Suburban DYNALINE DL3-0712 Service manual

1 Suburban DynaLine Owner's Manual 10/2017 Rev.1
WARNING! If the information in these instructions are
not followed exactly, a re or explosion may result causing
property damage, personal injury or loss of life.
Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach a gas supplier, call the re
department.
Installation and service must be performed by
a qualied installer, service agency or the gas
supplier.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
WARNING! Improper installation, adjustment, alteration,
service or maintenance can cause property damage, personal
injury or loss of life. Refer to the installation instructions and/
or owners manual provided with this appliance. Installation
and service must be performed by a qualied installer, service
agency or the gas supplier.
FOREWORD
You have just purchased a Suburban Packaged Terminal Air Conditioner. Models
0712, 0912, 1220 AND 1622 are certied by the Canadian Standard Association
under Z21.86-2008/CSA 2.32-2008 UL484.
To simplify the proper installation and to assure that the unit will operate in
conformity with generally accepted safety regulations, it requires that you read
carefully and fully understand the step-by-step instructions outlined in this manual.
CAUTION: Due to the differences in vinyl siding, this appliance should not
be installed on vinyl siding without rst consulting with the manufacturer
of the siding or cutting the siding away from the area around the appliance
vent.
NOTE: Do not deviate from the instructions as outlined in this manual. Failure
to follow the installation, operating and maintenance instructions will void the
responsibility of Suburban Manufacturing Company.
DYNALINE™
PACKAGED TERMINAL AIR CONDITIONER
MODELS: DL3-0712 • DL3-0912 • DL3-1220 • DL3-1622
OWNER’S MANUAL
INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS
This book contains instructions for installation and operation of your unit. Keep it in a safe place for ready reference.
Should you require further information, contact your dealer.
INSPECTING FOR FREIGHT DAMAGES
Your unit was carefully packed in a container which complies with the National
Safe Transit Test. This means that the packaged product, with normal handling,
will withstand the load conditions encountered in normal transit and in handling.
Your unit should be inspected immediately after unpacking to determine if any
damage is present due to shipping or handling. If any damage is discovered, do
not install the unit. Notify the transportation company immediately and le a
damage claim.
The manufacturer can bear no responsibility for damages which occur in transit or
for improper operation of the unit as a result of shipping damages.
For future reference, you should record the following information from the units.
MODEL NUMBER _______________________________________________
SERIAL NUMBER ______________________________________________
STOCK NUMBER _______________________________________________
DATE OF PURCHASE ___________________________________________
UNIT SPECIFICATIONS
Do not operate the unit during construction period; this
may be a breach of the warranty conditions.
HEATING
MODEL
DL3-0712 DL3-0912 DL3-1220 DL3-1622
BTU INPUT 12,000 12,000 18,000 20,000
VOLTS 208/230 208/230 208/230 208/230
AMPS 2.0 2.0 2.0 2.0
GAS
CONNECTION 3/8” IPS 3/8” IPS 3/8” IPS 3/8” IPS
COOLING
MODEL
DL3-0712 DL3-0912 DL3-1220 DL3-1622
COOLING
CAPACITY 7600/7800 9300/9500 11500/11700 15000
VOLTS 208/230 208/230 208/230 208/230
WATTS 675/705 830/855 1075/1125 1520/1580
REFRIGERANT
CHARGE SEE INFORMATION STICKER ON UNIT
REFRIGERANT R410A
Part Number 81758
10-31-2017
AIRXCEL, INC.
SUBURBAN APPLIED PRODUCTS
156 Seedling Drive
Cordele, GA 31015
(229) 273-3636
www.SuburbanHVACproducts.com

Suburban DynaLine Owner's Manual 10/2017 Rev.1 2
3. The wall sleeve may be installed directly on nished oor as illustrated in
Figure 2, however, considerations should be given to the location of gas lines
and electrical service. NOTE: If mounted on top of oor, the gas connection
should be made from rear of unit. For the best nished results, Suburban
suggests the wall sleeve be mounted a minimum of 3-1/2” off of the nished
oor, as illustrated in Figure 3. This allows sufcient space for the gas and
electrical connections to be made below the wall case. An accessory base
panel, Suburban Kit #520873, may then be attached to the cabinet front to
conceal these service connections. NOTE: This base panel is non-loading
bearing.
4. When installing below a window, the installer should consider the possibility of
curtains interfering with discharge air and/or accessory air discharge package
and take steps to eliminate these restrictions.
5. The installer should allow for drywall or other interior wall nishes when
locating sleeve during rough-in. (See Figures 5 or 6.)
6. Prior to installing the wall sleeve, one must consider the method to be used to
drain the condensate from the wall sleeve. Two methods may be used:
a. Free Drain (External)- A general acceptable alternative where the
condensate drains from the wall sleeve through three exterior drain holes
and drops to open ground. (See Figure 4.) The condenser fan is designed
to pick up normal condensate and evaporate it off the condenser coil.
b. Drain Kit - A condensate drain kit is recommended for positive drainage
when specied or code requires or when condensate is heavy under
conditions of extreme humidity for extended periods of time. The drain
tube assemblies may be installed externally on rear ange of the wall
sleeve or underneath the wall sleeve to the external side of building. (See
Figure 7) The condensate can be freely drained to ground level or routed
in tubing to a disposable location. Drain tube kits are designed for 1/2”
O.D. copper tubing.
NOTE: Excessive rain water entering the unit through the outside grille may not
be entirely removed during operation of the unit. Excessive rain water will drain
through the raised weep holes provided on the rear of the wall sleeve.
7. After selecting a location for wall sleeve, inspect the wall and oor areas
to determine that there are no hidden electrical wires, propane or other
ammable gas-liquid piping or tubing, ducts, girders or wall studs that will
interfere with the proper installation and safe operation of the unit or the
proper installation of gas supply lines and electrical service
8. The cabinet front is shipped with the unit chassis. Side anges on chassis are
secured to sleeve from inside room to insure proper security and mounting.
INSTALLATION
Before beginning the installation, it is suggested that the cabinet front and air lter
be removed to avoid damage during installation of the unit.
1. Cut an opening in the outside wall and frame to the minimum opening as
illustrated in Figures 2 or 3. Refer to Table 1 for minimum clearances to
obstruction. Use conventional construction methods to frame opening. Do
not use wall sleeve as a lintel. The framed opening should allow for the
sloping of the sleeve toward outside wall as illustrated in Figures 5 or 6, in
order to assure proper drainage. Do not install wall sleeve level or slope
toward room.
2. Unfold the sides of the wall sleeve and assemble the top, being sure that
the sides wedge between the top ange on the top and the retaining angle
as illustrated in Figure 4. Secure at top corners with screws provided. If the
opening in the rear of the sleeve for rear gas hook-up is not used, you may
block the opening using the bird guard supplied with the sleeve. (See Figure
4A for illustration.)
3. Install wall sleeve into framed opening with the three drain holes to the
outside. Minimum projection of wall sleeve into the room is ush with nished
wall or molding, as illustrated by “x” dimension in Figures 5 or 6.
CAUTION: Be sure sleeve protrudes far enough into the room to allow for
any interior wall studding, insulation and dry wall or nished wall to be
added during construction.
Do not install sleeve ush with nished exterior wall.
If sleeve installed with oor clearance from 0” to less than 3-1/2”, the sleeve
must protrude a minimum of 1-5/8” beyond nished surface of exterior wall. (See
Figure 5.) This is to allow for rear gas hook-up. If sleeve is installed with oor
clearance of 3-1/2” or greater, the sleeve must protrude a minimum of 1/4” beyond
nished surface of exterior wall. (See Figure 6.)
NOTE: Wall sleeve installations that protrude into the room 4” or more require the
use of Leg Leveling Kit #520600 or other means of supporting the wall sleeve.
(See Figure 8). Failure to support the wall sleeve front in such installations may
cause improper sleeve slope(1/4” rear slope required - see Step 4 below), which
may result in improper condensate leakage into the interior room space.
For installations in windows and/or curtain or panel walls of 2”, it is suggested that
a minimum of two eld supports be installed under wall sleeve since no screws
can be used in bottom of sleeve to the wall.
Field supplied wall sleeve angles 1” x 1” x .065/.055 are to be used on top, sides
and bottom of wall sleeve. (See Figure 9).
CAUTION: Do not drill holes in bottom of sleeve. Bottom angle is for support
only and is to be secured to wall.
4. Secure wall sleeve to wall as illustrated in Figures 5 or 6. Be sure wall case is
level (side to side-parallel to oor) and sloped 1/4” from front to rear. Do not
put holes in bottom of sleeve, water damage to wall and oor will occur.
5. Caulk around wall sleeve between the sleeve and building to form a weather
tight seal against rain and snow. Use only weather proof caulking. (See
Figures 5 or 6).
PRE-INSTALLATION TIPS AND CONSIDERATION
MINIMUM OPERATIONAL CLEARANCES
The following minimum outside clearance from rear grille must be maintained:
Rear of unit to nearest obstruction - 36”
Side of unit to nearest obstruction - 0”
CAUTION: This appliance should not be installed on or near adjacent
walls with vinyl siding without rst consulting with the manufacturer of
the siding or cutting the siding away from the area around the appliance
vent.
Bottom of unit to obstruction and/or ground - This requirement is determined
by local climate and environmental conditions. The unit must be above ground
and high enough off of the ground to prevent snow, water, leaves or any other
obstruction from blocking rear of unit.
The following minimum inside clearances from cabinet front must be
maintained:
The ow of discharge air must not be obstructed for a minimum of 12”
Side of cabinet to nearest obstruction - 1”
Top of unit to ceiling - 12”
Cabinet front to nearest obstruction - 12” *
*Obstruction must be removable for service of unit.
Otherwise a minimum clearance of 36” is required.
Bottom of cabinet front to nished oor - 0”
Minimum Clearances to Combustible Construction
Units are approved for 0” clearance to combustible construction top, sides
and bottom. Front and rear clearances not applicable as there can be no
construction combustible or non-combustible to the front or rear of the opening.
Keep burner and control compartment clean. See installation and operating
instructions accompanying appliance.
TABLE 1
INTRODUCTION
WARNING! Installation of this appliance must be made in accordance with the written
instructions provided in this manual. No agent, representative or employee of Suburban or
other person has the authority to change, modify or waive any provision of the instructions
contained in this manual.
This manual is intended to familiarize the installer, serviceman and user with the
installation, operation and maintenance of the heating and cooling unit.
The unit is designed for a wall thickness of 1” minimum to 14-1/2” maximum.
NOTE: Maximum wall thickness cannot exceed 12-5/8” if rear gas hook-up is to
be used. The wall sleeves must be installed as illustrated in Figures 5 or 6 so that
the unit chassis when slid into the sleeve is vented to the outside atmosphere.
Do not install in an alcove or recess.
Special sleeve and grille applications must be brought to the attention of Suburban
as they may impair the operation of the unit.
IMPORTANT: Installation of the rear grille must be made prior to installing
the chassis as it secures from inside the wall sleeve.
In the U.S.A., this appliance must be installed in accordance with local codes
and regulations. In the absence of local codes and regulations, installation must
comply with the latest edition of:
1. National Fuel Gas Code ANSI Z223.1/NFPA 54.
2. National Electrical Code NFPA 70.
In Canada, the installation must be in accordance with local codes or in the
absence of local codes, with the current CANI-B149 Installation Code.
REQUIREMENTS FOR INSTALLATIONS IN COMMONWEALTH OF
MASSACHUSETTS, SEE PAGE 16.
1. When choosing a location for the sleeve, remember that the unit chassis
must be vented to the outside atmosphere, therefore, the sleeve must be
mounted in the outside wall of the room. A location should be selected with
consideration for circulation of discharge (room) air. Generally, the location
which provides the most effective circulation is midway along the wall of the
room the unit is to serve and away from a stairwell or other openings. Do not
locate sleeve behind a door or at a point where a door, if left open, would tend
to obstruct the unit when installed into the sleeve.
2. In choosing a location for the sleeve, one must consider the minimum
operation clearances as specied in Table 1. These clearances assure
adequate accessibility for servicing and proper operation of the unit and
therefore, must be maintained.

