Thermo King SB-210+ User manual

Operator’s Manual
Ingersoll Rand’s Climate Solutions sector delivers energy-effi cient HVACR solutions for
customers globally. Its world class brands include Thermo King, the leader in transport
temperature control and Trane, a provider of energy effi cient heating, ventilating and
air conditioning systems, building and contracting services, parts support and advanced
controls for commercial buildings and homes.
©2011 Ingersoll-Rand Company
Printed in U.S.A.
SB-210+/SB-310+
TK 53942-2-OP (Rev. 1, 11/09)
Operator’s Manual
Ingersoll Rand’s Climate Solutions sector delivers energy-effi cient HVACR solutions for
customers globally. Its world class brands include Thermo King, the leader in transport
temperature control and Trane, a provider of energy effi cient heating, ventilating and
air conditioning systems, building and contracting services, parts support and advanced
controls for commercial buildings and homes.
©2011 Ingersoll-Rand Company
Printed in U.S.A.
SB-210+/SB-310+
TK 53942-2-OP (Rev. 1, 11/09)

Copyright© 2009 Thermo King Corp., Minneapolis, MN, USA
Printed in USA
SB-210+/SB-310+
TK 53942-2-OP (Rev. 1, 11/09)
Copyright© 2009 Thermo King Corp., Minneapolis, MN, USA
Printed in USA
SB-210+/SB-310+
TK 53942-2-OP (Rev. 1, 11/09)

Disclaimer
This manual is published for informational purposes only. Thermo King Corporation makes no
representations or warranties, express or implied, with respect to the information, recommendations and
descriptions contained in this manual and such information, recommendations and descriptions should
not be regarded as all-inclusive or covering all contingencies. If you have questions or require further
information, please contact your local Thermo King dealer.
The procedures described herein should be undertaken only by qualified personnel. Failure to implement
these procedures correctly may cause damage to the Thermo King unit or other property or personal
injury.
Thermo King Corporation and its affiliates shall have no liability in contract or tort (including negligence
and/or strict liability) or otherwise, to any person or entity for any personal injury, property damage or any
other direct, indirect, special or consequential damage or liability whatsoever, arising out of or resulting
from any actions by any person that are contrary to this manual or any of the information,
recommendations or descriptions contained herein or the failure of any person to implement the
procedures described herein correctly or to follow caution and safety decals located on the Thermo King
unit.
Disclaimer
This manual is published for informational purposes only. Thermo King Corporation makes no
representations or warranties, express or implied, with respect to the information, recommendations and
descriptions contained in this manual and such information, recommendations and descriptions should
not be regarded as all-inclusive or covering all contingencies. If you have questions or require further
information, please contact your local Thermo King dealer.
The procedures described herein should be undertaken only by qualified personnel. Failure to implement
these procedures correctly may cause damage to the Thermo King unit or other property or personal
injury.
Thermo King Corporation and its affiliates shall have no liability in contract or tort (including negligence
and/or strict liability) or otherwise, to any person or entity for any personal injury, property damage or any
other direct, indirect, special or consequential damage or liability whatsoever, arising out of or resulting
from any actions by any person that are contrary to this manual or any of the information,
recommendations or descriptions contained herein or the failure of any person to implement the
procedures described herein correctly or to follow caution and safety decals located on the Thermo King
unit.

3
Table of Contents
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Safety Practices . . . . . . . . . . . . . . . . . . . . . . 13
Automatic Start/Stop Operation . . . . . . . . . . . . . . . . . 14
Electrical Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant Oil . . . . . . . . . . . . . . . . . . . . 15
Safety Decals and Locations . . . . . . . . . . . . . . . . . . . 16
EPA Emission Control System Warranty
Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Thermo King Corporation Responsibilities . . . . . .20
Owner Responsibilities . . . . . . . . . . . . . . . . . . . . .21
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Unit Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Diesel Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
ELC (Extended Life Coolant) . . . . . . . . . . . . . . . . . . . .27
EMI 3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Thermo King X430L Reciprocating Compressor . . . . .28
Electronic Throttling Valve . . . . . . . . . . . . . . . . . . . . . .28
SMART REEFER 2 (SR-2) Control System . . . . . . . . .29
CYCLE-SENTRY Operation . . . . . . . . . . . . . . . . .29
Continuous Run Operation . . . . . . . . . . . . . . . . . .29
CYCLE-SENTRY Start-Stop Controls . . . . . . . . . .30
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
FreshSet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
3
Table of Contents
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Safety Practices . . . . . . . . . . . . . . . . . . . . . . 13
Automatic Start/Stop Operation . . . . . . . . . . . . . . . . . 14
Electrical Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant Oil . . . . . . . . . . . . . . . . . . . . 15
Safety Decals and Locations . . . . . . . . . . . . . . . . . . . 16
EPA Emission Control System Warranty
Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Thermo King Corporation Responsibilities . . . . . .20
Owner Responsibilities . . . . . . . . . . . . . . . . . . . . .21
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Unit Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Diesel Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
ELC (Extended Life Coolant) . . . . . . . . . . . . . . . . . . . .27
EMI 3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Thermo King X430L Reciprocating Compressor . . . . .28
Electronic Throttling Valve . . . . . . . . . . . . . . . . . . . . . .28
SMART REEFER 2 (SR-2) Control System . . . . . . . . .29
CYCLE-SENTRY Operation . . . . . . . . . . . . . . . . .29
Continuous Run Operation . . . . . . . . . . . . . . . . . .29
CYCLE-SENTRY Start-Stop Controls . . . . . . . . . .30
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
FreshSet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

