Famco GST DC-9102E User manual

30312267 Issue 1.08
Features
Integrated algorithm of analyzing fire, recognize black smoke
quickly.
Drift sensitivity, suit to environment extensively.
Removable innovative sensing chamber, easy for maintenance.
The fire LED allows 360°viewing.
Providing remote terminals connect with remote indicator.
Featuring magnetic test.
2-level sensitivities (complying with EN 54-7 just when sensitivity is
level 1).
Description
DC-9102E Conventional Photoelectric Smoke Detector is a
new-generation product. With built-in microprocessor, the detector is
highly fixed with reliable fire judging program, which make it stable and
reliable performance.
When the detector checks fire signal, it will send fire information to the
control panel or addressable zone monitor unit by means of current
changing. The detector keeps turning on the LED to indicate alarm state
until it is reset.
The detector is developed from sensing chamber by scattering theory. It
has the ability to resist dust contamination and environmental light.
The detector utilizes drift compensation algorithm: When the environment
is changing, such as dust accumulation, humidity and temperature
changing, the detector can figure out these drift variation to make up for
sensitivity, thus the amount of smoke needed to generate an alarm
remains constant, irrespective of environmental conditions. The principle
diagram is shown as Fig. 1.
Smoke density Smoke density
a Fixed sensitivity b Environment value after drifting (prone
to nuisance alarm)
c Normal environment value A Variable sensitivity
Fig. 1
Connection and cabling
The orientation base is shown in Fig. 3.
C
B
A
Fig. 2 Fig. 3
There are four terminals with number on the base. “1”is connected with
output anode of addressable zone monitor unit or the anode of the power
supply; “2”is used as output, connected with anode of next detector
(Terminal 1) and also connected with anode of remote indicator; “3”is
connected with output cathode of addressable zone monitor unit or the
cathode of the power supply as well as the cathode of next detector; “4”
connects with the cathode of remote indicator.
Recommended Wiring
1.0mm2 or above fire cable for all terminals laid through metal conduit or
flame proof conduit, subject to local codes.
Note: Different color cables are used to avoid wiring mistake.
Installation
Fix the base with two taping screws. Then align A (Fig.2) on the bottom of
the detector to B (Fig.3) of the base, and rotate the detector clockwise to
mark C.
Mounting of the detector is shown in Fig.4.
Electrical Box
Conduit
Detector
51.5mm
Orientation Base
Fig. 4
Application
Notes: The alarm current depends on the current limit of the control
panel. 24VDC cannot power the detector directly. Otherwise the
detector will be blown up for lack of current limit resistor.
The sensitivity level 1 and polling LED status is “ON”are default, which
can be modified by P-9910B programmer.
Program parameters: In power-on state, input unlocking password and
press Clear to unlock. Press Function, then press “3”, the screen shows
“-” at the last digit. Input corresponding sensitivity or parameter and press
Program, the screen will show a “P”, the corresponding sensitivity or
parameter is programmed. Press Clear to clear the "P". Input locking
password and press Clear to return.
Table 1 Parameters Setup
Parameter
Smoke
Sensitivity
Polling LED
Status
1
1
ON
2
2
ON
129
1
OFF
130
2
OFF
Read sensitivity: On power-on time, press Test, the LCD screen shows
the address of the detector; Press Up, it shows in turn the sensitivity,
device type, initial sensitivity.
The detector is suitable for hotels, restaurants, office buildings, teaching
buildings, banks, warehouses, libraries, computer rooms and switch
rooms, etc.
When the detector connects with conventional fire alarm control
panel or addressable zone monitor unit from GST, and if DP-9907 Active
End of Line Unit is connected to the end of output loop, DB-01D base
should be used.
Used as the detector base, DP-9907 Active End of Line is
used to be installed a conventional detector on it. The system
connection is shown in Fig. 5.
O-
O+
Fig. 5
DC-9102E
Conventional Photoelectric
Smoke Detector
Time
Time
a
b
c
a
b
c
A
548d/03
2831-CPR-F0003
GST-0007-01
14

