Swegon RX/HC User manual

We reserve the right to alter specifications.
GB.FUNKRXHC.180907
www.swegon.com 1
Guide to the GOLD version F functions,
Reversible heat pump, RX/HC
1. General
RX/HC is a complete reversible heat pump, fully integrated
in the GOLD air handling unit.
There are three options to defrost the coils
in the exhaust air:
Option 1. Reversing the media circuit.
Option 2. Reversing the media circuit +
electric air heater
Option 3. Reversing the media circuit +
air recirculation section RX/HC
1.1 Installation
See the separate installation and maintenance instructions
to install RX/HC.
See the separate installation instructions to install the air
recirculation section RX/HC, if used.
2. Material specification
Air handling unit with integrated
reversible heat pump GOLD RX/HC
For defrosting according to option 2 (see section 1):
Electric air heater for defrosting. Installed in GOLD RX/HC
from the factory.
For defrosting according to option 3 (see section 1):
Air recirculation section RX/HC for defrosting.

GB.FUNKRXHC.180907
We reserve the right to alter specifications.
2 www.swegon.com
3. Function
3.1 General
RX/HC has a reversible heat pump function that is con-
trolled by the GOLD air handling unit’s control system
IQlogic via bus communication to the refrigerant circuit’s
control system iPro.
Operation and setting occurs via the GOLD air handling
unit’s hand-held micro terminal (see section 5. Settings).
The reversible heat pump circuit is controlled
with three signals:
• Stop/Start (0/1)
• Heating/Cooling (0/1)
• Speed level compressor in per cent (25-100%)
When operation is requested, a start signal is sent for the
production of heating or cooling.
Depending on the need in question, a signal is also sent
for the operating level, 25-100%. When operation is
not required, a stop signal is sent and 0 % signal for the
operating level.
3.2 Start of RX/HC air handling units
Start of the reversible heat pump occurs after the GOLD
air handling unit’s ordinary start sequence. Operation of
RX/HC is blocked during the GOLD air handling unit’s
ordinary start sequence.
3.3 Stop of RX/HC air handling unit
When stopping the GOLD air handling unit, operation of
the reversible heat pump is shut down immediately.
Post-cooling of the refrigerant circuit and electric air
heater for defrosting (if fitted) is carried out. After cooling
is in progress two minutes after the last operation of the
compressor or electric air heater.
3.4 Temperature regulation
The heat pump has its own control sequence (HC) in the
GOLD air handling unit’s temperature sequence. The
sequence regulates the temperature requirement 0-100%,
for the heating and cooling sequence respectively.
The heat pump is enabled when the temperature require-
ment exceeds 3% for 60 seconds and is disabled when
the temperature requirement drops below 1% for 60
seconds (applies for Operating mode - Standard).
Size 011 - 035 (one compressor)
The refrigerant circuit contains a speed controlled com-
pressor.
The compressor works between a MIN level (normal 25%)
and maximum speed.
At a temperature requirement below 25% the compressor
is run at 25% of max, at a need above 25% the compres-
sor follows the temperature requirement. (see the diagram
below)
3
25%%%
25%
100%
100%
%1
Temperature require-
ment, GOLD
Operation level, HC
Temperature requirement
Compressor operation