Table of Contents
4
Opening the Front Doors . . . . . . . . . . . . . . . . . . . . . . .34
Opening the Secondary Door Latch . . . . . . . . . . .34
Closing the Front Doors . . . . . . . . . . . . . . . . . . . . . . . .35
Engine Compartment Components . . . . . . . . . . . . . . .36
Unit Protection Devices . . . . . . . . . . . . . . . . . . . . . . . .37
Remote Status Display (Optional) . . . . . . . . . . . . . . 41
Manual Pretrip Inspection
(Before Starting the Unit) . . . . . . . . . . . . . . . . . . . . .45
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . .47
SMART REEFER 2 (SR-2) Controller Overview . . . . .47
HMI Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Control Panel Display . . . . . . . . . . . . . . . . . . . . . .49
Control Panel Keys . . . . . . . . . . . . . . . . . . . . . . . .50
Turning Unit On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Turning Unit Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Standard Display Variations . . . . . . . . . . . . . . . . . . . .55
Temperature Watch Display . . . . . . . . . . . . . . . . . . . .56
Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Starting the Diesel Engine . . . . . . . . . . . . . . . . . . . . . .58
Unit Fails To Start . . . . . . . . . . . . . . . . . . . . . . . . .58
After Start Inspection . . . . . . . . . . . . . . . . . . . . . . 59
Electric Standby Operation . . . . . . . . . . . . . . . . . . . . . 60
Starting the Unit on Electric Standby Operation . 61
Unit Fails to Start . . . . . . . . . . . . . . . . . . . . . . . . . 62
Switching from Diesel to Electric . . . . . . . . . . . . . 63
Switching from Electric to Diesel . . . . . . . . . . . . . 64
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . 65
Selection of Operating Modes . . . . . . . . . . . . . . . . . . 68
Selecting CYCLE-SENTRY or Continuous Mode . . . 69
Initiating a Manual Defrost Cycle . . . . . . . . . . . . . . . . 71
Terminating a Defrost Cycle . . . . . . . . . . . . . . . . . . . . 72
Viewing Gauge Readings . . . . . . . . . . . . . . . . . . . . . . 73
Viewing Sensor Readings . . . . . . . . . . . . . . . . . . . . . 75
Navigating the Main Menu . . . . . . . . . . . . . . . . . . . . . 79
Main Menu Choices . . . . . . . . . . . . . . . . . . . . . . . 80
Language Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Alarms Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Important Alarm Notes . . . . . . . . . . . . . . . . . . . . . 86
Datalogger Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Initiating a Start of Trip . . . . . . . . . . . . . . . . . . . . . 88
Printing a Trip Report . . . . . . . . . . . . . . . . . . . . . . 90
Hourmeters Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Mode Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Turning CYCLE-SENTRY On or Off . . . . . . . . . . 97
Table of Contents
4
Opening the Front Doors . . . . . . . . . . . . . . . . . . . . . . .34
Opening the Secondary Door Latch . . . . . . . . . . .34
Closing the Front Doors . . . . . . . . . . . . . . . . . . . . . . . .35
Engine Compartment Components . . . . . . . . . . . . . . .36
Unit Protection Devices . . . . . . . . . . . . . . . . . . . . . . . .37
Remote Status Display (Optional) . . . . . . . . . . . . . . 41
Manual Pretrip Inspection
(Before Starting the Unit) . . . . . . . . . . . . . . . . . . . . .45
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . .47
SMART REEFER 2 (SR-2) Controller Overview . . . . .47
HMI Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Control Panel Display . . . . . . . . . . . . . . . . . . . . . .49
Control Panel Keys . . . . . . . . . . . . . . . . . . . . . . . .50
Turning Unit On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Turning Unit Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Standard Display Variations . . . . . . . . . . . . . . . . . . . .55
Temperature Watch Display . . . . . . . . . . . . . . . . . . . .56
Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Starting the Diesel Engine . . . . . . . . . . . . . . . . . . . . . .58
Unit Fails To Start . . . . . . . . . . . . . . . . . . . . . . . . .58
After Start Inspection . . . . . . . . . . . . . . . . . . . . . . 59
Electric Standby Operation . . . . . . . . . . . . . . . . . . . . . 60
Starting the Unit on Electric Standby Operation . 61
Unit Fails to Start . . . . . . . . . . . . . . . . . . . . . . . . . 62
Switching from Diesel to Electric . . . . . . . . . . . . . 63
Switching from Electric to Diesel . . . . . . . . . . . . . 64
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . 65
Selection of Operating Modes . . . . . . . . . . . . . . . . . . 68
Selecting CYCLE-SENTRY or Continuous Mode . . . 69
Initiating a Manual Defrost Cycle . . . . . . . . . . . . . . . . 71
Terminating a Defrost Cycle . . . . . . . . . . . . . . . . . . . . 72
Viewing Gauge Readings . . . . . . . . . . . . . . . . . . . . . . 73
Viewing Sensor Readings . . . . . . . . . . . . . . . . . . . . . 75
Navigating the Main Menu . . . . . . . . . . . . . . . . . . . . . 79
Main Menu Choices . . . . . . . . . . . . . . . . . . . . . . . 80
Language Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Alarms Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Important Alarm Notes . . . . . . . . . . . . . . . . . . . . . 86
Datalogger Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Initiating a Start of Trip . . . . . . . . . . . . . . . . . . . . . 88
Printing a Trip Report . . . . . . . . . . . . . . . . . . . . . . 90
Hourmeters Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Mode Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Turning CYCLE-SENTRY On or Off . . . . . . . . . . 97

Table of Contents
5
Selecting Keypad Lockout . . . . . . . . . . . . . . . . . . 99
Selecting Sleep Mode . . . . . . . . . . . . . . . . . . . . . 101
Pretrip Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Initiating a Pretrip Test . . . . . . . . . . . . . . . . . . . . 106
Stopping a Pretrip Test . . . . . . . . . . . . . . . . . . . . 107
Electric Standby/Diesel Mode . . . . . . . . . . . . . . . . . . 109
Adjust Brightness Menu . . . . . . . . . . . . . . . . . . . . . . 111
Time Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Selecting a Named Product . . . . . . . . . . . . . . . . 117
Changing the Setpoint for a Named Product . . . 122
Selecting a Setpoint . . . . . . . . . . . . . . . . . . . . . . 125
Optional Rear Remote Control Panel . . . . . . . . . . 129
Rear Remote Control Panel Functions . . . . . . . . . . . 130
Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Stand By . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Reading a Typical Remote Standard Display . . . . . . 135
Remote Control Panel Lockout . . . . . . . . . . . . . . . . . 135
Turning the Unit On or Off (Configured for STAND BY
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Turning the Unit On and Off (Configured for RUN
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . .137
Selecting Cycle-Sentry or Continuous Mode . . . . . . .138
Displaying the Discharge Air Temperature . . . . . . . .139
Viewing and Clearing Alarm Codes . . . . . . . . . . . . . .140
Starting a Manual Defrost Cycle . . . . . . . . . . . . . . . .141
Sending a Start of Trip Marker . . . . . . . . . . . . . . . . . .142
Running a Pretrip Test . . . . . . . . . . . . . . . . . . . . . . . .143
Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Corrective Action . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Loading and Enroute Inspections . . . . . . . . . . . . .165
Pre-Loading Inspection . . . . . . . . . . . . . . . . . . . . . . .165
Post-Loading Inspection . . . . . . . . . . . . . . . . . . . . . .167
Enroute Inspections . . . . . . . . . . . . . . . . . . . . . . .168
Jump Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178
Table of Contents
5
Selecting Keypad Lockout . . . . . . . . . . . . . . . . . . 99
Selecting Sleep Mode . . . . . . . . . . . . . . . . . . . . . 101
Pretrip Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Initiating a Pretrip Test . . . . . . . . . . . . . . . . . . . . 106
Stopping a Pretrip Test . . . . . . . . . . . . . . . . . . . . 107
Electric Standby/Diesel Mode . . . . . . . . . . . . . . . . . . 109
Adjust Brightness Menu . . . . . . . . . . . . . . . . . . . . . . 111
Time Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Selecting a Named Product . . . . . . . . . . . . . . . . 117
Changing the Setpoint for a Named Product . . . 122
Selecting a Setpoint . . . . . . . . . . . . . . . . . . . . . . 125
Optional Rear Remote Control Panel . . . . . . . . . . 129
Rear Remote Control Panel Functions . . . . . . . . . . . 130
Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Stand By . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Reading a Typical Remote Standard Display . . . . . . 135
Remote Control Panel Lockout . . . . . . . . . . . . . . . . . 135
Turning the Unit On or Off (Configured for STAND BY
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Turning the Unit On and Off (Configured for RUN
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . .137
Selecting Cycle-Sentry or Continuous Mode . . . . . . .138
Displaying the Discharge Air Temperature . . . . . . . .139
Viewing and Clearing Alarm Codes . . . . . . . . . . . . . .140
Starting a Manual Defrost Cycle . . . . . . . . . . . . . . . .141
Sending a Start of Trip Marker . . . . . . . . . . . . . . . . . .142
Running a Pretrip Test . . . . . . . . . . . . . . . . . . . . . . . .143
Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Corrective Action . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Loading and Enroute Inspections . . . . . . . . . . . . .165
Pre-Loading Inspection . . . . . . . . . . . . . . . . . . . . . . .165
Post-Loading Inspection . . . . . . . . . . . . . . . . . . . . . .167
Enroute Inspections . . . . . . . . . . . . . . . . . . . . . . .168
Jump Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178

