SymCom MOTORSAVER 460 User manual

INSTALLATION INSTRUCTIONS FOR SYMCOM’S
MOTORSAVER®MODEL 460
BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!!
FOLLOW NATIONAL, STATE AND LOCAL CODES!
CONNECTIONS
1. Mount the MOTORSAVER®in a convenient location in or near the motor control panel. If the
location is wet or dusty, then the MOTORSAVER®should be mounted in a NEMA 4 or 12
enclosure. The 460 can be mounted to a back panel using two #6 or #8 x 5/8 screws or can be
snapped on to a DIN rail.
2. Connect L1, L2 and L3 on the MotorSaver’s terminal strip to the LINE SIDE of the motor starter.
(See Figure No. 1).
3. Connect the output relay to the circuitry to be controlled. Connect the normally open contact in
series with the magnetic coil of the motor starter as shown in Figure No. 1 for motor control.
Connect normally closed contact in control circuit as shown in figure No. 2 for alarm operation.
Figure No. 1: Motor Control Wiring Diagram
LIGHT
Figure No. 2: Alarm Wiring Diagram
2880 North Plaza Drive, Rapid City, SD 57702 •(800) 843-8848

SETTINGS
1. LINE VOLTAGE ADJUSTMENT:Rotate the LINE VOLTAGE
ADJUSTMENT to the nominal three-phase line voltage
feeding the motor to be protected. The Model 460 will
automatically sense whether it is connected to a 200V or
400V 60 Hz or 380V - 416V 50Hz power system.
2. RESTARTdelay: Rotate the RESTART delay to the
desired position. The restart delay is the time between the
MOTORSAVER®seeing acceptable power and the
MOTORSAVER®closing its output contacts. For compressor
applications, the restart delay should be set for the
approximate time it takes for the head pressure to bleed
off of the compressor. For other applications, the restart
delay is typically set at 2 seconds.
(NOTE: This delay is also the minimum cycle time or rapid
cycle timer for the motor or compressor when control power
is lost such as the operation of a Thermostat.)
3. UNBALANCE TRIP: Rotate the UNBALANCE TRIP to the
desired voltage unbalance trip level. The NEMA MG1
standard does not recommend operating a motor above a
1% voltage unbalance as determined by the following formula
without derating the motor.
% Voltage Unbalance = [(Maximum Deviation from the Average) / Average] x 100%
The NEMA MG1 standard also recommends against operating a motor above a 5% voltage unbalance
under any circumstances. Therefore, a 5% setting on "UB" is a good place to start but SymCom
recommends consulting the motor manufacturer for specific tolerances.
4. TRIP DELAYADJUSTMENT:Rotate the TRIP DELAY ADJUSTMENT to the desired setting.
The adjustment does not affect the trip delay on a single-phasing fault. Typically, the TRIP DELAY
ADJUSTMENT is set to 4 seconds. In areas where voltage fluctuations are frequent, the TRIP DELAY
ADJUSTMENT may be set between 10 and 20 seconds.
POWER-UP
Turn on the power to the motor. The green RUN LIGHT will blink during the RESTART delay.
After the RESTART delay, the MOTORSAVER®will energize its output contacts and the green RUN
LIGHT will light. If the contacts do not energize and the RUN LIGHT does not light, then see the
TROUBLESHOOTING section.
CONGRATULATIONS!!! YOU HAVE JUST INSTALLED
THE FINEST MOTOR PROTECTION AVAILABLE!
HAVE QUESTIONS? CALL 1-800-843-8848
08/02 - 2 -

MOTPMYS THGIL
NRETTAPNRETTAP NRETTAP NRETTAPNRETTAP NOITULOS
tinuehT.noerasthgiloN
.daedyletelpmocsmees AN
eht,CAV051woleberasegatlovehtfoynafI.segatlovenil-ot-enileerhtehterusaeM
.scinortcelelanretnistietarepootrewophguoneevahtonseod064ledoM
.metsysdesahp-elgnisanoruccoyamsihT
.8488-348-008-1@moCmySllac,tcerrocerasegatlovehtfI
nogniknilbsithgildeR
.purewopnoitallatsnilaitini
.3Lro2L,1L:064ledoMehtgnirewopsdaelowtynapawS.rewopesahp-eerhtehtffonruT
nonruT.emittsrifehtyltcerrocpu3Ldna2L,1Lgnitcennocfoecnahc05-05aevahuoY
.rewopesahp-eerhteht
gniknilbsithgildeR
neebsahrotomehtretfa
.gninnurylsuoiverp
rotomehtgnitneverpsi064ledoMehT.desahpesreverneebevahsenilgnimocniehT
.ecneuqesesahpehttcerroC.sdrawkcabgninnurmorf
gniknilbsithgildeR
.nrettapsihtni
ecnalabnu%etaluclacdnasegatlovenilgnimocnierusaeM.ecnalabnuegatlovsetacidnI
ehtnotesecnalabnu%ehtdeecxetonseodecnalabnuegatlovfI.1egapnonwohssa
tamoCmySllac,064ehttesertonseodsihtfI.nottubteserlaunamehtgnisserpyrt,tnorf
.8488-348-008-1
.ydaetsnosithgildeRAN
ehtfI.segatloveerhtehtfoegarevaehtetaluclaC.segatlovenil-ot-enileerhtehterusaeM
neht,TSUJDAEGATLOVENILybtessaegatlovlanimonehtfo%7–foedistuosiegareva
gnisserpyrt,wodniwteserehtnihtiwsiegatlovehtfI.ylreporpgninoitcnufsi064ledoMeht
.8488-348-008-1@moCmySllac,064ehttesertonseodsihtfI.nottubteserlaunameht
tubsknilbthgilneerG
.tratstonseodrotom
.yaledtratsernisi064ledoMehT
)ecalpnisirepmujteserlaunamehtnehwylnosruccosihT(
tubydaetsnosithgilneerG
.tratstonseodrotom AN. sehctiwsgninoitcnuflamroseriwesoolroftiucriclortnockcehC
thgilneergdnadeR
nosinunihsalf .teserlaunamarofgnitiawsi064ehT
INDICATOR LIGHT DIAGNOSTICS
TROUBLESHOOTING
- 3 - 08/02

