Temptek CF Series User manual

I.O.M. #123 updated 11/06/2018
INSTRUCTION MANUAL • INSTALLATION • OPERATION • MAINTENANCE
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, IN 46142
317-887-0729 fax: 317-881-1277
Service Department fax: 317-885-8683
www.Temptek.com
E-mail: [email protected]
Covering models
From 5 to 40 tons
With ‘M1’ Instruments
& Scroll Compressors
Model:
Serial Number :


INSTRUCTION MANUAL
With CF INSTRUMENT
& SCROLL COMPRESSORS
AIR & WATER-COOLED MODELS
COVERING
INSTALLATION
OPERATION
MAINTENANCE
TEMPTEK, INC. 525 East Stop 18 Road Greenwood, IN 46142
Phone: 317-887-0729 fax: 317-881-1277 Service Department fax: 317-885-8683
www.Temptek.com E-mail: [email protected]

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 4
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
TABLE OF CONTENTS
1.0 GENERAL 7
1.1 Introduction 8
1.2 Safety 8
1.3 Receiving instructions 9
1.4 Efciency 9
1.5 Clean air act 9
1.6 Water Treatment 10
1.7 Components 10
2.0 INSTALLATION 13
2.1 General 14
2.2 To and From process connections 14
2.3 Water supply connection 15
2.4 Water make-up supply connection 15
2.5 Air-cooled condenser 16
2.6 Water-cooled condenser 18
2.7 Electrical connection 18
3.0 OPERATIONS 23
3.1 General 24
3.2 Start up/operations procedure 24
3.3 Instrument/operation 32
3.4 Shut down procedure 36
4.0 TROUBLESHOOTING 37
4.1 Unit Will Not Start 38
4.2 Compressor Hums But Will Not Start 38
4.3 Shuts Off On High Pressure 38
4.4 Shuts Off On Low Pressure 39
4.5 Compressor Shuts Off On Internal Overload 40
4.6 Low Or No Process Pressure Or Water Flow 40
4.7 Cooling Capacity Inadequate 41
4.8 Sensor 41
4.9 Coolant Pump 41
4.10 Chiller Controller 41
5.0 MAINTENANCE 43
5.1 Warranty service procedure 44
5.2 Periodic preventative maintenance 44
5.3 Special maintenance 45
5.4 Solenoid valve service 46
5.5 Pump seal service 48
5.6 Checking the refrigerant charge 51
5.7 Proper cleaning procedure for brazed plate evaporators 551
6.0 COMPONENTS 53
6.1 Water system 54
6.2 Refrigeration system 54
6.3 Options 57

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 5
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
7.0 RELATED DRAWINGS 59
7.1 Mechanical Schematic : Water-Cooled : 5 - 10 Tons 60
7.2 Mechanical Schematic : Water-Cooled : 15 - 40 Tons 61
7.3 Mechanical Schematic : Air-Cooled : 5 - 10 Tons 62
7.4 Mechanical Schematic : Air-Cooled : 15 - 30 Tons 63
7.5 Typical Electrical : Air-Cooled 64
7.6 Typical Electrical : Water-Cooled 65
7.7 Typical Physical : Air-Cooled : 5 Tons 66
7.8 Typical Physical : Air-Cooled : 7.5 - 10 Tons 67
7.9 Typical Physical : Air-Cooled : 15 - 20 Tons Fan Cooled 68
7.10 Typical Physical : Air-Cooled : 15 - 30 Tons Blower 69
7.11 Typical Physical : Air-Cooled : 5 - 10 Tons With Remote Condenser 70
7.12 Typical Physical : Air-Cooled : 15 - 30 Tons With Remote Condenser 71
7.13 Typical Physical : Water-Cooled : 5 Tons 72
7.14 Typical Physical : Water-Cooled : 7.5 - 10 Tons 73
7.15 Typical Physical : Water-Cooled : 15 - 30 Tons 74
7.16 Typical Physical : Water-Cooled : 40 Tons 75
7.17 Duct Schematic for Air-Cooled Chillers 76
8.0 APPENDIX 77
8.1 Operationsbelow48°Fuidor38°Fambient 78
8.2 Operating with glycol (antifreeze) and with a set point above 48°F
or below 38°F ambient 80
8.3 Refrigerant pressure-temperature chart 81
8.4 Inhibited propylene glycol 82
8.5 Chiller capacity and derate chart 82