Table of Contents
6
Electrical Control System . . . . . . . . . . . . . . . . . . . . .179
Electric Standby (Model 50 Units Only) . . . . . . . . . . .180
Electric Fuel Heater (Optional) . . . . . . . . . . . . . . . . .181
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . .182
Maintenance Inspection Schedule . . . . . . . . . . . . .183
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .189
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .191
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .197
Serial Number Locations . . . . . . . . . . . . . . . . . . . . 201
Emergency Cold Line . . . . . . . . . . . . . . . . . . . . . . . 205
Recover Refrigerant . . . . . . . . . . . . . . . . . . . . . . . .206
CALIFORNIA
Proposition 65 Warning . . . . . . . . . . . . . . . . . . . . . 207
Table of Contents
6
Electrical Control System . . . . . . . . . . . . . . . . . . . . .179
Electric Standby (Model 50 Units Only) . . . . . . . . . . .180
Electric Fuel Heater (Optional) . . . . . . . . . . . . . . . . .181
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . .182
Maintenance Inspection Schedule . . . . . . . . . . . . .183
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .189
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .191
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .197
Serial Number Locations . . . . . . . . . . . . . . . . . . . . 201
Emergency Cold Line . . . . . . . . . . . . . . . . . . . . . . . 205
Recover Refrigerant . . . . . . . . . . . . . . . . . . . . . . . .206
CALIFORNIA
Proposition 65 Warning . . . . . . . . . . . . . . . . . . . . . 207

7
List of Figures
Figure 1:ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC) . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 2:Belt Warning
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 3:Belt Replacement Caution
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 4:Automatic Start Caution
(Locations vary depending on model. Decals are
located near areas that contain moving parts which
cancause severeinjuriesif handsorclothing become
tangled when unit automatically starts.) . . . . . . . . 17
Figure 5:Fan Caution
(Locations vary depending on model. Decals are
located near areas that contain fans which can cause
severe injuries when unit automatically starts.) . . 17
Figure 6:Door Latch Warning
(Located on curbside door) . . . . . . . . . . . . . . . . . . 18
Figure 7:Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 8:TK486V (TK486VH is Similar) Tier 2 . . . . . . 26
Figure 9:Compressors . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 10:HMI Controller and Data Ports . . . . . . . . . . .31
Figure 11:Door Latch Location . . . . . . . . . . . . . . . . . . .34
Figure 12:Opening Secondary Door Latch . . . . . . . . .34
Figure 13:Engine Compartment . . . . . . . . . . . . . . . . . .36
Figure 14:Control Box With Service Door Open . . . . .39
Figure 15:Control Box With Control Box Door Open . .40
Figure 16:Interface Board . . . . . . . . . . . . . . . . . . . . . .40
Figure 17:Remote Status Display (All LEDs Shown) . .41
Figure 18:Normal Operation No Alarms . . . . . . . . . . . .41
Figure 19:Check Alarm . . . . . . . . . . . . . . . . . . . . . . . .42
Figure 20:Shutdown Alarm . . . . . . . . . . . . . . . . . . . . .42
Figure 21:Remote Status Display with Fuel Level . . . .43
Figure 22:Remote Status Display
with Fuel Level and Temperature . . . . . . . . . . . . .43
Figure 23:SR-2 HMI Control Panel . . . . . . . . . . . . . . .47
Figure 24:Control Box With Service Door Open . . . . .48
Figure 25:Control Panel Display and Keys . . . . . . . . .49
Figure 26:Press On Key . . . . . . . . . . . . . . . . . . . . . . . .51
Figure 27:Turning Unit On Screen Sequence . . . . . . .52
Figure 28:Press Off Key . . . . . . . . . . . . . . . . . . . . . . . .53
Figure 29:Turning Unit Off Screen Sequence . . . . . . .53
7
List of Figures
Figure 1:ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC) . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 2:Belt Warning
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 3:Belt Replacement Caution
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 4:Automatic Start Caution
(Locations vary depending on model. Decals are
located near areas that contain moving parts which
cancause severeinjuriesif handsorclothing become
tangled when unit automatically starts.) . . . . . . . . 17
Figure 5:Fan Caution
(Locations vary depending on model. Decals are
located near areas that contain fans which can cause
severe injuries when unit automatically starts.) . . 17
Figure 6:Door Latch Warning
(Located on curbside door) . . . . . . . . . . . . . . . . . . 18
Figure 7:Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 8:TK486V (TK486VH is Similar) Tier 2 . . . . . . 26
Figure 9:Compressors . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 10:HMI Controller and Data Ports . . . . . . . . . . .31
Figure 11:Door Latch Location . . . . . . . . . . . . . . . . . . .34
Figure 12:Opening Secondary Door Latch . . . . . . . . .34
Figure 13:Engine Compartment . . . . . . . . . . . . . . . . . .36
Figure 14:Control Box With Service Door Open . . . . .39
Figure 15:Control Box With Control Box Door Open . .40
Figure 16:Interface Board . . . . . . . . . . . . . . . . . . . . . .40
Figure 17:Remote Status Display (All LEDs Shown) . .41
Figure 18:Normal Operation No Alarms . . . . . . . . . . . .41
Figure 19:Check Alarm . . . . . . . . . . . . . . . . . . . . . . . .42
Figure 20:Shutdown Alarm . . . . . . . . . . . . . . . . . . . . .42
Figure 21:Remote Status Display with Fuel Level . . . .43
Figure 22:Remote Status Display
with Fuel Level and Temperature . . . . . . . . . . . . .43
Figure 23:SR-2 HMI Control Panel . . . . . . . . . . . . . . .47
Figure 24:Control Box With Service Door Open . . . . .48
Figure 25:Control Panel Display and Keys . . . . . . . . .49
Figure 26:Press On Key . . . . . . . . . . . . . . . . . . . . . . . .51
Figure 27:Turning Unit On Screen Sequence . . . . . . .52
Figure 28:Press Off Key . . . . . . . . . . . . . . . . . . . . . . . .53
Figure 29:Turning Unit Off Screen Sequence . . . . . . .53