30312267 Issue 1.08
When DP-9907 Active End of Line Unit is not used as the
detector base, a cover should be added to it. The system
connection is shown in Fig.6.
Fig. 6
When the detector is connected with conventional fire alarm control
panel or the addressable zone monitor unit from GST, if a 4.7KΩ
terminal resistor is connected to the end of output loop, then DB-01 base
is used. The system connection is shown in Fig. 7.
O-
O+
Fig. 7
When a remote indicator connects with a few of detectors, a diode
1N5819 needs connecting with Terminal 4 of the orientation base in
series and with anode of the remote indicator. Either DB-01 or DB-01D is
used depends on which DP-9907 Active End of Line Unit or 4.7KΩ
terminal resistor is connected. The system composition is shown in Fig. 8.
O+
O-
Fig. 8
Output loop of the addressable zone monitor unit can be connected with
up to 15 conventional field devices. The addressable zone monitor unit
features loop checking. When the loop is broken, the addressable zone
monitor unit will send fault signal to fire alarm control panel. When any
field device in the output loop is removed, the addressable zone monitor
unit reports fault. If a DP-9907 Active End of Line Unit is connected, it will
not affect the normal operation of other field devices.
Testing
Before testing, please ensure that the detector has been installed
correctly and powered up. After 10 seconds, testing can begin.
1. The detector must be tested after installation and periodical
maintenance.
2. Testing method
1) Magnetic test
Magnetic test zone is shown in Fig. 9. Put the magnet of commission tool
close to that of the detector and hold on for a few seconds until the
detector generates alarm.
Test zone
Fig. 9 Fig. 10
2) Smoke test
Taking a cotton rope burning without flame close to the detector, blow the
smoke into the detector until the detector generates alarm.
3. After testing, cut power for 10 seconds at least and reset the detector.
Notify the proper authorities that the system returns to normal state.
Clean the failure detector in the test according to Maintenance, and test it
again. If it is still fail to pass, please return it to repair.
Maintenance
1. The detector should be installed just before commission and kept well
before installation, taken corresponding measures for dust-proof,
damp-proof and corrosion-proof.
2. The dust cover cannot be removed until the project has been plunged
into usage. Otherwise it can’t alarm normally.
3. Clean the detector at least once a year to ensure normal operation of
the system.
4. If nuisance alarms are often found of the detector on site, the sensing
chamber should be cleaned and replaced when necessary.
a) Open the top cover of detector, and draw out the sensing
chamber by slightly lifting its two sides using a straight
screwdriver, as shown in Fig. 10.
b) Clean the sensing chamber by alcohol cotton swab clipped by
tweezers, and also by clear water and brush. Please note not
to leave any cotton in the chamber.
c) Install the sensing chamber and top cover back.
5. Before cleaning, notify the proper authorities that the system is
undergoing maintenance and will temporarily be out of service. Disable
the zone or system undergoing maintenance to avoid unwanted alarms.
6. The detector should be tested again after cleaning and re-installing.
7. Protect the metal component on the PCB against damp and improper
distortion.
8. Fire simulation test should be made to the detector at least once half a
year.
Specification
Operating Voltage
24VDC(16VDC~28VDC )
Standby Current
≤60μA
Alarm Current
≤55mA
Fire LED
Red, periodically flash once in polling when
the status is set to “ON”; don’t illuminate when
the status is set to “OFF”. Periodically flash
twice in fault or sensing chamber dirty;
illuminate in alarming.
Remote indication
output
Polarity-sensitive output, directly connecting
with remote indicator (built in 10k resistor in
series, max. output current is 2mA); don’t
illuminate when in normal; flash in alarming.
Max. ripple
voltage
2V(peak to peak value)
Alarm reset
Instant power down (10s Min, 1.0VDC Max
Sensitivity setting
The sensitivity can be set by hand held
programmer. There are two sensitivity levels:
level 1 (default), level 2.
Wiring
Two-wire, polarity sensitive.
Environment
Temperature
-10℃~+50℃
Relative Humidity
≤95%, non condensing
Material
ABS
Ingress Protection
Rating
IP2X
Dimension
Diameter:100mm Height: 44.5mm (without
base)
Mounting Hole
Spacing
45mm~75mm
Weight
About 110g
Accessories and Tools
Model
Name
Remark
P-9910B
Hand held programmer
Supplied separately
DB-01
Base
Supplied separately
DB-01D
Base
Supplied separately
DP-9907
Active End of Line Unit
Supplied separately
T-MT
Commission tool
Supplied separately
WEEE Information
2012/19/EU (WEEE directive): Products marked with this
symbol cannot be disposed of as unsorted municipal waste in
the European Union. For proper recycling, return this product
to your local supplier upon the purchase of equivalent new
equipment, or dispose of it at designated collection points.
Limited Warranty
GST warrants that the product will be free from defects in design,
materials and workmanship during the warranty period. This warranty
shall not apply to any product that is found to have been improperly
installed or used in any way not in accordance with the instructions
supplied with the product. Anybody, including the agents, distributors or
employees, is not in the position to amend the contents of this warranty.
Please contact your local distributor for products not covered by this
warranty.
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
service.gst@fs.utc.com www.gst.com.cn