3 Suburban DynaLine Owner's Manual 10/2017 Rev.1
6. Seal around sleeve between nished interior wall and sleeve to minimize heat/
cooling loss around sleeve. Seal may be caulking, or if preferred, installer
may trim around sleeve with molding or other suitable materials.
IMPORTANT: Installation of the rear grille must be made prior to installing
the chassis as it secures from inside the wall sleeve.
7. Slide unit into wall sleeve and secure it to sleeve using the four #10 x 1/2
screws provided.
8. Connect gas and electrical supply. Refer to Figure 10 for centerline location
of gas connection and electrical connection when unit is installed into wall
sleeve.
NOTE: This unit is factory set for 230 volt operation. If you wish to operate unit on
208 volts, the rocker switch located behind the cabinet front on the controls panel
(reference Item No. 25, Figure 15) must be switched to 208 volts.
NOTE: On occasions, the voltage on a 230 volt model may drop. If the voltage
drop is at or below 208 volts, the switch should be switched to 208 volts.
9. The operation of this unit is controlled by a built-in thermostat. A digital
temperature read out will be displayed on the control panel.
For remote thermostat operation, connect the thermostat wiring to the terminal
block located on the module board. Move switch #1 on the thermostat switch to
“on”. (See Figure 12.)
To reset controls, turn power off then back on.
NOTE: Connecting remote thermostat overrides the built-in thermostat and you
will not get a digital read out on the control panel. There is no need to disconnect
the built-in thermostat as shipped from factory.
10. Reinstall air lter.
11. The outlet air grille can be installed in either of two positions. The unit is
delivered for horizontal air ow. If vertical air ow is desired, remove grille and
reinstall in alternate position. See gure below.
12. Reinstall cabinet front. Do not operate unit with cabinet front removed.
MAKING GAS CONNECTIONS
The unit is factory equipped with a 3/8” NPT gas connection. The size of the pipe
should be computed according to the type of gas and the length of the run. Table
2 gives a reasonably accurate size for the service line. The quantities given in the
table are for cubic feet per hour. To convert BTU capacity to cubic feet, divide total
BTU load by the BTU value of the gas being used. The table is for natural gas only.
To convert to liqueed petroleum (LP) gas, multiply by .633. The pressure drop
caused by other gas appliances being served by any portion of the line provided
for this installation must be considered. If the new line is takeoff from an existing
line to another appliance, pressure drop computation with the table must include
the demand of the other appliance.
CAUTION: Suburban does not recommend the use of ex tubing to make the
gas connections to the unit unless the ex tubing is a high quality stainless
certied by AGA and approved for use by local code.
Minimum gas supply pressure for purposes of input adjustment:
Minimum Maximum
Natural Gas 5” W.C.* 7” W.C.
Liqueed Petroleum (LP) Gas 11” W.C. 13” W.C.
(*Water Column)
OPERATING PRESSURE
All units for burning natural gas are equipped with a valve having a built-in
regulator preset at 3.5” W.C. pressure. All units for burning liqueed petroleum
(LP) gas are equipped with a valve having a built-in regulator preset at 10.5” W.C.
pressure. Do not adjust the regulator set screw on the valve. Over ring of the
unit may occur.
It is recommended that the installer install a manual shut-off valve in the gas
supply line to the unit. It is also recommended that a ground joint union be
installed between the unit and this shut-off valve.
A condensate trap should also be installed in the gas supply line as close to the
unit as possible.
In order to maintain a check on gas supply pressure to the unit, Suburban advises
the installer to provide a 1/8” NPT plug tap for test gauge connection immediately
upstream of the gas supply connection to the unit.
The unit and its individual shut-off valve must be disconnected from the gas supply
piping system during any pressure testing of the gas system at test pressures in
excess of 1/2 PSIG. The unit must be isolated from the gas supply piping system
by closing its individual manual shut-off valve during any pressure testing of the
gas supply system at test pressures equal to or less than 1/2 PSIG.
WARNING! A pipe thread compound resistant to the action of liqueed petroleum (LP)
and natural gas must be used on all pipe joints.
All gas piping should be tested with a soap and water solution to assure gas-tight
connections.
WARNING! Do not use an open ame to check for leaks!
MAKING ELECTRICAL CONNECTIONS
(208 - 230 Volts)
If local codes permit, the service cord as supplied with the unit may be used. The
service cord is added at the factory for testing during production. If local codes
do not permit the use of a service cord, it must be removed and the electrical
connections made in the junction box.
All external wiring must comply with local codes or national electrical codes.
It is recommended that the wiring be on a separate permanent line electrical
circuit. The electrical circuit must be protected using dual 15 amp fuse or HACR
type circuit breaker.
In the U.S.A., the unit when installed, must be electrically grounded in accordance
with local codes or, in the absence of local codes, with the latest edition of National
Electrical Code ANSI/NFPA No. 70. Proper operation of this unit is dependent on
adequate earth ground. If the installation is made using gas piping of any material
other than metal pipe, then adequate steps must be taken to assure adequate
earth ground.
In Canada, the unit must be electrically connected and grounded in accordance
with local codes or in the absence of local codes with the current CSA C22.1
Canadian Electrical Code.
24 VAC EMERGENCY POWER CONNECTION
(COMPRESSOR LOCK-OUT)
Two 1/4” male terminals labeled “PWR DOWN” are available on the module
board. If 24 VAC is applied to these terminals, the compressor and condensor fan
operation are disabled. During a call for cooling, the indoor blower will run and the
“SERVICE SYSTEM” light will be on.
1. Remove the display panel (save the 5 screws for re-use (See Figure 13).
2. Route wiring from an external 24 VAC source through the bushing in the base
of the unit.
3. Terminate two wires with 1/4” female pre-insulated terminals.
4. Connect wires to the “PWR DOWN” terminals on the module board (See
wiring diagram).
5. Replace the display panel.
OPERATING INSTRUCTIONS
A. HEAT MODE - Initial Lighting Instructions (See Figure 11)
NOTE: During initial ring of this furnace, a burn-off of excess paint and oils
remaining from manufacturing process may cause “smoking” for 5 - 10 minutes.
NOTE: If your unit has the optional air discharge package installed, we recommend
the room air blower be operated on high (Select high fan speed).
1. Open the manual shut-off valve. The valve is fully open when the handle is
level or parallel to the gas line. Never attempt to operate unit with manual
valve partially closed.
2. Depress “System” key pad until heat lamp is illuminated.
3. Depress “Fan” key pad until desired speed lamp is illuminated.
4. Set thermostat to desired setting by depressing temperature indicating arrows
until desired temperature is displayed.
5. If the thermostat circuit is closed at the setting chosen in step 4, the ignition
sequence begins.
6. After ignition, the operation of the unit will be controlled automatically by the
thermostat.
TO SHUT DOWN FOR AN EXTENDED PERIOD OF TIME
1. Depress “System” key pad until stand by lamp is illuminated.
2. Close manual shut-off valve.
POSITION POUR GRILL
FLUX D'AIR HORIZONTAL
GRILL POSITION FOR
HORIZONTAL AIR FLOW
POSITION GRILLE POUR
FLUX D'AIR VERTICAL
GRILL POSITION FOR
VERTICAL AIR FLOW

