TriangleTube PSRKIT65 User manual

restige SOLO 110 and EXCELLENCE
Natural to L Conversion
1
Kit art Numbers: SRKIT65
arts List
1. Burner Head - K IT Style
2. Burner Head Gasket
3. Stainless Steel Phillips Screws. (For attaching the
new burner head to the burner mounting plate.)
4. PS 110 LP Orifice 0.203
5. T-25 Torx Wrench
6. Conversion Label
7. Rating Label
8. Combustion Chamber Insulation
9. Insulation Alignment Tool
Recommended tools:
A. Pipe Wrench.
B. Phillips Screw Driver.
C. 10 mm Socket and/or 10 mm Open Ended
Wrench and/or Adjustable Wrench.
D. Flat Blade Putty Knife.
Indicates a potentially hazardous situation
which, if ignored, can result in serious
injury or substantial property damage.
For your safety, turn off electrical power
supply at service panel and allow unit to cool
before proceeding. Failure to do so can cause
severe personal injury or death.
Indicates special instructions on installa-
tion, operation or maintenance, which are
important to equipment but not related to
personal injury hazards.
Failure to follow instructions below can
result in severe personal injury or damage if
ignored.
• Instructions are for a qualified installer/
service technician.
• Read all instructions before proceeding.
• Follow instructions in proper order.
WARNING WARNING
NOTICE
WARNING
restige SOLO 110 and EXCELLENCE
Natural to L Conversion
Instructions:
1. Turn power to the unit “OFF” and allow unit to
cool.
2. Shut off gas supply to the inlet of the unit at the
main manual shutoff valve to the unit.
3. Remove the front panel of the Prestige by
removing the thumb screw on the upper edge of
the unit. Lift the panel up and pull forward to
remove the front panel from the unit.
4a. Remove the retaining screw from the control
panel. Open the display panel cover and swing
the control panel out (MCBA).
4b. Depress the retaining clips and tilt the control
panel down (TriMax).
5. Remove the air inlet elbow from the venturi
using a twisting motion.
6. Disconnect the gas supply piping inside the
Prestige enclosure at the brass union located
just below the gas valve.
7. Unscrew the Phillips screw securing the rectifi-
er cable / plug to the gas valve. Disconnect the
rectifier plug from the gas valve (MCBA).
8. Remove molex plug from gas valve (TriMax).
9. Disconnect the ignition cable from the igniter
(MCBA), and remove the ground wire at the
igniter.
To ease the removal of the burner assembly,
remove the top jacket access panel.
10. Disconnect the wiring harness connectors from
the blower and remove the blower retaining
screws. Remove the blower with venturi and
gas valve from the unit.
11. Remove the 10 mm nuts and remove the burn-
er mounting plate assembly from the heat
exchanger body.
12. Remove the combustion chamber insulation
from the heat exchanger. See WAR I G on
page 7.
13. Remove the Phillips head screws attaching the
burner head to the burner mounting plate.
Remove and discard the old burner head and
burner head gasket.
If the gasket “sticks” to the burner mounting
plate use a flat blade putty knife to remove
any gasket material. Ensure not to scratch or
score the mating surface.
For the reassembly process do not use adhe-
sives on ANY gasket surface.
14. With the new gasket in place attach the new burn-
er head to the burner mounting plate using the
screws supplied in the kit, as shown in Fig. 2.
NOTICE
NOTICE
NOTICE
2
Gas Piping
Union Connection
Combustion
Chamber Insulation
10 mm
Mounting Nuts
Ignition Cable
Fig. 1: Burner Assembly
restige SOLO 110 and EXCELLENCE
Natural to L Conversion
3
15. Using a T-25 Torx wrench remove the three
screws attaching the gas valve to the venturi.
ote the orientation of the gas valve to the ven-
turi for reference later when the gas valve is
reassembled to the venturi.
16. Seat the brass orifice into the black gasket on
the gas valve. The black rubber orifice gasket
must remain attached to the gas valve as it will
hold the orifice. See Fig. 3.