List of Figures
8
Figure 30:Standard Display . . . . . . . . . . . . . . . . . . . . .54
Figure 31: Standard Display Variations . . . . . . . . . . . .55
Figure 32:Temperature Watch Display . . . . . . . . . . . .56
Figure 33:Alarm Display . . . . . . . . . . . . . . . . . . . . . . .57
Figure 34:Electric Power Receptacle . . . . . . . . . . . . .60
Figure 35:Electric Standby Detected Screen . . . . . . . .61
Figure 36:Electric Motor Starting Screen . . . . . . . . . . .62
Figure 37:Electric Standby Detected Screen . . . . . . . .63
Figure 38:Programming Electric Standby Screen . . . .63
Figure 39:Electric Standby Undetected Screen . . . . . .64
Figure 40:Programming Diesel Mode Screen . . . . . . .64
Figure 41:Changing Setpoint . . . . . . . . . . . . . . . . . . . .65
Figure 42:Changing the Setpoint Screen Sequence . .67
Figure 43:Changing Mode . . . . . . . . . . . . . . . . . . . . . .69
Figure 44:Screen Sequence for Changing from
CYCLE-SENTRY Mode to Continuous Mode . . . .70
Figure 45:Screen Sequence for Changing from
Continuous Mode to CYCLE-SENTRY Mode . . . .70
Figure 46:Initiating a Manual Defrost Cycle . . . . . . . . .71
Figure 47:Initiating Manual Defrost Screen Sequence 72
Figure 48:Viewing Gauges . . . . . . . . . . . . . . . . . . . . .73
Figure 49:Viewing Gauges Screen Sequence . . . . . . .74
Figure 50:Viewing Sensors . . . . . . . . . . . . . . . . . . . . .75
Figure 51:Viewing Sensors Screen Sequence (continued
on next page) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 52:Viewing Sensors Screen Sequence (continued
from previous page) . . . . . . . . . . . . . . . . . . . . . . . 78
Figure 53:Accessing Main Menu . . . . . . . . . . . . . . . . 79
Figure 54:Main Menu Choices . . . . . . . . . . . . . . . . . . 80
Figure 55:Standard Display . . . . . . . . . . . . . . . . . . . . 82
Figure 56:Standard Display . . . . . . . . . . . . . . . . . . . . 83
Figure 57:Change Language Screen Sequence . . . . 84
Figure 58:Standard Display . . . . . . . . . . . . . . . . . . . . 85
Figure59:Viewingand ClearingAlarmsScreen Sequence
87
Figure 60:Standard Display . . . . . . . . . . . . . . . . . . . . 88
Figure 61:Start of Trip Screen Sequence . . . . . . . . . . 89
Figure 62:Printer Port Location . . . . . . . . . . . . . . . . . 90
Figure 63:Standard Display . . . . . . . . . . . . . . . . . . . . 91
Figure 64:Print Report Screen Sequence . . . . . . . . . 92
Figure 65:Standard Display . . . . . . . . . . . . . . . . . . . . 93
Figure 66:Viewing Hourmeters Screen Sequence
(continued on next page) . . . . . . . . . . . . . . . . . . . 94
Figure 67:Viewing Hourmeters Screen Sequence
(continued from previous page) . . . . . . . . . . . . . . 95
Figure 68:Standard Display . . . . . . . . . . . . . . . . . . . . 97
Figure 69:Selecting Mode Screen Sequence . . . . . . . 98
Figure 70:Standard Display . . . . . . . . . . . . . . . . . . . . 99
List of Figures
8
Figure 30:Standard Display . . . . . . . . . . . . . . . . . . . . .54
Figure 31: Standard Display Variations . . . . . . . . . . . .55
Figure 32:Temperature Watch Display . . . . . . . . . . . .56
Figure 33:Alarm Display . . . . . . . . . . . . . . . . . . . . . . .57
Figure 34:Electric Power Receptacle . . . . . . . . . . . . .60
Figure 35:Electric Standby Detected Screen . . . . . . . .61
Figure 36:Electric Motor Starting Screen . . . . . . . . . . .62
Figure 37:Electric Standby Detected Screen . . . . . . . .63
Figure 38:Programming Electric Standby Screen . . . .63
Figure 39:Electric Standby Undetected Screen . . . . . .64
Figure 40:Programming Diesel Mode Screen . . . . . . .64
Figure 41:Changing Setpoint . . . . . . . . . . . . . . . . . . . .65
Figure 42:Changing the Setpoint Screen Sequence . .67
Figure 43:Changing Mode . . . . . . . . . . . . . . . . . . . . . .69
Figure 44:Screen Sequence for Changing from
CYCLE-SENTRY Mode to Continuous Mode . . . .70
Figure 45:Screen Sequence for Changing from
Continuous Mode to CYCLE-SENTRY Mode . . . .70
Figure 46:Initiating a Manual Defrost Cycle . . . . . . . . .71
Figure 47:Initiating Manual Defrost Screen Sequence 72
Figure 48:Viewing Gauges . . . . . . . . . . . . . . . . . . . . .73
Figure 49:Viewing Gauges Screen Sequence . . . . . . .74
Figure 50:Viewing Sensors . . . . . . . . . . . . . . . . . . . . .75
Figure 51:Viewing Sensors Screen Sequence (continued
on next page) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 52:Viewing Sensors Screen Sequence (continued
from previous page) . . . . . . . . . . . . . . . . . . . . . . . 78
Figure 53:Accessing Main Menu . . . . . . . . . . . . . . . . 79
Figure 54:Main Menu Choices . . . . . . . . . . . . . . . . . . 80
Figure 55:Standard Display . . . . . . . . . . . . . . . . . . . . 82
Figure 56:Standard Display . . . . . . . . . . . . . . . . . . . . 83
Figure 57:Change Language Screen Sequence . . . . 84
Figure 58:Standard Display . . . . . . . . . . . . . . . . . . . . 85
Figure59:Viewingand ClearingAlarmsScreen Sequence
87
Figure 60:Standard Display . . . . . . . . . . . . . . . . . . . . 88
Figure 61:Start of Trip Screen Sequence . . . . . . . . . . 89
Figure 62:Printer Port Location . . . . . . . . . . . . . . . . . 90
Figure 63:Standard Display . . . . . . . . . . . . . . . . . . . . 91
Figure 64:Print Report Screen Sequence . . . . . . . . . 92
Figure 65:Standard Display . . . . . . . . . . . . . . . . . . . . 93
Figure 66:Viewing Hourmeters Screen Sequence
(continued on next page) . . . . . . . . . . . . . . . . . . . 94
Figure 67:Viewing Hourmeters Screen Sequence
(continued from previous page) . . . . . . . . . . . . . . 95
Figure 68:Standard Display . . . . . . . . . . . . . . . . . . . . 97
Figure 69:Selecting Mode Screen Sequence . . . . . . . 98
Figure 70:Standard Display . . . . . . . . . . . . . . . . . . . . 99