Suburban DynaLine Owner's Manual 10/2017 Rev.1 4
SEQUENCE OF NORMAL OPERATION - HEAT MODE
1. When heat is required, the thermostat closes and energizes the combustion
air motor.
2. As the blower reaches approximately 90% of the normal RPM, the pressure
created by the combustion air motor causes the diaphragm in the pressure
switch to move, closing the contacts. This completes the electrical circuit to
the input of the module board and a 10 second warm-up period for the glo-
bar is established. During the warm up period, the glo-bar comes on for 7
seconds, then the valve opens. The glo-bar remains on another 3 seconds
after the valve opens and then goes off. When the valve opens, it will remain
open for 6 seconds. Gas will ow to the burner and be ignited by the glo-bar.
3. If the main burner ame is sensed, the burner will remain on until the
thermostat is satised. If the ame is not sensed, the gas valve closes and
the ignition sequence automatically repeated two (2) times. If the burner does
not light during this trial for ignition period, the unit will lock-out for one (1) hour
and then re-set automatically.
NOTE: If lock-out should occur, the unit can be re-set manually by breaking
the power to the unit. When power is restored, the ignition procedures can be
repeated. Should repeated lock-out occur, shut unit down and contact your gas
service agency.
4. After proof of ignition (burner lights and ame properly sensed) a circuit is
completed to the room air blower and the blower comes on.
5. When the thermostat is satised, the valve closes. The combustion air motor
will remain on for a 20 second purge cycle, then goes off. The room air blower
will continue to operate for approximately 90 seconds at which time the circuit
is opened and the room air blower goes off.
NOTE: If your unit is controlled by a wall thermostat, the ignition sequence is the
same as with built-in thermostat; however, the temperature setting and system
functions are selected at the wall thermostat. The “Fan” speed is controlled in the
same manner as with built-in thermostat.
B. COOLING MODE - Normal Operation (See Figure 11)
1. Depress “System” key pad until cool lamp is illuminated.
2. Depress “Fan” key pad until desired speed lamp is illuminated.
3. Set thermostat to desired setting by depressing temperature indicating arrows
until desired temperature is displayed.
4. If the thermostat circuit is closed at the setting chosen in Step 3, the cooling
cycle begins. NOTE: On initial start-up, the compressor will not be energized
for ve (5) minutes even though the system functions have been properly
selected.
Whenever the outside temperature is below 65° and the humidity is high, frost
could form on the evaporator coil during extended cooling operation. To eliminate
frost formation, a de-ice switch in the compressor circuit will sense a frost
condition and open the compressor circuit. Upon temperature rise, the switch
will close and the compressor will again come on provided the thermostat is still
calling for cooling.
NOTE: This unit has a built-in 5 minute delay between compressor cycles. Any
time the compressor cycle is interrupted either manually, through thermostat, a
power interruption, etc., the compressor will not restart for 5 minutes.
C. OPTIONAL CARBON MONOXIDE (CO) DETECTOR (See Figure 25)
This Dynaline unit may be equipped with an integrated carbon monoxide (CO)
detector (System Sensor Model C01224T). To access the CO detector remove the
DL front. The CO detector is located on the left side of the unit and consists of the
detector and a power supply board. See gure 25. The system connected carbon
monoxide detector known as CO1224T was tested at a National Recognized Test
Laboratory and has been veried to perform in the detection of carbon monoxide
up to 12,000 ft above sea level. During this testing by the National Recognized
Test Laboratory the detector alarmed within the time specied by ANSI/UL 2034
for carbon monoxide concentrations of 70, 150 and 400 parts per million (ppm).
CO DETECTOR TABLE 1. DETECTOR OPERATION MODES:
OPERATION
MODE GREEN LED RED LED SOUNDER
Normal (Standby) Blink 1 per minute OFF OFF
Alarm OFF Temp 4 pattern Temp 4 pattern
Alarm Test OFF Temp 4 pattern Temp 4 pattern
End of Life OFF OFF OFF
CO Trouble OFF Blink 1 per minute OFF
Power Loss / Cell
Fault OFF OFF OFF
Alarm Test: Will send alarm signal to panel.
Hush feature / Alarm Silence: The audible alarm can be silenced for 5 minutes
by pushing the button marked “Test/Hush”. The red alarm light will continue to
ash in temp 4 pattern. If carbon monoxide is still present after the 5 minute hush
period, the audible alarm will sound. The hush feature will not operate at levels
above 350 ppm carbon monoxide.
Trouble Feature: When the sensor supervision is in a trouble condition (e.g. such
as a sensor that has been tampered with, or the cell itself has prematurely dried
out due to environmental conditions, etc.), the detector will send a trouble signal
to the panel. The detector must then be replaced. The green LED turns off and
the red LED blinks every minute when the detector is in trouble.
End of Life Timer Feature: When the detector has reached the end of its life, the
trouble contact will open. This indicates that the CO sensor inside the detector
has passed the end of its life and must be replaced. This detector’s lifespan is
approximately six years from the date of manufacture. The green LED turns off
when the detector is in trouble. Periodically check the “Replace by” sticker located
under the detector cover. The detector must be replaced by this date. Order a
replacement CO Detector number 233207 from the installer of the PTAC or the
selling dealer.
CAUTION: Airborne dust particles can enter the detector. Suburban recommends
the installation of Dynaline units with System Sensor carbon monoxide detectors
after construction or any other dust producing activity.
TESTING
Detector must be tested after installation.
Test the detector as follows:
1. A test button is located on the detector housing (see Figure 25).
2. Use the tip of your nger to press and hold the test button.
3. If the sounder beeps and the LEDs light up after 1-4 seconds, the detector is
operational.
If detector fails the above test method, its wiring should be checked. If the detector
still fails after rewiring, it should be replaced.
Resetting the CO detector:
This Dynaline unit with integrated CO detector is equipped with a manual reset
button located at the plate immediately to the left of the CO detector. The manual
reset button is identied by a label on the plate. When the test/ hush button
on the CO detector is depressed the detector will audibly alarm, the green LED
will extinguish and the red LED will ash. Power to the DL gas valve will be
interrupted and the gas valve will close. Following the required test of the CO
detector, it will be necessary to depress the manual reset button to reset the CO
detector and allow the DL unit to reopen the gas valve circuit.
What to do if the carbon monoxide detector goes into alarm:
Should the CO detector go into alarm mode due to the detection of CO the power
to the gas valve will be interrupted and the gas valve will close. Do not ignore the
alarm and shutdown. Immediately move to a spot where fresh air is available,
preferably outdoors. Find a phone in an area where the air is safe and call your
building manager and ask them to have the Dynaline unit and/or other fuel burning
appliances in the dwelling checked for proper operation. Do not return to a room
or dwelling where the CO detector continues to alarm. After the cause of the
alarm is determined and corrected, it will be necessary to depress the manual
reset button to reset the CO detector and allow the DL unit to reopen the gas
valve circuit.
DETECTOR REPLACEMENT
WARNING! Remove Power before replacing detector.
This detector is manufactured with a long-life carbon monoxide sensor. Over time
the sensor will lose sensitivity, and will need to be replaced with a new System
Sensor carbon monoxide detector. This detector’s lifespan is approximately six
years from date of manufacture. Periodically check the detector’s replacement
date. Using a small, at screw driver, push in the small tab located on the
underside of the detector. Once the snap is loosened, lift the bottom end of the
cover up and unhinge the top to remove the cover. With the cover removed
removed, refer to the sticker placed on the inside of the detector. The sticker
will indicate the date that the detector shall be replaced. This detector is also
equipped with a feature that will open the trouble relay once it has reached the
end of its useful life. If this occurs, it is time to replace the detector.
CAUTION: This carbon monoxide detector is designed for indoor use only. Do
not expose to rain or moisture. Do not knock or drop the detector. Do not open
or tamper with the detector as this could cause malfunction. The detector will not
protect against the risk of carbon monoxide poisoning if not properly wired. The
detector will only indicate the presence of carbon monoxide gas at the sensor.
Carbon monoxide gas may be present in other areas.
This carbon monoxide detector is NOT:
• Designed to detect smoke, re or any gas other than carbon monoxide
• To be seen as a substitute for the proper servicing of fuel-burning appliance or
the sweeping of chimneys
• To be used on an intermittent basis, or as a portable alarm for the spillage of
combustion products from fuel-burning appliances or chimneys.
Carbon monoxide gas is a highly poisonous gas which is released when fuels are
burnt. It is invisible, has no smell and is therefore impossible to detect with the
human senses. Under normal conditions in a room where fuel burning appliances
are well maintained and correctly ventilated, the amount of carbon monoxide
released into the room by appliances should not be dangerous.

5 Suburban DynaLine Owner's Manual 10/2017 Rev.1
LIMITATIONS OF CARBON MONOXIDE (CO) DETECTORS
Manufacturer recommends that carbon monoxide (CO) detectors be located
throughout a protected premise following the recommendations of the current
edition of the National Fire Protection Association Standard 720, National Fire
Alarm Code (NFPA 720), manufacturer's recommendations, and state and local
codes. While carbon monoxide detectors are designed to provide warning against
carbon monoxide, they do not guarantee warning or protection against carbon
monoxide. Any alarm system with carbon monoxide detectors is subject to
compromise or failure to warn for a variety of reasons. For example:
• Molecules of carbon monoxide may not reach the sensing chambers of the
carbon monoxide detector because:
- Barriers such as closed or partially closed doors, walls, or chimneys may
inhibit ow.
- Molecules of carbon monoxide may be blown away from detectors by air
outlets.
In general, carbon monoxide detectors on one level of a structure cannot be
expected to sense carbon monoxide developing on another level.
• The amount of carbon monoxide present may be insufcient to alarm carbon
monoxide detectors. Carbon Monoxide detectors are designed to alarm at
various levels of carbon monoxide density, or ppm (parts per million). If such
ppm levels are not created by developing carbon monoxide at the location of
detectors, the detectors will not go into alarm.
• Carbon monoxide detectors are subject to false alarms and nuisance
alarms. For example, a carbon monoxide detector located too close to a
fuel burning appliance may go into nuisance alarm during normal operation
of the appliance. If the location of a carbon monoxide detector causes an
abundance of false alarms or nuisance alarms, do not disconnect the
carbon monoxide detector; call a professional to analyze the situation and
recommend a solution.
• Warning devices (including horns, sirens, bells, and sounders on carbon
monoxide detectors) may not alert people or wake up sleepers who are
located on the other side of closed or partially open doors. A warning device
that activates on a different oor or level of a dwelling or structure is less likely
to awaken or alert people. Even persons who are awake may not notice the
warning if the alarm is mufed by noise from a stereo, radio, air conditioner or
other appliance, or by passing trafc. Audible warning devices may not alert
the hearing-impaired (strobes or other devices should be provided to warn
these people). Any warning device may fail to alert people with a disability,
deep sleepers, people who have recently used alcohol or drugs, or people on
medication or sleeping pills.
Please note that:
i) Strobes can, under certain circumstances, cause seizures in people with
conditions such as epilepsy.
ii) Carbon monoxide detectors may be installed as part of a re alarm system.
Studies have shown that certain people, even when they hear a re alarm
signal, do not respond or comprehend the meaning of the signal. It is
the property owner's responsibility to conduct re drills and other training
exercises to make people aware of re alarm signals and instruct on the
proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or
permanent hearing loss.
• Telephone lines needed to transmit alarm signals from a premises to a
central station may be out of service or temporarily out of service. For
added protection against telephone line failure, backup radio transmission
systems are recommended.
• System components, though designed to last many years, can fail at any
time. As a precautionary measure, it is recommended that carbon monoxide
detectors be checked, maintained, and replaced per manufacturer's
recommendations.
• System components will not work without electrical power. If system
batteries are not serviced or replaced regularly, they may not provide battery
backup when AC power fails.
• Environments with high air velocity or that are dusty or dirty require more
frequent maintenance.
In general, re alarm systems with carbon monoxide detectors will not work
without power and will not function properly unless they are maintained and tested
regularly.
D. OPERATING TIPS - HEAT MODE OR COOLING MODE
1. At times it may be desirable to reduce the operating sound level. This is
possible by selecting “Low Cool” position. At this setting, the cooling capacity
is not reduced - only the blower speed and air movement is reduced.
2. Circulation of room air with no heat or cooling may be obtained if desired.
For fan only operation, depress “System” key pad until fan only lamp is
illuminated. Depress “Fan” key pad until desired speed lamp is illumintaed.
UNIT CONTROLS AND THEIR FUNCTION
Limit Switch - The purpose of the limit control is to turn off the gas to the main
burner if, for any reason, the heating section of the unit becomes hotter than that
which is safe. Cycling on limit does not always indicate a defective limit switch.
If the circulating air is blocked or only partially so, the limit control will function
and cause the main burner to go off. Cycling on limit is not always undesirable
- if it happens only occasionally. This is a good indication of safe operation and
will most likely happen on a warm day. If cycling happens too often or for an
extended period, the circulating air system should be thoroughly cleaned. (See
“Maintenance and Cleaning.”)
If for any reason, the limit switch is found to be defective, it must be replaced.
There is no recommended method of repairing it. Because of the importance of
the limit switch, for safety reasons, never shunt the limit switch - even for only
temporary operation.
Pressure Switch - The purpose of the pressure switch is to sense the air
pressure generated by the combustion air blower. When the pressure is adequate
to support combustion, the contacts in the switch close. This completes the
circuit to the input of the module board and the ignition sequence begins. If for
some reason the pressure is not sufcient to support combustion, the switch
will not operate. Reasons for insufcient pressure: 1) slow combustion air motor
2) restriction in intake and 3) loose pressure switch tube or a blockage in the
pressure switch tubing.
Fresh Air Vent - The purpose of the fresh air vent is to provide a means of
introducing outside air into the living. The control rod is located in the lower left
front corner of the unit. To gain access to the control rod, the cabinet front must be
pivoted forward. (See Figure 13).
NOTE: Operating the unit with the vent open could reduce efciency of the unit in
both heat and cooling modes.
Overload Protection - These units are equipped with an electrical safety overload
which stops the compressor in the event of electrical overload. If repeated
overload cycling occurs, call your dealer or a local repair agency equipped to
service air conditioning equipment.
REMOVING UNIT FOR SERVICE
1. Shut off gas supply to unit.
2. Break electrical circuit to unit at fuse box if wired permanently. Disconnect
wiring in junction box on unit. If service cord is used, unplug from wall
receptacle.
3. Disconnect inlet gas line to unit.
4. Disconnect thermostat wiring at terminal block on module board, if unit is
wired for remote thermostat.
5. Pull unit from wall case.
6. To reinstall, reverse above procedure.
7. Check gas connections for leaks using a soap and water solution. Do not use
an open ame to check for leaks. Correct any gas leaks immediately.
PREVENTIVE MAINTENANCE
WARNING! If the user of this appliance fails to maintain it in the condition in which it was
shipped from the factory or if the appliance is not used solely for its intended purpose or if
appliance is not maintained in accordance with the instructions in this manual, then the risk
of a re and/or the production of carbon monoxide exists which can cause personal injury,
property damage or loss of life.
IMPORTANT: Always verify proper operation after servicing.
WARNING! Always disconnect electrical supply before cleaning unit or performing any
maintenance.
The unit should be inspected by a qualied service person yearly before turning
the unit on heat for the winter. Particular attention should be given to the following:
1. Inspect all gaskets. If any gaskets show signs of leakage or deterioration, they
must be replaced. Safe operation of the unit depends on all gaskets being
tight.
2. Inspect combustion chamber and venting to assure that these components
are physically sound without holes or excessive corrosion. Replace if found to
be defective.
3. Inspect exhaust and intake for restrictions and for adequate sealing of any
mating parts. (See “Minimum Outside Clearances”.)
WARNING! It is imperative that the products of combustion be properly vented to the
outside atmosphere and that all combustion air supplied to the burner be drawn from the
outside atmosphere.
4. Check outside grille to be sure it is clean and free of any obstructions.
5. Check the control compartment, burner and circulating air passageways of
the unit. These areas must be kept clean. NOTE: More frequent cleaning may
be required due to excessive lint from carpeting, bedding material, etc.
6. Check burner for proper operation. A proper ame will have a blue inner cone
with well dened pattern and an orange outer cone with slightly yellow tips.
A ame that is yellow in appearance with an erratic ame pattern indicates a
restriction in the air supply. Shut the unit down and have the burner and air
passage ways checked and cleaned as needed. The surface of the burner
and each burner port should be cleaned with a steel wire brush and blown
clean using compressed air. (See Figure 16 for illustration of a correct and
incorrect burner ame.)
7. Check all gas connections and gas controls (electrical valves, manual shut-off
valves, regulators, etc.) for leaks.
8. This inspection should include a complete operational check of the unit
including all electrical and mechanical components. NOTE: If cabinet front
was removed in order to inspect the unit and controls, it must be reinstalled
prior to operating the unit.