Page: 6
THIS PAGE INTENTIONALLY BLANK

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 7
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
1.0 GENERAL
1.1 Introduction
1.2 Safety
1.3 Receiving Instructions
1.4 Efciency
1.5 Clean Air Act
1.6 Miscellaneous
1.7 Water Treatment
1.8 Components

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 8
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
1.1 INTRODUCTION
A. This manual covers portable chillers from 5 to 40 tons (17 to 140 kW) of cooling capacity
usingtheTemptekCFmicroprocessorcontrolinstrumentandxeddisplacementscroll
compressorsanddigitalscrollcompressors.Thestandarduidoperatingtemperature
range for this chiller is 20°F to 80°F for units using R410A refrigerant. Units using other
refrigerantshavedifferentstandardoperatingranges.Unitsoperatingbelow48°Fuid
require the use of a water/propylene glycol to prevent freezing. Customized units may
have different operating ranges. Consult the factory if you have questions about the
operating range of your chiller.
B. The intent of this manual is to serve as a guide in the installation, operation and
maintenance of your chiller. Improper installation can lead to equipment damage
and poor performance. Failure to follow the installation, operation and maintenance
instructions may result in damage to the unit that is not covered under the limited
warranty. This manual is for standard products. The information contained in this manual
is intended to be general in nature. The information is typical only and may not represent
the actual unit purchased.
C. Chemical refrigerants are used in this unit. The refrigerant is sealed and tested in a
pressurized system however a system failure will release it. Refrigerant gas can cause
toxicfumesifexposedtore.Installthisunitinawell-ventilatedareaawayfromopen
ames.Failuretofollowtheseinstructionsmayresultinahazardouscondition.Recover
refrigerant to relieve pressure before opening the system. See nameplate for refrigerant
type. Do not use non-approved refrigerants or refrigerant substitutes.
D. Customers should implement a refrigerant management program to document the type
and quantity of refrigerant in each chiller. All refrigeration service technicians performing
workonthischillermustbelicensedandcertied.
E. WhencallingforassistancefromtheManufacturer’sServiceDepartment,itisimportant
to know the model and serial number of the particular unit. The model number includes
criticalunitinformationwhichishelpfulwhentroubleshootingoperatingdifculties.The
serial number allows the service team to locate manufacturing and testing records which
can have additional information relating to a particular unit.
1.2 SAFETY
A. It is important to become thoroughly familiar with this manual and the operating
characteristics of the unit.
B. Itistheowner’sresponsibilitytoassureproperoperatortraining,installation,operation,
and maintenance of the unit.
C. Observe all warning and safety placards applied to the chiller. Failure to observe all
warnings can result in serious injury or death to the operator and severe mechanical
damage to the unit.
D. Observe all safety precautions during installation, startup and service of this equipment
duetothepresenceofhighvoltageandrefrigerantcharge.Onlyqualiedpersonnel
should install, startup and service this equipment.

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 9
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
E. When working on this equipment, observe precautions in literature and on tags, stickers
and labels located on the equipment. Wear work gloves and safety glasses.
F. Samples of Warning Labels applied to typical chillers.
1. Alerts users to the danger of high
voltage.
2. Alerts user to the danger of the rotating
condenser fans on air condensed units.
3. Alerts user to the danger of belt drive
systems on unit with blowers.
4. This symbol is seen on all chillers to alert user to the
danger of the refrigeration system under pressure.
System should only be serviced by a licensed
technician.
WARNING: This equipment contains hazardous voltages that can cause severe injury or death.
Disconnect and lock out incoming power before installing or servicing the equipment.
WARNING: This equipment contains refrigerant under pressure. Accidental release of refrigerant
under pressure can cause personal injury and or property damage. Exercise care while working
on or around this equipment.
WARNING: Vent all refrigerant relief valves in accordance to ANSI/ASHRAE Standard 15,
Safety Code for Mechanical Refrigeration. This equipment should be located within a well-
ventilated area. Inhalation of refrigerant can be hazardous to your health and the accumulation
of refrigerant within an enclosed space can displace oxygen and cause suffocation
WARNING
J5318-BF
WARNING