We reserve the right to alter specifications.
GB.FUNKRXHC.180907
www.swegon.com 3
Size 040 - 080 (two compressors)
The refrigerant circuit contains a speed controlled com-
pressor and a compressor of the on/off type.
The speed controlled compressor works between a MIN
level (total 12.5% per compressor, corresponding to 25%
of the speed controlled compressor) and maximum speed.
Increasing temperature requirement
At a temperature requirement below 12.5% the speed
controlled compressor is run at 25% of max, speed.
When the temperature requirement increases above
12.5%, the speed controlled compressor is regulated to
follow the temperature requirement.
At a temperature requirement above 50%, the speed
controlled compressor runs to max, speed.
When the temperature requirement increases above
62.5%, the on/off compressor and the speed controlled
compressor are regulated to follow the temperature re-
quirement.
At a temperature requirement of 100%, both compressors
run at max, speed.
Decreasing temperature requirement
When the temperature requirement decreases below
100%, the on/off compressor is operational and the speed
controlled compressor is regulated to follow the tempera-
ture requirement.
At a temperature requirement below 62.5% the speed
controlled compressor is run at 25% of max, speed and
the on/off compressor is operational.
When the temperature requirement decreases below
50%, the on/off compressor shuts down and the speed
controlled compressor is regulated to follow the tempera-
ture requirement.
At a temperature requirement below 12.5% the speed
controlled compressor runs at 25% of max, speed.
Total output
The diagram shows the total capacity in per cent, which is
the same as the control signal from the control system.
Compressor, on/off
Temperature requirement
Compressor operation
Compressor speed controlled
Temperature requirement
Compressor operation
Total output
Temperature requirement
Total output
0
20
100%908070605040302010
1
0
40
60
80
100%
0
20
100%908070605040302010
1
0
40
60
80
100
%
0
20
100%908070605040302010
1
0
40
60
80
100%
60
0
20
100%908070605040302010
1
0
40
60
80
100
%
0
20
100%908070605040302010
1
0
40
60
80
100%
0
20
100%908070605040302010
1
0
40
60
80
100%
60
0
20
100%908070605040302010
1
0
40
60
80
100%
0
20
100%908070605040302010
1
0
40
60
80
100%
0
20
100%908070605040302010
1
0
40
60
80
100
%
60
Temp. requirement, GOLD
Operation level, HC

GB.FUNKRXHC.180907
We reserve the right to alter specifications.
4 www.swegon.com
3.5 Stabilization
In certain circumstances, there is a need to stabilise opera-
tion of the refrigerant circuit and the temperature control
for GOLD.
During stabilization, operation of the refrigeration circuit
is forced to be between MIN-100% of the compressor
speed, regardless of the temperature control requirement.
The stabilisation time is normally 4 minutes + any time
between sending the start request of the refrigeration
circuit and the actual start of compressor operations. If the
cooling circuit is (or recently been in) in operating mode
Adapted operations, the stabilisation time is extended to 8
minutes.
Stabilization starts when one of the following occurs:
• The refrigerant circuit starts in stopped mode
• Defrosting is complete
• Oil return is terminated
• The number of compressors in operation is changed
(except when the number changes from one to zero).
Operations return to normal mode after stabilization is
complete and is controlled between MIN-100% according
to section 3.4 Temperature control.
Stabilization stops when one of the following occurs:
• Stop of the GOLD air handing unit
• Defrosting requirement occurs (see section 3.9)
• Oil return starts (see section 3.8)
3.6 Comfort function
The comfort function is possible to select for heating and/
or the cooling function.
When there is a need of low cooling/heating capacities,
the lowest compressor speed will be too high, the func-
tion prioritises comfort before economy.
If the comfort function is selected and the temperature
requirement is low (the corresponding compressor oper-
ation is lower than MIN level), comfort mode is enabled.
Operation of the reversible heat pump is then locked
to MIN level of the compressor speed. The rotary heat
exchanger is allowed to regulate to maintain the required
supply air temperature. If instead the temperature require-
ment exceeds MIN level, operations return to normal
mode.
If any of the following occurs the comfort function is can-
celled and operation of the reversible heat pump stops:
• Stop of the GOLD air handing unit
• Time for comfort mode exceeds 30 minutes (factory
setting, can be set 5 – 30 minutes)
• Airflow limits for the supply air and/or extract air drop
below the permitted minimum limit (factory setting 40%
of the GOLD air handling unit’s maximum flow, can be set
0 – 100%)
• Outdoor temperature limits for heating or cooling func-
tion are not met (factory setting, heating -20°C, cooling
+15°C. Can be set, heating -50 – +50°C, cooling 0 –
50°C)
• The supply air temperature deviates from the set point to
such an extent that it is within 1 K from the limit value for
any of the alarms Supply air temperature above/below set
point.
• Reheating attempts to start when operations are in heat-
ing mode or reheating attempts to start when operations
are in cooling mode. This means that the rotor’s heating/
cooling capacity is not sufficient to balance the tempera-
ture and that there is an active regulation sequence after
the rotor.
3.7 Adapted operations
When the evaporation and condensation temperatures
are in a position outside of the optimal working range, the
speed of the compressor is adapted to attempt to reach
the optimal working range.
This is indicated on the hand-held micro terminal of the
GOLD unit.
3.8 Oil return
If the speed of the compressor has been below 28% for
more than 50 minutes, the speed is increased briefly to
extend the life of the compressor.
This results in a larger delivered supply air capacity than
requested. In order to avoid unnecessary system fluctua-
tions, refrigeration circuit shut-off is prevented (independ-
ent of the temperature regulator’s requirement) after the
oil return is completed. This is done by starting the stabili-
zation function.