Suburban DynaLine Owner's Manual 10/2017 Rev.1 6
You as the owner/user should inspect the unit periodically during the
heating season. Particular attention should be given to the following:
A. Periodically observe the main burner ame to assure it is burning with a hard
blue ame with well-dened burner ports. (See Figure 16.) If ame appears
yellow or burner has a lazy ame, shut furnace down and contact a qualied
service person.
B. Periodically inspect the vent for obstructions or presence of soot. Soot is
formed whenever combustion is incomplete. This is your visual warning that
the furnace is operating in an unsafe manner. If soot is present, immediately
shut furnace down and contact your dealer or a qualied service person.
C. Circulating air through the front grille must not be blocked. Keep lter clean to
assure adequate air ow.
The removable, washable type lter should be cleaned or replaced several
times during the year. This will depend upon the usage and location of the unit.
Dirty lters restrict air ow across the heat exchanger and coils. This results
in inadequate cooling and shortens the life expectancy of the heat exchanger,
motors and compressor.
FILTER REMOVAL
1. The lter is located behind the cabinet front. Remove cabinet front by lifting
up. Slide lter up until free of left tab.
2. Filter may be washed in a soapy solution and rinsed in clear water. Let lter
dry before reinstalling it on the unit.
3. Reinstall lter.
NOTE: NEVER OPERATE UNIT WITH FILTER REMOVED. Evaporator coil and/
or drain pan may become restricted.
4. Reinstall cabinet front.
CLEANING CONDENSER COIL
NOTE: Work should be performed by a qualied service person.
NOTE: Use a coil cleaner recommended by one of these manufacturers:
Nu Calgon, Rector Seal
NOTE: Make sure gas and electrical supply is "OFF to unit.
1. Remove cabinet front. Remove four(4) screws from left and right side panels;
set aside for reinstallation.
2. Remove unit from wall sleeve.
3. After unit is removed, move to an open area.
4. To begin process of cleaning the condenser coil, remove the following screws:
a) Remove four(4) screws from condenser housing braces. (see A gure 17)
Set braces aside for reinstallation.
b) Remove condenser coil cover- (2) additional screws. (see B gure 17) Set
aside for reinstallation.
5. Motor should be covered during cleaning.
6. Be sure to follow the manufacturers instructions in the use and disposal of
their products.
7. Apply the cleaning solution to the coil by trickle method across the top of the
coil until solution runs from drain.
8. The coil can then be cleaned with a water hose by back washing it until all dirt
is drained from weep holes in the chassis. Unit should be tilted back so water
will drain to the back. Allow unit to air dry.
9. Reassemble condenser coil cover and braces.
10. Reinstall unit into wall sleeve.
11. Reinstall cabinet front.
NOTE: After unit is reinstalled, check for gas leaks and verify proper operation in
heat and A/C modes.
Listed below are several safety related items that you should follow during the
heating season to assure continued safe operation of the furnace.
1. Never operate the unit if you smell gas. Do not assume that the smell of gas is
normal. Any time you detect the odor of gas, it is to be considered life threatening
and corrected immediately. (See safety notice on front cover of this manual.)
2. Immediately shut unit down and call a service agency if unit cycles erratically
or delays on ignition.
WARNING! Should overheating occur, or the gas supply fail to shut off, shut off the
manual gas valve to the appliance before shutting off the electrical supply.
3. Do not restrict the ow of combustion air or the warm air circulation to the unit.
To do so could cause personal injury and/or death.
WARNING! Do not install screens over the vent for any reason. Screens will become
restricted and cause unsafe furnace operation.
4. Keep unit clean. More frequent cleaning may be required due to excessive lint
from carpeting, bedding material, etc. It is imperative that control compartments,
burners and circulating air passageways of the appliance be kept clean.
5. Keep the furnace area clear of any combustible materials, gasoline or other
ammable vapor and liquids.
6. Do not use this appliance if any part has been submerged under water.
Immediately call a qualied service technician to inspect the appliance and
to replace any part of the control system and any gas control that has been
submerged under water.
7. Always follow the operating instructions. Do not deviate from the step-by-step procedures.
8. Never attempt to repair damaged parts. Always have them replaced by a
qualied service agency.
9. Never attempt to repair the furnace yourself. Seek the help of a qualied service person.
10. The room air motor, the condenser motor and the combustion air motor are
maintenance free motors and require no oiling.
GENERAL NOTES
The efciency rating of this unit is a product thermal efciency rating determined
under continuous operating conditions and was determined independent of any
installed system.
Children and adults should be alerted to the hazards of high surface
temperatures and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same
room as the unit.
Clothing or other ammable material should not be placed on or near
the unit.
Any safety screen or guard removed for servicing the unit must be
replaced prior to operating the unit.
Installation and repairs should be done by a qualied service person.
The appliance should be inspected before use and at least annually by a
qualied service person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It is imperative that
control compartments, burners and circulating air passageways of the
appliance be kept clean.
Never operate unit with lter removed. Evaporator coil and/or drain pan
may become restricted.
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 PSIG or Less and a Pressure Drop of 0.3 Inch Water Column
(Based on a 0.60 Specic Gravity Gas)
Nominal
Iron Pipe
Size, in Inches
Internal
Diameter,
in Inches
LENGTH OF PIPE, Feet
10 20 30 40 50 60 70 80 90 100 125 150 175 200
1/4 .364 32 22 18 15 14 12 11 11 10 9 8 8 7 6
3/8 .493 72 49 40 34 30 27 25 23 22 21 18 17 15 14
1/2 .622 132 92 73 63 56 50 46 43 40 38 34 31 28 26
3/4 .824 278 190 152 130 115 105 96 90 84 79 72 64 59 55
11.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100
1 - 1/4 1.380 1,050 730 590 500 440 400 370 350 320 305 275 250 225 210
1 - 1/2 1.610 1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320
22.067 3,050 2,100 1,650 1,450 1,270 1,150 1,050 990 930 870 780 710 650 610
2 - 1/2 2.469 4,800 3,300 2,700 2,300 2,000 1,850 1,700 1,600 1,500 1,400 1,250 1,130 1,050 980
33.068 8,500 5,900 4,700 4,100 3,600 3,250 3,000 2,800 2,600 2,500 2,200 2,000 1,850 1,700
44.025 17,500 12,000 9,700 8,300 7,400 6,800 6,200 5,800 5,400 5,100 4,500 4,100 3,800 3,500
TABLE 2

7 Suburban DynaLine Owner's Manual 10/2017 Rev.1
16
42
4
1"
4
1" MIN.
MIN.
HEADER
(STEEL LINTEL IN BRICK CONSTRUCTION)
SURFACE OF FINISHED FLOOR
WALL SLEEVE FRAMING DIMENSIONS
REAR GAS HOOK-UP
Figure 2
CABINET FRONT
REAR GRILL
SLEEVE
CHASSIS
CHASSIS
SLEEVE
VENT CAP ASSEMBLY
REAR VIEW
SIDE VIEW
42"
14 3
4"
16"
11
16 "
3
8"
725
32 "
22 29
32 "
513
32 "
37
8"
UNIT OVERALL DIMENSIONS
Figure 1

