manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Static Power
  6. •
  7. Industrial Electrical
  8. •
  9. Static Power iSTS R User manual

Static Power iSTS R User manual

1
Supply 1Input
Push
-
in terminal suits 4mm² cable, use a small blade type screwdriver in the top slot and press in; insert the
cable and release.
Repeat for the Neutral Conductor. Note the neutral is not fused. Bare the wire just 8mm.
2
Output Terminal
Push
-in terminal suits 4mm² cable, use a small blade type screwdriver in the top slot and press in;
insert
the
cable and release. Bare the wire just 8mm.
3
Alarm LED
When
there is an alarm that has not been acknowledged this LEDs will flash. If the alarm has
been
ac
knowledgedbut the condition still exists, the LEDs will remain on.
The
Alarm LED and the Remote Contact will be triggered when:
▪On Supply 1 when priority is Supply 2
▪On Supply 2 when priority is Supply 1
▪Not in Synchronism
▪Supply 1 or Supply 2 are not in spec.
▪There is/was an overcurrent/overload/load fault condition or Overtemperature condition
▪There has been a thyristor/SCR Fault
▪The Auto retransfer to preferred source has locked out & max number of automatic re-transfers
has been exceeded.
4
Alarm Cancellation Button
Pressing
this button acknowledges new alarms, causing the audible alarm to turn off and the LEDs to
go
from
flashing to solid.
5
Preferred Indicator
These
three LEDs indicate which supply is selected as the preferred supply. Supply 1 ‘I’, Supply 2 ‘II’
or
neither
may be selected.
6
Preferred Button
Pressing
this button repeatedly will scroll through which supply is selected as the preferred supply.
7
Supply 1 Okay LED
Green/Red
indicated that Supply 1 is within/out of tolerance. If fuse is open or blown or there is
no
power
present the power available LED will be Red.
8
Supply 2 Okay LED
Green/Red
indicated that Supply 2 is within/out of tolerance. If fuse is open or blown or there is
no
power
present the power available LED will be Red.
9
Sync Okay LED
Green/Red
indicated whether Supply 1 and Supply 2 are within/not within enough degrees
of
synchronisation
of each other to perform a transparent transfer.
10
On Supply 1 LED
Green/Red
indicates the load is on/not on Supply 1.
11
On Supply 2 LED
Green/Red
indicates the load is on/not on Supply 2.
12
Supply 2 Input
Push
-
in terminal suits 4mm² cable, use a small blade type screwdriver in the top slot and press in; insert the
cable and release.
Repeat for the Neutral Conductor. Note the neutral is not fused. Bare the wire just 8mm.
13
Output Okay LED
Green/Red
indicated the output is OK/faulty.
14
Load LEDs
There
are eight LEDs, the bottom six are Green and indicate roughly 10% - 90% loaded. The seventh
LED
is
orange and indicates 100% loaded. The eighth LED is Red and indicates that the iSTS is over loaded.
15
Remote Contact
Voltage
free alarm for integration into BMS. Do not connect any more than 50V/0.5A, not suitable
for
230
VAC. Contacts are Normally Closed. Contact is held Open when there is no alarm. When power
fails
the
relay contact closes (fail safe). The Remote Contact and the Red Alarm LED are driven by the
same
logic
.
iSTS R
2 3 5 7 9 10 13 14
!III
!
I
II ≠
1F
14 6 8 11 12 15
121
N P
N P
N P
IN1 IN2 OUT
STATIC POWER Pty Ltd
ABN 42 101 765 913
iSTS R
–Quick Starter Guide R03
Post to:
Box 2003
Research Delivery centre
Research, VIC 3095 - Australia
Manufactured at:
5 Candlebark Court
Research, VIC 3095
Australia
Contact us:
+61 3 9437 0494
[email protected]
www.staticpower.com.au
A. INSTALLATION
a.
The Model R is a 2 pole, single phase DIN Rail mount STS that suits 35mm x 7.5mm rail.
b.
The STS is powered from two separate sources. All precautions to guarantee people’s safety shall be undertaken.
c.
The iSTS R is supplied with 2 DIN rail mounted fuse disconnectors (10x38 aR -20A) placed near the unit
with
sufficient space for cooling. The iSTS and fuses can only be mounted vertically.
d.
Incoming source should be terminated to the fused switch disconnector and then to the STS active inputs.
The
neutrals are not fused and should be terminated directly to the iSTS inputs. Ensure the cables are
securely
connected and supported.
B. SETUP
a.
Ensure that the two input sources are within tolerance, and that they are in synchronism (±15%of rated
voltage,
<10% THD, <15º phase difference)
b.
Connect your critical load to the OUTPUT. NOTE: Due to the nature of Silicone Controlled Rectifiers (SCRs),
some
load (~0.2A) is required for correct operation.
c.
Connect the sources to SUPPLY 1 and SUPPLY 2. If you wish to Confirm Operation you will need to be able
to
switch both sources on and off.
C. STARTUP
a.
Apply power to both input sources.
b.
There will be a short (15 sec) start-up period, after which the iSTS will begin powering your load.
c.
Confirm that the load is receiving power.
d.
Ensure that LEDs are correctly representing the supply status and load. NOTE: Only On Supply 1 LED or On
Supply
2 LED should be Red.
D. CONFIRM
a.
Use the Preferred Button to highlight ‘I’on the Preferred Indicator. Wait for the On Supply 1 LED to turn green
(if
is not already).
b.
Turn OFF Supply 1, and confirm that the iSTS transfers to ‘II’(On Supply 2 LED - green).
c.
Turn ON Supply 1, and confirm that the iSTS auto transfers to Supply 1 after a 3 second delay (On Supply 1 LED
-
green).
d.
Use the Preferred Button to highlight ‘II’. Wait for the iSTS to transfer to Supply 2 (On Supply 2 LED - green).
e.
Turn OFF Supply 2, and confirm that the iSTS transfers to Supply 1 (On Supply 1 LED - green).
f.
Turn ON Supply 2, and confirm that the iSTS auto transfers to Supply 2 after a 3 second delay (On Supply 1 LED
-
green).
iSTS R
STATIC POWER Pty Ltd
ABN 42 101 765 913
iSTS R
–Quick Starter Guide R03
Post to:
Box 2003
Research Delivery centre
Research, VIC 3095 - Australia
Manufactured at:
5 Candlebark Court
Research, VIC 3095
Australia
Contact us:
+61 3 9437 0494
[email protected]
www.staticpower.com.au