List of Figures
9
Figure 71:Mode Menu Display . . . . . . . . . . . . . . . . . . 99
Figure 72:Keypad Lockout Display . . . . . . . . . . . . . . 100
Figure 73:Standard Display . . . . . . . . . . . . . . . . . . . 101
Figure 74:Selecting Sleep Mode Screen Sequence . 103
Figure 75:Standard Display . . . . . . . . . . . . . . . . . . . 106
Figure 76:No Pretrip Alarm Active Display . . . . . . . . 106
Figure 77:Pretrip Test Screen Sequence . . . . . . . . . 108
Figure 78:Standard Display . . . . . . . . . . . . . . . . . . . 109
Figure 79:Programming Diesel Mode . . . . . . . . . . . . 110
Figure 80:Programming Electric Standby Mode . . . . 111
Figure 81:Standard Display . . . . . . . . . . . . . . . . . . . 112
Figure82:AdjustingDisplay BrightnessScreen Sequence
113
Figure 83:Time and Date Screens . . . . . . . . . . . . . . 114
Figure 84:Standard Display with Product Soft Key . . 115
Figure 85:Standard Display with
Product/Setpoint Soft Key . . . . . . . . . . . . . . . . . 116
Figure 86:Selecting Named Product . . . . . . . . . . . . . 117
Figure 87:Selecting or Changing Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 88:Selecting Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 89:Changing Setpoint for Named Product . . . 122
Figure 90:Changing Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Figure 91:Selecting or Changing Setpoint . . . . . . . . .125
Figure 92:Selecting or Changing Numeric Setpoint
Screen Sequence . . . . . . . . . . . . . . . . . . . . . . . .127
Figure 93:Rear Remote Control Panel . . . . . . . . . . . .129
Figure 94:Rear Remote Control Panel Display . . . . .131
Figure 95:Unit HMI Control Panel Display . . . . . . . . .131
Figure 96:Press Select Key . . . . . . . . . . . . . . . . . . . .132
Figure 97:Rear Remote Control Panel . . . . . . . . . . . .133
Figure 98:Rear Remote Control Panel . . . . . . . . . . . .134
Figure 99:Remote Standard Display . . . . . . . . . . . . .135
Figure 100:Remote Lock Out Display . . . . . . . . . . . .135
Figure 101:Stand By Display . . . . . . . . . . . . . . . . . . .136
Figure 102:Standard Display . . . . . . . . . . . . . . . . . . .136
Figure 103:Press Up or Down Arrow Keys . . . . . . . .137
Figure 104:Press Enter Key . . . . . . . . . . . . . . . . . . . .137
Figure 105:Press Select Key . . . . . . . . . . . . . . . . . . .138
Figure 106:Press Up or Down Arrow Keys . . . . . . . .138
Figure 107:Press Enter Key . . . . . . . . . . . . . . . . . . . .138
Figure 108:Press Select Key Twice . . . . . . . . . . . . . .139
Figure 109:Press Select Key Three Times . . . . . . . .140
Figure 110:Press Enter Key . . . . . . . . . . . . . . . . . . . .140
Figure 111:No Alarms Display . . . . . . . . . . . . . . . . . .140
Figure 112:Press Defrost Key . . . . . . . . . . . . . . . . . .141
List of Figures
9
Figure 71:Mode Menu Display . . . . . . . . . . . . . . . . . . 99
Figure 72:Keypad Lockout Display . . . . . . . . . . . . . . 100
Figure 73:Standard Display . . . . . . . . . . . . . . . . . . . 101
Figure 74:Selecting Sleep Mode Screen Sequence . 103
Figure 75:Standard Display . . . . . . . . . . . . . . . . . . . 106
Figure 76:No Pretrip Alarm Active Display . . . . . . . . 106
Figure 77:Pretrip Test Screen Sequence . . . . . . . . . 108
Figure 78:Standard Display . . . . . . . . . . . . . . . . . . . 109
Figure 79:Programming Diesel Mode . . . . . . . . . . . . 110
Figure 80:Programming Electric Standby Mode . . . . 111
Figure 81:Standard Display . . . . . . . . . . . . . . . . . . . 112
Figure82:AdjustingDisplay BrightnessScreen Sequence
113
Figure 83:Time and Date Screens . . . . . . . . . . . . . . 114
Figure 84:Standard Display with Product Soft Key . . 115
Figure 85:Standard Display with
Product/Setpoint Soft Key . . . . . . . . . . . . . . . . . 116
Figure 86:Selecting Named Product . . . . . . . . . . . . . 117
Figure 87:Selecting or Changing Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 88:Selecting Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 89:Changing Setpoint for Named Product . . . 122
Figure 90:Changing Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Figure 91:Selecting or Changing Setpoint . . . . . . . . .125
Figure 92:Selecting or Changing Numeric Setpoint
Screen Sequence . . . . . . . . . . . . . . . . . . . . . . . .127
Figure 93:Rear Remote Control Panel . . . . . . . . . . . .129
Figure 94:Rear Remote Control Panel Display . . . . .131
Figure 95:Unit HMI Control Panel Display . . . . . . . . .131
Figure 96:Press Select Key . . . . . . . . . . . . . . . . . . . .132
Figure 97:Rear Remote Control Panel . . . . . . . . . . . .133
Figure 98:Rear Remote Control Panel . . . . . . . . . . . .134
Figure 99:Remote Standard Display . . . . . . . . . . . . .135
Figure 100:Remote Lock Out Display . . . . . . . . . . . .135
Figure 101:Stand By Display . . . . . . . . . . . . . . . . . . .136
Figure 102:Standard Display . . . . . . . . . . . . . . . . . . .136
Figure 103:Press Up or Down Arrow Keys . . . . . . . .137
Figure 104:Press Enter Key . . . . . . . . . . . . . . . . . . . .137
Figure 105:Press Select Key . . . . . . . . . . . . . . . . . . .138
Figure 106:Press Up or Down Arrow Keys . . . . . . . .138
Figure 107:Press Enter Key . . . . . . . . . . . . . . . . . . . .138
Figure 108:Press Select Key Twice . . . . . . . . . . . . . .139
Figure 109:Press Select Key Three Times . . . . . . . .140
Figure 110:Press Enter Key . . . . . . . . . . . . . . . . . . . .140
Figure 111:No Alarms Display . . . . . . . . . . . . . . . . . .140
Figure 112:Press Defrost Key . . . . . . . . . . . . . . . . . .141