Suburban DynaLine Owner's Manual 10/2017 Rev.1 8
NOTE: UNITS APPROVED FOR 0" CLEARANCE TO COMBUSTIBLE CONSTUCTIONS TOP, SIDES, AND BOTTOM. FRONT AND REAR CLEARANCE
NOT APPLICABLE AS THERE CAN BE NO CONSTRUCTION COMBUSTIBLE OR NON-COMBUSTIBLE TO THE FRONT OR REAROF THE OPENING.
WALL SLEEVE FRAMING DIMENSIONS
FRONT GAS HOOK-UP
16
42
4
1"
4
1" MIN.
MIN.
HEADER
(STEEL LINTEL IN BRICK CONSTRUCTION)
FINISHED FLOOR
32
1" MIN.
SUB-FLOOR
Figure 3
GASKET
NOTCH FOR OPTIONAL
REARGAS HOOKUP
BE SURE DRAIN
HOLES ARE TO
OUTSIDE REAR
FRONT
SLEEVE TOP
INSERT SIDES BETWEEN TOP FLANGE
AND RETAINING ANGLE
SLEEVE BOTTOM AND SIDES
Figure 4
BIRD GUARD
SCREW #8 X 1/2
Figure 4A
SLOPE DOWN TO THE OUTSIDE
1"
4
SURFACE OF FINISHED
FLOOR OR TOP OF CARPET
1 MIN. (PROJECTION BEYOND EXTERIOR WALL)
5"
8
Y"
X"
MOUNTING HOLES AND SCREWS
(BY INSTALLER.)
DO NOT PUT HOLES THROUGH
WALL SLEEVE BOTTOM!
REAR GRILLE
CAULK AROUND WALL SLEEVE
SURFACE OF FINISHED EXTERIOR WALL
Y" = 14 - ( X" + 1 )
3"
48
5"
SURFACE OF FINISHED INTERIOR WALL
CABINET FRONT
X" REPRESENTS EITHER THE
DIMENSION REQUIRED TO FLUSH
SLEEVE TO FINISHED TRIM OR
MOLDING, OR THE DISTANCE
SLEEVE PROJECTS INTO ROOM
BEYOND FINISHED INTERIOR
WALL.
NOTE: X" CAN BE 0" IF
SLEEVE IS FLUSH WITH
FINISHED INTERIOR WALL.
WALL INSTALLATION
REAR GAS HOOKUP
Figure 5

9 Suburban DynaLine Owner's Manual 10/2017 Rev.1
SLOPE DOWN TO THE OUTSIDE
1"
4
SURFACE OF FINISHED
FLOOR OR TOP OF CARPET
MIN. (PROJECTION BEYOND EXTERIOR WALL)
1"
4
3 (MIN.)
1"
2
Y"
X"
MOUNTING HOLES AND SCREWS
(BY INSTALLER.)
DO NOT PUT HOLES THROUGH
WALL SLEEVE BOTTOM!
REAR GRILLE
CAULK AROUND WALL SLEEVE
SURFACE OF FINISHED EXTERIOR WALL
Y" = 14
SURFACE OF FINISHED INTERIOR WALL
CABINET FRONT
X" REPRESENTS EITHER THE
DIMENSION REQUIRED TO FLUSH
SLEEVE TO FINISHED TRIM OR
MOLDING, OR THE DISTANCE
SLEEVE PROJECTS INTO ROOM
BEYOND FINISHED INTERIOR
WALL.
NOTE: X" CAN BE 0"
IF SLEEVE IS FLUSH
WITH FINISHED
INTERIOR WALL.
4- ( X" + )
4
3 1
WALL INSTALLATION
FRONT GAS HOOKUP
Figure 6
CAULK (MUST BE WATER TIGHT).
DRAIN TUBE ASSEMBLY INSTALLED
UNDERNEATH WALL SLEEVE
NOTE: FOR THIS TYPE INSTALLATION,
WALL SLEEVE MUST EXTEND BEYOND
WALL A MINIMUM OF 1 1/8".
LOCATE DRAIN IN
BOTTOM OF WALL
SLEEVE. MUST BE
TO THE EXTERIOR
SIDE OF BUILDING.
AT DESIRED LOCATION
MARK AND DRILL ONE
9/16" DIA. HOLE AND
TWO 1/8" DIA. HOLES
AS ILLUSTRATED.
CAULK (MUST BE WATER TIGHT).
PRIMARY DRAIN HOLES FOR
CONDENSATE DRAINAGE TO
BUILDING EXTERIOR WHEN
USING ACCESSORY DRAIN KITS.
NOT
DRAIN TUBE ASSEMBLY INSTALLED
ON REAR FLANGE OF WALL SLEEVE
Figure 7
SIDE VIEW
1"
4SLOPE DOWN TO
THE OUTSIDE
LEVELING LEGS
CABINET FRONT
WALL SLEEVE
SURFACE OF FINISHED FLOOR
OR TOP OF CARPET
5" MAX./3 1/2" MIN.
(1) INSTALL UNIT IN WALL AS DESCRIBED IN INSTALLATION MANUAL.
(2) POSITION LEVELING LEG--ONE ON EACH SIDE OF WALL SLEEVE
AND LOCATE FOUR (4) MOUNTING HOLES.
(3) DRILL FOUR 1/8" DIA. HOLES AND MOUNT LEGS USING #10 X 1/2" SCREWS PROVIDED.
(4) LEVEL UNIT BY ADJUSTING SCREW IN LEG.
FRONT VIEW
LEVELING LEGS INSTALLATION
Figure 8

Suburban DynaLine Owner's Manual 10/2017 Rev.1 10
SLOPE DOWN TO THE OUTSIDE
1"
4
SURFACE OF FINISHED
FLOOROR TOP OF CARPET
MIN. (PROJECTIONBEYOND WALL)
1"
4
3(MIN.)
1"
2
CABINET FRONT
WALL SLEEVE
2 (MIN.) SUPPORTS
(BY INSTALLER)
WALL SLEEVE ANGLES & SCREWS
(BY INSTALLER.)
DO NOT PUT HOLES THROUGH OR DRIVE
SCREWS INTO WALL SLEEVE BOTTOM!
REARGRILLE
CAULK AROUND WALL SLEEVE
WINDOW OR WALL
(MAX.) LONG SCREWS FOR SECURING
ANGLES TO TOP & SIDES OF SLEEVE.
2
1"
WINDOW, CURTAIN WALL, OR WALL PANEL INSTALLATION
Figure 9
CENTER LINE LOCATION FOR REAR GAS
CONNECTION
CENTER LINE LOCATION FOR
ELECTRICAL CONNECTION ON
UNIT WHEN INSTALLED INTO
WALL SLEEVE
WALL SLEEVE (OUTLINE)
UNIT (OUTLINE)
CENTER LINE LOCATION FOR FRONT GAS CONNECTION
WHEN INSTALLED INTO WALL SLEEVE
FRONT SURFACE
OF WALL SLEEVE
7 3/4"
5 5/8"
1 9/16"
5"
2 9/64"
TOP VIEW
SIDE VIEW
1/4"
Figure 10
CONTROL ROD
(FRESH AIR VENT)
DISPLAY PANEL
WARMER
LOW
HIGH
FAN
SYSTEM
FANONLY
COOL
HEAT
STANDBY
SETCOOLER
Figure 13
FAN
LOW
HIGH
STANDBY
SYSTEM
COOL
FAN ONLY
HEAT
SET
COOLER
WARMER
Figure 11
R
C
G
Y
W
12
O
N
REMOTE THERMOSTAT TERMINAL BLOCK
MODULE BOARD (LOCATED
ON CONTROL PANEL)
THERMOSTAT SWITCH: SLIDE #1 SWITCH
TO "ON", SWITCH #2 REMAINS IN "OFF"
POSITION
NOTE: THERE IS A 5/8" HOLE IN THE BASE NEAR THE JUNCTION BOX FOR ROUTING THE WIRING
FOR REMOTE THERMOSTAT. THE 5/8" STRAIN RELIEF BUSHING PROVIDED IN THE PACK-OUT BAG
SUPPLIED WITH THE UNIT MUST BE USED TO SECURE THE THERMOSTAT WIRING FOR
REMOTE THERMOSTAT.
Figure 12

11 Suburban DynaLine Owner's Manual 10/2017 Rev.1
WITH CARBON MONOXIDE DETECTOR
Figure 14b
WITHOUT CARBON MONOXIDE DETECTOR
Figure 14a
WITHOUT CARBON MONOXIDE DETECTOR
Figure 15a
81856
L2
L1
COMPRESSOR
CONTACT
COMPRESSOR
L1
10
5
COMPRESSOR
RELAY
8
1HI-LIMIT
2
11
PRESSURE
7
4
CONDENSOR
MOTOR
TEMP. SENSE
LO HI
AIR
MOTOR
ROOM
POWER
EMERGENCY
12
3
EXHAUST
MOTOR
230V
6
9
FLAME PROBE
ROCKER SWITCH
208VAC
230VAC
SW.
FLUE LIMIT
G
230V
120V
IGNITOR
208V
208V
GAS VALVE
GAS VALVE
DE-ICER
SWITCH
PRESSURE
CONTROLLER
SWITCH N.C.
IGNITOR
RELAY
IGNITOR CONTACT
DE-ICER
SWITCH
PRESSURE
CONTROLLER
SWITCH N.C.
81873
L2
L1
COMPRESSOR
CONTACT
COMPRESSOR
L1
10
5
COMPRESSOR
RELAY
8
1HI-LIMIT
2
11
PRESSURE
7
4
CONDENSOR
MOTOR
TEMP. SENSE
LO HI
AIR
MOTOR
ROOM
POWER
EMERGENCY
12
3
EXHAUST
MOTOR
24V.
230V
6
9
FLAME PROBE
ROCKER SWITCH
208VAC
230VAC
SW.
FLUE LIMIT
G
24VAC
GND
CONT
GAS
VALVE
POWER SUPPLY BOARD
BL
Y
CO DETECTOR
BL
Y
BK
GY
R
BL
T
T
NC
C
T
C
A
NO
(+)
(-)
(+)
(-)
230V
120V
IGNITOR
208V
208V
GAS VALVE
GAS VALVE
IGNITOR
RELAY
CONTACT
CO DETECTOR
IGNITOR CONTACT
O
C
S
BR Y
R
Y
COMPRESSOR
MOTOR
BR
ROOM AIR
BR
BK EXHAUST
MOTOR BK MOTOR
BR BR
24
3
1
IGNITOR
10
11
12
7
8
9
4
5
6
1
2
3
TRANSFORMER
24V
1L
TERM.
BLOCK
L 2
BK
BK
R
PRESSURE
HI LIMIT
SW. N.C. SW. N.O.
VALVE
O
TEMP. SENSE
BK
BK
W
W
Y
Y
BK
BL
Y
BK
Y
R
R
R
R
BR
BR
BK
BK
COMPRESSOR
RELAY
Y
Y
L2
R
BK
L1
WHITE
YELLOW
BROWN
BLACK
RED
BLUE
ORANGE
COLOR
R
W
Y
BR
BL
BK
CODE
O
FLAME
CONDENSER
BK
BL
MODULE
BOARD O
BR
1234
(BUILT-IN T-STAT)
PROBE
O
DE-ICER
SW.
R
R
BK
NOTE: ALL WIRES ARE 18 A.W.G. UNLESS
OTHERWISE SPECIFIED.
MAXIMUM RATING OF SUPPLY CIRCUIT
PROTECTIVE DEVICE 15 AMPS.
IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH
THE APPLIANCE MUST BE REPLACED, IT MUST BE
REPLACED WITH TYPE 105ĀC WIRE OR TYPE 150ĀC
WIRE WHERE SPECIFIED OR ITS EQUIVALENT.
105ĀC THERMOPLATIC 14 A.W.G. WIRE
TGS 200°C 18GA STRANDED TEFLON COATED
N.C.
FLUE LIMIT
R
HIGH LOW L1 COMB COND
BLWR
FLAME
DOWNPWR
FAN
MED
BK
BK
Y
R
C 208 230
208/230 V.A.C. WIRING DIAGRAM
TRANSFORMER
120V
W/BK
W
BK
BK
R
BK
OBK
PRESSURE
SW. N.C.
81857
BK
BK
R
R
W/BK WHITE/BLACK
24
3
1
BL
BL
W
W
BK
IGNITOR
RELAY
BK
ROCKER
SWITCH
BK
BL
R
R
O
O
C 208 230
G