We reserve the right to alter specifications.
GB.FUNKRXHC.180907
www.swegon.com 5
When defrosting is completed, the outdoor air damper
and the exhaust air damper open, the recirculation
damper closes and stabilization operations are run.
In order to reduce the risk of freezing, a termination
sequence is started at the same time when the recircula-
tion damper is opened and closed a number of times.
Electrical air heater RX/HC (accessory)
When there is a defrosting requirement, the electric air
heater is enabled immediately.
Overheating protection is installed. Post-cooling is car-
ried out if the air handling unit stops during or just after
defrosting.
Critical defrosting
If the evaporation temperature in the heating circuit drops
below a critical limit, defrosting starts.
If the control system discovers ongoing ordinary defrost-
ing, critical defrosting is adapted to the ordinary defrost-
ing sequence, e.g. recirculation starts.
3.10 Limitations
For operations outside the outdoor temperature limits
and/or below air limits, the reversible heat pump function
stops and the air handling unit acts as a GOLD RX.
Outdoor temperature limit, cooling
Operation of the reversible heat pump in cooling mode
is only permitted at an outdoor temperature above 15°C
(adjustable value).
Outdoor temperature limit, heating
Operation of the reversible heat pump in heating mode
is only permitted at an outdoor temperature above -25°C
(adjustable value).
Air flow limits
Operation of the reversible heat pump is only permitted
when the extract airflow and supply airflow exceed a
minimum airflow limit. Values can be set for the extract air
and supply air.
3.9 Defrosting
Freezing occurs when operations are in heating mode and
the temperature across the exhaust coil is below 0 °C.
Depending on the temperature, compressor speed, airflow
as well as moisture content in the extract air and fresh air,
freezing occurs with varying speed and behaviour.
The pressure drop across the exhaust coil is measured
to detect the defrosting requirement or stop ongoing
defrosting. Defrosting starts when the pressure drop
exceeds a specific limit. When the pressure drop falls
below another lower limit defrosting stops.
At defrosting with recirculation, the recirculation damper
have a finishing sequence for protection against freezing.
Phases
Defrosting occurs by reversing the heat pump circuit. The
exhaust coil then works as a condenser (as with the cool-
ing function) and heats.
Start delay
When the pressure drop across the exhaust air coil exceeds
the start limit, for a period longer than 60 seconds,
defrosting starts.
Initiation
When defrosting is detected the Initiation phase starts.
The recirculation damper then opens for recirculation, and
if there is an electric air heater this starts. For recirculation
the signal is sent with a delay of 60 seconds, if there is no
recirculation the signal is sent without a delay.
Pre-defrosting
When the defrosting process starts, a signal is sent to the
heating circuit which lowers the compressor speed and
turns the flow directions through the four-way valve.
Defrosting
The defrosting process continues through ramping up the
compressor speed and running until the control system
requests that defrosting stops or until the maximum
defrosting time has been reached.
Runoff
In the last part of the defrosting process, the compressor
speed drops and the flow directions through the four-way
valve are turned back.
Adaptive start and stop
Start and stop of the defrosting process is controlled by
calculations in the control system, which take a number
of different factors into consideration that are measured
continuously.
Adaptation is performed after each defrosting to optimise
the process.
Air recirculation section RX/HC (accessory)
When there is a defrosting requirement, the recircula-
tion damper opens, and the outdoor air damper and the
exhaust air damper close.
Recirculation operation is ensured before defrosting starts.

