InstallationInstallation
Fixing
The unit mu be securely xed
to a single smooth at surface.
Any orientation is possible.
Locate a site for mounting the Titon CME3.1,
take into consideration the position of:
xThe rooms to be ventilated
xThe Electrical services
xThe exhau port orientation.
Ensure there is adequate access
for inallation and maintenance,
see Dimensions for sizes.
Securely mount the unit through the mounting
holes on the casing using the appropriate
xings for the subrate and the CME3.1.
Ensure the unit is not diorted by
the xings or mounting surface.
The xing slots on the unit are 6mm wide, it
may be necessary to use washers to prevent
damage to the CME3.1's xing slots.
Tighten screws by hand, DO NOT over tighten
screws or use power tools.
Ducting Connections
Titon recommend that:
1. Ø125mm ducting is used for the
connection of the Output Port to Outside.
2. Ø125mm or Ø100mm ducting is used
for connection to the other ports.
3. A minimum diance of 200mm
between the CME3.1 unit and any
sharp bends in duct work.
4. Ducting should be insulated
where it passes through
unheated areas and voids.
5. Unit should be insulated when
tted in unheated area.
6. Where a duct extends externally above
roof level the section above the roof
should be insulated or a condensate trap
should be tted ju below roof level.
7. Where ducts pass through re barriers,
they mu be appropriately re opped in
accordance with the requirements of Part
B Building Regulations (England & Wales).
8. A ducting condensate drain
mu be tted to vertical Output
Port to Outside duct work.
9. Condensate drain pipe work mu be
adequately secured, inalled to have
a minimum 5° fall and be insulated if
any part of the pipe passes though an
unheated void. All insulation to be the
equivalent of at lea 25mm of insulating
material with a thermal conductivity
of 0.04 W/(mK).
10. Ducting mu be inalled in such a way
that resiance to airow is minimised.
11. Ducting connected to the Output Port
to Outside mu be to the external
air outside the building envelope.
12. All ducting joints including those to
the CME3.1 unit’s Duct Ports and
Convertible Port Covers mu be
permanently connected and sealed.
13. Do not diort ducting, Convertible
Port Cover or Duct Ports.