
MORTEXPRODUCTSINCFORTWORTH,TX76106Page10
10. Check the blower wheel for dust and debris. Use the
brush and the vacuum cleaner to remove any dust or
debris from the wheel. Be careful not the move or
accidentally remove the blower wheel balance weight
located on the wheel blade. If it is moved or removed it
will cause the blower wheel to vibrate. If the wheel is
vibrating, you must replace it.
11. Check the blower motor for dust and debris. Be sure to
clean the openings on the motor housing as these
openings are used to cool the motor. If the dust, dirt or
debris has not been removed from these openings it will
cause the motor to run hotter than normal and will shorten
the life of the motor.
12. Check and clean with the brush and vacuum cleaner any
dust in the supply and return ducts as far as you can reach.
If these ducts look like they have an excessive amount of
dust, dirt or debris you should recommend to the home
owner or user to call a professional to properly clean the
duct system.
13. Check and clean any dust, dirt, or debris from all of the
controls and all of the surfaces in the control box. If dust
or dirt is left on the components they will operate at a
much hotter temperature causing premature component
failure.
14. Reinstall the blower assembly and secure the assembly to
the casing by using the screws that was removed in step 5.
15. Reinstall the lower access door on the front of the
evaporator coil compartment.
16. Reinstall the upper access door on the air handler.
17. Follow the instructions exactly as shown in Startup and
Shutdown Section in this manual to properly startup this
appliance.
SECTION III: AIR HANDLER CONTROLS
Electric Heat Models
This section discusses the air handler controls and how they
operate. Refer to Figure 9 for component locations.
1. The Limit Controls – Each electric heater element has a
limit control directly in front of it to sense overheating of
the element and open if the temperature gets above the set
point of the limit control.
2. The Heater Relays – The electric heater relays simply
turn the heater elements on and off. The relays are
controlled by the thermostat. On a call for heat 24 VAC is
sent to the relay(s) 24 VAC coil energizing the relay.
When the call for heat has been satisfied the 24 VAC is
removed from the relays 24 VAC coil de-energizing the
relay(s).
3. Cooling Time Delay Relay (TDR) – The cooling
sequencer relay is used only on models with a PSC motor.
When the thermostat calls for cooling or the fan switch on
the thermostat is moved from the “AUTO” to the “ON”
position, 24 VAC is placed on the “G” terminal from the
thermostat to the 24 VAC coil on the sequencer relay. The
relay controls the blower on time delay and is not
adjustable. The sequencer setting is approximately 30 - 45
seconds on and 1 – 20 off.
4. Circuit breakers – The circuit breakers are designed as
over-current protection for the air handler internal
electrical components. Field wiring must be protected by
field supplied circuit breakers or fuses sized to protect the
wire connected to the air handler circuit breakers.
5. Transformer – The transformer is used to step down
voltage from 240 VAC to 24 VAC. The transformer
provides the required 24 VAC for the system control
circuit.
6. Blower Motor Isolation Relay - This relay is used to
load the TDR when using a PSC or X-13 motor or for
isolation between the high and low speeds of a motor. The
wiring has been designed so that the normally closed
contacts are used for heating and the normally open
contacts are used for cooling. The relay coil is energized
after the thermostat has a call from the “G” terminal
starting the time delay cycle on the sequencer relay. Once
the time delay relay has reached the delay setting the relay
contacts close energizing the isolation relay coil. The
normally closed contacts on the isolation relay open and
the normally open contacts close, energizing the motor on
the selected cooling speed.
ECM Motor Isolation Relay - This relay is not used on the
ECM motor which has programmable heating and cooling
blower time delays along with climate profile time delays. See
climate profile section for more information.
Hydronic Heat Models
This section discusses the air handler controls and how they
operate. Refer to Figure 10 for component locations.
1. Transformer – The transformer is used to step down
voltage from 240 VAC to 24 VAC. The transformer
provides the required 24 VAC for the system control
circuit.
2. Pump Relay – This relay is not used on all hydronic
models. This relay is a single pole single throw relay that
energizes the water pump on a call for heat. The 24 VAC
coil is connected to the thermostat “W” terminal. The coil
is energized on a call for heat closing the normally open
terminals sending 120 VAC thru the relay contacts to the
water pump motor. Once the call for heat has been
satisfied, the 24 VAC is removed from the thermostat
“W” terminal de-energizing the relay coil and opening the
contacts to the water pump motor.
3. PSC Blower Motor Isolation Relay - This relay is a
single pole double throw relay. Is required for isolation
between the high and low speeds of a motor. The wiring
has been designed so that the normally closed contacts are
used for heating and the normally open contacts are used
for cooling. The relay coil is energized after the
thermostat has a call from the “G” terminal. The normally
closed contacts on the isolation relay open and the
normally open contacts close, energizing the motor on the
selected cooling speed.
4. ECM Motor Isolation Relay - This relay is not used on
the ECM motor has programmable heating and cooling
blower time delays along with climate profile time delays.
See climate profile section for more information.
SECTION IV: SEQUENCE OF OPERATION
Continuous Blower – Electric Heat Models
The thermostat has a manual fan switch that can be moved to
the “On” position or it can be programmed for continuous fan