manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tekmar
  6. •
  7. Thermostat
  8. •
  9. Tekmar 545 tekmarNet 4 User manual

Tekmar 545 tekmarNet 4 User manual

1 of 40 © 2005 D545 - 06/05
D545
06/05
tekmarNet®4 Thermostat 545
- Brochure
Information
Brochure
Choose controls
to match
application
1Application
Brochure
Design your
mechanical
applications
2Rough In
Wiring
Rough-in
wiring
instructions
3Wiring
Brochure
Wiring and
installation of
specific control
4Job
Record
Record settings &
wiring details for
future reference
6
Data
Brochure
Control settings
and sequence of
operation
5
•
• tN4 Compatible
•
• Automatic Heat/Cool Switchover
•
• 2 Auxiliary Temperature Sensor Inputs
•
• Pulse Width Modulation
•
• Programmable Setback and Setup Scheduling
•
• Scenes
•
• Cooling Group
•
• Radiant Base Load
The tekmarNet®4 thermostat 545 operates two stages of heating equipment, one stage of cooling equipment, and one fan.
The fan operation includes logic to operate ventilation. The 545 can operate as a stand alone device, or communicate with
a group of tekmarNet®4 thermostats.
Introduction
Features
Y1 Rc G1 G1
R
C
tN4
S1
S2
Com
W1
Rh1 Rh2
W2
© 2005 D545 - 06/05 2 of 40
Table of Contents
Table of Contents............................................................2
Display and DIP Switches ..............................................2
Dip Switches ...........................................................2
Access Levels .........................................................3
Display and Symbols Description ...........................3
User Interface .........................................................4
Setup ..............................................................................5
View Menu .............................................................5
Adjust Menu............................................................6
Time Menu ............................................................ 13
Scene Menu.......................................................... 14
Schedule Menu.....................................................16
Monitor Menu........................................................19
Test Menu ............................................................21
Miscellaneous Menu ............................................22
Testing .........................................................................23
Thermostat Operation ..................................................24
Auxiliary Sensors .................................................24
Heat or Cool Mode of Operation ..........................25
Adjusting the Temperature ...................................25
Cycles Per Hour ...................................................26
Heating Terminal Units .........................................26
Heating Operation ................................................27
Cooling Operation ................................................29
Cool Groups .........................................................29
Fan Operation ......................................................30
Filter Change .......................................................31
Time Clock ........................................................... 31
Setting the Schedule.............................................32
Optimum Start / Stop ...........................................33
Scenes .................................................................33
Away Hold ............................................................34
Radiant Base Load ..............................................35
Offset ...................................................................35
Warm Weather Shutdown ....................................35
Cold Weather Shutdown ......................................35
Units of Temperature ............................................35
Backlight ..............................................................35
tN4 Address .........................................................36
Error Messages ............................................................36
Cleaning the Thermostat ......................................39
Warranty .......................................................................40
Display and DIP Switches
Dip Switches
Y1 Rc G1 G1
R
C
tN4
S1
S2
Com
W1
Rh1 Rh2
W2
tN4 System Control (DIP Switch #2)
A tN4 System Control is a control, not a thermostat, that
the 545 thermostat connects to through the tN4 bus. All
tN4 compatible Outdoor Reset Modules are tN4 System
Controls.
•
• If the thermostat is connected to a tN4 System Control,
set the tN4 System Control DIP switch to tN4 System
Control.
•
• If the thermostat is not connected to a tN4 System
Control, set the tN4 System Control DIP switch to
None.
Lock/Unlock (DIP Switch #1)
Use the Lock/Unlock DIP switch to lock or unlock the
Access Level of the 545.
•
• To unlock the Access Level, set the DIP switch to the
unlocked position.
•
• To lock the Access Level, set the DIP switch to the locked
