Terofire Products Saffire Mk2 Guide

Saffire
Mk2
User & Installation Manual
IMPORTANT
This manual should be left with the panel after installation.
Wereservethe rightto changeproduct specificationswithout priornotice.
Copyright© TerofireProducts 1999.

Terofire Products
2
Introduction
The information provided in this manual covers the Saffire range of fire
alarm control panels. The Saffire range is designed to meet the
requirements of BS5839 Parts 1 & 4 1988 and includes panels of 1 and
2 zones.
This product should be installed, commissioned and maintained by
suitably qualified service personnel with reference to IEE regulations
and any statutory requirements.
General Description
The Saffire is a microprocessor controlled fire alarm control panel. It is
provided with one or two sense zones (detector zones) to connect to fire
detection devices, two alarm zones (bell zones) to connect to audio/
visual devices and a set of volt free changeover contacts which operate
on fire. If a fire is detected by a device on a sense zone, the alarm
zone devices will operate automatically and the zone that detected the
fire will be indicated on the front panel. The panel also allows the user
to operate the alarms manually.
Installation Procedure
Before proceeding with the installation, please read the section
Panel
Operation
- You will need to know the access code during installation.
Installation of the panel should be carried out by qualified
personnel.
Using the metal box as a template, mark the position of the fixing holes
on the wall. Drill and plug the wall then screw the panel to the wall.
Ensure the panel is free from knockout discs, swarf and other debris.
Do not connect any cables until after the following test is performed.
All end of line resistors should be fitted in the panel at this stage.
Connect the panel mains input to an exclusive 240V AC fused supply.
Switch the mains supply on. The internal buzzer will sound. Connect
two sealed lead acid batteries to the panel. They should be connected
in series, providing a 24V DC supply. With both the mains and battery
supplies connected, the panel should be silent and in its normal
operating mode (power lamp on, alarms & buzzer silent).

Saffire Instruction Manual
3
If a fault is indicated, refer to the fault finding section before
proceeding. Disconnect the batteries and switch off the mains supply.
Remove the 3k3 end of line resistor from sense zone 1. Terminate
sense zone 1 circuit wiring in the panel observing correct polarity and fit
the end of line resistor at the extreme end of the circuit. Check that all
the detectors and call points are correctly wired. With sense zone 1
connected and all other end of line resistors fitted inside the panel,
connect the mains and battery supplies. If the panel indicates a fault,
refer to the fault finding section before proceeding. Do not megger
cables connected to either the panel or any field devices. If no faults
are indicated then power down the panel and follow the same procedure
with the additional sense zones and then the alarm zones. Adding the
zones one at a time makes fault finding and commissioning much
simpler. Make sure that no bare wires come into contact with the panel
circuit boards during installation.
Detector Head Removal
The Saffire range of panels support head removal. The basic principle
of head removal is to ensure that all call points will function even if a
detector head has been removed. When a detector head is removed,
the panel will show a fault but the sense zone circuit will remain intact.
Head removal requires either zener clamp bases or schottky diode
bases with the appropriate end of line device to be fitted. Consult the
table on page 7 for more information.

Terofire Products
4
Panel Operation
Entering the access code.
Before being able to access the Reset, Silence and Evacuate functions,
the panel access code must first be entered. To activate the keypad,
press the front panel buttons in the following sequence: 1-3-1-2
The panel should bleep after each button press. The Enabled lamp
flashing indicates that the keypad is now active. If no button is pressed
for approximately 2 minutes the keypad will deactivate.
Performing a lamp test.
If the panel is in its normal condition, pressing the Reset button will
cause the panel to perform a lamp test. This will also deactivate the
keypad.
Resetting the panel after a fire is detected.
To reset the panel after a fire condition, press the Silence button
followed by the Reset button.
Resetting the panel.
If any of the panel functions have been activated, pressing the Reset
button will return the panel to its normal condition.
Silencing the alarms.
If a fire is detected, the panel will automatically activate the alarm
circuits. To silence the alarms, press the Silence button. The internal
buzzer will continue to sound until the Reset button is pressed.
Silencing the internal buzzer.
If a fault is detected by the panel, the internal buzzer will sound. To
silence the buzzer press the Silence button. The buzzer will continue to
bleep every 25 seconds. A CPU Fault cannot be silenced.
Manually sounding the alarms.
Pressing the Evacuate button will sound the alarms. To silence the
alarms after the Evacuate button has been pressed, press the Reset
button.

