Are there scratches or dents on the existing pipes?
Is it possible to operate the existing air conditioner?
yAfter the existing air conditioner is operated in
cooling mode for approx. 30 minutes or longer,*
recover the refrigerant.
yRefer to “13 Refrigerant recovery”
yFor cleaning the pipes and recovering oil
yRefrigerant recovery: Pump down method
yRemove the existing air conditioner from the piping
and carry out flushing (nitrogen pressure 0.5 MPa)
to remove any remains inside of the pipe.
Connect the indoor / outdoor units to the existing
pipe.
yUse a flare nut attached to the main unit for the
indoor / outdoor units. (Do not use the flare nut of
the existing pipe.)
yRe-machine the flare machining size to size for
R32.
y(Airtight test), Vacuum dry, Refrigerant charge, Gas
leak check
Test run
Was largely discolored oil or a large quantity
of remains discharged? (When the oil deteriorates,
the color of the oil changes to a muddy or
black color.)
Existing pipes: Cannot be used.
yUse new pipes.
Clean the pipes or use new pipes.
Piping necessary to change the flare nut / machining
size due to pipe compression
1) Flare nut width: H
H
(mm)
Copper pipe outer
diameter Ø6.4 Ø9.5 Ø12.7
For R32, R410A 17 22 26
For R22 Same as above 24
2) Flare machining size: A
A
(mm)
Copper pipe outer
diameter Ø6.4 Ø9.5 Ø12.7
For R32, R410A 9.1 13.2 16.6
For R22 9.0 13.0 16.2
Becomes a little larger for R32/R410A
Do not apply refrigerator oil to the flare surface.
(If there is discharge of remains, it is judged that a
large quantity of remains are present.)
YES
YES
NO
NO
NO
YES
Nitrogen gas pressure 0.5 MPa
14 Appendix
Work instructions
The existing R22 and R410A piping can be reused for
our digital inverter R32 product installations.
WARNING
Confirming the existence of scratches or dents on
the existing pipes and confirming the reliability of
the pipe strength are conventionally referred to the
local site.
If the specified conditions can be cleared, it is
possible to update existing R22 and R410A pipes
to those for R32 models.
Basic conditions needed to reuse existing
pipes
Check and observe the presence of three conditions in
the refrigerant piping works.
1. Dry (There is no moisture inside of the pipes.)
2. Clean (There is no dust inside of the pipes.)
3. Tight (There are no refrigerant leaks.)
Restrictions for use of existing pipes
In the following cases, the existing pipes should
not be reused as they are. Clean the existing pipes
or exchange them with new pipes.
1. When a scratch or dent is heavy, be sure to use
new pipes for the refrigerant piping works.
2. When the existing pipe thickness is thinner than the
specified “Pipe diameter and thickness,” be sure to
use new pipes for the refrigerant piping works.
yThe operating pressure of R32 is high. If there is
a scratch or dent on the pipe or a thinner pipe is
used, the pressure strength may be inadequate,
which may cause the pipe to break in the worst
case.
* Pipe diameter and thickness (mm)
Pipe outer diameter Ø6.4 Ø9.5 Ø12.7
Thickness R32/R410A 0.8 0.8 0.8
R22
yIn case the pipe diameter is Ø12.7 mm or less
and the thickness is less than 0.7 mm, be sure to
use new pipes for the refrigerant piping works.
3. When the outdoor unit was left with the pipes
disconnected, or the gas leaked from the pipes and
the pipes were not repaired and refilled.
yThere is the possibility of rain water or air,
including moisture, entering the pipe.
4. When refrigerant cannot be recovered using a
refrigerant recovery unit.
yThere is the possibility that a large quantity of dirty
oil or moisture remains inside the pipes.
5. When a commercially available dryer is attached to
the existing pipes.
yThere is the possibility that copper green rust has
been generated.
6. When the existing air conditioner is removed after
refrigerant has been recovered.
Check if the oil is judged to be clearly different from
normal oil.
yThe refrigerator oil is copper rust green in color:
There is the possibility that moisture has mixed
with the oil and rust has been generated inside
the pipe.
yThere is discolored oil, a large quantity of residue,
or a bad smell.
yA large quantity of shiny metal dust or other wear
residue can be seen in the refrigerant oil.
7. When the air conditioner has a history of the
compressor failing and being replaced.
yWhen discolored oil, a large quantity of residue,
shiny metal dust, or other wear residue or mixture
of foreign matter is observed, trouble will occur.
8. When temporary installation and removal of the air
conditioner are repeated such as when leased etc.
9. If the type of refrigerator oil of the existing air
conditioner is other than the following oil (Mineral
oil), Suniso, Freol-S, MS (Synthetic oil), alkyl
benzene (HAB, Barrel-freeze), ester series, PVE
only of ether series.
yThe winding-insulation of the compressor may
deteriorate.
NOTE
The above descriptions are results have been
confirmed by our company and represent our views on
our air conditioners, but do not guarantee the use of
the existing pipes of air conditioners that have adopted
R32/R410A in other companies.
Curing of pipes
When removing and opening the indoor or outdoor unit
for a long time, cure the pipes as follows:
yOtherwise rust may be generated when moisture or
foreign matter due to condensation enters the pipes.
yThe rust cannot be removed by cleaning, and new
pipes are necessary.
Placement
location Term Curing manner
Outdoors 1 month or more Pinching
Less than 1 month Pinching or taping
Indoors Every time