position. Once locked, a padlock is displayed in the lower
right corner of the display and the Access Level cannot
be changed.
Note: The tN4 System Control’s Lock/Unlock DIP switch
overrides the Lock/Unlock DIP switch on the 545. Set
the tN4 System Control’s Lock/Unlock DIP switch to the
Unlock position before Access Levels can be changed on
the thermostat.
3 of 40 © 2005 D545 - 06/05
Access Levels
The Access Level restricts the number of Menus, Items
and Adjustments that can be accessed by the user. The
Access Level setting is found in the Miscellaneous (MISC)
menu. Select the appropriate access level for the people
who work with the thermostat on a regular basis.
The 545 has five Access Levels:
•
• Advanced (ADV): access to all settings
•
• Installer (INST): settings required for installation
•
• User (USER): for property owners
•
• Limited (LTD): limited temperature adjustment
•
• Secure (SEC): for commercial and public installations
For more information, see the Misc (Miscellaneous) Menu
section.
In the following menu tables, the access level the item is
visable in is shown in the access column.
To adjust the Access Level:
1. Set the Unlock/ Lock DIP switch to the unlock position.
If a tN4 System Control is connected to the 545, the
Unlock/Lock DIP switch on the tN4 System Control
must be set to the unlock position.
2. Use the Menu button to select the Misc menu.
3. Use the Item button to select the Access menu item.
4. Use the Up and Down button to select the required
Access Level.
Display
Item Field
Displays an abbreviated
name of the selected item
Number Field
Displays the current value
of the selected item
Status Field
Displays the current status
of the control’s inputs,
outputs and operation
Menu Field
Displays the
current menu
Symbols Description
MODE OF OPERATION
Displays whether the device is in heating
or cooling mode.
FIRST STAGE HEAT
First stage heating is operating.
SECOND STAGE HEAT
Second stage heating is operating.
FIRST STAGE COOL
First stage cooling is operating.
FAN
Fan is operating.
FILTER
Replace the filter.
SCHEDULE MASTER
Indicates that this thermostat is a
schedule master.
tN4 COMMUNICATION
A tN4 network is detected.
COOL GROUP MASTER
This thermostat is a cool group master.
LOCK
The Access Levels are locked. A menu
option is visible but not adjustable.
OPTIMUM START / STOP
The Optimum Start or Optimum Stop
feature is active.
WARNING
An error is present.
TEMPORARY HOLD
The temperature has been temporarily
adjusted from the scheduled event.
SCHEDULED EVENT
Displays the current scheduled event.
© 2005 D545 - 06/05 4 of 40
User Interface
Continue
to next Item
Continue to next Menu
Continue
to next Item
Continue
to next Item
Use the User Interface available on the Liquid Crystal Display
(LCD) to setup and monitor the operation of the thermostat.
Use the four push buttons below the LCD (Menu, Item, Up,
Down) to select settings. As you enter settings, record the
settings in the Job Record J545.
Menu
The menus display in the Menu Field at the left of the
LCD.
Eight menus are available:
Adjusting a Setting
To adjust a setting:
1. Use the Menu button to select the appropriate menu.
2. Use the Item button to select a menu item.
3. Use the Up or Down button to adjust the setting.
Default Item
•
• To set the default item in the View Menu, display the
item for more than five seconds.
After navigating menus, the display reverts back to the
default item after 60 seconds of button inactivity.
Copy Settings
To save time in setting thermostats, you can copy the settings
from one tN4 thermostat to a second tN4 thermostat.
Refer to the COPY item in the Misc menu on page 22.
•
• View
•
• Adjust
•
• Time
•
• Scene
•
• Schedule
•
• Monitor
•
• Test
•
• Miscellaneous
To select a menu, press and release the Menu button.
Item
In each menu, a group of items can be selected. The
abbreviated name of the selected item displays in the Item
field of the LCD display.
•
• To view the next available item, press and release the
Item button.
•
• To view the previous item, hold down the Item button
and press and release the Up button.
5 of 40 © 2005 D545 - 06/05
Display Menus
View Menu (1 of 2)
Item Field Range
Access
Description
-58 to 212°F
(-50.0 to 100.0°C)
SEC
LTD
USER
INST
ADV
COOL AVERAGE SECTION H
Average room temperature of the cool group master
and members.
Note: This item is only available when Cooling Stage is
set to 1 and this thermostat is a cool group master.
-58 to 212°F
(-50.0 to 100.0°C)
SEC
LTD
USER
INST
ADV
ROOM SECTION A
Current air temperature in the room.
Note: This item is only available when the Room Sensor
is set to On or Sensor 1 or 2 is set to Room.
– – –, 40 to 95°F
(– – –, 4.5 to 35.0°C)
USER
INST
ADV
ROOM SET SECTION A
Selected room temperature.
Note: This item is only available when the Room Sensor
is set to On or Sensor 1 or 2 is set to Room.
– – – (if no recent
message),
-58 to 212°F
(-50.0 to 100.0°C)
SEC
LTD
USER
INST
ADV
OUTDOOR SECTION A
