teko ASTRA-BRA User manual

Rev. BRA-v1_6_en
Astra-BRA
Addressable Relay Unit
User guide
This operating manual is intended to study the principle of operation, proper
use, storage and maintenance of the Astra-BRA addressable relay unit.The
manufacturer reserves the right to make changes to the design, firmware,
circuit solutions and product packaging that do not worsen its technical char-
acteristics, do not violate mandatory regulatory requirements, without prior
notice to the consumer.
Abbreviations:
SLC –Signaling line circuit;
ARM –Monitoring software;
IU -indication unit Astra-863;
BRA–Addressable relay unit Astra-BRA
Zone –notification source;
Tutorial - User guide built into the PKM Astra Pro or Astra-812 Pro setup
instructions (available on the website www.teko.biz);
Control Panel –control panel Astra-8945 Pro or Astra-812 Pro with firm-
ware version 5_0 and higher;
PKM Astra Pro –Astra Pro monitoring software package (available on the
website www.teko.biz);
Keypad –Astra-814 Pro control keypad;
RPA–signalling line extender "Astra-A RPA»;
LP–Laser pointer Astra-942»;
NC –normally closed;
NO –normally open;
AL –alarm loop.
1 Function
1.1 BRA is designed to control smoke ventilation dampers, fire dampers
of general ventilation, deluge dampers and other actuators powered by
220 V. The BRA is designed to operate in the SLC formed by the RPA.
1.2 BRA provides:
possibility to control the damper of fire dampers of types: electro-
mechanical with return spring, reversible, electromagnetic by command of
the Control Panel received via SLC;
monitoring the load of the relay for open and short circuits and trans-
ferring information about the integrity of the load line to the Control
Panel;
valve position control by limit switches;
LED indication of BRA operation, valve status, outputs and SLC;
Valve test
1.3 The BRA can operate in two modes:
“Valve” mode, in which the BRA implements special valve control algo-
rithms,
"Relay unit" mode, in which the BRA provides operation
one relay output with load circuit control.
In both modes, the BRA can operate with or without load continuity su-
pervision (depending on configuration)
1.4 The sources of notifications for the BRA are partitions of the Control
Panel.
1.5 BRA can only be controlled by one Control Panel.
1.6 BRA provides configuring of operating modes using the menu of the
PKM Astra Pro configuration module.
1.7 The BRA (signal part) is powered from the SLC power line (terminals "+"
and "-"), the power part (L1, N, L2) - from the 220 V AC network.
1.8 The power supply of the power part of the BRA (relay, AL) is carried out
from the main (terminals L1, N) and backup (terminals L2, N) 220 V power
supplies. In the absence of the main power supply, the BRA automatically
switches to the backup; when the main power is restored - switches to the
main power.
Attention!
ONLY 1 AND THE SAME PHASE CAN BE SUPPLIED TO INPUTS L1
AND L2! SUPPLY OF DIFFERENT PHASES IS FORBIDDEN!
2 Specifications
Power supply voltage, V:
- power unit..................................................................from 187 to 242 AC
- signal part (from SLC)............................................... from 6.0 to 27.6 DC
(power and signal parts are galvanically isolated)
Current consumption from 220 V, mA, not more ....................................20
Current consumption from SLC, mA, not more......................................0.5
Power consumption from 220 V (excluding consumption
valve),W, not more...................................................................................5
SLC interface cable length from BRA to RPA, m, max .......................1000
Number of relays .....................................................................................1
Relay specification (in "Relay unit" mode) (terminals
RAB and Ncl):
Maximum switching voltage, V.............................................................. 250
Maximum switching current at a voltage of 250 V, A................................1
Minimum switching current, mA *.......................................................... 0.6
AL Specification (terminals +Zone1- , +Zone2-, +TST-):
Standby voltage, V*...............................................................from 8.5 to 14
ripple voltage value on terminals AL, mV, no more................................ 50
Short circuit current AL, mA, no more.................................................... 20
AL integration time, msec ...............................................................300±30
AL wire resistance (excluding remote element), Ohm, no more ........... 150
Leakage resistance between loop wires or each
wire and "Ground", kOhm, not less than.................................................... 50
Loop resistance, kOhm....................................................... see tables 7, 8
Boot time, sec, not more........................................................................ 10
Overall dimensions, mm ........................................................ 216×135×39
Weight, kg, not more .......................................................................... 0.35
Operation conditions
Temperature range, ºС...................................................... from -30 to +55
Relative humidity .....................................................up to 93 at +40 0С
without moisture condensation
3 Delivery set
Relay unit wired address "Astra-BRA" ............................................1 pcs
Resistor 3.9 kOhm..........................................................................6 pcs
Screw.............................................................................................4 pcs
Dowel .............................................................................................4 pcs
Sticker............................................................................................2 pcs
4 Design
4.1 Structurally, the BRA is made in the form of a unit consisting of a base
and a removable cover. PCB with radio elements is mounted inside the
unit.
4.2 The PCB has indicators for monitoring the state of power supply and
outputs of the BRA:
- OPERATING LED –is for indicate the power supply status of the BRA
- OUTPUT LED - to display the status of the valve control outputs;
- STATUS LED - to display valve position and faults;
- SLC LED - status indication SLC BRA with RPA.
4.3 The PCB has a tampering switch to control the state of the case
(opened / closed).
4.4 The PCB has screw terminal units, the purpose of which is given in
the table 1.
Table 1
Terminal
Terminal function
А, В
Connection to the data L1 (L2) RPA
+, -
Connection to the power L1 (L2) RPA
+Zone1-
Connecting the valve limit switch
+Zone2-
Connecting the valve limit switch
+TST-
Connecting the TEST button
РАБ
Valve connection
Nкл
ИСХ
L1, N
Input for connecting the main power supply 220 V
L2, N
Input for connecting the main power supply 220 V
________________________________
* for relay in load circuit monitoring mode