SymCom warrants its microcontroller based products against defects in material or workmanship for a
period of five (5) years from the date of manufacture. All other products manufactured by SymCom shall
be warranted against defects in material and workmanship for a period of two (2) years from the date of
manufacture. For complete information on warranty, liability, terms, returns, and cancellations, please
refer to the SymCom Terms and Conditions of Sale document.
08/02 - 4 -
Specifications
3-Phase Line Voltage ..................................190 - 480 VAC
......................................................................(475 - 600 VAC Optional)
......................................................................(95 - 120 VAC Optional)
Frequency ..................................................50* or 60 Hz
Low Voltage (% of set point)
•Trip ................................................................90% ±1%
•Reset ............................................................93% ±1%
High Voltage (% of set point)
•Trip ................................................................110% ±1%
•Reset ............................................................107% ±1%
Voltage Unbalance (NEMA)
•Trip ................................................................2 - 8% Adjustable
•Reset ............................................................Trip setting minus 1% (5 - 8%)
......................................................................Trip setting minus .5% (2 - 4%)
Trip Delay Time
•Low & High Voltage and Unbalance ............1 - 30 seconds adjustable
•Single Phasing Faults (>25% UB) ................1 second fixed
Restart Delay Time
•After a Fault ..................................................1 - 500 seconds adjustable
•After a Complete Power Loss ......................1 - 500 seconds adjustable
Output Contact Rating
•1-Form C ......................................................10 A General Purpose @240 VAC
......................................................................Pilot Duty 480VA @ 240 VAC, B300
Power Consumption ..................................6 Watts (Max.)
Weight ..........................................................14 oz.
Enclosure ......................................................polycarbonate
Terminal Torque............................................6lbs-in.
Wire Type ......................................................Stranded or solid 12-20 AWG, one per terminal
Safety Marks
•UL..................................................................UL508
•CE ................................................................IEC 60947-6-2
Standards Passed
•Electrostatic Discharge (ESD) ......................IEC 1000-4-2, Level 3, 6kV contact, 8kV air
•Radio Frequency Immunity, Radiated ..........150 MHz, 10V/m
•Fast Transient Burst......................................IEC 1000-4-4, Level 3, 3.5 kV input power & controls
Surge
•IEC ................................................................IEC 1000-4-5, Level 3, 4kV line-to-line;
......................................................................Level 4, 4kV line-to-ground
•ANSI/IEEE ....................................................C62.41 Surge and Ring Wave Compliance
......................................................................to a level of 6kV line-to-line
•Hi-potential Test ............................................Meets UL508 (2 x rated V +1000V for 1 minute)
Environmental
Temperature Range........................................Ambient Operating: -20°- 70°C (-4°- 158°F)
......................................................................Ambient Storage: -40°- 80°C (-40°- 176°F)
Class of Protection ........................................IP20, NEMA 1 (FINGER SAFE)
Relative Humidity ..........................................10-95%, non-condensing per IEC 68-2-3
*Note: 50 Hz will increase all delay timers by 20%
Table of contents
Other SymCom Relay manuals
Popular Relay manuals by other brands

Schrack
Schrack LSZ6W Series Assembly

OEZ
OEZ MCR-TK-001-UNI Instructions for use

Pilz
Pilz PNOZ 16SP operating instructions

LOVATO ELECTRIC
LOVATO ELECTRIC PMV95N***NFC Series user manual

RIESE
RIESE SAFE 2 operating instructions

Hydrolevel Company
Hydrolevel Company HYDROZONE 6000 Series Installation instructions and operating manual

Reznor
Reznor EGHB Series installation instructions

I-Gard
I-Gard SIGMA 3 manual

Schweitzer Engineering Laboratories
Schweitzer Engineering Laboratories SEL-352-1 instruction manual

SPEL
SPEL Smart4house RE-00 Series Installation and operating instructions

Velleman
Velleman VMA331 user manual

Circutor
Circutor RGU-2 instruction manual