GB.FUNKRXHC.180907
We reserve the right to alter specifications.
6 www.swegon.com
SD
WLAN
CPU 1
CPU 2
1
A2
B3
GN D 4
+5
-6
+7
-8
+9
-10
+11
-12
+13
-
SA Te mpCom 5Com 4Com 3Com 2Com 1
14
+15
-16
+17
-18
+19
-
Heat Cool
20
C21
NO 22
C23
NO 24
C25
NO 26
C27
NO 28
P29
G30
G0 31
G32
G0
24V AC
Sensor 1 Sensor 2 Sensor 4Sensor 3 Com 6 Com 7 Com 8 Com 9 Com 10 Com 11
+
33 -
34 G
35 G0
36 Y
37 U
38 39 40
24V AC In
41 42
18V AC In
45 46
230V AC In
4743 44
230V AC Ou t
-
97
+
98
GND
99
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
P1
COM POWER
IQlogic+
1234 5678 9101112
-+-+ -++--S-S
C
13
NO
14
C
15
NO
16
+
17
-
18
+
19
-
20
G
21
G0
22
Com 1Heat/Cool Com 2
SD
WLAN
CPU 1
CPU 2
1
A2
B3
GN D 4
+5
-6
+7
-8
+9
-10
+11
-12
+13
-
SA Te mpCom 5Com 4Com 3Com 2Com 1
14
+
15
-
16
+
17
-
18
+
19
-
Heat Cool
20
C
21
NO
22
C
23
NO
24
C
25
NO
26
C
27
NO
28
P
29
G
30
G0
31
G
32
G0
24V AC
Sensor 1 Sensor 2Sensor 4Sensor 3 Com 6 Com 7 Com 8 Com 9 Com 10 Com 11
+
33
-
34
G
35
G0
36
Y
37
U
38 39 40
24V AC In
41 42
18V AC In
45 46
230V AC In
4743 44
230V AC Ou t
4. Wiring diagram
The following wiring diagram deals with connected com-
ponents in addition to a standard air handling unit GOLD
RX. For the wiring diagram standard GOLD RX, see the
separate document.
Control card
IQlogic
Control card iPro,
cooling circuit
control
Pressure sensor for pressure drop
measurement over the cooling circuit’s
exhaust air coil (function selector
switch in D position).
Temperature sensor for density cor-
rection of the airflow. The sensor is
placed between the coil and fan in the
exhaust air/supply air.
Temperature sensor for density cor-
rection of the airflow. The sensor is
placed between the coil and fan in the
exhaust air/supply air.
Electric air heater for defrosting (accessory)
Connect from any of connectors COM1 or COM2 on the
IQLogic+module to one of the connectors on the air han-
dling unit's IQLogic control unit marked COM6-11.
The function
selector switch
must be set to
position 5.
Electric air
heater
Control card
IQlogic
IQlog-
ic+-module
Connect from connec-
tor HEAT/COOL on the
IQlogic+-module to the
RJ45 connector on the
electric air heater.
Communication cable between connector COM4 on the air
handling unit’s IQlogic control unit and communication termi-
nals 97, 98, 99 on the iPro cooling circuit control.
Communication cable between connector SENSOR4
on the air handling unit’s IQlogic control unit and
temperature sensor.
Communication cable between connector SENSOR3
on the air handling unit’s IQlogic control unit and
temperature sensor.
Communication cable between any connector
COM6-11 on the air handling unit’s
IQlogic control unit and pressure sensor.