Current temperature at the outdoor sensor.
Note: This item is only available when an outdoor
sensor is connected to the tN4 network.
-58 to 212°F
(-50.0 to 100.0°C)
SEC
LTD
USER
INST
ADV
FLOOR SECTION A
Current floor temperature.
Note: This item is only available when Sensor 1 or
2 is set to Floor.
-58 to 212°F
(-50.0 to 100.0°C)
USER
INST
ADV
REMOTE SENSOR SECTION A
Current temperature at the remote sensor location.
Note: This item is only available when Sensor 1 is
set to Remote.
-58 to 212°F
(-50.0 to 100.0°C)
INST
ADV
COIL SENSOR SECTION A
Current temperature at the coil sensor.
Note: This item is only available when Sensor 2 is
set to Coil.
The View menu items display the current operating
temperatures and status information of the system.
Continued on next page.
VIEW MENU
© 2005 D545 - 06/05 6 of 40
Item Field Range
Access
Description
-58 to 212°F
(-50.0 to 100.0°C)
INST
ADV
DUCT SENSOR SECTION A
Current temperature at the duct sensor.
Note: This item is only available when Sensor 2 is
set to Duct.
-22 to 266°F
(-30.0 to 130.0°C)
INST
ADV
SUPPLY TEMPERATURE OF TN4 BUS
SECTION F
Actual water temperature of the tN4 bus for the first
stage of heat.
Note: This item is only available when the thermostat
is connected to an Outdoor Reset Module and the
DIP switch is set to tN4 System Control.
View Menu (2 of 2)
After the last item, the control returns to the first item in the menu.
VIEW MENU
Item Field Range Access Description
YES, NO
Default = NO
USER
INST
ADV
CLEAR FILTER SECTION J
Indicates when to reset the air filter timer.
Note: This item is only available when Filter is set to
ON, the air filter timer has expired and the Fan Mode
is set to 1 or 2.
OFF, HEAT,
AUTO, COOL
Default = AUTO
USER
INST
ADV
MODE OF OPERATION SECTION B
Mode of operation of the thermostat or cool group.
40 to 95°F
(4.5 to 35.0°C)
LTD
USER
INST
ADV
SET HEAT SECTION C
Selected air heating temperature for each event.
Note: At the Limited Access Level, you can only
adjust the temperature +/-3°F (1.5°C) from the last
setting.
Wake
Default = 70°F (21.0°C)
UnOccupied
Default = 62°F (16.5°C)
Occupied
Default = 70°F (21.0°C)
Sleep
Default = 62°F (16.5°C)
Away
Default = 62°F (16.5°C)
Adjust Menu (1 of 7)
The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.
Continued on next page.
ADJUST MENU
7 of 40 © 2005 D545 - 06/05
Item Field Range Access Description
50 to 100°F
(10.0 to 38.0°C)
LTD
USER
INST
ADV
SET COOL SECTION C
Select the cooling room temperature for each event.
Note: At the Limited Access Level, you can only
adjust the temperature +/-3°F (1.5°C) from the last
setting.
Wake
Default = 78°F (25.5°C)
UnOccupied
Default = 85°F (29.5°C)
Occupied
Default = 70°F (21.0°C)
Sleep
Default = 85°F (29.5°C)
Away
Default = 85°F (29.5°C)
OFF, 40 to 122°F
(OFF, 4.5 to 50.0°C)
LTD
USER
INST
ADV
FLOOR MINIMUM SECTION F
Select the minimum floor temperature for each
event.
Note: This item is only available when Sensor 1 or 2
is set to Floor. At the Limited Access Level, you can
only adjust the temperature +/-3°F (1.5°C) from the
last setting.
Wake
Default = 70°F (21.0°C)
UnOccupied
Default = OFF
Occupied
Default = 70°F (21.0°C)
Sleep
Default = OFF
40 to 122°F
(4.5 to 50.0°C)
Default = 85°F
(29.5°C)
ADV
FLOOR MAXIMUM SECTION F
Maximum floor temperature.
Note: This item is only available when Sensor 1 or
2 is set to Floor.
OFF, ROOM,
FLOR (Floor),
REM (Remote)
Default = OFF
INST
ADV
SENSOR 1 SECTION A
Select the type of sensor connected to auxiliary
sensor input 1.
OFF, ROOM,
FLOR (Floor),
OUT (Outdoor),
COIL, DUCT
Default = OFF
INST
ADV
SENSOR 2 SECTION A
Select the type of sensor connected to auxiliary
sensor input 2.
OFF, ON
Default = ON
INST
ADV
ROOM SENSOR SECTION A
Selects whether the built-in room sensor is functional.
Adjust Menu (2 of 7)
ADJUST MENU
Continued on next page.
© 2005 D545 - 06/05 8 of 40
Item Field Range Access Description
SYNC, AUTO
2 to 12
Default = AUTO
ADV
HEAT CYCLES PER HOUR SECTION D
Select the number of heating cycles per hour. SYNC
results in 5 CPH. All tN4 thermostats that are connected
and have the SYNC setting selected synchronize their
cycle to the same starting time.
Note: This item is only available when the tN4 System
Control DIP switch is set to Off.
CTRL, HRF1, HRF2,
COIL, CONV, RAD,
BASE, OTHR ,FURN
Default =CTRL
INST
ADV
HEAT 1 TERMINAL SECTION E
Select the type of heating terminal for first stage
heat.
Note: If CTRL is selected, the terminal unit selected
on the tN4 System Control is used.
OFF, ON
Default = ON
INST
ADV
HEAT 1 PUMP SECTION F
Select whether the system, primary, or mixing pump
on a tN4 System Control must operate while the first
stage heat is operating.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
OFF, ON
Default = OFF
INST
ADV
HEAT 1 DELAY SECTION F
Select whether the system, primary, or mixing pump
on a tN4 System Control is delayed to allow a first
stage heat thermal motor zone valve to open. Select
On for thermal motor, select Off for zone pump or