Description
DI-9102E Intelligent Photoelectric Smoke Detector is
addressable type fire detection device, build up fire alarm
system together with fire alarm panel and other alarm
devices. By light-scattering technology, the detector is
suitable for hotel, restaurant, office building, school, bank,
warehouse, library, computer room, switch room, and etc
Below figures show the detector bottom and terminals
of the base.
1.0mm2or above fire cable is recommended,but
subject to local codes.
There are four terminals with marks on the base.
1&3: Loop connection (non-polarized)
2: Positive terminal of remote indicator
4: Negative terminal of remote indicator
The base is suitable to be installed onto standard
European embedded back box, with hole-distance
45mm to 75mm
Terminals and Installation Holes
Features and Benefits
Recommended Cabling
http://www.gst.com.cn/en/index.asp
Gulf Security Technology Co., Ltd.
Page 1 / 2
DI-9102E
Intelligent Photoelectric
Smoke Detector
DS10106287
IMPORTANT: This publication is a generic version in which product information is shown for informational purposes only and does not constitute a
specific commitment or guarantee. We are constantly pursuing the improvement of product technology to improve product performance, for which
we reserve the right to adjust the configuration and technical information of the related products without notice. In addition, the description of
system performance in this publication applies only to the usual situation. As a result, there may be a variety of unpredictable special circumstanc-
es in the real world, so the realization of the relevant product performance will depend on the professional investigation and analysis and the
design plan. Please contact us and we will be happy to provide you with professional advice.
● Electrically addressed, can be modified by programmer
● Strong environmental adaptability due to drift
compensation
● Self-diagnostic, reed switch test
● Dirty chamber checking
● Fire LED allows 360° viewing
● Possible to switch off polling LED
● Remote indicator output
● Removable innovative sensing chamber, easy for
maintenance
● 2 levels sensitivities programmable (Level 1 certified)
● LPCB approved at EN 54-7
548d/04 2831-CPR-F0004
GST-0007-01
14
https://www.gst.com.cn
Gulf Security Technology Co., Ltd.
IMPORTANT: This publication is a generic version in which product information is shown for informational purposes only and does not constitute a specific commitment or guarantee. We are constantly
pursuing the improvement of product technology to improve product performance, for which we reserve the right to adjust the configuration and technical information of the related products without notice. In
addition, the description of system performance in this publication applies only to the usual situation. As a result, there may be a variety of unpredictable special circumstances in the real world, so the realiza-
tion of the relevant product performance will depend on the professional investigation and analysis and the design plan. Please contact us and we will be happy to provide you with professional advice.
Page 1 / 2
https://www.gst.com.cn/en/about.asp
© Gulf Security Technology Co., Ltd.Carrier World Headquarters
Page 1 / 2
DS10106287
IMPORTANT: This publication is a generic version in which product information is shown for informational purposes only and does not constitute a specific commitment or guarantee. We are constantly
pursuing the improvement of product technology to improve product performance, for which we reserve the right to adjust the configuration and technical information of the related products without notice. In
addition, the description of system performance in this publication applies only to the usual situation. As a result, there may be a variety of unpredictable special circumstances in the real world, so the realiza-
tion of the relevant product performance will depend on the professional investigation and analysis and the design plan. Please contact us and we will be happy to provide you with professional advice.
13995 Pasteur Boulevard
Palm Beach Gardens, Florida 33418 USA