We reserve the right to alter specifications.
GB.FUNKRXHC.180907
www.swegon.com 7
IQlogic+
Damper
actua-
tor
5. Electrical connection of the air recirculation section RX/HC (accessory)
Requisite accessories
Outdoor air damper TBSA-X-xxx-xxx-x-1 or
TCSA-xxx, spring return
Exhaust air damper TBSA-X-xxx-xxx-x-1 or
TCSA-xxx spring return
Function
In normal mode the recirculation damper must be fully
closed (deenergized state).
When defrosting is selected, the air recirculation damper
should be completely open (actuating time: 90 seconds).
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
P1
COM POWER
IQlogic+
1234 5678 9101112
-+-+ -++--S-S
C
13
NO
14
C
15
NO
16
+
17
-
18
+
19
-
20
G
21
G0
22
Com 1Heat/Cool Com 2
28 30
GG0 YU
GG0
31 32
PG0 GG0
12 1212 89
GG0
Communication cable to the control unit of
the air handling unit, where it is connected
to one of the outlets for COM 6-11.
The function
selector switch
must be set to
position 5.
Outdoor air
damper
Exhaust air
damper
Air recirculation
damper
GOLD Control unit
The electrical connections are to be wired by a qualified
electrician in accordance with local electrical safety regu-
lations.
The IQlogic+ module is placed
in the electrical cabinet on the
GOLD air handling unit.
The damper motor has a 0.9 metre long connection cable,
4 x 0.75 mm2and is connected in the junction box, IP54.

GB.FUNKRXHC.180907
We reserve the right to alter specifications.
8 www.swegon.com
Function
6. Settings
For basic details on how to use the hand-held terminal,
see the Operation and Maintenance Instructions for the
GOLD Air Handling Unit.
The functions for the reversible heat pump are activated
manually under Functions/HC. This is only possible for
GOLD RX (rotary heat exchanger).
HC is activated by setting Position HC in On. Other possi-
ble settings are shown when HC is activated.
If any of the accessories electric air heater HC or air
recirculation section HC are fitted, these are activated
by selecting the required accessory from the menu HC
defrosting accessory.
Set the required heating and cooling function, standard or
comfort.
Set the required values for outdoor temperature limits for
heating and cooling.
Set the required values for airflow limits for supply air and
extract air.
Calibration is carried out at the factory. If recalibration is
required, this can be carried out by pressing the calibra-
tion button. Remaining time is shown when calibration is
in progress. Calibration date and lowest/highest air flow/
pressure drop are shown when calibration is performed.
HC
Outdoor temperature limits
Air flow limits
Regulation sequence
Temperature
Regulation sequence for heating and cooling can be set,
see the separate Function manual installation.
Calibration
Table of contents
Other Swegon Heat Pump manuals
Popular Heat Pump manuals by other brands

evoheat
evoheat Evo270-1 Installation & operation manual

LK Armatur
LK Armatur SmartSolar LK 202 instruction manual

Carrier
Carrier 50KQ006-019 Installation, Start-Up and Service Instructions

C.P.A.
C.P.A. CLIMEXEL Series manual

Omega
Omega VSHPe Series Installation and operation manual

NeoRe
NeoRe TG MINI Series user manual

Olimpia splendid
Olimpia splendid Sherpa 8M Instructions for installation, use and maintenance

Dimplex
Dimplex LIK 8TE Installation and operating instructions

Daikin
Daikin EKHH2E200AAV3 Installation and user manual

Daikin
Daikin EHVZ-E9W User reference guide

Robur
Robur K18 Simplygas Installation, use and maintenance manual

LG
LG THERMA V owner's manual