motorized zone valve.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
NONE, CTRL, HRF1,
HRF2, COIL, CONV,
RAD, BASE, OTHR,
FURN
Default =CTRL
INST
ADV
HEAT 2 TERMINAL SECTION E
Select the type of heating terminal for second stage
heat. If NONE is selected, the second stage heat is
disabled.
Note: If CTRL is selected, the terminal unit selected
on the tN4 System Control is used.
NONE, BOIL,
MIX1, MIX4
Default = BOIL
ADV
HEAT 2 SOURCE SECTION F
Select the tN4 bus on which the second stage
heat zone operates. This setting determines water
temperature and system pump operation.
Note: This item is only available when the H2 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
OFF, ON
Default = ON
INST
ADV
HEAT 2 PUMP SECTION F
Select whether the system, primary, or mixing pump
on a tN4 System Control must operate while the
second stage heat is operating.
Note: This item is only available when the H2 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
Adjust Menu (3 of 7)
Continued on next page.
ADJUST MENU
9 of 40 © 2005 D545 - 06/05
Item Field Range Access Description
OFF, ON
Default = OFF
INST
ADV
HEAT 2 DELAY SECTION F
Select whether the system, primary, or mixing pump
on a tN4 System Control is delayed to allow a second
stage heat thermal motor zone valve to open. Select
On for thermal motor, select Off for zone pump or
motorized zone valve.
Note: This item is only available when the H2 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
NONE, 1 to 16
Default = NONE ADV
COOL MASTER SECTION H
Select the cool group for which this thermostat is the
master. Select None if this thermostat is not a cool
group master.
Note: This item is only available when the thermostat
is connected to a tN4 network and the Cool Stage
is set to 1.
NONE, 1 to 16
Default = NONE ADV
COOL MEMBER SECTION H
Select the cool group of which this thermostat is a
member. Select None if this thermostat is not a cool
group member.
Note: This item is only available when the thermostat
is connected to a tN4 network, Cool Master is set to
NONE and the Cool Stage is set to NONE.
NONE, 1
Default = 1
INST
ADV
COOL STAGES SECTION G
Select the number of cooling stages. Select None if
cooling is not used.
0:30 to 6:00 min
Default = 2:00 ADV
MINIMUM COOL RUN TIME SECTION G
Select the minimum running time for the cooling
equipment.
Note: This item is only available when the Cool Stage
is set to 1.
0:30 to 10:00 min
Default = 5:00 ADV
MINIMUM COOL OFF TIME SECTION G
Select the minimum off time for the cooling
equipment.
Note: This item is only available when the Cool Stage
is set to 1.
AUTO, 2 to 12
Default = AUTO ADV
COOL CYCLES PER HOUR SECTION D
Select the number of cooling cycles per hour.
Note: This item is only available when the Cool Stage
is set to 1.
10 to 180 min
Default = 30 ADV
INTERLOCK SECTION G
Select how long heating must be off before cooling
starts.
Note: This item is only available when the Cool Stage
is set to 1.
Adjust Menu (4 of 7)
Continued on next page.
ADJUST MENU
© 2005 D545 - 06/05 10 of 40
Item Field Range Access Description
HEAT, COOL
Default = COOL ADV
PRIORITY HEATING OR COOLING SECTION G
Select whether heating has priority or cooling has
priority.
Note: This item is only available when the Cool Stage
is set to 1.
NONE, 1, 2
Default = 1
INST
ADV
FAN MODE SECTION I
Select the operation of the Fan 1 output.
OFF, ON
Default = OFF ADV
FAN 1 VENTILATION SECTION I
Select whether Fan 1 output operates to provide
ventilation.
Note: This item is only available when the Fan Mode
is set to None.
OFF, 1 to 60 min
Default = OFF ADV
VENTILATION PRE-VENT SECTION I
Select how long the ventilation operates continuously
prior to the Wake or Occupied events.
Note: This item is only available when the Fan Mode
is set to None and F1 Vent is set to On.
AUTO, OFF,
10% to 80%, ON
Default = AUTO
LTD
USER
INST
ADV
FAN OPERATION SECTION I
The minimum percentage of time the ventilation fan
operates during each event.
Auto operates with heat or cool.
On operates continuously.
% sets a minimum On time for each cycle.
Note: This item is only available when the Fan Mode
is set to 1 or F1 Vent is set to On.
Wake
UnOccupied
Occupied
Sleep
OFF, 70 to 180°F
(OFF, 21.0 to 82.0°C)
Default = 110°F
(43.0°C)
ADV
HEAT COIL MINIMUM SECTION I
Set the minimum coil temperature before turning on
the fan for heating. This allows the fan coil to heat up
and prevents the fan from blowing cold air.
Note: This item is only available when H1 or H2
Terminal is set to Coil, Sensor 2 is set to Coil and
Fan Mode is set to 2.
40 to 80°F, OFF
(4.5 to 26.5°C, OFF)
Default = OFF
ADV
COOL COIL MAXIMUM SECTION I
Set the maximum coil temperature before turning on
the fan for cooling. This allows the fan coil to cool off
and prevents the fan from blowing hot air.
Note: This item is only available when Cool Stage
is set to 1, Sensor 2 is set to Coil and Fan Mode is
set to 1 or 2.
Adjust Menu (5 of 7)
Continued on next page.
ADJUST MENU