Failure to retain the rubber orifice gasket on the gas
valve will cause an improper seal between the gas
valve and the venturi resulting in a potential gas
leak. Any potential gas leakage may result in death,
serious injury or substantial property damage.
17. Reassemble the gas valve onto the venturi using
the three T-25 Torx screws. Ensure the gas valve
is orientated with the venturi correctly.
18. Use the included alignment tool to install the
new combustion chamber insulation in the heat
exchanger.
- Insert the alignment tool into the igniter
opening as shown in Fig. 4.
- Install the new combustion chamber insula-
tion in the heat exchanger so that the align-
ment tool goes over the correct heat
exchanger stud as shown in Fig. 5.
- Remove the alignment tool.
19. Re-assemble the burner mounting plate assembly
onto the heat exchanger. Ensure the burner plate
gasket and combustion chamber insulation is in
place and not damaged, replace gasket if necessary.
WARNING
Burner Head
Burner Mounting
Plate
Burner Head
Gasket
Fig. 2: Burner Head and Gasket Assembly
Gas Valve
Blower
Venturi Throttle
Screw
Insert Brass
Propane Orifice.
Maintain Black Gasket
on Gas Valve
Fig. 3: Venturi/Gas Valve Assembly Fig. 4: Alignment Tool Installation
restige SOLO 110 and EXCELLENCE
Natural to L Conversion
4
20. Check combustion chamber insulation alignment
with the burner mounting plate. The combustion
chamber insulation igniter cutout should align
with the opening in the burner mounting plate. If
not properly aligned, remove the burner mount-
ing plate and reposition combustion chamber
insulation.
Misalignment of combustion chamber insulation
can cause unreliable boiler operation.
21. Hand tighten the burner mounting plate nuts to
hold the burner plate in place. Once all mount-
ing nuts are in place, use a wrench to tighten
using an alternating pattern until the gasket is
slightly compressed. See Table 2, page 7 for
torque specifications.
22. Re-assemble the blower onto the burner mount-
ing plate and reconnect the wiring harness con-
nectors. Tighten screws evenly. See Table 2,
page 7 for torque specifications.
23. Re-assemble the gas supply connection and
wire harness to the gas valve. Tighten the union
using two wrenches. See Table 2, page 7 for
torque specifications. Open the external manual
gas valve. Check gas piping for any leaks and
repair if necessary.
Do not check for gas leaks with an open flame.
Use a bubble test. Failure to check for gas
leaks can cause severe personal injury, death
or substantial property damage.
24. Re-attach the ignition cable (MCBA) and the
ground wire to the ignitor.
25. Reattach the air inlet elbow to the venturi.
26. Reposition the control panel.
27. Replace the front jacket panel and secure with
the thumb screw on the upper edge of the unit.
28. Install the top jacket access panel
29. Turn power to the unit “O ”. The unit is now
ready to be placed back into service.
COMBUSTION TEST/ADJUSTEMENT
The installer must perform a complete combustion
check to ensure the following combustion levels are
met at high and low input firing rates and the burn-
er is operating at optimum conditions.
The combustion testing and adjustments
must be performed by a qualified installer,
service agency or the gas supplier. All com-
bustion measurements must be perform with
calibrated equipment to ensure proper read-
ings and accuracy.
Failure to perform a complete combustion
test at both high and low input rates may
result in incomplete combustion and the pro-
duction of carbon monoxide, which can
cause severe personal injury, death or sub-
stantial property damage.
NOTICE
WARNING
WARNING
WARNING
Natural Gas Propane
O2 Min. 2.30% 2.70%
O2 Max. 5.30% 4.70%
CO2 Min. 8.80% 10.70%
CO2 Max. 10.50% 12.00%
CO Max. 100 ppm 100 ppm
Table 1: Recommended Combustion Levels
Fig. 5: Combustion Chamber Insulation Installation
MCBA Instructions
1. Manually place the boiler into high fire mode
by pressing the MODE button with “+” button
simultaneously on the control panel display
while in the standby (STBY) mode.
The control panel will display a H followed
by the current boiler temperature when
placed into high fire test mode.