Saffire Instruction Manual
5
Fault Finding
Reset, Silence & Evacuate buttons not working.
Enter access code to enable keypad. Press the buttons in the following
sequence: 1-3-1-2. The panel should bleep after each button press.
Fault lamp & zone fault lamp flashing, internal buzzer sounding.
Faults monitored are:
• Open circuits on the sense zone wiring.
• Short circuits on the sense zone wiring.
• Detector head removal
Check all detectors and call points on the sense zone indicated. Check
wiring is as in example diagrams and ensure the end of line monitor is
a 3k3 resistor or an active end of line device.
Fault lamp lit and internal buzzer sounding.
Faults monitored are:
• Open circuits on the alarm zone wiring.
• Short circuits on the alarm zone wiring.
• Blown alarm fuses.
• Blown battery fuse or battery supply missing.
• Blown mains fuse or mains supply missing.
• CPU fault.
Check all fuses. If blown replace only with identical parts. Check
alarm zone wiring is as in example diagrams and ensure the end of line
monitor is a 10k resistor. Check incoming mains supply and condition
of batteries. If no problems are found then reset the processor. Inside
the panel on the main circuit board are two push buttons marked CPU
RESET and W/D RESET. Press CPU RESET followed by W/D
RESET.
Panel does not indicate fire when a call point or detector is tested.
Either a faulty call point/detector or wiring not as shown in diagrams.
Check the firing resistance of the device is 510 ± 200 ohms and ensure
end of line monitor is a 3k3 resistor or active end of line device.
Head removal not working.
Check compatible base is being used and is wired correctly. Either a
zener clamp base with a 3k3 end of line resistor or a schottky diode
base with an active end of line device must be used.

Terofire Products
6
)CAV(egatloVsniaM042
)CDV(egatloVmetsyS4.82
)Am(tnerruCtnecseiuQ36
)Am(tluaFdecnelisnU,tnerruCtnecseiuQ57
deriuqeRV21x2-)hA(eziSyrettaBmuminiM1.2
)CDV(egatloVrotceteD42
senoZesneSforebmuN2ro1
enoZrepsrotceteDforebmuNmumixaM02
)smhO(ecnatsiseRgniriF002±015
)smhO(eniLfodnEenoZesneS3k3
)CDV(egatloVmralA4.82
senoZmralAforebmuN2
)Am(enoZreptnerruCmralAmumixaM052
enoZrepsrednuoSforebmuNmumixaM21
)smhO(eniLfodnEenoZmralAk01
)gk(seirettaBgnidulcnIthgieWlenaP5
)mm(snoisnemiDlenaP59x632x021
Panel Specification
Please ensure all calculations take into account the startup current of
the devices used. This is especially important if you intend using xenon
beacons.

Saffire Instruction Manual
7
.oNtraP ikihcoH DZ5/R-KBY ikihcoH 4/R-NBY 06SollopA esaBedoiD 06SollopA esaBnommoC nattiN RDS4-BTS atihsustaM esaBedoiD CAK tnioPllaC noelluF tnioP-llaC
nIevitisoP1L2 NI1LNI1L4A1 smhO074
tuOevitisoP2L1 TUO1LTUO1L4A1smhO074
nIevitageN5C52L2L11B2 NOMMOC
tuOevitageN6C62L2L6B2 NOMMOC
rotacidnIetomeR evitisoP 1LA/NNI1LNI1L4AA/NA/N
rotacidnIetomeR evitageN 3SA/NR-R-5LA/NA/N
eniLfodnE eciveD rotsiseR3k3rotsiseR3k3 fodnEevitcA eniL rotsiseR3k3 fodnEevitcA eniL fodnEevitcA eniL
tiuSoT rotceteD esaB
tiuSoT rotceteD esaB
lavomeRdaeH detroppuS seYoNseYoNseYseY
Detector Base and Call Point Wiring Information