11 of 40 © 2005 D 545 - 06/05
Item Field Range Access Description
0:00 to 2:00 min
(10 sec increments)
Default = 0:30
ADV
FAN DELAY SECTION I
Set the fan’s delay time after a heating zone calls for
heat. This allows the fan coil to heat up and prevents
the fan from blowing cold air.
Note: This item is only available when H1 or H2
Terminal is set to Coil or Furnace, Sensor 2 is not
set to Coil and Fan Mode is set to 1 or 2.
0:00 to 3:00 min
(10 sec increments)
Default = 0:30
ADV
FAN PURGE SECTION I
Set how long the fan operates after the call for heat
stops. This purges heat remaining in the fan coil.
Note: This item is only available when H1 or H2
Terminal is set to Coil or Furnace, Sensor 2 is not
set to Duct and Fan Mode is set to 1 or 2.
70 to 160°F, OFF
(21.0 to 71.0°C, OFF)
Default = 110°F
(43.0°C)
ADV
HEAT PURGE FAN SECTION I
Set the minimum duct temperature. This purges heat
from the coil after the call for heat is removed.
Note: This item is only available when H1 or H2
Terminal is set to Coil or Furnace, Sensor 2 is set to
Duct and Fan Mode is set to 2.
OFF, 40 to 70°F
(OFF, 4.5 to 21.0°C)
Default = 60°F
(15.5°C)
ADV
COOL PURGE FAN SECTION I
Set the maximum duct temperature. This purges cooling
from the coil after the call for cooling is removed.
Note: This item is only available when Cool Stage
is set to 1, Sensor 2 is set to Duct and Fan Mode is
set to 1 or 2.
OFF, 200 to 2000 hr
Default = 500 hr
INST
ADV
FILTER SECTION J
Set the number of hours Fan 1 should operate before
you replace the filter. When the time expires, the filter
symbol appears.
Note: This item is only available when the Fan Mode
is set to 1 or 2.
NONE, ZONE, CTRL
Default = CTRL ADV
WARM WEATHER SHUT DOWN SECTION R
Set the outdoor temperature at which warm weather
shutdown occurs. Select whether the thermostat
follows the tN4 System Control’s or the zone’s WWSD
for scheduled events.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 72°F
(22.0°C)
INST
ADV
WWSD OCCUPIED AND WAKE SECTION R
Set the Warm Weather Shut Down (WWSD) temperature
during Occupied and Wake events.
Note: This item is only available when WWSD is set
to Zone.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 60°F
(15.5°C)
INST
ADV
WWSD UNOCCUPIED AND SLEEP SECTION R
Set the Warm Weather Shut Down temperature during
Unoccupied and Sleep events.
Note: This item is only available when WWSD is set
to Zone.
Adjust Menu (6 of 7)
Continued on next page.
ADJUST MENU
© 2005 D545 - 06/05 12 of 40
Item Field Range Access Description
OFF, 35 to 100°F
(OFF, 1.5 to 38.0°C)
Default = OFF
ADV
CWSD OCCUPIED AND WAKE SECTION S
Set the Cold Weather Shut Down (CWSD) temperature
for the cooling system during the Occupied and Wake
events.
Note: This item is only available when Cool Stage
is set to 1.
OFF, 35 to 100°F
(OFF, 1.5 to 38.0°C)
Default = OFF
ADV
CWSD UNOCCUPIED AND SLEEP SECTION S
Set the Cold Weather Shut Down temperature for
the cooling system during the Unoccupied and Sleep
events.
Note: This item is only available when Cool Stage
is set to 1.
HEAT, COOL,
H/C, OFF
Default = H/C
INST
ADV
OPTIMUM START / STOP SECTION M
Select whether to use Optimum Start / Stop for heating,
cooling, or both.
Note: This item is only available when either a heating
schedule and / or a cooling schedule is selected.
Lo, 2, 3, Hi
Default = Hi ADV
RADIANT BASE LOAD SECTION P
Select the radiant heating load relative to the overall
heating load.
Note: This item is only available when H1 Terminal
is set to HRF1 or HRF2. H2 Terminal is set to Coil,
Convector, Radiator, Baseboard or Other, and Sensor
1 and 2 are not set to FLOR.
Adjust Menu (7 of 7)
ADJUST MENU
After the last item, the control returns to the first item in the menu.
13 of 40 © 2005 D545 - 06/05
Item Field Range
Access
Description
SUNDAY, MONDAY,
TUESDAY,
WEDNESDAY,
THURSDAY, FRIDAY,
SATURDAY
Default = MONDAY
SEC
LTD
USER
INST
ADV
CURRENT TIME AND DAY SECTION K
Displays the current time and day of the week. The
time and date flash if the time is not set.
Default = JAN 01 2005
USER
INST
ADV
CURRENT DATE SECTION K
Display the current month, day, and year. Use this date
to determine daylight savings time.
Note: This item is only available when Daylight Savings
Time (DST) is set to On.
12:00 to :59
Default = :12:00 AM
USER
INST
ADV
CLOCK MINUTES SECTION K
Set the minutes.
12:00 AM to
11:59 PM or
00:00 to 23:59
Default = 12:00 AM
USER
INST
ADV
CLOCK HOURS SECTION K
Set the hours.
SUNDAY ...
WEDNESDAY ...
SATURDAY
Default = SUNDAY
USER
INST
ADV
DAY OF THE WEEK SECTION K
Set the day of the week.
ON to OFF
Default = OFF
INST
ADV
DAYLIGHT SAVINGS TIME SECTION K
Selects whether to use Daylight Savings Time. The
time is automatically adjusted if set to ON.
JAN, FEB,
MAR ... DEC
Default = JAN
USER
INST
ADV
MONTH SECTION K
Set the current month of the year.
Note: This item is only available when Daylight Savings
Time is set to ON.
The Time menu items set the time clock, day and date.
Time Menu (1 of 2)