Rev.BRA-v1_6_en
2
5 Indication
Table 2 –Notifications on the OPERATING LED and in the Control Panel
(for both modes)
Status
OPERATING LED
Control
Panel
Power-on test
X1 green/yellow altenate
switching on for 2 sec
-
Power at inputs L1 and L2
is norm
Green
+
No main power at inputs
L1)
x1 green flashes every 1 sec
+
No back up powerat inputs
L2)
x2 green flashes per sec
+
Generic failure
x1 yellow flash every sec
+
Firmware update
-
No L1 and L2 power sup-
ply
Off
+
"+" –notification issued, "–" –notification is not issued
Table 3 - Notifications to the OUTPUT LED and to the Control Panel (for
both modes)
Status
OUTPUT LED
Control
Panel
Power-on test
1 red/green alternate switching
on for 2 sec
-
Power supply at the out-
put of the РАБ is normal
x1 green flash every sec
+
Output power is normal
x2 green flashes every sec.
+
No power on
РАБ and ИСХ outputs
Off
-
Short circuit on one of
the outputs (РАБ or
ИСХ)
x2 yellow flashes every sec
+
Open circuit at one of the
outputs (РАБ or ИСХ)
x1 yellow flash every sec
+
"+" –notification issued, "–" –notification is not issued
Table 4 - Notifications to the STATUS LED and to the Control Panel
Status
STATUS LED
Control
Panel
Power-on test
x1 green/red alternate flash for 2
sec.
-
Initial
Solid green
+
Work
Solid red
+
Failure
x1 yellow flash every sec
+
Valve test
Solid Yellow
+
Condition change(
for the transition
delay time)
x2 green/red altenate flashes
every sec
+
"+" –notification issued, "–" –notification not issued
Table 5 - Notifications to the SLC LED and to the Control Panel
Status
SLC LED
Control
Panel
SLC power failure
3-times flashes with a period of 25
sec.
+
Laser pointer test*
x1 flash for 2 sec.
+
Registration (via LP) *
x1 flash for 2 sec
-
«*» - service indication used during commissioning and maintenance
of the BRA,
«+» – notification issued, «-»–notification not issued
6 BRA operating modes
6.1 BRA operating modes are set from the PKM Astra Pro software:
1) when specified from the PKM Astra Pro in the Configuration Module -
in the menu item Hardwired devices / List of hardwired devices / BRA,
6.2 In the window "Setting the BRA" select the device type (Valve or Re-
lay unit) and set its parameters.
Table 6 –Factory settings
Status
Initial condi-
tion
Range
Changes
Operating mode
Valve
Valve
Relay unit
Valve type
Closed
In the original closed
(Closed)
In the original opened
(Opened)
Control of the integrity
of the output circuits
РАБ, ИСХ
no
no; ИСХ+РАБ; ИСХ; РАБ
РАБ output control tac-
tics
No control
No control Switch on
Switch on for some time
(from 1 to 255 sec)
ИСХ output control
tactics
No control
No control Switch on
Switch on for some time
(from 1 to 255 sec)
Control time of the
valve to the operating
position
30 sec
from 1 to 255 sec
Control time for the
valve to return to its
initial position
30 sec
from 1 to 255 sec
Valve operating position
(Zone1)
Not used
In the “Valve” operating
mode, the following types
of loops are available:
- not used (no limit switch
control)
- valve position control -
"Limit switch closed"
- valve position control -
"Limit open"
Valve initial position
(Zone2)
Valve test (TST)
Not used
In the “Valve” operating ,
the following types of
loops available:
- valve test
- not used
6.3 «Valve»operating mode
6.3.1 “Valve” operating mode BRA:
1) controls the condition of the valve limit switches via AL1 иAL2
(+Zone1- and +Zone2-)
2) if the control of limit switches is not configured, then the BRA deter-
mines the position of the valve according to the state of the outputs РАБ
and ИСХ;
3) BRA through its AL (terminal TST) controls the state of the TEST but-
ton. According to the status of the alarm loop, the BRA generates a con-
trol impulse to transfer / return the valve to the working / initial state for
local control (operability check);
4) The BRA stores the current state of the valve, limit switches, the TEST
button, the state of the outputs РАБ and ИСХ, the state of the power
inputs L1 and L2 and, based on this information, generates control com-
mands to display the state on its own built-in indicators.
6.3.2 In the “Valve” mode, the BRA has no system outputs.
6.3.3 In the “Valve” operating mode, 3 types of loops are available for selec-
tion:
- «Limit switch closed»,
- «Limit switch open»,
- «Limit switch not active» (no limit switch control).
Table 7 –AL1 and AL2 parameters (Zone1)/(Zone2)
Type of limit
switch
Resistance, kOhm
0 –1.5
1.5–3
3 –5
5 -12
More
than
12
Limit switch
closed
short
circuit
Norm
Alarm
Alarm
Open
circ
Limit switch
open
short
circuit
Alarm
Norm
Alarm
Open
circ
End switch
not active
-
-
-
-
-
Note
1 When setting up, select the type of AL2, which is the opposite in mean-
ing to that selected for AL1 (if the type "Limit switch closed" is selected for
AL1, then the type "Limit switch is open" must be selected for AL2).
2 The determination of the state of the valve is always carried out by the
state of the two limit switches. Therefore, the setting should provide for
the use of only two limit switches at the same time, the limit switches
cannot be used separately.