Address can be set through P-9910B programmer,
also the sensitivity. Below table shows relative codes
for sensitivity levels and working modes. Factory
defaults at Level 1 + Normal LED.
Part No.: DC-9504E
Device name: Base Mount Isolator
Product No.: 10105103
Part No.: DB-01
Device name: Standard Base
Product No.: 30205764
Part No.: C-9314P
Device name: Remote Indicator
Product No.: 10102339
Part No.: P-9910B
Device name: Handheld Programmer
Product No.: 10104894
The typical wiring diagram is shown below.
Technical Specification
Accessories and Tools
Application
Certificates and Compliance
Order Information
http://www.gst.com.cn/en/index.asp
Gulf Security Technology Co., Ltd.
Page 2 / 2 DS10106287
IMPORTANT: This publication is a generic version in which product information is shown for informational purposes only and does not constitute a
specific commitment or guarantee. We are constantly pursuing the improvement of product technology to improve product performance, for which
we reserve the right to adjust the configuration and technical information of the related products without notice. In addition, the description of
system performance in this publication applies only to the usual situation. As a result, there may be a variety of unpredictable special circumstanc-
es in the real world, so the realization of the relevant product performance will depend on the professional investigation and analysis and the
design plan. Please contact us and we will be happy to provide you with professional advice.
Part No. DI-9102E
Device Name Intelligent Photoelectric
Smoke Detectorr
Product No. 10106287
Compatible
Products
GST100 Intelligent Fire Alarm Control Panel
GST200-2 Intelligent Fire Alarm Control Panel
GST200N Intelligent Fire Alarm Control Panel
GST- IFP8 Intelligent Fire Alarm Control Panel
Detector Code
1
1
Normal
Normal
Close
Close
Sensitivity Polling LED
1
22
2
129
130
● Standards: EN54-7
● Certifications: LPCB
SIGNALING
Operating Voltage loop 24V (16V ~ 28V)
Standby Current ≤0.8mA
Alarm Current
Indicator
≤1.8mA (without remote indicator)
≤ 3.8mA (with remote indicator)
Red. Flashes in polling, and illuminates in
alarm
Programming Method Electronically programming
Code Range
Wiring
Sensitivity Level
1 ~ 242
Non-polarized 2-core for loop.
Polarized 2-core for remote indicator.
2
Environment
Temperature -10°C ~ 50°C
Relative Humidity ≤95%, non condensing
Material of Enclosure
Dimensions
Mounting Hole Distance
Ingress Protection Rating
ABS
IP2X
Diameter: 100mm
Height: 54.5mm (with base)
45mm ~ 75mm
Weight About 110g
https://www.gst.com.cn
Gulf Security Technology Co., Ltd.
IMPORTANT: This publication is a generic version in which product information is shown for informational purposes only and does not constitute a specific commitment or guarantee. We are constantly
pursuing the improvement of product technology to improve product performance, for which we reserve the right to adjust the configuration and technical information of the related products without notice. In
addition, the description of system performance in this publication applies only to the usual situation. As a result, there may be a variety of unpredictable special circumstances in the real world, so the realiza-
tion of the relevant product performance will depend on the professional investigation and analysis and the design plan. Please contact us and we will be happy to provide you with professional advice.
Page 2 / 2
https://www.gst.com.cn/en/about.asp
© Gulf Security Technology Co., Ltd.Carrier World Headquarters
Page 2 / 2
DS10106287
13995 Pasteur Boulevard
Palm Beach Gardens, Florida 33418 USA
IMPORTANT: This publication is a generic version in which product information is shown for informational purposes only and does not constitute a specific commitment or guarantee. We are constantly
pursuing the improvement of product technology to improve product performance, for which we reserve the right to adjust the configuration and technical information of the related products without notice. In
addition, the description of system performance in this publication applies only to the usual situation. As a result, there may be a variety of unpredictable special circumstances in the real world, so the realiza-
tion of the relevant product performance will depend on the professional investigation and analysis and the design plan. Please contact us and we will be happy to provide you with professional advice.
Popular Smoke Alarm manuals by other brands

Mini Gadgets
Mini Gadgets BB3Smoke user manual

Ei Electronics
Ei Electronics EI129 instruction manual

Essence Security
Essence Security ES700SK2 Installation

Honeywell
Honeywell 5800COMBO-CN Quick installation guide

Teletek electronics
Teletek electronics IRIS installation manual

Carrier
Carrier Cavius 2007 user guide

System Sensor
System Sensor FTX-P1 Installation and maintenance instructions

Panasonic
Panasonic 1735 Specification sheet

Kidde
Kidde KN-COSM-BCA user guide

Spectrex
Spectrex SharpEye 20/20U User and maintenance manual

SITERWELL ELECTRONICS CO.,LIMITED
SITERWELL ELECTRONICS CO.,LIMITED GS522 user manual

Kidde
Kidde i12060 user guide