Toshiba RBC-VNMC-HE1 User manual

TOSHIBA
Air Conditioning
VN Unit Heater Controls
RBC-VNMC-HE1 Controller
Installation and operating Instructions 3
RBC-VNMH1, 2 ,3 and 4 Duct Heaters
Installation Instructions 4
THECONFIGERATIONCODESASDETAILEDIN THIS
MANUALMUST BESET FAILURETODO THISCOULD
RESULT INBUILDINGDAMAGE

2
VN Unit Heater Controls Description and Contents
This manual covers the VN unit heater options. Each of the components are
ordered and supplied separately.
RBC-VNMC (HE1) Heater Controller
The controller will enable the pre-heater if the temperature falls below the
value set in configuration item 67 (Please see the Table 1) the heater will
operate for a fixed period of time set in configuration item 68 (Please refer to
Table 2). The heater will only operate when the Heat Exchange Unit is
operating and will provide a run on time to remove any residual heat if the unit
is switched off on the remote controller.
Contents:
Control Panel
Installation/Operating Manual.
RBC-VNMH1, RBC-VNMH2, RBC-VNMH3 & RBC-VNMH4 Heat Exchanger
unit Heater Batteries
The heater batteries are available in three sizes for use with your selected VN
unit. The heater batteries can be used as a pre-heater.
Model
Heater Size
Duct Diameter
VN Model
RBC-VNMH1
1x1KwHeater
100
VN-M150HE
VN-U00151SYE
RBC-VNMH2
1x1KwHeater
150
VN-M250HE & VN-M350HE
VN-U00251SY-E & VN-U00351SY-E
RBC-VNMH3
2x1KwHeater
200
VN-M500HE & VN-M650HE
VN-U00501SY-E & VN-U00651SY-E
RBC-VNMH4
2x1KwHeater
250
VN-M800/1000HE & VN-M1000HE(HE1)
VN-U00801SY-E & VN-U01001SY-E
Contents:
Heater Battery.
Airflow Pressure Switch
Installation/Operating Manual.

3
RBC-VNMC(HE1) Heater Controller
Installation Operating Instructions VN-M Units
Installation
THE HEATER CONTROLLER AND THE HEAT EXCHANGE UNIT MUST
BE SUPPLIED FROM THE SAME PHASE
The controller must be used with the correct RBC-VNMHX heater battery for
the selected Heat Exchange unit.
The controller should be mounted adjacent to the Heat Exchange unit and
duct heater.
The controller is Class 1 and must be Earthed.
Connect the controller as per the wiring diagram on page 8
Connectcontroller
here (CN32)

4
DN code Configuration
Connect a remote controller and set the DN codes as required. To access the
DN codes Press the Test Set and Cl. You can then press the temperature up
and down arrows to select the code to be modified. Once the selected code
has been updated press the SET button to register the change and then the
Spanner button to exit.
THESECONFIGERATIONCODESMUST BESET
FAILURETODO THISCOULDRESULT INBUILDINGDAMAGE
Set DN Code 67 to the required on temperature.
Table 1
Set DN Code 68 to the required heater operation time.
Table 2
Heater Operation
When the unit air on sensor in the unit reaches the value set in (Table 1) the
heater will be enabled. The heater will operate for the time set in (Table 2) at
the end of this time the heater will switch off. If the unit air on value is still
below the set value in Table 1 the process stars again. if it is above the heater
remains OFF. Should the temperature significantly rise the heater will turn off.
If the unit is switched off on the remotecontroller the fan willrun on for approximately
30s.

5
RBC-VNMC(HE1) Heater Controller
Installation Operating Instructions VN-U Units
Installation
THE HEATER CONTROLLER AND THE HEAT EXCHANGE UNIT MUST
BE SUPPLIED FROM THE SAME PHASE
The controller must be used with the correct RBC-VNMHX heater battery for
the selected Heat Exchange unit.
The controller should be mounted adjacent to the Heat Exchange unit and
duct heater.
The controller is Class 1 and must be Earthed.
Connect the controller as per the wiring diagram on page 8
Connectcontroller
here (CN610)

6
DN code Configuration
Connect a remote controller and set the DN codes as required. To access the
DN codes Press the Test Set and Cl. You can then press the temperature up
and down arrows to select the code to be modified. Once the selected code
has been updated press the SET button to register the change and then the
Spanner button to exit.
THESECONFIGERATIONCODESMUST BESET
FAILURETODO THISCOULDRESULT INBUILDINGDAMAGE
Set DN Code 67 to the required on temperature.
Table 1
Set DN Code 68 to the required heater operation time.
Table 2
Set DN Code 69 to the required heater run on time. When switched off on the remote
controller
Table 3
Heater Operation
When the unit air on sensor in the unit reaches the value set in (Table 1) the heater
will be enabled. The heater willoperate for the time set in (Table 2) at the end of this
time the heater will switch off. If the unit air on value is still below the set value in
Table 1 the process stars again. if it is above the heater remains OFF. Should the
temperature significantly rise the heater willturn off. If theunit isswitched off on the
remote controller the fan will run on for the time set in table 3

7
RBC-VNMH1, RBC-VNMH2 RBC-VNMH3 & RBC-VNMH4
Heat Exchanger unit Heater Batteries
Installation Instructions
The electric heater is of resistance type care should be taken to ensure the
heater is correctly mounted in the ductwork system with the terminal box
accessible. The heater should not be mounted near to materials that can be
damaged by heat. Recommended one-meter minimum of duct before the VN
unit.
The heaters are supplied in different sizes depending on the VN unit that has
been selected.
The heaters are fitted with two thermal cut-outs. The cut-outs are to be wired
in series with the airflow switch. The thermal cut-outs are of the manual reset
type and their purpose is to ensure the power supply is disconnected in the
event of an over-heat condition.
THE SAFETY CIRCUITS MUST BE CONNECTED, FAILURE TO DO THIS
COULD RESULT IN SERIOUS BUILDING DAMAGE.
Wiring
The wiring should be under-taken by a competent electrician taking into
account current IEE wiring regulations. The wiring should be in accordance
with the supplied wiring diagram on page 6. Local isolation should be included
where necessary. It is important that the cables connected to the heaters are
insulated with suitable heat protective sleeving.
Air Flow Switch
The airflow switch that is provided is to be connected into the safety circuit as
indicated on the wiring diagram on page 6. The airflow pressure switch
ensures the heater will not operate without the fan in the VN unit operating.
The airflow switch should be set up in accordance with the supplied
installation instructions.

8
Wiring diagram
CN32 / CN610
This manual suits for next models
4
Table of contents
Other Toshiba Heater manuals
Popular Heater manuals by other brands

Klarstein
Klarstein Hot Spot Wave manual

Rinnai
Rinnai FS35ETRBL/US Operation and installation manual

Orbegozo
Orbegozo BP 5000 instruction manual

Dyna-Glo
Dyna-Glo Delux KFA650DGD User's manual and operating instructions

EUROM
EUROM HEAT Plug-in 700 instruction manual

RADSON
RADSON FLORES E T - MOUNTING Instruction