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 10
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
1.3 RECEIVING INSTRUCTIONS
A. Chillers are shipped skid mounted and wrapped in plastic prior to shipment. Check the
overall condition of the equipment prior to accepting delivery.
B. Check for visible damage and document any evident damage on the delivery receipt.
Check the refrigerant gauges to be sure the system charge is intact. See the chart
in section 8.3 for proper pressure readings based on the ambient temperature and
refrigerant type used in the chiller. Shipping damage is the responsibility of the carrier.
C. In order to expedite payment for damages, should they occur, follow proper procedures
and keep detailed records. Take photographs of any suspected damage.
1.4 EFFICIENCY
A. Longtermefciencyofoperationislargelydeterminedbypropermaintenanceofthe
mechanical parts of the unit and the water quality. The Manufacturer recommends
lteringtheprocesswatertopreventsolidsfrompluggingcriticalparts.TheManufacturer
highlyrecommendsthattheservicesofaqualiedwatertreatmentspecialistbeobtained
and their recommendations be followed. The Manufacturer accepts no responsibility for
inefcientoperation,ordamagecausedbyforeignmaterialsorfailuretouseadequate
water treatment.
1.5 CLEAN AIR ACT
A. Units manufactured after January 1, 2010 may contain refrigerant HFC-410A, HFC-407C,
HFC-404A or HFC-134A. Most units manufactured prior to January 1, 2010 contain
refrigerant HCFC-22.
B. It is unlawful for any person in the course of maintaining, servicing, repairing, or disposing
of refrigeration equipment to knowingly vent or otherwise dispose of any substance used
as a refrigerant in the manner which permits such substance to enter the atmosphere.
C. Very small releases associated with good faith attempts to recapture, reclaim or
recycle such substance shall not be subject to the prohibition set forth in the preceding
paragraph.
D. Customers should implement a refrigerant management program to document the type
and quantity of refrigerant in each chiller. All refrigeration service technicians performing
workonthischillermustbelicensedandcertied.
E. Vent all refrigerant relief valves in accordance to ANSI/ASHRAE Standard 15.
WARNING: Vent all refrigerant relief valves in accordance to ANSI/ASHRAE Standard 15,
Safety Code for Mechanical Refrigeration. This equipment should be located within a well-
ventilated area. Inhalation of refrigerant can be hazardous to your health and the accumulation
of refrigerant within an enclosed space can displace oxygen and cause suffocation.

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 11
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
1.6 WATER TREATMENT
A. The use of untreated or improperly treated water in a portable chiller may result in
scaling, erosion, corrosion, algae or slime.
B. Itisrecommendedthattheservicesofaqualiedwatertreatmentspecialistbeengaged
to determine what water treatment is required.
C. Advantage assumes no responsibility for equipment failures which result from untreated
or improperly treated water.
D. Do not use deionized water in this unit. Some customized units may be compatible with
deionized water. Consult the factory before using deionized water.
1.7 COMPONENTS
WARNING: Improper water treatment will void unit warranty.
Air-Cooled.
Water-Cooled.
Pressure Gauges
Cover Panel
Enclosure Panel
Electrical Panel
Enclosure
Casters
Instrument

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 12
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
Air-Cooled Model 10 ton unit shown.
ABS fascia and enclosure panels
removed for photo.
Water-Cooled Model 10 ton unit shown.
ABS fascia, top and enclosure panels
removed for photo.
Caster
Compressor
Liquid Line Solenoid
Filter Drier
Refrigerant Site Glass
Fan Motor
Protective Fan Shroud
Bypass
Bypass
Water Regulator
Valve
Coolant Pump
Water-Cooled
Condenser
Electrical Cabinet
Pressure Gauges
Compressor
Insulated
Reservoir
Air Discharge
Coolant Pump
Pressure Gauges
Expansion Valve
Insulated Reservoir Tank
Electrical Cabinet
Refrigerant Low Pressure Limit
Refrigerant High Pressure Limit
Air-Cooled Condenser

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 13
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
2.0 INSTALLATION
2.1 General
2.2 Unit Location
2.3 To and From Process Connections
2.4 Make-Up Water Supply Connection
2.5 Air-Cooled Condenser Installation
2.6 Water-Cooled Condenser Installation
2.7 Electrical Connection