List of Figures
10
Figure 113:Press Enter Key . . . . . . . . . . . . . . . . . . .141
Figure 114:Defrost Icon Displayed . . . . . . . . . . . . . .141
Figure 115:Press TK Logo Key . . . . . . . . . . . . . . . . .142
Figure 116:Press Enter Key . . . . . . . . . . . . . . . . . . .142
Figure 117:Press Pretrip Key . . . . . . . . . . . . . . . . . .143
Figure 118:Press Enter Key . . . . . . . . . . . . . . . . . . .143
Figure 119:Pretrip Display . . . . . . . . . . . . . . . . . . . . .144
Figure 120:Pass Pretrip Display . . . . . . . . . . . . . . . .144
Figure 121:Log Alarms Screen . . . . . . . . . . . . . . . . .145
Figure 122:Alarm Display . . . . . . . . . . . . . . . . . . . . .146
Figure 123:Shutdown Alarm Display . . . . . . . . . . . . .147
Figure 124:Loading Considerations . . . . . . . . . . . . . .166
Figure 125:Unit Battery . . . . . . . . . . . . . . . . . . . . . . .172
Figure 126:Sequence for Connecting Jumper Cables . . .
172
Figure 127:Unit Engine . . . . . . . . . . . . . . . . . . . . . . .173
Figure 128:Sequence for Disconnecting Jumper Cables
174
Figure 129:Compressor Serial Number Location . . .202
Figure 130:Engine Serial Number Location . . . . . . . .202
Figure 131:Unit Serial Number Plate Locations
(on the bulkhead above compressor inside
curbside door and on roadside of evaporator) . .203
Figure 132:Unit Serial Number Plate . . . . . . . . . . . . .203
List of Figures
10
Figure 113:Press Enter Key . . . . . . . . . . . . . . . . . . .141
Figure 114:Defrost Icon Displayed . . . . . . . . . . . . . .141
Figure 115:Press TK Logo Key . . . . . . . . . . . . . . . . .142
Figure 116:Press Enter Key . . . . . . . . . . . . . . . . . . .142
Figure 117:Press Pretrip Key . . . . . . . . . . . . . . . . . .143
Figure 118:Press Enter Key . . . . . . . . . . . . . . . . . . .143
Figure 119:Pretrip Display . . . . . . . . . . . . . . . . . . . . .144
Figure 120:Pass Pretrip Display . . . . . . . . . . . . . . . .144
Figure 121:Log Alarms Screen . . . . . . . . . . . . . . . . .145
Figure 122:Alarm Display . . . . . . . . . . . . . . . . . . . . .146
Figure 123:Shutdown Alarm Display . . . . . . . . . . . . .147
Figure 124:Loading Considerations . . . . . . . . . . . . . .166
Figure 125:Unit Battery . . . . . . . . . . . . . . . . . . . . . . .172
Figure 126:Sequence for Connecting Jumper Cables . . .
172
Figure 127:Unit Engine . . . . . . . . . . . . . . . . . . . . . . .173
Figure 128:Sequence for Disconnecting Jumper Cables
174
Figure 129:Compressor Serial Number Location . . .202
Figure 130:Engine Serial Number Location . . . . . . . .202
Figure 131:Unit Serial Number Plate Locations
(on the bulkhead above compressor inside
curbside door and on roadside of evaporator) . .203
Figure 132:Unit Serial Number Plate . . . . . . . . . . . . .203

11
Introduction
There is nothing complicated about operating and maintaining
your Thermo King unit, but a few minutes studying this
manual will be time well spent.
Performing pre-trip checks and enroute inspections on a
regular basis will minimize on-the-road operating problems. A
regular maintenance program will also help to keep your unit
in top operating condition. If factory recommended procedures
are followed, you will find that you have purchased the most
efficient and dependable temperature control system available.
All service requirements, major and minor, should be handled
by a Thermo King dealer for four very important reasons:
• They are equipped with the factory recommended tools to
perform all service functions
• They have factory trained and certified technicians
• They have genuine Thermo King replacement parts
• The warranty on your new unit is valid only when the
repair and replacement of component parts is performed
by an authorized Thermo King dealer.
IMPORTANT: This manual is published for informational
purposes only and the information furnished herein should
not be considered as all-inclusive or meant to cover all
contingencies. If more information is required, consult your
Thermo King Service Directory for the location and
telephone number of the local dealer.
11
Introduction
There is nothing complicated about operating and maintaining
your Thermo King unit, but a few minutes studying this
manual will be time well spent.
Performing pre-trip checks and enroute inspections on a
regular basis will minimize on-the-road operating problems. A
regular maintenance program will also help to keep your unit
in top operating condition. If factory recommended procedures
are followed, you will find that you have purchased the most
efficient and dependable temperature control system available.
All service requirements, major and minor, should be handled
by a Thermo King dealer for four very important reasons:
• They are equipped with the factory recommended tools to
perform all service functions
• They have factory trained and certified technicians
• They have genuine Thermo King replacement parts
• The warranty on your new unit is valid only when the
repair and replacement of component parts is performed
by an authorized Thermo King dealer.
IMPORTANT: This manual is published for informational
purposes only and the information furnished herein should
not be considered as all-inclusive or meant to cover all
contingencies. If more information is required, consult your
Thermo King Service Directory for the location and
telephone number of the local dealer.

