TeleAlarm RM-LES900 User manual

Wireless Smoke
Detector
RM-LES900
Wireless Smoke Detector RM-LES900 Page 1/7
Operating Instructions
Wireless Smoke Detector RM-LES900
1 Use, Transport and Storage
1.1 Use
The radio mounting base is intended solely for use in connection with the smoke detector
head for optical detection of smoke development from fire. It is for indoor use only.
Before you mount it, test the radio range at the installation site:
Put the battery into the radio base
Screw the smoke detector head into the radio base
Switch off all possible sources of electronic interference in the room, such as
televisions, radios, mobile phones and computers.
Prepare the TeleAlarm Carephone for connection
Press the alarm head – Warning: A short, loud signal will sound
Make sure the connection between the wireless smoke detector and the TeleAlarm
Carephone is working
Trigger a test alarm by pressing the smoke detector head
CAUTION
Danger of explosion and fire
Replacing the battery by an incompatible type or inserting it with reversed polarity can
cause excessive heat, fire or explosion.
Danger of hearing loss
The Wireless Smoke Detector generates a very loud and shrill tone. When testing its
function keep a minimum distance of 50cm or wear suitable ear protectors.
The alarm call should be triggered after pressing the alarm head just once.If the
alarm call is only triggered after repeatedly pressing the button, the radio connection is not
stable. Find another set-up location for the TeleAlarm Carephone and repeat the
connection test. Observe all provisions, norms and safety rules applicable at the
installation site.
Do not use in rooms where the ceiling is higher than 6m.

Wireless Smoke
Detector
RM-LES900
Wireless Smoke Detector RM-LES900 Page 2/7
1.2 Transport and Storage
The product can be damaged from improper transport and storage.
Only transport in the original packaging.
During storage and transportation, the specified ambient conditions must be
maintained.
The devices must be protected from impact when stored and during transport.
Failure to heed these instructions can lead to damage that does not fall under
guarantee and warranty.

Wireless Smoke
Detector
RM-LES900
Wireless Smoke Detector RM-LES900 Page 3/7
2 Product Description
2.1 Overview of Components
base plate
radio mounting base
assembly

Wireless Smoke
Detector
RM-LES900
Wireless Smoke Detector RM-LES900 Page 4/7
2.2 Function
The device only functions when fully assembled. The smoke detector head will not
function without the radio base. Each device has a unique identification code. If
using multiple Wireless Smoke Detectors, the Carephone can differentiate them
through their code.
2.3 Permit documents, certificates, declaration
The Wireless Smoke Detector RM-LES900 conforms to:
EMC Directive (2014/30/EU)
Low Voltage Directive (2014/35/EU)
RED Directive (2014/53/EU)
RoHS Directive (2011/65/EU)
EN62368 Safety Standard
EN14604 Smoke Alarm Device Standard
2.4 Technical Data
Radio Mounting Base
Dimensions (H × ØB)
22 × 86mm
52g
Weight
Material housing
PC/ABS
Colour
White, similar to RAL 9003
Operating temperature
+4° to +38°C
Storage temperature
-20° to +60°C
Max. humidity
90% (non-condensing)
Battery
CR 1/2AA – Varta 3.6V Lithium,
interchangeable, polarity indicated in
the overview of components
Protection class
III (EN 60730-1; SELV)
Ingress protection
IP 30 (EN 60529)

Wireless Smoke
Detector
RM-LES900
Wireless Smoke Detector RM-LES900 Page 5/7
Smoke Detector Head
Dimensions (ØB × H)
40 × 43mm
45g
Weight
Housing material
PC/ABS
Colour
White, similar to RAL 9003
Operating temperature
+4° to +38°C
Storage temperature
-20° to +60°C
Max. humidity
90% (non-condensing)
Smoke detector type
Optical
Area of use
Private apartments/houses; indoor
Battery
Lithium 3V, 1600mAh (not interchangeable)
lifetime
Minimum 8 years with normal use (one test
per week)
Status indicator
low battery
A brief tone sounds and the red LED blinks
every 48 seconds
When this display starts the smoke
detector’s alarm head can still be operated
for 30 days or emit an alarm for 4 minutes
when triggered
Normal operation
The red LED blinks every 48 seconds
Fire alarm
Three tones one after the other, LED blinks
every 0.5 seconds
Sound pressure level
85dB @ 3m
LED display
- Fire alarm
- Increased sampling
- Normal operation
- blinks every 0.5 seconds
- blinks every 2 seconds
- blinks every 48 seconds
Press button
- in normal operation
- in fire alarm
- Function test: tone and LED blinks
- Pressing the button mutes the alarm for 10
minutes
Permits
CNPP, AFNOR
EN 14604:2005, EN 60065
RoHS, REACH

Wireless Smoke
Detector
RM-LES900
Wireless Smoke Detector RM-LES900 Page 6/7
3 Assembly
3.1 Assemble radio base
When installing Wireless Smoke Detectors on the ceiling, a minimum distance of
50cm to the wall must be observed. On slanted roofs the highest point in the
ceiling should be selected. If installed on a wall, a minimum distance of 30cm and
a maximum distance of 50cm to the ceiling must be selected.
The base plate can be loosened from the radio mounting base by turning it.
Mount the base plate using the enclosed mounting materials (anchors and
screws).
When mounting, pay attention to the composition of the ceiling and the suitability
of the enclosed mounting materials. Select an installation site on the ceiling on
which secure mounting is possible.
Turn the radio mounting base on the base plate to lock it in place.
The smoke detector head must be inserted into the radio mounting base taking the
coding bar and locked into place by turning it with the help of the bayonet catch.
4 Operational Start-Up
4.1 Function test
Instruction
Do not press the button on the smoke detector head with pointed objects. Failure
to heed this instruction can damage it.
Press the button on the alarm head.
A signal tone will sound.
The LED will blink red twice.
A connection will be established with the Carephone.

Wireless Smoke
Detector
RM-LES900
Wireless Smoke Detector RM-LES900 Page 7/7
5 Maintenance
5.1 Maintenance Intervals
Interval
Job
1 × per month
Carry out a function test as described at
section 4.1
Before the end-of-life
date – see back of
smoke detector head
The smoke detector head must be replaced
5.2 Maintenance Work
Replace the smoke detector head
1. The bayonet catch between the smoke detector head and the
radio mounting base must be loosened.
2. The smoke detector head should be disposed of as described in section 6.
3. The new smoke detector head should be twisted into place in the radio
mounting base with the assistance of the bayonet catch until it audibly locks
in place.
6 Decommissioning and Disposal
The product must be disposed of in compliance with the applicable provisions,
norms and safety regulations.
Electronic components may not be disposed of as household waste.