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 14
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
2.1 GENERAL
A. Chillers are shipped skid mounted and wrapped in plastic prior to shipment. Check the
overall condition of the equipment prior to accepting delivery. Check for visible damage
and document any evident damage on the delivery receipt. Shipping damage is the
responsibility of the carrier.
B. Allprocesspipingmaterials(suchashose,rigidpiping,valvesorlters)usedinprocess
water piping circuitry must be rated for 100°F minimum temperature and 100 PSI
minimum pressure.
C. All such materials must have the equivalent or larger diameter of the particular process
connection that length of process water piping is connected to.
2.2 UNIT LOCATION
A. Foundation. The chiller must be installed on a rigid and level mounting surface with
adequate strength to support the operating weight of the chiller including the weight of
water and attached piping.
This unit will contain water or water/glycol when operating. Locate the chiller
where an unforeseen uid leak will not cause damage to the surroundings or
install the unit in such a way that an unforeseen uid leak will not damage its
surroundings.
B. For air-cooled and water-cooled models:
1. These units are designed for indoor use only.
2. Formostefcientoperation,locatethechillerinalevel,clean,dryandwell
ventilated environment.
C. For air-cooled models:
1. The unit has an air-cooled refrigerant condenser. For air- cooled condensers, a
motor driven fan (on models from 5 to 20 tons) or a centrifugal blower (standard
onmodelsfrom25to30tonsandoptionalonothermodels)generatesairow
through the condenser to remove heat from the refrigerant system. The air
cooledcondenserontheunitwilldischargeapproximately15,000BTU’sperhour
pertonofcoolingandtheairowrateisapproximately1,000cfm/nominalton.
2. The unit must have a minimum entering air temperature of 60°F and a maximum
enteringairtemperatureof95°Fforefcientoperation.
3. The unit must have a minimum of two feet clearance at the air intake and six
feet at the vertical exhaust air discharge and must have adequate ventilation to
dissipate the rejected heat. The unit must not be placed in non-ventilated areas.
4. The unit must have all enclosure panels in place before operating the
compressor. Air will not be drawn through the condenser coil if the panels are not
in place. Starting the unit without all the enclosure panels in place will result in a
high pressure refrigerant fault.

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 15
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
5. Units with a motor-driven fan may not use duct work unless a booster fan of
equal volume rating has been installed in the duct.
2.3 TO AND FROM PROCESS CONNECTIONS
A. Useappropriatelyratedhoseoruidpipingtoconnecttheprocesspipinggoingtoyour
process to the “to process” connection on the chiller.
B. Useappropriatelyratedhoseoruidpipingtoconnecttheprocess
piping coming back from your process to the “from process” connection
on the chiller.
C. Install a high volume basket strainer in the From Process line with
isolationvalves.Abasketstrainerorbaglterwithameshscreen
of 20-40 microns will protect the unit. A “wye” type strainer is not
recommended because it does not have adequate debris holding
capacity.
D. Process water piping should be designed to avoid excessive elbows
and/orlengthsofpipeorhose.Ifusingexiblehoseavoidtighttwists
or curls and excessive lengths.
E. Valvesandltersmaybeinstalledintheprocesswaterpipingto
facilitate service and maintenance provided that such devices maintain
the full inside diameter of the process connection. If installed, all such devices must be
open and clean during unit operation.
F. It is important to check all external process connections for leaks prior to starting the unit.
It is also important to check external connections for leaks and internal hose clamps and
connections for leaks after servicing the unit.
From Process
Make-Up Water Supply
To Process
To Process
From Process
Condenser Water Out
Make-Up Water Supply
Condenser Water In
From ProcessTo Process
This label marks the
To Process connection
From Process
This label marks the
From Process connection
Typical wye strainer -
Not recommended.