Introduction
12
Introduction
12

13
Safety Precautions
Thermo King recommends that servicing be done only by a
Thermo King dealer. However, you should be aware of several
safety practices. This chapter gives basic safety precautions for
working with Thermo King units and describes the safety
stickers on your unit that you should be familiar with.
General Safety Practices
DANGER: NEVER operate the unit with the
compressor discharge valve closed. Doing so could
cause the compressor to explode, causing death or
serious injury.
WARNING: Always wear goggles or safety glasses
when working with or around the refrigeration system
or battery. Refrigerant or battery acid can cause
permanent damage if it comes in contact with your
eyes.
WARNING: Keep hands and loose clothing clear of
fans and belts at all times when the unit is operating
or when opening or closing compressor service
valves.
WARNING: Exposed coil fins can cause painful
lacerations. Service work on the evaporator or
condenser coils should be done by a certified Thermo
King technician.
WARNING: Do not apply heat to a closed cooling
system. Before applying heat to a cooling system,
drain it. Then flush it with water and drain the water.
Antifreeze contains water and ethylene glycol. The
ethylene glycol is flammable and can ignite if the
antifreeze is heated enough to boil off the water.
13
Safety Precautions
Thermo King recommends that servicing be done only by a
Thermo King dealer. However, you should be aware of several
safety practices. This chapter gives basic safety precautions for
working with Thermo King units and describes the safety
stickers on your unit that you should be familiar with.
General Safety Practices
DANGER: NEVER operate the unit with the
compressor discharge valve closed. Doing so could
cause the compressor to explode, causing death or
serious injury.
WARNING: Always wear goggles or safety glasses
when working with or around the refrigeration system
or battery. Refrigerant or battery acid can cause
permanent damage if it comes in contact with your
eyes.
WARNING: Keep hands and loose clothing clear of
fans and belts at all times when the unit is operating
or when opening or closing compressor service
valves.
WARNING: Exposed coil fins can cause painful
lacerations. Service work on the evaporator or
condenser coils should be done by a certified Thermo
King technician.
WARNING: Do not apply heat to a closed cooling
system. Before applying heat to a cooling system,
drain it. Then flush it with water and drain the water.
Antifreeze contains water and ethylene glycol. The
ethylene glycol is flammable and can ignite if the
antifreeze is heated enough to boil off the water.

Safety Precautions
14
Automatic Start/Stop Operation
This unit is capable of automatic operation and could start at
any time without warning.
Electrical Hazard
Refrigerant
Although fluorocarbon refrigerants are classified as safe, use
caution when working with refrigerants or in areas where they
are being used.
CAUTION: Use extreme caution when drilling holes
in the unit. Drilling into electrical wiring or
refrigerant lines could cause a fire. Do not drill into
structural components.
WARNING: The unit can start at any time without
warning. Press the OFF key on the HMI control panel
and place the microprocessor On/Off switch in the
Off position before inspecting or servicing any part of
the unit.
CAUTION: Turn off the high voltage power supply
and disconnect the electric cable before working on
the unit. Units with electric standby present a
potential electrical hazard.
DANGER: Fluorocarbon refrigerants can produce
toxic gases. In the presence of an open flame or
electrical short, these gases are severe respiratory
irritants CAPABLE OF CAUSING DEATH.
DANGER: Fluorocarbon refrigerants tend to
displace air and can cause oxygen depletion which
could result in DEATH BY SUFFOCATION. Provide
adequate ventilation in enclosed or confined areas.
WARNING: Fluorocarbon refrigerants evaporate
rapidly, freezing anything they contact if accidentally
released into the atmosphere from the liquid state.
Safety Precautions
14
Automatic Start/Stop Operation
This unit is capable of automatic operation and could start at
any time without warning.
Electrical Hazard
Refrigerant
Although fluorocarbon refrigerants are classified as safe, use
caution when working with refrigerants or in areas where they
are being used.
CAUTION: Use extreme caution when drilling holes
in the unit. Drilling into electrical wiring or
refrigerant lines could cause a fire. Do not drill into
structural components.
WARNING: The unit can start at any time without
warning. Press the OFF key on the HMI control panel
and place the microprocessor On/Off switch in the
Off position before inspecting or servicing any part of
the unit.
CAUTION: Turn off the high voltage power supply
and disconnect the electric cable before working on
the unit. Units with electric standby present a
potential electrical hazard.
DANGER: Fluorocarbon refrigerants can produce
toxic gases. In the presence of an open flame or
electrical short, these gases are severe respiratory
irritants CAPABLE OF CAUSING DEATH.
DANGER: Fluorocarbon refrigerants tend to
displace air and can cause oxygen depletion which
could result in DEATH BY SUFFOCATION. Provide
adequate ventilation in enclosed or confined areas.
WARNING: Fluorocarbon refrigerants evaporate
rapidly, freezing anything they contact if accidentally
released into the atmosphere from the liquid state.

Safety Precautions
15
Refrigerant Oil
Observe the following precautions when working with or
around refrigerant oil:
First Aid
First Aid–Refrigerant
Eyes: For contact with liquid, immediately flush eyes with
large amounts of water. Get prompt medical attention.
Skin: Flush areas with large amounts of warm water. Do not
apply heat. Wrap burns with dry, sterile, bulky dressing to
protect from infection or injury. Get prompt medical attention.
Inhalation: Move victim to fresh air and restore breathing if
necessary. Stay with victim until emergency personnel arrive.
First Aid–Refrigerant Oil
Eyes: Immediately flush eyes with large amounts of water for
at least 15 minutes while holding the eyelids open. Get prompt
medical attention.
Skin: Remove contaminated clothing. Wash thoroughly with
soap and water. Get medical attention if irritation persists.
Inhalation: Move victim to fresh air and restore breathing if
necessary. Stay with victim until emergency personnel arrive.
Ingestion: Do not induce vomiting. Immediately contact
local poison control center or physician.
WARNING: Always wear goggles or safety glasses to
protect eyes from refrigerant oil contact.
WARNING: Protect skin and clothing from
prolonged or repeated contact with refrigerant oil.
Rubber gloves are recommended.
WARNING: Wash thoroughly immediately after
handling refrigerant oil to prevent irritation.
Safety Precautions
15
Refrigerant Oil
Observe the following precautions when working with or
around refrigerant oil:
First Aid
First Aid–Refrigerant
Eyes: For contact with liquid, immediately flush eyes with
large amounts of water. Get prompt medical attention.
Skin: Flush areas with large amounts of warm water. Do not
apply heat. Wrap burns with dry, sterile, bulky dressing to
protect from infection or injury. Get prompt medical attention.
Inhalation: Move victim to fresh air and restore breathing if
necessary. Stay with victim until emergency personnel arrive.
First Aid–Refrigerant Oil
Eyes: Immediately flush eyes with large amounts of water for
at least 15 minutes while holding the eyelids open. Get prompt
medical attention.
Skin: Remove contaminated clothing. Wash thoroughly with
soap and water. Get medical attention if irritation persists.
Inhalation: Move victim to fresh air and restore breathing if
necessary. Stay with victim until emergency personnel arrive.
Ingestion: Do not induce vomiting. Immediately contact
local poison control center or physician.
WARNING: Always wear goggles or safety glasses to
protect eyes from refrigerant oil contact.
WARNING: Protect skin and clothing from
prolonged or repeated contact with refrigerant oil.
Rubber gloves are recommended.
WARNING: Wash thoroughly immediately after
handling refrigerant oil to prevent irritation.