Other manuals for iSTS R

2

Popular Industrial Electrical manuals by other brands

Siemens MOBIC T8 for Windows CE 3.0 manual

Siemens

Siemens MOBIC T8 for Windows CE 3.0 manual

ABB SACE PR021/K manual

ABB

ABB SACE PR021/K manual

Murata GRM0225C1E680GA02 Series Reference sheet

Murata

Murata GRM0225C1E680GA02 Series Reference sheet

schmersal AZM 161 AS operating instructions

schmersal

schmersal AZM 161 AS operating instructions

Murata GJM1555C1H6R0DB01 Series Reference sheet

Murata

Murata GJM1555C1H6R0DB01 Series Reference sheet

Murata GRM0335C1H8R8DA01 Series Reference sheet

Murata

Murata GRM0335C1H8R8DA01 Series Reference sheet

ABB SACE Emax 2 manual

ABB

ABB SACE Emax 2 manual

ewo airmate operating guide

ewo

ewo airmate operating guide

M-system RPPD instruction manual

M-system

M-system RPPD instruction manual

3M 4220VB instructions

3M

3M 4220VB instructions

CATH-TECH CI-100TS Operation manual

CATH-TECH

CATH-TECH CI-100TS Operation manual

Murata GRT188R61E225ME13 Series Reference sheet

Murata

Murata GRT188R61E225ME13 Series Reference sheet

Eaton DILM12-XSL Instruction leaflet

Eaton

Eaton DILM12-XSL Instruction leaflet

L&T Electrical & Automation GIS GV3N Operation & maintenance manual

L&T Electrical & Automation

L&T Electrical & Automation GIS GV3N Operation & maintenance manual

efacec NORMAFIX instructions

efacec

efacec NORMAFIX instructions

THORLABS KPA101 Kinesis User Guide

THORLABS

THORLABS KPA101 Kinesis User Guide

Moeller NZM4 60 Series installation instructions

Moeller

Moeller NZM4 60 Series installation instructions

Murata GJM1555C1H120JB01 Series Reference sheet

Murata

Murata GJM1555C1H120JB01 Series Reference sheet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.