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 16
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
2.4 MAKE-UP WATER SUPPLY CONNECTION
A. The automatic water make-up system continually monitors the
reservoirtankandllsitwhenneeded.Connectasfollows:
1. Usingappropriatelyratedhoseoruidpipingconnectthe
“watermake-up”connectiontotheplant’swatersource.
2. Minimum make-up water supply pressure is normally 20 psi.
3. Install an owner supplied shut off valve in the
make-up water supply line. Install this valve on
the outside of the unit.
4. Useabackowpreventiondeviceasmaybe
required by local codes to prevent possible
contamination of potable water.
B. Do not use automatic water make-up system when
operating with glycol below 48°F.
2.5 AIR COOLED CONDENSER
A. Air-cooled condensers require ambient air temperatures
between60°Fand95°Fforefcientoperation.Operating
above 95°F may result in elevated condensing pressures
and eventual shut-down on the high pressure limit
switch. Air temperatures below 60°F may result in
over condensing pressures and cause a low pressure
refrigerantfault.ConsultwiththeManufacturer’s service
department for more information on operating with
ambients air temperatures above 95°F or below 60°F.
B. Airowisgeneratedbythemotormountedfansor
centrifugalblowers.Airowisfromtheoutsideofthe
chiller, through the condenser and exhausted through
the top of the unit. On centrifugal blowers models,
exhaustaircanbeductedoutsideoftheplant’s
interior environment. Special duct work is required
and a HVAC contractor should be consulted for sizing
andmaterialspecications.Exhaustaircannotbe
ducted on motor mounted fan models.
C. A free air space of at least two (2) feet is required at
the condenser intake and six (6) feet at the condenser
dischargetoallowforproperairow.
Typical fan assembly
Typical blower assembly
CFM RATINGS
Model
5 Tons
7.5 Tons
10 Tons
15 Tons
20 Tons
25 Tons
30 Tons
CFM
5,000
7,500
10,000
15,000
20,000
25,000
30,000
From ProcessTo Process
Condenser
Water In
Condenser
Water Out
Water Make-up
This label marks the Water
Make-up connection
WARNING: Check local codes to determine proper use of back ow prevention device in water
make-up supply line.

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 17
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
D. At full load, the chiller will discharge
approximately15,000BTU’sperhourper
ton of cooling.
E. On blower units, air discharge duct work
shouldbesizedbyaqualiedHVAC
engineer. Sizing shall be according to
rated CFM at the static pressure of .90
inchesofwater.Seegureatright.
F. On blower units, a damper control
assembly is required in low ambient
temperature areas or when outdoor air
make-up is used. The assembly works
in conjunction with refrigerant head
pressuretoregulateairowtomaintain
proper refrigerant head pressure when
condenser intake air temperature will be
lessthan60°F.Seeguretotheright.
G. All air cooled units MUST have all enclosure panels in place before operating
compressor. Air will not be drawn through the condenser coil if the panels are not in
place. Starting the unit without the enclosure panels in place will result in a refrigerant
fault.
H. Condenser Air Filtering.Usealterthatproducesverylowairowrestrictions.
GenerallyadisposableberglasslterwithaMERVratingof2-3providesadequateair
ltration.Thepurposeofthelteristopreventlargeparticlessuchasdust,lintanddebris
fromfoulingthecondenser.Youshouldbeabletoseethroughtheltermedia.Using
restrictiveltermediacancauselossofchillercapacity,difcultyrunninginwarmweather
and fan motor overheating.
WARNING: Do not attempt to duct exhaust air from a portable chiller using motor driven fans.
Exhaust air can only be ducted from a portable chiller using a blower assembly.
Damper assembly
Punch hole
in top panel
1/4" Copper line
Optional
Liquid receiver
(located inside
chiller on base)
Angle valve and cap
1/4" copper line connection
Typical Filter materials.
Typical Filter shown on 10 ton air-cooled unit.
WARNING: Do not attempt to start or operate an air-cooled portable chiller without all cabinetry
panels in place. Air-cooled chillers require air to be drawn through the air-cooled condenser. This
will not occur if the panels are not in place.