Safety Precautions
16
Safety Decals and Locations
Figure 1: ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC)
Figure 2: Belt Warning
(Located on condenser housing)
Figure 3: Belt Replacement Caution
(Located on condenser housing)
AJA1947
AKB65
AKB66
Safety Precautions
16
Safety Decals and Locations
Figure 1: ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC)
Figure 2: Belt Warning
(Located on condenser housing)
Figure 3: Belt Replacement Caution
(Located on condenser housing)
AJA1947
AKB65
AKB66

Safety Precautions
17
Figure 4: Automatic Start Caution
(Locations vary depending on model. Decals are
located near areas that contain moving parts which
cancause severe injuries if hands or clothing become
tangled when unit automatically starts.)
Figure 5: Fan Caution
(Locations vary depending on model. Decals are
located near areas that contain fans which can cause
severe injuries when unit automatically starts.)
AKB67 AKB68
Safety Precautions
17
Figure 4: Automatic Start Caution
(Locations vary depending on model. Decals are
located near areas that contain moving parts which
cancause severe injuries if hands or clothing become
tangled when unit automatically starts.)
Figure 5: Fan Caution
(Locations vary depending on model. Decals are
located near areas that contain fans which can cause
severe injuries when unit automatically starts.)
AKB67 AKB68

Safety Precautions
18
Figure 6: Door Latch Warning
(Located on curbside door)
WARNING
ATENCIÓN
NEW DOOR LATCH DESIGN
REQUIRES DOOR TO BE SLAMMED
SHUT BEFORE MOVING TRAILER.
FAILURE TO CLOSE DOOR FIRMLY
CAN ALLOW WIND TO TEAR DOOR
FROM REFRIGERATION UNIT AND
CAUSE INJURY TO OTHERS.
NUEVO DESEÑO DE CERRADURA
REQUIERE ASOTAR LA PUERTA ANTES
DE CONDUCIR EL TRAILER.
AL NO CERRAR LA PUERTA CON
FIRMEZA EL VIENTO PODRÍA
DESPRENDER LA PUERTA DE LA
UNIDAD DE REFRIGERACIÓN Y
CAUSAR DAÑOS A OTROS. AEA2422
Safety Precautions
18
Figure 6: Door Latch Warning
(Located on curbside door)
WARNING
ATENCIÓN
NEW DOOR LATCH DESIGN
REQUIRES DOOR TO BE SLAMMED
SHUT BEFORE MOVING TRAILER.
FAILURE TO CLOSE DOOR FIRMLY
CAN ALLOW WIND TO TEAR DOOR
FROM REFRIGERATION UNIT AND
CAUSE INJURY TO OTHERS.
NUEVO DESEÑO DE CERRADURA
REQUIERE ASOTAR LA PUERTA ANTES
DE CONDUCIR EL TRAILER.
AL NO CERRAR LA PUERTA CON
FIRMEZA EL VIENTO PODRÍA
DESPRENDER LA PUERTA DE LA
UNIDAD DE REFRIGERACIÓN Y
CAUSAR DAÑOS A OTROS. AEA2422

19
EPA Emission Control System Warranty
Statement
Thermo King warrants to the initial owner and each subsequent
owner that the certified, non-road diesel engine in your unit is:
1. Designed, built and equipped so as to conform, at the time
of sale, with all applicable regulations adopted by the
United States Environmental Protection Agency (EPA).
2. Free from defects in materials and workmanship in
specific emission related parts for a period of five years or
3,000 hours of operation, whichever comes first, after date
of delivery to the initial owner.
If an emission-related part or component fails during the
warranty period, it will be repaired or replaced. Any such part
or component repaired or replaced under warranty is warranted
for the warranty period.
During the term of this warranty, Thermo King will provide,
through a Thermo King authorized service dealer or other
establishment authorized by Thermo King, repair or
replacement of any warranted part at no charge to the non-road
engine owner.
In emergency, repairs may be performed at any service
establishment, or by the owner, using any replacement part.
Thermo King will reimburse the owner for their expenses,
including diagnostic charges for such emergency repair. These
expenses shall not exceed Thermo King’s suggested retail price
for all warranted parts replaced, and labor changes based on
Thermo King’s recommended time allowance for the warranty
repair and the geographically appropriate hourly labor rate.
19
EPA Emission Control System Warranty
Statement
Thermo King warrants to the initial owner and each subsequent
owner that the certified, non-road diesel engine in your unit is:
1. Designed, built and equipped so as to conform, at the time
of sale, with all applicable regulations adopted by the
United States Environmental Protection Agency (EPA).
2. Free from defects in materials and workmanship in
specific emission related parts for a period of five years or
3,000 hours of operation, whichever comes first, after date
of delivery to the initial owner.
If an emission-related part or component fails during the
warranty period, it will be repaired or replaced. Any such part
or component repaired or replaced under warranty is warranted
for the warranty period.
During the term of this warranty, Thermo King will provide,
through a Thermo King authorized service dealer or other
establishment authorized by Thermo King, repair or
replacement of any warranted part at no charge to the non-road
engine owner.
In emergency, repairs may be performed at any service
establishment, or by the owner, using any replacement part.
Thermo King will reimburse the owner for their expenses,
including diagnostic charges for such emergency repair. These
expenses shall not exceed Thermo King’s suggested retail price
for all warranted parts replaced, and labor changes based on
Thermo King’s recommended time allowance for the warranty
repair and the geographically appropriate hourly labor rate.
This manual suits for next models
1
Table of contents
Other Thermo King Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Watlow Electric
Watlow Electric 602 Series datasheet

Arroyo Instruments
Arroyo Instruments TECPak 586 Series user manual

Maico
Maico WS-VH 160 installation instructions

eltherm
eltherm ELTC-14P operating instructions

ALSENSE
ALSENSE ALS Brake Wired install guide

Vive Comfort
Vive Comfort TP-N-721 operating manual