TIME MENU
Continued on next page.
© 2005 D545 - 06/05 14 of 40
Item Field Range
Access
Description
01 ... 31
(number of days is
dependent on month)
Default = 01
USER
INST
ADV
DAY OF THE MONTH SECTION K
Set the day of the month.
Note: This item is only available when Daylight Savings
Time is set to On.
2000 ... 2255
Default = 2005
USER
INST
ADV
YEAR SECTION K
Set the current year.
Note: This item is only available when Daylight Savings
Time is set to On.
12 hr to 24 hr
Default = 12 ADV
MODE SECTION K
Select whether time should be displayed using a 12
or a 24 hour clock.
Time Menu (2 of 2)
TIME MENU
After the last item, the control returns to the first item in the menu.
Item Field Range
Access
Description
Occ
Away
PERM1
PERM Away 2
PERM UnOcc 3,
PERM 4
PERM5
TMPY Occ 6
TMPY7
TMPY 8
Default = Occ PERM 1
USER
INST
ADV
SELECT SECTION N
Select the scene for the building.
Note: Only Occ and AWAY are available when either
no schedule is selected or the SCENE menu is set
to OFF.
INF, 1 to 180 days
Default = INF
USER
INST
ADV
AWAY HOLD SECTION O
Set the number of days for the Permanent Away 2
scene. When the scene is selected, the thermostat
remains in that scene for the set number of days then
reverts to the last permanent scene.
Schd1
Wake 1
Occ1
UnOcc1
Sleep1
Away 1
Default = SCHD
INST
ADV
SET PERMANENT 1 SECTION N
Select an action for the Permanent 1 scene.
Note: This item is only available when SCENE menu
is set to ON and a schedule has been selected.
Scene Menu (1 of 2)
The Scene Menu items set the current scene as well
as the scene settings.
Continued on next page.
SCENE MENU
15 of 40 © 2005 D545 - 06/05
Item Field Range
Access
Description
Schd4
Wake 4
Occ4
UnOcc4
Sleep4
Away 4
Default = SCHD
INST
ADV
SET PERMANENT 4 SECTION N
Select an action for the Permanent 4 scene.
Note: This item is only available when SCENE menu
is set to ON and a schedule has been selected.
Schd5
Wake 5
Occ5
UnOcc5
Sleep5
Away 5
Default = SCHD
INST
ADV
SET PERMANENT 5 SECTION N
Select an action for the Permanent 5 scene.
Note: This item is only available when SCENE menu
is set to ON and a schedule has been selected.
Schd7
Wake 7
Occ7
UnOcc7
Sleep7
Away 7
Default = SCHD
INST
ADV
SET TEMPORARY 7 SECTION N
Select an action for the Temporary 7 scene. The
scene lasts for 4 hours before reverting to the previous
permanent scene.
Note: This item is only available when SCENE menu
is set to ON and a schedule has been selected.
Schd8
Wake 8
Occ8
UnOcc8
Sleep8
Away 8
Default = SCHD
INST
ADV
SET TEMPORARY 8 SECTION N
Select an action for the Temporary 8 scene. The
scene lasts for 8 hours before reverting to the previous
permanent scene.
Note: This item is only available when SCENE menu
is set to ON and a schedule has been selected.
1:00 to 10:00 hr
(½ hr intervals)
Default = 3:00
USER
INST
ADV
TEMPORARY ZONE HOLD SECTION C
Select the number of hours the temporary hold affects
this zone.
OFF. ON
Default = OFF
INST
ADV
SCENE MENU SECTION N
Select the Scene feature of the thermostat.
Scene Menu (2 of 2)
SCENE MENU
After the last item, the control returns to the first item in the menu.
© 2005 D545 - 06/05 16 of 40
Item Field Range
Access
Description
NONE, ZONE,
MST1, MST2,
MST3, MST4,
MBR1, MBR2,
MBR3, MBR4
Default = NONE
USER
INST
ADV
HEAT SCHEDULE SECTION L
If a schedule is not required, select NONE.
If the schedule is only used by this thermostat, select
ZONE.
If the schedule is shared with other thermostats,
select MST1 to MST4.
If the schedule is set on another thermostat, select
MBR1 to MBR4.
Note: This item is only available when the COOL SCH
is set to either NONE or MBR1 to MBR4. This item
can be viewed in the USER and INST access levels
but can only be adjusted in the ADV access level.
NONE, ZONE,
MST1, MST2,
MST3, MST4,
MBR1, MBR2,
MBR3, MBR4
Default = NONE
USER
INST
ADV
COOL SCHEDULE SECTION L
If a schedule is not required, select NONE.
If the schedule is only used by this thermostat, select
ZONE.
If the schedule is shared with other thermostats,
select MST1 to MST4.
If the schedule is set on another thermostat, select
MBR1 to MBR4.
Note: This item is only available when the HEAT SCH
is set to either NONE or MBR1 to MBR4. This item
can be viewed in the USER and INST access levels
but can only be adjusted in the ADV access level.
24 hr, 5-2,
5-11, 7dAY
Default = 5-11
USER
INST
ADV
SCHEDULE TYPE SECTION L
Select the type of schedule.
Note: This item is only available when the Heat or
Cool Schedule are set to ZONE or MST1 to MST4.
2 (Occ, UnOcc),
4 (Wake, UnOcc,
Occ, Sleep)
Default = 4
USER
INST
ADV
SCHEDULE MODE SECTION L
Select the number of events per day.
Note: This item is only available when the Heat or Cool
Schedules are set to ZONE or MST1 to MST4.
Schedule Menu (1 of 4)
The Schedule menu items set the schedule type, the
number of events per day, and the event times.
Continued on next page.
SCHEDULE MENU
17 of 40 © 2005 D545 - 06/05
Item Field Range
Access
Description
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM
USER
INST
ADV
ALL DAYS OF THE WEEK SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 24 hr.
Wake Default = 6:00 AM
UnOccupied
Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM
USER
INST
ADV
MONDAY THROUGH FRIDAY SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 5-2 or 5-11.
Wake Default = 6:00 AM
UnOccupied
Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM
USER
INST
ADV
SATURDAY AND SUNDAY SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 5-2.
Wake Default = 6:00 AM
UnOccupied
Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM
USER
INST
ADV
SATURDAY SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 5-11 or 7dAY.
Wake Default = 6:00 AM
UnOccupied
Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
Schedule Menu (2 of 4)
Continued on next page.
SCHEDULE MENU
© 2005 D545 - 06/05 18 of 40
Item Field Range
Access
Description
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM
USER
INST
ADV
SUNDAY SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 5-11 or 7dAY.
Wake Default = 6:00 AM
UnOccupied Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM
USER
INST
ADV
MONDAY SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 7dAY.
Wake Default = 6:00 AM
UnOccupied Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM
USER
INST
ADV
TUESDAY SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 7dAY.
Wake Default = 6:00 AM
UnOccupied Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM
USER
INST
ADV
WEDNESDAY SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 7dAY.
Wake Default = 6:00 AM
UnOccupied Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
Schedule Menu (3 of 4)
Continued on next page.
SCHEDULE MENU
19 of 40 © 2005 D545 - 06/05
Item Field Range
Access
Description
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM USER
INST
ADV
THURSDAY SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 7dAY.
Wake Default = 6:00 AM
UnOccupied Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
– –:– – to 11:50 PM
or
– –:– – to 23:50 PM USER
INST
ADV
FRIDAY SECTION L
Select the times for the scheduled events.
Note: This item is only available when the Schedule
Type is set to 7dAY.
Wake Default = 6:00 AM
UnOccupied Default = 8:00 AM
Occupied Default = 6:00 PM
Sleep Default = 10:00 PM
Schedule Menu (4 of 4)
After the last item, the control returns to the first item in the menu.
SCHEDULE MENU
Item Field Range
Access
Description
-76 to 149°F
(-60.0 to 65.0°C)
LTD
USER
INST
ADV
OUTDOOR HIGH SECTION A
Records the highest outdoor temperature. Press Up
and Down buttons to clear.
Note: This item is only available when an outdoor
sensor is connected to the tN4 network.
-76 to 149°F
(-60.0 to 65.0°C)
LTD
USER
INST
ADV
OUTDOOR LOW SECTION A
Records the lowest outdoor temperature. Press Up
and Down buttons to clear.
Note: This item is only available when an outdoor
sensor is connected to the tN4 network.
-22 to 266°F
(-30.0 to 130.0°C)
USER
INST
ADV
ROOM HIGH SECTION A
Records the highest room temperature. Press Up
and Down buttons to clear.
Note: This item is only available when there is at
least one active room sensor.
Monitor Menu (1 of 2)
The Monitor menu items record the high and low
temperatures and the number of running hours of
mechanical equipment.
Continued on next page.
MONITOR MENU
© 2005 D545 - 06/05 20 of 40
Monitor Menu (2 of 2)
Item Field Range
Access
Description
-22 to 266°F
(-30.0 to 130.0°C)
USER
INST
ADV
ROOM LOW SECTION A
Records the lowest room temperature. Press Up and
Down buttons to clear.
Note: This item is only available when there is at
least one active room sensor.
50 to 120°F, OFF
(10.0 to 49.0°C, OFF)
Default = OFF
ADV
ROOM HOT SECTION A
Provides a warning message when the room temperature
exceeds this setting.
Note: This item is only available when there is at
least one active room sensor.
OFF, 20 to 80°F
(OFF, -6.5 to 26.5°C)
Default = OFF
ADV
ROOM COLD SECTION A
Provides a warning message when the room temperature
drops below this setting.
Note: This item is only available when there is at
least one active room sensor.
0 to 9999 hr INST
ADV
HEAT 1 RUN TIME SECTION F
Records the number of hours that first stage heat
runs. Press Up and Down buttons to clear.
0 to 9999 hr INST
ADV
HEAT 2 RUN TIME SECTION F
Records the number of hours that second stage heat
runs. Press Up and Down buttons to clear.
Note: This item is only available when the thermostat
is used for two stage heating.
0 to 9999 hr INST
ADV
COOL RUN TIME SECTION G
Records the number of hours that first stage cool
runs. Press Up and Down buttons to clear.
Note: This item is only available when the thermostat
is used for cooling.
0 to 9999 hr INST
ADV
FAN RUN TIME SECTION I
Records the number of hours that the Fan runs. Press
Up and Down buttons to clear.
Note: This item is only available when Fan Mode is
set to 1 through 5, or Fan 1 Vent is set to On.
After the last item, the control returns to the first item in the menu.
MONITOR MENU