Suburban DynaLine Owner's Manual 10/2017 Rev.1 12
C
S
BR Y
R
Y
COMPRESSOR
MOTOR
BR
ROOM AIR
BR
BK EXHAUST
MOTOR BK MOTOR
BR BR
24
3
1
IGNITOR
10
11
12
7
8
9
4
5
6
1
2
3
TRANSFORMER
24V
1L
TERM.
BLOCK
L 2
BK
BK
R
PRESSURE
HI LIMIT
SW. N.C. SW. N.O.
VALVE
O
TEMP. SENSE
BK
BK
W
W
Y
Y
BK
BL
Y
BK
Y
R
R
R
R
O
BR
BK
BK
COMPRESSOR
RELAY
Y
Y
L2
R
BK
L1
WHITE
YELLOW
BROWN
BLACK
RED
BLUE
ORANGE
COLOR
R
W
Y
BR
BL
BK
CODE
O
FLAME
CONDENSER
BK
BL
MODULE
BOARD
O
BR
1234
(BUILT-IN T-STAT)
PROBE
O
DE-ICER
SW.
R
R
BK
NOTE: ALL WIRES ARE 18 A.W.G. UNLESS OTHERWISE SPECIFIED.
MAXIMUM RATING OF SUPPLY CIRCUIT PROTECTIVE DEVICE 15 AMPS.
IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THE APPLIANCE MUST BE
REPLACED, IT MUST BE REPLACED WITH TYPE 105ĀC WIRE OR TYPE 150ĀC WIRE
WHERE SPECIFIED OR ITS EQUIVALENT.
105ĀC THERMOPLATIC 14 A.W.G. WIRE
TGS 200°C 18GA STRANDED TEFLON COATED
N.C.
FLUE LIMIT
R
HIGH LOW L1 COMB COND
BLWR
FLAME
DOWNPWR
FAN
MED
BK
BK
Y
R
C 208 230
TRANSFORMER
120V
W/BK
W
BK
BK
R
BK
OBK
PRESSURE
SW. N.C.
81872
BK
BK
R
R
W/BK WHITE/BLACK
24
3
1
BL
BL
W
W
BK
IGNITOR
RELAY
BK
ROCKER
SWITCH
BK
BL
R
R
O
O
24VAC
GND
CONT
GAS
VALVE
POWER SUPPLY BOARD CO DETECTOR
BL
Y
BK
GY
R
BL
T
T
NC
C
T
C
A
NO
(+)
(-)
(+)
(-)
BR
BL
BL
Y
Y
BR
O
4
3
2
1
BL
O
O
Y
GREY
GY
LOCKING
CONNECTOR
C 208 230
G
CHAMBER
BURNER
CORRECT FLAME
BURNER OBSERVATION
WINDOW
ORANGE OUTER CONE
WELL DEFINED PATTERN
BURNER
CHAMBER
INCORRECT FLAME
BURNER OBSERVATION
WINDOW
YELLOW OUTER FLAME
ERRATIC PATTERN
ORANGE, YELLOW INNER FLAME
ERRATIC PATTERN
CHAMBER
BURNER
CORRECT FLAME
BURNER OBSERVATION
WINDOW
ORANGE OUTER CONE
WELL DEFINED PATTERN
BURNER
CHAMBER
INCORRECT FLAME
BURNER OBSERVATION
WINDOW
YELLOW OUTER FLAME
ERRATIC PATTERN
ORANGE, YELLOW INNER FLAME
ERRATIC PATTERN
REMOVE (4) STICKERS FROM BRACES
& REMOVE BRACES
RETIRER LES QUATRE (4) VIS DES
SUPPORTS ET RETIRER LES SUPPORTS
REMOVE (2) SCREWS & REMOVE
CONDENSER COVER
RETIRER LES DEUX (2) VIS ET RETIRER
LE COUVERCLE DU CONDENSEUR
A
B B
WITH CARBON MONOXIDE DETECTOR
Figure 15b
Figure 16
Figure 17

13 Suburban DynaLine Owner's Manual 10/2017 Rev.1
OPERABLE
FIXED
CLOSED FIXED
CLOSED
INSIDE
CORNER DETAIL
G
OPERABLE
A
C
FB
B
B
B
A
J
B
I
H
MK
E
D
L
B
VENT TERMINAL AIR SUPPLY INLET
XAREA WHERE TERMINAL IS NOT PERMITTED
A=
CLEARANCE ABOVE GRADE,
VERANDA, PORCH, DECK, OR
BALCONY
12 INCHES (30cm)
(SEE NOTE a)
12 INCHES (30cm)
(SEE NOTE a)
J= CLEARANCE TO NONMECHANICAL
AIR SUPPLY INLET TO BUILDING
OR THE COMBUSTION AIR INLET
TO ANY OTHER APPLIANCE.
CANADIAN INSTALLATIONS US INSTALLATIONS
1 2
6 INCHES (15cm) FOR
APPLIANCES< 10,000 Btuh (3kw),
12 INCHES (30cm) FOR
APPLIANCES> 10,000 Btuh (3kw)
AND< 100,000 btuh (30kw)
6 INCHES (15cm) FOR APPLIANCES
<10,000 Btuh (3kw),
9 INCHES (23cm) FOR APPLIANCES
>10,000 Btuh (3kw) AND< 50,000
Btuh (15kw)
12 INCHES (30CM) FOR
APPLIANCES> 50,000 Btuh (15kw)
B=
CLEARANCE TO WINDOW OR
DOOR THAT MAY BE OPENED
6 INCHES (15cm) FOR
APPLIANCES <10,000 Btuh (3kw),
12 INCHES (30cm) FOR
APPLIANCES > 10,000 Btuh (3kw)
AND < 100,000 btuh (30kw)
CANADIAN INSTALLATIONS US INSTALLATIONS
1 2
6 INCHES (15cm) FOR APPLIANCES
<10,000 Btuh (3kw),
9 INCHES (23cm) FOR APPLIANCES>
10,000 Btuh (3kw) AND< 50,000
btuh (15kw)
12 INCHES (30CM) FOR APPLIANCES>
50,000 Btuh (15kw)
K= CLEARANCE TO A MECHANICAL
AIR SUPPLY INLET 6 FEET (1.83m) 3 FEET (91cm) ABOVE IF WITHIN 10FEET
(3m) HORIZONTALLY
C=
CLEARANCE TO WINDOW OR
DOOR THAT MAY BE OPENED
* a * a
L= CLEARANCE ABOVE PAVED
SIDEWALK OR PAVED DRIVEWAY
LOCATIED ON PUBLIC PROPERTY
7 FEET (2.13m)
* a
D=
VERTICAL CLEARANCE TO
VENTILATED SOFFIT LOCATED
ABOVE THE TERMINAL WITHIN A
HORIZONTAL DISTANCE OF 2 FEET
(61cm) FROM THE CENTER LINE
OF THE TERMINAL
* a * a
M= CLEARANCE UNDER VERANDA,
PORCH, DECK, OR BALCONY 12 INCHES (30cm)
* a
E=
CLEARANCE TO UNVENTILATED SOFFIT
* a * a
F=
CLEARANCE TO OUTSIDE CORNER
* a * a
G=
CLEARANCE TO INSIDE CORNER
* a * a
H=
CLEARANCE TO EACH SIDE OF
CENTER LINE EXTENDED ABOVE
METER / REGULATOR ASSEMBLY
3 FEET (91cm) WITHIN A HEIGHT 15 FEET
(4.5m) ABOVE THE METER / REGULATOR
ASSEMBLY
* a
I=
CLEARANCE TO SERVICE
REGULATOR VENT OUTLET
3 FEET (91cm) * a
1IN ACCORDANCE WITH THE CURRENT CSA B149.1, NATURAL GAS AND PROPANE INSTALLATION CODE
2IN ACCORDANCE WITH THE CURRENT ANSI Z223.1/NFPA 54, NATIONAL FUEL GAS CODE
A VENT SHALL NOT TERMINATE DIRECTL ABOVE A SIDEWALK OR PAVED DRIVEWAY THT IS LOCATED BETWEEN TWO SINGLE
FAMILY DWELLINGS AND SERVES BOTH DWELLINGS
PERMITTED ONLY IF VERANDA, PORCH, DECK, OR BALCONY IS FULLY OPEN ON A MINUMUM OF TWO SIDES
BENEATH THE FLOOR.
FOR CLEARANCES NOT SPECIFIED IN ANSI Z223.1/NFPA 54 OR CSA B149.1, ONE OF THE FOLLOWING SHALL BE
INDICATED:
*
A REFERENCE TO THE FOLLOWING FOOTNOTE:
"CLEARANCE IN ACCORDANCE WITH LOCAL INSTALLATION CODES AND THE REQUIREMENTS OF THE GAS SUPPLIER AND
MANUFACTURERS INSTALLATION INSTRUCTIONS (SEE MANUAL SUPPLIED WITH APPLIANCE)
a)

