
1800 Hurd Drive ● Irving, Texas 75038 ● (972) 580-0200 ● (888) 580-0202 ● Fax (972) 580-0277
URL: www.thermaledge.com ● Email: support@thermaledge.com
SP-ENG-210-HL0-07 2.3 17 | P a g e
“LA” Minimum Temperature Alarm: P1 < 45 °F for 3
minutes (after initial 30 min. startup delay)
No Action/Alarm Only
*2
“HA2” Condenser High Temperature Alarm: P2 > 164 °F for
3 minutes
Compressor turned Off by pressure switch if
temperature continues to rise *2
“LA2” Condenser Low Temperature Alarm: P2 < 50 °F for 3
minutes
No Action/Alarm Only
*2
“CA” Evaporator Coil Alarm: Low Pressure for 2 minutes Compressor Off
*2
“noP” Invalid Probe Selected: Low Evaporator Coil No Action/Alarm Only
*2Note: When both Heater and Dry Contact options are included, Dry Contact (Alarm Contact) Relay is
activated.
ALARM RECOVERY
If the compressor is turned off due to an alarm, it will be able to res tart after the AC anti short-cycle time
delay. (Parameter AC = 3 minutes)
Probe alarm P1 is cleared with no time delay after the fault is cleared.
Probe alarm P2 starts and stops with no time delay.
Temperature alarm HA automatically clears as soon as the temperature returns to below 105°F (the ALU setpoint) -2°F
= 103°F. Temperature alarm LA automatically clears as soon as the temperature returns to above 45°F (the ALL
setpoint) +2°F = 47°F. Temperature alarm HA2 automatically clears as soon as the condenser coils temperature
returns to below 164°F. Temperature alarm LA2 automatically clears as soon as the condenser coils temperature
returns to above 60°F. Temperature alarm CA automatically clears as soon as the pressure returns to normal.
Preventative Maintenance
Air conditioners require regular cleaning of the condenser air inlet filter. Wash filter often if
washable using proper cleaning compound and back flushing the dirt out, or replace if not
washable whenever it appears physically dirty. Restriction to the flow of air over the condenser
coil will degrade the performance of the equipment, cause it to overheat, reduce cooling and
can damage the compressor. The overload switch in the compressor may cause the
compressor to cycle if the condensing coil pressure becomes too high due to air restriction. A
further safety feature is the refrigerant high pressure cut off switch which will stop the
compressor if the condensing pressure becomes too high due restricted condenser air flow or
some other cause.
Restricted air flow due to neglecting a dirty filter will cause unit to repeatedly turn off and then
turn back on after it cools off. An operation in this safety cycling mode will eventually damage the
equipment and void the warranty.
Refer to Field Serviceable Parts section in this manual for details on parts that can be changed
to help increase the uninterruptable life of the Air Conditioner.
Air Filter Service
Remove the air conditioner filter and wash if washable or replace if not washable. Dry
thoroughly before replacing. THERMAL EDGE Air Filter Treatment Spray in aerosol cans or
spray bottle is recommended to enhance air filter efficiency. Replacement filters are readily
available from THERMAL EDGE Customer Service. DO NOT operate the air conditioner without