2) The quanty and size of indoor units installed.
(Qty and size of Standard indoor units, Air to Air Heat Exchangers, Fresh Air Units)
Addional refrigerant is added to the system for each indoor unit connected in the system, this is worked
out dependant on the type of indoor unit installed;
Fresh Air Intake Units, MMD-UP0481/0721/0961/1121/1281HFP-E/E1 - 0kg/HP
Standard Units, MMK, MMU (MH,HP,WH,YH), MMC, MMD (SPH, BH, H), MML (BH, H, NH), MMF = g7
High eciency 4-way blow cassee, MMU (UP####H-E) = g 8
Hot Water Modules, MMW (UP####LQ-E, AP####CHQ-E) = g 9
DX Coil Interfaces, M(C)MY-MHP####HT-E = g 10
3) The Diversity of the system,.
i.e the Total HP of the installed indoor units mulplied by the Total HP of the outdoor units forming the
system, (Outdoor units connected together electrically, via U5 & U6) the result is the Diversity, = g 11
4) Liquid Line Installed.
Measure the lengths of Liquid Line pipe installed, STRAIGHT PIPE ONLY, (Linear), DO NOT CALCULATE FOR
BENDS OR FITTINGS, mulply by the corresponding kg/m = g 12
Examples.
1) A 60HP system, MMY-UP6211HT8P-E ( 2x24hp (2 x MMY-MUP2401HT8P-E) + 1 x 12hp, (1 x MMY-MUP1201HT8P-
E), with 2 x 10hp,MMD-MUP0961HP-E1 (28kW-Cool, High Stac Ducted units) plus 8 x 4hp, MMDUP0361BHP-E
(11.2kW-Cool, Standard Ducted Units), plus 5 x 2hp, MMD-MUP0181BHP-E (5.6kW-Cool, Standard Ducted Units),
Indoor to Outdoor Diversity = 103.33%, Correct Charge 0kg, with 35m of 7/8” Liquid Line, 20m of 3/4” Liquid Line,
10m of 5/8” Liquid Line, 30m of 1/2” Liquid Line, 30m of 3/8” Liquid Line and 25m of 1/4” Liquid Line.
13.3kg + (2 x 1kg [2kg]+ 8 x 0.6kg [4.8kg]+ 5 x 0.4kg [2kg]) = 8.8kg + (35 x 0.370=12.25kg + 20 x 0.250=5kg + 10 x
0.160=1.6kg + 30 x 0.105=3.15kg + 30 x 0.055=1.65kg + 25 x 0.025=0.625kg) = 24.275kg + Diversity 0kg
13.3 + 8.8 + 24.275 + 0 = 46.375kg
2) A 60HP system, MMY-UP6211HT8P-E ( 2x24hp (2 x MMY-MUP2401HT8P-E) + 1 x 12hp, (1 x MMY-MUP1201HT8P-
E), with (2 x 10hp,MMD-MUP0961HP-E1 (28kW-Cool, High Stac Ducted units) plus) (8) 7x 4hp, MMDUP0361BHP-E
(11.2kW-Cool, Standard Ducted Units), plus 5 x 2hp, MMD-MUP0181BHP-E (5.6kW-Cool, Standard Ducted Units),
Indoor to Outdoor Diversity = (103.33%) 63.33%, Correct Charge (0kg) -2kg, with 35m of 7/8” Liquid Line, 20m of
3/4” Liquid Line, 10m of 5/8” Liquid Line, (30m) 10m of 1/2” Liquid Line, 30m of 3/8” Liquid Line and 25m of 1/4”
Liquid Line.
13.3kg + (2 x 1kg [2kg]+ (8) 7x 0.6kg [4.2kg]+ 5 x 0.4kg [2kg]) = 6.2kg + (35 x 0.370=12.25kg + 20 x 0.250=5kg + 10 x
0.160=1.6kg + (30) 10 x 0.105=1.05kg + 30 x 0.055=1.65kg + 25 x 0.025=0.625kg) = 22.175kg + Diversity -2kg
13.3 + 6.2+ 22.175 -2 = 39.675kg
Figures in red removed or modied on example 2.