Other Tekmar Thermostat manuals

Tekmar Eight Stage Boiler Control 258 User manual

Tekmar

Tekmar Eight Stage Boiler Control 258 User manual

Tekmar 509 User manual

Tekmar

Tekmar 509 User manual

Tekmar D 507 User manual

Tekmar

Tekmar D 507 User manual

Tekmar 519 User manual

Tekmar

Tekmar 519 User manual

Tekmar tNt 540 User manual

Tekmar

Tekmar tNt 540 User manual

Tekmar tekmarNet 553 User manual

Tekmar

Tekmar tekmarNet 553 User manual

Tekmar tekmarNet 2 House Control 402 User manual

Tekmar

Tekmar tekmarNet 2 House Control 402 User manual

Tekmar 528 User manual

Tekmar

Tekmar 528 User manual

Tekmar 561 User manual

Tekmar

Tekmar 561 User manual

Tekmar 538 User manual

Tekmar

Tekmar 538 User manual

Tekmar 4 Series User manual

Tekmar

Tekmar 4 Series User manual

Tekmar tekmarNet 2 Thermostat 529 User manual

Tekmar

Tekmar tekmarNet 2 Thermostat 529 User manual

Tekmar 521 User manual

Tekmar

Tekmar 521 User manual

Tekmar tekmarNet 552 User manual

Tekmar

Tekmar tekmarNet 552 User manual

Tekmar tekmarNet 4 User manual

Tekmar

Tekmar tekmarNet 4 User manual

Tekmar Invita User manual

Tekmar

Tekmar Invita User manual

Tekmar 308 User manual

Tekmar

Tekmar 308 User manual

Tekmar 511 User manual

Tekmar

Tekmar 511 User manual

Tekmar tekmarNet 553 User manual

Tekmar

Tekmar tekmarNet 553 User manual

Tekmar 562 User manual

Tekmar

Tekmar 562 User manual

Tekmar tekmarNet 552 User manual

Tekmar

Tekmar tekmarNet 552 User manual

Tekmar tekmarNet 532 User manual

Tekmar

Tekmar tekmarNet 532 User manual

Tekmar tekmarNet 552 User manual

Tekmar

Tekmar tekmarNet 552 User manual

Tekmar 508 User manual

Tekmar

Tekmar 508 User manual

Popular Thermostat manuals by other brands

Dometic Comfort Control Center 2 user guide

Dometic

Dometic Comfort Control Center 2 user guide

VERNAL TT-2W user guide

VERNAL

VERNAL TT-2W user guide

Carrier 33CS420-01 installation instructions

Carrier

Carrier 33CS420-01 installation instructions

TOTALINE Signature CPV210 owner's manual

TOTALINE

TOTALINE Signature CPV210 owner's manual

Bosch OR30 OT operating instructions

Bosch

Bosch OR30 OT operating instructions

Beretta Alpha 7D installer and user manual

Beretta

Beretta Alpha 7D installer and user manual

Salus HTRS230 Installer manual

Salus

Salus HTRS230 Installer manual

Emerson White-Rodgers 1F75H-21PR user manual

Emerson

Emerson White-Rodgers 1F75H-21PR user manual

DEVI DEVIreg Touch installation guide

DEVI

DEVI DEVIreg Touch installation guide

Theben RAMSES 722 operating instructions

Theben

Theben RAMSES 722 operating instructions

IDEAL Halo Combi RF installation guide

IDEAL

IDEAL Halo Combi RF installation guide

White Rodgers TYPE 152 installation instructions

White Rodgers

White Rodgers TYPE 152 installation instructions

White Rodgers 1F86-344 Installation and operation instructions

White Rodgers

White Rodgers 1F86-344 Installation and operation instructions

AMX PCC-300SR Specifications

AMX

AMX PCC-300SR Specifications

RCS TBZ48A installation guide

RCS

RCS TBZ48A installation guide

ritetemp 8082C Operation manual

ritetemp

ritetemp 8082C Operation manual

Satel ART-200 Quick installation guide

Satel

Satel ART-200 Quick installation guide

Watts Industries WATTSTEMP 8 series installation guide

Watts Industries

Watts Industries WATTSTEMP 8 series installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.