Rev.BRA-v1_6_en
3
Table 8 –AL3 parameters (TST)
AL Type
Resistance, kOhm
0 –1.5
1.5–3
3 –5
5 -12
More
than
12
Valve test
short
circuit
violation
norm
violation
Open
circuit
Not used
-
-
-
-
-
6.4 Mode «Relay unit»
6.4.1 In the "Relay unit" mode, the BRA is one power relay output: (ter-
minals РАБ and ИСХ)
- open (off) –no 220 V power supply to the load;
- closed (on) –there is 220 V power supply to the load from one of the
power supply input lines L1 or L2 (with the ability to configure control of
load communication lines).
Notice - In the "Relay unit" operating mode, loops are not available The
tactics of the system output of the BRA is selected from the list offered in
the Configuration Module of the PKM Astra Pro software.
7 Preparing for operating and set up
7.1 After transportation under conditions different from the operating
conditions, the BRA should be kept unpacked in the operating conditions
for at least 4 hours.
7.2 BRA registration into RPA (Extender)
1) Connect RPA to Control Panel via RS-485 interface.
2) Register the RPA in the Control Panel in accordance with the Instructions
for Astra-812 Pro or the Instructions built into the Configuration Module of the
PKM Astra Pro software.
3) Connect the BRA to the power line (terminals "+", "-") and the infor-
mation line (terminals A and B) of the RPA, connect with the power off.
4) Turn on the power of the RPA, BRA.
5) Start the Registration mode of devices in the RPA on the Control
Panel using the command via the Astra Pro or Pconf-Pro PKM menu, or
the Astra-812 Pro Control Panel menu in accordance with the Instruc-
tions.
The mode takes 60 sec to register one device.
6) Run the registration mode on the BRA by lighting the SLC indicator
from the bottom button of the Astra-942 laser remote control for at least 1
sec.
Attention!
Simultaneous launch of the registration procedure on several ad-
dress devices is prohibited.
7) The registration test:
- in case of successful registration, the screen will display the
abbreviated name “BRA” or the message: “BRAxxx registered”,
- in case of unsuccessful registration, you must repeat the
registration.
8) After registration, the BRA indicators will display the current power and
load status in accordance with tables 2-5.
9) BRA registration is completed.
7.3 Removing BRA from RPA memory.
Deleting of the BRA from the RPA memory is carried out through the
Configuration Module of the Astra Pro PKM software, or from the Astra-
812 Pro control panel menu.
7.4 BRA setting
7.4.1 Setting and changing the operating modes of the BRA is performed:
1) using PKM Astra Pro from the menu item of the Configuration Module
of PKM Astra Pro "Hardwired devices / List of addressable devices /
BRAs",
In the window "Setting the BRA" select the device type (Valve or Relay
unit) and set its parameters.
7.4.2 All BRA notification sources in the "Valve" and "Relay unit" modes
must be assigned to technological partitions (to monitor the status of
"Tampering", "Power failure", "Short circuit" or "Open circuit" of communi-
cation lines with the relay, etc.), see table 9 .
7.4.3 The number of BRA’s notification sources and their purpose are pre-
sented in Table 9.
Table 9 –Display of BRA notification sources in Control Panel, PKM
BRA notification sources in "Valve"
operating mode
BRA notification sources in
“Valve” operating mode
BRA #ххх
BRA #ххх –Tamper status, com-
munication via SLC, power status
via SLC, status of power inputs L1
and L2, test by laser control panel.
BRA #ххх/1 –Control of the integ-
rity of the output line "WORK.";
Limit switch control (Zone 1).BRA
#ххх/2 –Control of the integrity of
the output line "OUT."; Limit switch
control (Zone 2).BRA #ххх/3 –
Checking the status of the "Test"
button.BRA #ххх/4 –Valve condi-
tion monitoring
BRA #ххх
BRA #ххх –Tamper status,
communication via SLC, power
status via SLC, status of power
inputs L1 and L2, test by laser
control panel.BRA #ххх/1 –
Control of the integrity of the
output line "Working"
To configure the display of the valve status on the Astra-863 indication
unit, on the System outputs/IU, select “Valve status display” and assign
the valves to the IU LEDs.
8 Installation
8.1 Specialists who have studied this user guide and are allowed to work
with electrical installations up to 1000 V are allowed to work on the instal-
lation, maintenance and operation of the BRA.
8.2 Installation, mounting-dismantling should be carried out with the pow-
er supply of the BRA turned off.
8.3 BRA is installed on the walls or other structures of the protected
premises in places protected from the effects of precipitation, mechanical
damage and access by unauthorized persons.
8.4 When installing, it is allowed to use mounting devices (cabinets, box-
es, etc.)
8.5 Installation order
1 Remove the cover by unscrewing the 2 screws on the bottom end
surface of the BRA housing
2 Mark the mounting holes on the bearing surface along the base of
the BRA, mount the fasteners
3 Conduct wires from the power supply, interfaces
RS-485, SLC, BRA outputs through wire entry hole.
4 Fix the BRA on the bearing surface with screws
5 Conduct electrical installation to the output terminals of the BRA in
accordance with Table 1 and the wiring diagram (p.9)
6 Replace the cover, tighten two screws.