Suburban DynaLine Owner's Manual 10/2017 Rev.1 14
OPTIONAL ACCESSORIES
ALUMINUM GRILLE
STOCK NO. 1625
INTRODUCTION
The grille was specially designed for the DL3 Dynaline. Do not attempt to bend
or alter the design of the grille or the venting system of the Dynaline unit.
The grille will also work, as designed, for those models with rear gas hook-up.
IMPORTANT: Installation of the rear grille must be made prior to installing
the chassis as it secures from inside the wall sleeve.
ARCHITECTURAL STYLE GRILLES
NATURAL FINISH ALUMINUM GRILLE
STOCK NO. 1420
DARK BRONZE FINISH GRILLE
STOCK NO. 1418
INTRODUCTION
These architectural grilles are designed to be used as an optional/alternate for
the standard aluminum grille #1625. They are to be installed so that the angle
of the grille is in the downward position. Remember, these are special grilles.
Do not attempt to bend or alter the design of the grille, the venting system or the
Dynaline unit.
These grilles will also work, as designed, for those models with rear gas hook-
up. IMPORTANT: Installation of the rear grille must be made prior to
installing the chassis as it secures from inside the wall sleeve.
SCREW
(5) REQUIRED
WALL SLEEVE
GRILLE
A
Figure 19
SCREW
(5) REQUIRED
WALL SLEEVE
REAR GRILLE
A
Figure 18

15 Suburban DynaLine Owner's Manual 10/2017 Rev.1
DL3 AIR DISCHARGE PACKAGE
STOCK NO. 1651 - ADAPTOR
STOCK NO. 1623 - EXTENSION
STOCK NO. 1624 - CONNECTOR
INTRODUCTION
This optional package allows for distribution of air into an adjacent zone requiring a controlled temperature. This assembly will discharge the
conditioned air to either the right or left depending upon which end the cap is placed. (See Figure 23.)
This package, when installed on a DL3-0712 and DL3-0912 series cannot be lengthened. Maximum length, not including adaptor, is 43 1/4". On
model DL3-1220 and DL3-1622, additional lengths may be added.
If additional length is required, connector assembly (No. 1624) may be used. No more than two (2) connectors may be used. Maximum length not
including the adaptor is 130" (10.8 Feet). NOTE: Installer must provide wall support brackets for the connector and extension. Not recommended
for use on models with built-in thermostats.
Figure 20
BOTTOM OF SLEEVE TO TOP OF
AIR DISCHARGE ADAPTOR
SCORE LINE
GRILLE
ADAPTOR (1651)
CAP
TINNERMAN
BAFFLE
CONNECTOR (1624)
EXTENSION (1623)
COLLAR
(SEE DETAIL VIEW)
BRACKET
DL3 DYNALINE INSTALLED IN WALL.
(SHOWN ONLY FOR THE PURPOSE OF
ILLUSTRATING AIR PACKAGE INSTALLATION).
ADAPTOR
COLLAR
CHANNEL
DETAIL VIEW
Figure 21
4 PIN FEMALE HOUSING
4 PIN MALE HOUSING
(ONLY FOR UNITS WITH
OPTIONAL CARBON
MONOXIDE DETECTOR)
RESET
BUTTON
TEST/HUSH
BUTTON
OPTIONAL CARBON MONOXIDE DETECTOR
Figure 22

Suburban DynaLine Owner's Manual 10/2017 Rev.1 16
REQUIREMENTS FOR INSTALLATION
COMMONWEALTH OF MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet above nished grade in the area of the venting, including
but not limited to decks and porches, the following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing plumber or gas tter shall observe that a hard wired
carbon monoxide detector with an alarm and battery back-up is installed on the oor level where the gas
equipment is to be installed. In addition, the installing plumber or gas tter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the
dwelling , building or structure served by the side wall horizontal vented gas fueled equipment. It shall be
the responsibility of the property owner to secure the services of qualied licensed professionals for the
installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl
space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may
be installed on the next adjacent oor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30) days to comply with the above requirements;
provided, however, that during said thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in
accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS
certied.
3. SIGNAGE. A metal or plastic identication plate shall be permanently mounted to the exterior of the
building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal
for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print
size no less than one0half (½) inch in size, “GAS VENT DIRECTLY BELOW, KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure
separate from the dwelling, building or structure used in whole or in part for residential purposes.

17 Suburban DynaLine Owner's Manual 10/2017 Rev.1
SUBURBAN LIMITED WARRANTY
DYNALINE
ONE YEAR LIMITED WARRANTY
This SUBURBAN product is warranted to the original purchaser to be free from defects in material and workmanship under normal use and
maintenance for a period of one year from the date of installation whether or not actual use begins on that date. It is the responsibility of the
consumer/owner to establish the warranty period. Suburban does not use warranty registration cards for its standard warranty. You are required to
furnish proof of installation date which may be a Bill of Sale or other payment records which veries the original installation. A new or remanufactured
part to replace any defective part will be provided to your dealer, service agency or local gas company, at Suburban’s sole option, without charge
for the part itself, FOB the shipping point. THE EXCHANGED PART WILL BE WARRANTED FOR ONLY THE UNEXPIRED PORTION OF THE
ORIGINAL WARRANTY. Defective parts must be returned to Suburban, transportation charges prepaid (Suburban is not responsible for any
freight charges), where Suburban will establish to its sole satisfaction that the part was or became defective under normal use and maintenance.
Said rst year repairs, made by a recommended Suburban service agency, will qualify for labor reimbursement (to the service agency only) up to
a maximum as established by Suburban’s at rate schedule effective at that time. No reimbursement will be made for transportation, diagnosing,
shipping or handling. THIS WARRANTY APPLIES ONLY TO THE PRODUCT IN ITS ORIGINAL INSTALLATION LOCATION AND IS VOIDED IF
THE PRODUCT IS REINSTALLED ELSEWHERE.
Suburban reserves the right to examine the alleged defect in the unit or component parts, and it is the owner's obligation to return the unit and/
or component parts to Suburban or its representative. When returning a unit, it must include all component parts and the serial number plate.
Returned component parts must be individually tagged and identied with the unit's model number, serial number and date of installation.
FOUR YEAR LIMITED WARRANTY ON HEAT EXCHANGER AND COMPRESSOR
During the second through fth years after the date of original installation, Suburban further warrants the heat exchanger against defects in material
and workmanship under normal use and maintenance. A replacement heat exchanger will be provided under the same conditions as stated in the
one year warranty EXCEPT no labor reimbursement will be provided.
During the second through fth years after the date of original installation, Suburban further warrants the compressor against defects in material
or workmanship under normal use and maintenance. A new or re-manufactured compressor will be provided at Suburban’s sole option under the
same conditions as stated in the one year warranty EXCEPT no labor reimbursement will be provided.
LIMITATION OF WARRANTIES
ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO THE
PERIOD FOR WHICH EACH LIMITED WARRANTY IS GIVEN. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED
WARRANTY LASTS SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU. THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY
ARE EXCLUSIVE AND MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER OR OTHER PERSON
WHOMSOEVER.
ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS. ALL REPLACEMENT
PARTS ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY.
SUBURBAN WILL NOT BE RESPONSIBLE FOR:
1. Normal maintenance as outlined in the owner’s installation, operating and service instructions manual including cleaning of component parts;
such as, orices and burners.
2. Failure to start and/or operate due to voltage or gas conditions, blown fuses, open circuit breakers, loose or disconnected wires, low gas
pressure or other damages due to inadequacy or interruption or electrical service or gas supply.
3. Damage or repairs required as a consequence of faulty or incorrect installation not in conformance with Suburban instructions.
4. Damage as a result of oods, winds, lightning, accidents, corrosive atmosphere or other conditions beyond the control of Suburban.
5. Costs incurred in gaining access to the furnace.
6. Any damage (cracks, chips, scratches, etc.) to any painted parts.
7. Parts or accessories not supplied by Suburban.
8. Damage or repairs needed as a consequence of any misapplication, abuse, unreasonable use, unauthorized alteration, improper service,
improper operation or failure to provide reasonable and necessary maintenance.
9. Freight charges incurred from parts replacements.
10. Fuel or electricity costs or increases in such costs from any reason whatsoever.
11. Suburban products whose serial number has been altered, defaced or removed.
12. Suburban products installed or warranty claims originating outside the Continental U.S.A., Alaska, Hawaii and Canada.
13. ANY SPECIAL, INDIRECT OR CONSEQUENTIAL PROPERTY, ECONOMIC OR COMMERCIAL DAMAGE OF ANY NATURE WHATSOEVER.
Some states do not allow the exclusion of incidental or consequential damages, so the above limitation may not apply to you.
NO REPRESENTATIVE, DEALER OR OTHER PERSON IS AUTHORIZED TO ASSUME FOR SUBURBAN MANUFACTURING COMPANY ANY
ADDITIONAL, DIFFERENT OR OTHER LIABILITY IN CONNECTION WITH THE SALE OF THIS SUBURBAN PRODUCT.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
IF YOU HAVE A PRODUCT PROBLEM
FIRST: Contact the installer of the equipment or the selling dealer for warranty service. You may nd his name on the product or with your
homeowners manual. If his name is not known, call your builder or general contractor if yours is a new structure.
SECOND: Contact the Suburban distributor who supplied the product to the installer/dealer.
THIRD: Contact:
Suburban Applied Products - Customer Service Department
156 Seedling Drive
Cordele, GA 31015
(229) 273-3636
Fax: (229) 273-5154
www.SuburbanHVACproducts.com
Please consult the Suburban Manufacturing website at www.SuburbanManufacturing.com for the latest product literature. Detailed dimensional
data is available upon request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website.
As part of the Suburban continuous improvement program, specifications are subject to change without notice.
P.O. Box 400 • Cordele, GA 31010
156 Seedling Drive • Cordele, GA 31015
Ph: 229-273-3636 • Fax: 229-273-5154
Email: [email protected]
Manufactured by:

