Main menu > Expert > Settings > Functions > Fan
Hysteresis
Fan Mode
Minimum Speed
Medium Speed
Maximum Speed
6. Fault Finding
Under certain circumstances the thermostat may need to be reset. This may be as a result of external
issues with equipment that the thermostat is connected to.
6.1 Factory Reset
If the screen remains illuminated but is displaying odd or unexpected data this can be resolved by
performing a factory reset. Enter expert mode and select ‘Factory Settings’ as described earlier.
6.2 Hard Reset
If the thermostat screen is blank and will not illuminate then a hard reset may resolve the issue. Firstly,
isolate the thermostat by isolating the heating unit which is powering it. Reconnect the power and check
if the thermostat is still blank, if it is proceed as below. Isolate the power again and then remove the front
from the Modulo thermostat, replace the front and then reconnect the power.
Under no circumstances remove the front cover while the thermostat is powered - this may cause
irrecoverable damage.

16 IOM 81, Issue 2 - Modulo Thermostat
7. Appendix 1
7.1 Setting Up Menu Lock
The password can be reset via use of the master password: [CALEON]
(square brackets and capitals required).
Menu lock
Protect settings
with a password
Yes No
Step 2
Click on the ‘yes’ icon.
Expert
Select language
Date & Time
Settings
Service values
Menu lock
Factory settings
Step 1
To set up the menu
lock, go into the expert
section. Click on the
‘menu lock’.
Enter password
****E
A B C D E
F G H I J
K L M N O
P Q R S T
U V W X Y
Z abc 123 !#@
Step 3
Enter password.
Then click on the arrow.
Confirm password
****E
A B C D E
F G H I J
K L M N O
P Q R S T
U V W X Y
Z abc 123 !#@
Step 4
Re-enter password to
confi rm. Then click on
the arrow.
Enter password
****E
A B C D E
F G H I J
K L M N O
P Q R S T
U V W X Y
Z abc 123 !#@
Step 7
Enter the password
to remove menu lock,
click on the arrow.
Menu lock
Protect settings
with a password
Yes No
Step 6
To edit the settings or
remove the menu lock.
Go into ‘menu lock’, click
on the ‘no’ icon.
Expert
Date & Time
Service values
Menu lock
Step 5
After the password has
been set via menu lock.
All options for settings
will be removed/locked
besides these three
options.
17IOM 81, Issue 2 - Modulo Thermostat
Menu
Expert
Fan
80.2%
19.1ºC
Interface Mode
Full menu or hide menu (only
actual temperature and
humidity)?
Hide
Interface Mode
Full menu or hide menu (only
actual temperature and
humidity)?
Full
Settings
Functions
Location
Sensor Offset
Display Brightness
Interface Mode
Expert
Select language
Date & Time
Settings
Service values
Menu lock
Factory settings
7.2 Setting Up Interface Lock
Step 5
To deactivate
‘hide mode’, hold the
upper-right corner
of the display for
around 5 seconds.
Step 6
To return to ‘full mode’,
click on expert mode, go
back to interface mode
and select ‘full’ menu.
Step 1
To set up the interface
lock, go into the expert
section. Click on ‘settings’.
Step 2
Click on ‘interface mode’.
Step 3
Default setting is on full
menu. Click on either
the ‘positive’ or ‘negative’
icon to change mode.
Step 4
Once in hide mode.
Click on the arrow to
activate.

16 IOM 81, Issue 2 - Modulo Thermostat
7. Appendix 1
7.1 Setting Up Menu Lock
The password can be reset via use of the master password: [CALEON]
(square brackets and capitals required).
Menu lock
Protect settings
with a password
Yes No
Step 2
Click on the ‘yes’ icon.
Expert
Select language
Date & Time
Settings
Service values
Menu lock
Factory settings
Step 1
To set up the menu
lock, go into the expert
section. Click on the
‘menu lock’.
Enter password
****E
A B C D E
F G H I J
K L M N O
P Q R S T
U V W X Y
Z abc 123 !#@
Step 3
Enter password.
Then click on the arrow.
Confirm password
****E
A B C D E
F G H I J
K L M N O
P Q R S T
U V W X Y
Z abc 123 !#@
Step 4
Re-enter password to
confi rm. Then click on
the arrow.
Enter password
****E
A B C D E
F G H I J
K L M N O
P Q R S T
U V W X Y
Z abc 123 !#@
Step 7
Enter the password
to remove menu lock,
click on the arrow.
Menu lock
Protect settings
with a password
Yes No
Step 6
To edit the settings or
remove the menu lock.
Go into ‘menu lock’, click
on the ‘no’ icon.
Expert
Date & Time
Service values
Menu lock
Step 5
After the password has
been set via menu lock.
All options for settings
will be removed/locked
besides these three
options.
17IOM 81, Issue 2 - Modulo Thermostat
Menu
ExpertFan
80.2%
19.1ºC
Interface Mode
Full menu or hide menu (only
actual temperature and
humidity)?
Hide
Interface Mode
Full menu or hide menu (only
actual temperature and
humidity)?
Full
Settings
Functions
Location
Sensor Offset
Display Brightness
Interface Mode
Expert
Select language
Date & Time
Settings
Service values
Menu lock
Factory settings
7.2 Setting Up Interface Lock
Step 5
To deactivate
‘hide mode’, hold the
upper-right corner
of the display for
around 5 seconds.
Step 6
To return to ‘full mode’,
click on expert mode, go
back to interface mode
and select ‘full’ menu.
Step 1
To set up the interface
lock, go into the expert
section. Click on ‘settings’.
Step 2
Click on ‘interface mode’.
Step 3
Default setting is on full
menu. Click on either
the ‘positive’ or ‘negative’
icon to change mode.
Step 4
Once in hide mode.
Click on the arrow to
activate.

SPC House
Evington Valley Road
Leicester
LE5 5LU
T: 0116 249 0044
E: spc@spc-hvac.co.uk
spc-hvac.co.uk
IOM 81, Issue 2 - Modulo Thermostat
Final Declaration
Although these instruction have been created with the greatest possible care, the possibility of
incorrect or incomplete information cannot be excluded. Subject as a basic principle to errors and
technical changes.
Date and time of installation:
Name of installation company:
Space for notes:
Other manuals for Modulo
1
Table of contents
Other SPC Thermostat manuals
Popular Thermostat manuals by other brands

Johnson Controls
Johnson Controls METASYS TEC1100 Series Technical bulletin

Bryant
Bryant Legacy Series owner's manual

Danfoss
Danfoss DEVIreg Multi installation guide

Sygonix
Sygonix 2686283 operating instructions

Flextherm
Flextherm INSTINCT Connect FLP45-120/240GA user manual

ICM Controls
ICM Controls SC 2001 Installation, operation & application guide