Terofire Products
8
Sense Zone Wiring Diagrams
Find the detector bases you will be using in the table on page 7 and
check to see which end of line device is required - either a 3k3 resistor
or an active end of line unit. The 3k3 resistor should be used if a zone
is comprised entirely of call points.
Sense zone with a 3k3 end of line resistor.
The colour bars on a 3k3 resistor are
Sense zone with an active end of line.
The 100uF capacitor should be fitted at the sense zone terminals inside
the fire alarm panel. The Saffire panel is supplied with 3k3 sense zone
end of line resistors. Active end of line units are supplied separately.
Remote indicator connection details are shown in the table on page 7.
orange
orange
red
gold
+ in + out
- in -out
+ in + out
- in -out
3k3
EOL
Sense
Zone+
Sense
Zone-
Sense
Zone+
Sense
Zone-
Active
EOL
+ in + out
- in -out
+ in + out
- in -out
100uF
Capacitor
++

Saffire Instruction Manual
9
Alarm Zone Wiring Diagrams
The alarm zones are wired as in the diagram below. A 10k end of line
resistor must be fitted at the end of the circuit. Motorised fire bells may
be used, but solenoid bells MUST NOT be connected to the panel.
Some electronic sounders have a choice of tones available. Please see
the sounder instructions for further information.
brown
black
orange
gold
The Colour bars on a 10k resistor are
Attaching a relay to an alarm zone.
AlarmZone +
AlarmZone -
C1
C2
NO1
NO2
NC1
NC2
A relay may be connected
anywhere on the alarm zone
wiring, as long as two diodes
(1N4001 or equivalent) are fitted
as shown in the diagram. The
end of line resistor is not shown
here, but must be connected at
the end of the alarm zone wiring.
The relay must have a 24V DC
coil.
+in/out + in/out
-in/out - in/out
10k
EOL
Alarm
Zone+
Alarm
Zone-

Terofire Products
10
Additional Wiring Information
Signalling fire to another panel.
By connecting two panels as shown below, when panel B closes its
auxiliary contacts, panel A will go into fire.
Connecting magnetic door holders.
Magnetic door holders can be switched using the set of auxiliary
contacts in the panel. When the panel goes into fire, power to the door
holders is removed allowing the doors to close.
Sense
Zone+
Sense
Zone-
3k3or
Active
EOL
510RResistor
C-NOContacts
inPanel B
PanelA
24V
Door
Holder
Power
Supply
C NC
Door
Holder
Door
Holder Door
Holder
Panel
Auxiliary
Contacts
+
-

Saffire Instruction Manual
11
Saffire System Log Book
All events should be properly recorded in this log book. An ‘event’
should include fire alarms (whether real or false), faults, tests,
temporary disconnections and the dates of installing or servicing
engineer’s visits with a brief note of work carried out and outstanding.
Name and address ..............................................................................
of installation ..............................................................................
..............................................................................
..............................................................................
..............................................................................
Person responsible ............................................ Date....................
for log book ............................................ Date....................
............................................ Date....................
............................................ Date....................
System installed by ..............................................................................
..............................................................................
and is maintained under contract by ....................................................
Tel. ....................................................
Notes:

Terofire Products
12
etaDemiTenoZtnevEderiuqeRnoitcA etaD detelpmoC slaitinI
Table of contents
Other Terofire Products Control Panel manuals
Popular Control Panel manuals by other brands

AVE
AVE AF997 instruction sheet

Siemens
Siemens FIREFINDER-XLS Installation, operation and maintenance manual

Hussmann
Hussmann HCD install guide

American Standard
American Standard ACONT602AF22MA installation instructions

Siemens
Siemens SINAMICS G130 operating instructions

DeDietrich
DeDietrich Diematic iSystem Installation, user and service manual