Rev.BRA-v1_6_en
4
9 Wiringdiagram
R- resistance 3.9 kOhm ,
Е1- button with normally open contacts,
Е2- button with normally closed contacts,
K1, K2–valve limit switch
10 Test
Testing is taking place with one of two ways:
1 way –using button TEST which is connected to the TST terminal:
- set the TEST button to the “Violated” state (press or release depending
on the type and setting of the BRA);
- visually control the transition of the valve to the РАБ (operation) state,
then to ИСХ (initial);
- control the state of the valve in Astra Pro PKM (Astra-812 Pro Control
Panel, Astra-814 Pro keypad): after the test is completed, the status is
displayed as “Valve in the initial state”, which means that the equipment is
configured correctly. Otherwise, the status is displayed as “Failure” and
the BRA settings need to be adjusted.
2 way - using Astra-942:
-light up the SLC indicator of the BRA from the top button of the left side
for at least 1 sec;
- the test is performed in the same way as described in the first method.
If during the test execution the BRA receives a command from the control
panel, then the test execution is terminated, the new state “Transition to
...” is assigned to the valve state, the control panel generates the “Valve
test completed” event, and the BRA executes the command from the
control panel.
11 Warranty
The operation warranty period is 5 years from the date of operation start-
up, but no longer than 5 years 6 months from the date of manufacturing
subject to the requirements of User guide.
Manufacturer:
ZAO NTC TEKO
420108, Russia, Kazan,
Gafuri str., 71
Tel.:+7 843 528-03-69
www.teko.biz
Made in Russia
Other teko Relay manuals
Popular Relay manuals by other brands

Broyce Control
Broyce Control ELRV-30 quick start guide

GE
GE DIAC instruction manual

ABB
ABB Relion 615 series Protocol manual

Danfoss
Danfoss CS installation guide

Niko
Niko 10-831 quick start guide

Skuttle Indoor Air Quality Products
Skuttle Indoor Air Quality Products Current Sensing Relay A50 installation instructions

GE
GE CAL16A instructions

Mikro
Mikro RX330 user guide

Tridonic
Tridonic DALI RM CDM 30 10A 1CH manual

Leuze electronic
Leuze electronic MSI-SR5B Series Original operating instructions

Siemens
Siemens SIRIUS 3RP2005 Original operating instructions

KAEL Muhendislik Elektronik
KAEL Muhendislik Elektronik VARkombi-12-PC-TFT-OG manual