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 18
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
2.6 WATER-COOLED CONDENSER
A. Connect the facility cooling tower or city water supply to the
“condenser water in” connection on the unit.
1. Requiredowratefromacitywatersourceis1.5gpmat
65°F per ton of rated capacity.
2. Requiredowrateforatowerwatersourceis3gpmat85°Fpertonofrated
capacity.
B. Connect the facility tower system return or drain to the “condenser
water out” connection on the unit.
1. Note:Followalllocalcodesifdumpingtotheplant’s
sanitary or other drain.
C. The pressure differential requirement between the condenser “water in” and the
condenser “water out” lines must be 30 psi.
D. The installation of a strainer in the condenser “water in”
line is recommended. This removes solids from the water
supply and serves to protect the water saver (regulator)
valve.
E. The water regulator valve is normally factory set for
properoperation.Wheneldadjustmentsarerequired,
turn the adjusting nut on the top of the valve counter
clockwise to raise the refrigerant pressure and clockwise
to lower the pressure. Adjustments should be made only
when the chiller is running at full load.
2.7 ELECTRICAL CONNECTION
A. STANDARD MODELS
1. All electrical wiring must comply with local codes and the National Electric Code.
Typical water saver regulator valve.
WARNING: Do not connect the unit to a voltage supply not equal to the unit’s voltage
requirements as specied on the unit’s data plate. Use of incorrect voltage will void the unit’s
warranty and cause a signicant hazard that may result in serious personal injury and unit
damage.
WARNING: Electric Shock Hazard. High Voltage is present in the electrical cabinet. Disconnect
power before servicing. Follow all facility lock-out tag-out procedures.
From ProcessTo Process
Condenser
Water In
This label marks the
Condenser Water In
connection
From ProcessTo Process
Condenser
Water In
Condenser
Water Out
This label marks the
Condenser Water Out
connection

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 19
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
2. Electrical power supply requirements for standard units
areidentiedontheequipmentdatatag.Determine
thattheplant’svoltagesupplyisthesameastheunit’s
voltage requirements, taking into account the SSCR
Rating.
3. A customer supplied, four conductor cable is
required for connection to a customer supplied fused
disconnecting means. The fused disconnecting means
shallbesizedandinstalledaccordingtotheunit’s
power supply requirements and local electrical codes.
(Some custom units may include a fused or non-fused
disconnect switch.)
4. Connect the four conductor power cable to the power
entryterminalblockontheunit’selectricalpanel.Then
connect the power cable to the fused disconnect switch.
There is no power entry hole into the electrical cabinet. This allows the matching
oftheentryholesizeandlocationtothecustomersuppliedttings.
5. Aunitspecicelectricaldrawingisshippedwiththeunit.
6. Voltage supplies must be within +/- 10% of the name plate voltage and must be
within 2% from leg to leg. Extreme voltage imbalance or using the wrong voltage
can damage your chiller and cause premature unit failure as well as a safety risk.
7. A proper ground is required for the unit.
B. CONTROL CIRCUIT WIRING
1. Theunit’ssuppliedcontrolcircuitis110volt,1phase,60cycle.
2. The control circuit is supplied by the factory installed transformer. A control circuit
fuse is provided.
C. GENERAL
1. Makecertainallgroundconnectionstotheunitareproperlyafxed.
2. Make certain power conductor, disconnecting means, and fusing are properly
sizedaccordingtotheunit’spowersupplyrequirements.
3. Follow all local and national codes.
4. Make certain that all owner and factory wire connections are tight before applying
power to the unit.
Typical data tag.
WARNING: Check that all electrical connections are tight before starting.
Disconnect power before servicing. Follow all facility lock-out tag-out procedures.

CF Series Portable Chiller : Air & Water-Cooled : 5 - 40 Tons
Page: 20
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
Electrical Panel
Other manuals for CF Series
1
Table of contents
Other Temptek Chiller manuals
Popular Chiller manuals by other brands

Thermal Care
Thermal Care Accuchiller NQ Series Operation, installation, and maintenance manual

Crysalli
Crysalli CR-1 install guide

Data Aire
Data Aire DAC Series Operation and maintenance manual

Metos
Metos SC 500 Installation and operation manual

AERMEC
AERMEC NRA Technical and Installation Booklet

Clint
Clint R410A manual

Johnson Controls
Johnson Controls York YKEP Series manual

Carrier
Carrier 30GX080-265 Controls, start-up, operation, service, and troubleshooting

intensity
intensity ICHS-120KC-5 Installation & owner's manual

Trane
Trane BAYECCK001 Installer's guide

TECO
TECO ra 200 instruction manual

Bromic Heating
Bromic Heating MEDIFRIDGE MEDO374GD instruction manual