Suburban DynaLine Owner's Manual 10/2017 Rev.1
SUBURBAN - GARANTIE LIMITÉE
DYNALINE
GARANTIE LIMITÉE D’UNE ANNÉE
Ce produit Suburban est garanti au bénéce du premier acquéreur comme étant exempt de vice de matériau ou de fabrication, lorsqu’il est soumis aux conditions
normales d’utilisation et d’entretien, pendant une période d’une année à compter de la date d’achat, que l’appareil soit ou non mis en service à cette date. C’est au
consommateur/propriétaire qu’incombe la responsabilité de faire la preuve de la période de garantie. Suburban n’utilise pas de carte d’enregistrement de la garantie
pour sa garantie standard. Le propriétaire doit soumettre une preuve de la date d’achat, comme une facture ou un autre document attestant du paiement. Suburban
choisira de fournir gratuitement une pièce neuve ou rénovée, á votre concessionaire, centre de service ou le fournisseur local de gaz, F.à.B. point d’expédition, pour le
remplacement de la pièce défectueuse. LA PIÈCE REMPLACÉE NE BÉNÉFICIE DE LA GARANTIE QUE PENDANT LA FRACTION NON ÉCOULÉE DE LA PÉRIODE
DE GARANTIE D’ORIGINE. Les pièces défectueuses devront être retournées à Suburban, frais de transport prépayés (Suburban n’acceptera pas de payer les frais
de transport), et Suburban établira à sa seule satisfaction que la pièce était ou est devenue défectueuse dans les conditions normales de service et d’entretien. Les
réparations ainsi exécutées au cours de la première année par un établissement de service recommendé par Suburban donneront lieu au remboursement des frais de
main-d’oeuvre (directement à l’établissement effectuant les travaux) jusqu’à un montant maximum établi d’après le tarif forfaitaire de Suburban en vigueur à cette date.
Les frais de transport, diagnostic, expédition et manutention ne donneront lieu aucun remboursement. CETTE GARANTIE COUVRE UNIQUEMENT LE PRODUIT À
L’EMPLACEMENT DE SON INSTALLATION INITIALE; ELLE DEVIENT NULLE LORSQUE LE PRODUIT EST RÉINSTALLÉ AILLEURS.
Suburban réserves le droit d'examiner le vice allégué dans l'appareil ou ses composants, et c'est l'obligation du propriétaire de retourner l'appareil et / ou des pièces
détachées pour Suburban ou son représentant. Lors du retour d'une unité, il doit comporter tous les composants et la plaque de numéro de série. Composants
retournés doivent être étiquetée et identiée avec le numéro de modèle de l'appareil, le numéro de série et la date d'installation.
GARANTIE LIMITÉE DE QUATRE ANS SUR L’ÉCHANGEUR DE CHALEUR ET LE COMPRESSEUR
Depuis la seconde année jusqu’à la cinquième année après la date de l’installation initiale, Suburban garantit également l’échangeur de chaleur contre les vices de
matériau et de fabrication, dans les conditions normales de service et d’entretien. Un échangeur de chaleur de remplacement sera fourni dans les mêmes conditions
déjè décrites pour la garantie d’une année, à L’EXCEPTION que les frais de main-d’oeuvre ne seront pas remboursés.
Depuis la seconde année jusqu’à la cinquième année après la date de l’installation initiale, Suburban garantit également le compresseur contre les vices de matériau
et de fabrication, dans les conditions normales de service et d’entretien. Un compresseur de remplacement neuf ou rénové sera fourni dans les mêmes conditions déjè
décrites pour la garantie d’une année, à L’EXCEPTION que les frais de main-d’oeuvre ne seront pas remboursés.
LIMITATION DES GARANTIES
LA PÉRIODE DE VALIDITÉ DES GARANTIES IMPLICITES (CECI INCLUANT LES GARANTIES IMPLICITES DE QUALITÉ MARCHANDE) EST EXPRESSÉMENT
LIMITÉE À LA DURÉE DE CHAQUE PÉRIODE DE GARANTIE LIMITÉE ACCORDÉE. CERTAINES PROVINCES N’ADMETTENT PAS LA LIMITATION DE LA
DURÉE DE VALIDITÉ DES GARANTIES IMPLICITES; PAR CONSÉQUENT, LES LIMITATIONS CI-DESSUS PEUVENT NE PAS VOUS ÊTRE APPLICABLES.
LES GARANTIES EXPRESSES CONFÉRÉES PAR LE TEXTE QUI PRÉCÈDE SONT LES SEULES GARANTIES ACCORDÉES, ET ELLES NE PEUVENT ÛTRE
MODIFIÉES, ÉTENDUES OU PROLONGÉES PAR UN DISTRIBUTEUR, CONCESSIONNAIRE OU AUTRE PERSONNE.
TOUS LES TRAVAUX SOUS GARANTIE SERONT EXÉCUTÉS PENDANT LES HEURES DE TRAVAIL NORMALES. LES PIÈCES DE RECHANGE INSTALLÉES NE
SONT GARANTIES QUE PENDANT LE RÉSIDU DE LA PÉRIODE DE GARANTIE.
SUBURBAN N’ACCEPTERA AUCUNE RESPONSABILITÉ AU TITRE DE:
1. Entretien normal, tel qu’il est déni dans les instructions d’installation, utilisation et entretien du manuel de l’utilisateur, ceci incluant le nettoyage de composants
comme gicleur ou brûleur.
2. Défaillance de mise en marche et/ou de fonctionnement, du fait d’anomalies de l’alimentation électrique ou en gaz, fusible grillé, disjoncteur ouvert, l mal xé ou
déconnecté, pression de gaz insufsante ou autres dommages imputables à une décience ou à l’interruption de l’alimentation électrique ou en gaz.
3. Dommages ou réparations imputables à une installation déciente ou à une application non conforme aux instructions de Suburban.
4. Dommages imputables à inondation, vent, foudre, accidents, atmosphère corrosive et autres situations que Suburban ne peut contrôler.
5. Frais rendus nécessaires pour l’accès à l’appareil.
6. Tout dommage (ssures, ébréchures, égratignures, etc) pour les parties peintes.
7. Pièces ou accessoires non fournis par Suburban.
8. Dommages ou réparations imputables à toute utilisation impropre, irraisonnée ou abusive, modication non autorisée, travaux d’entretien incorrects, utilisation
incorrecte ou carence d’entretien.
9. Frais de transport afférents au remplacement de pièces.
10. Frais de combustible ou électricité, ou augmentation de ces frais, quelle qu’en soit la raison.
11. Produits Suburban dont le numéro de série a été modié, éliminé ou rendu illisible.
12. Demandes de travaux sous garantie pour des produits Suburban installés hors des zones géographiques suivantes: états continentaux des É.-U., Alaska, Hawaii
et Canada.
13. DOMMAGES SECONDAIRES OU INDIRECTS MATÉRIELS, ÉCONOMIQUES OU COMMERCIAUX, QUELLE QU’EN SOIT LA NATURE. Certaines provinces
n’admettent pas l’exclusion des dommages secondaires ou indirects; par conséquent, la limitation ci-dessus peut ne pas vous être applicable.
AUCUN REPRÉSENTANT, CONCESSIONNAIRE OU AUTRE PERSONNE N’EST AUTORISÉ À ASSUMER AU NOM DE SUBURBAN
MANUFACTURING COMPANY DES OBLIGATIONS ADDITIONNELLES OU DIFFÉRENTES EN RAPPORT AVEC LA VENTE DE CE PRODUIT
SUBURBAN.
Cette garantie vous confère des droits juridiques spéciques; vous pouvez également jouir d’autres droits, variables d’une province à une autre.
SI UN PROBLÈME SE MANIFESTE
TOUT D’ABORD: Pour les travaux de service, contacter l’installateur de l’équipement ou le concessionnaire qui l’a vendu. On peut trouver son
nom sur le produit, ou dans le manuel de l’utilisateur qui accompagne l’appareil. Si son nom n’y est pas mentionné, contacter
l’entrepreneur ou l’entrepreneur général qui a construit le bâtiment.
DEUXIÈMEMENT: Contacter le distributeur Suburban qui a fourni le produit à l’installateur ou au concessionnaire.
TROISIÈMEMENT: Contacter:
Suburban Manufacturing Company
Suburban Applied Products - Customer Service Department
156 Seedling Drive
Cordele, GA 31015
(229) 273-3636
Fax: (229) 273-5154
www.SuburbanHVACproducts.com
Veuillez consulter le Site Web de Suburban (www.SuburbanManufacturing.com) pour la documentation la plus récente sur le produit.
Des données dimensionnelles détaillées sont disponibles sur demande. Une description complète de la garantie se trouve dans chaque
manuel d’installation / utilisation du produit et sur le site Web. Dans le cadre du programme de Suburban d’améliorations continuelles, ces
spécifications sont susceptibles de changer sans préavis.
P.O. Box 400 • Cordele, GA 31010
156 Seedling Drive • Cordele, GA 31015
Ph: 229-273-3636 • Fax: 229-273-5154
Email: [email protected]
Fabriqué par:

Suburban DynaLine Owner's Manual 10/2017 Rev.1
4 PIN FEMALE HOUSING
4 PIN MALE HOUSING
(Uniquement pour des unités
avec détecteur optionnel de
monoxyde de carbone)
RESET
BUTTON
TEST/HUSH
BUTTON
DÉTECTEUR OPTIONNEL DE MONOXYDE DE CARBONE
Figure 25
16

Suburban DynaLine Owner's Manual 10/2017 Rev.1
RACCORD
ADAPTATEUR
PROFILÉ
EXTENSION (1623)
CONNECTEUR (1624)
ADAPTATEUR (1651)
BRIDE DE SUPPORT
RACCORD
(VOIR LA VUE DÉTAILÉE)
APPAREIL DL3 DYNALINE INSTALLÉ DANS LE MUR
(REPRÉSENTÉ ICI SEULEMENT POUR INSTALLATION DE
L'INSTALLATION DE L'ENSEMBLE DE PÈICES).
EMBOUT
ÉCROU TINNERMAN
VOLET
GRILLE
LIGNE DE PLAIGE
VUE DÉTAILLÉE
Figure 24
DISTANCE ENTRE LE BAS DU CARÉNAGE
LE SOMMET DE L'ADAPTATEUR
Figure 23
15
SYSTÈME DE DÉCHARGE DE L’AIR - APPAREIL DL3
Produit n° 1651 - Adaptateur
Produit n° 1623 - Extension
Produit n° 1624 - Connecteur
INTRODUCTION
Cet ensemble proposé en option permet la distribution de l’air dans une zone adjacente nécessitant un contrôle de la température. Cet ensemble décharge l’air chauffé
ou refroidi par la gauche ou par la droite, selon l’endroit où l’embout d’obturation est placé (voir gure 23).
On ne peut allonger cet ensemble lorsqu’il est installé sur un appareil DL3, série 0912. La longueur maximum sans l’adaptateur est 43 1/4 po. Dans les d’un appareil
DL3, série 1220 et DL3, série 1622, on peut ajouter une section additionnelle. N’est pas recommandé d’utiliser sur les modèles avec thermostats intégrés.
Si une section additionnelle est nécessaire, on peut utiliser le connecteur n° 1624. On ne peut pas utiliser plus de deux connecteurs. La longueur maximum sans
l’adaptateur est de 130 po (10,8 pi). REMARQUE: L’installateur doit fournir les brides de support mural pour le connecteur et l’extension.
This manual suits for next models
3
Table of contents
Other Suburban Air Conditioner manuals