2. If the combustion levels during high fire are
outside the recommended combustion settings
adjust the THROTTLE SCREW (see Fig. 6) as
follows:
Counter-clockwise adjustment of the THROT-
TLE SCREW at High Fire:
O2decreases and C02increases
Clockwise adjustment of the THROTTLE
SCREW at High Fire:
O2increases and CO2decreases
3. Once the combustion level is set at high fire,
manually place the boiler into low fire mode by
pressing the MODE button with “-” button
simultaneously on the control display while in
the standby (STBY) mode.
The control panel will display a L followed
by the current boiler temperature when
placed into low fire test mode.
4. If the CO2 combustion level at low fire is not
within +/- 0.2 of the combustion level measured
at high fire, remove the offset cover screw and
adjust the plastic OFFSET SCREW using a T-
40 Torx wrench (see Fig. 6) as follows:
Counter-clockwise adjustment of OFFSET
SCREW at Low Fire:
O2increases and CO2decreases
Clockwise adjustment of OFFSET SCREW at
Low Fire:
O2decreases and CO2increases
5. Press the “+” and “-” buttons simultaneously to
shutdown the burner.
Trimax Instructions
1. Press the round I STALLER button. See Fig. 7.
2. Enter the installer access code “054” by using
the LEFT and RIGHT buttons to select a digit
and the U and DOWN buttons to change the
digit. Press the OK button to enter the access
code.
NOTICE
NOTICE
restige SOLO 110 and EXCELLENCE
Natural to L Conversion
5
Throttle
Screw
Offset Pressure
Cover Screw
Fig. 6: Combustion Adjustment - restige Burner
Installer
Button
Fig. 7: Trimax Navigation Buttons
restige SOLO 110 and EXCELLENCE
Natural to L Conversion
6
3. Press the RIGHT button to highlight the
Manual Operation icon then press the OK
button.
4. Press the OK button while the FA icon is
highlighted to manually fire the burner and
power the CH circulator.
An adequate CH load must be present to dissi-
pate the heat generated during the combustion
test. If an adequate CH load is not available, an
indirect water heater can be used to dissipate the
heat by creating a DHW call which will enable
the DHW circulator.
5. Press the RIGHT button to adjust the firing rate
to 100% (high fire). Hold down the RIGHT
button to rapidly increase the firing rate.
6. If the combustion levels during high fire are
outside the recommended combustion settings
adjust the THROTTLE SCREW (see Fig. 6) as
follows:
Counter-clockwise adjustment of the THROT-
TLE SCREW at High Fire (100% firing rate):
O2decreases and C02increases
Clockwise adjustment of the THROTTLE
SCREW at High Fire (100% firing rate):
O2increases and CO2decreases
7. Once the combustion level is set at high fire,
manually place the boiler into low fire mode by
pressing the LEFT button to adjust firing rate
down to 1% (low fire).
8. If the CO2 combustion level at low fire is not
within +/-0.2 of the combustion level measured
at high fire, remove the offset cover screw and
adjust the plastic OFFSET SCREW (see Fig. 6)
using a T-40 Torx wrench as follows:
Counter-clockwise adjustment of OFFSET
SCREW at Low Fire (1% firing rate):
O2increases and CO2decreases
Clockwise adjustment of OFFSET SCREW at
Low Fire (1% firing rate):
O2decreases and CO2increases
9. Press the OK button while the fan icon is high-
lighted to shutdown the burner.
10. Press the DOWN button to highlight the home
screen icon then press OK to return to the
home screen.
NOTICE
Manual Operation
Released
O
O
O
CH
CH1
FAN
DHW
SYS
CH2
restige SOLO 110 and EXCELLENCE
Natural to L Conversion
7
The combustion chamber insulation con-
tains ceramic fibers, which are classified as
a possible human carcinogen. When
exposed to extremely high temperatures,
the ceramic fibers, which contain crys-
talline silica, can be converted into cristo-
balite.
Avoid Breathing and Contact with Skin and
Eyes
When removing or repairing the combustion
chamber insulation follow these precaution mea-
sures:
1. Use a IOSH approved respirator which
meets OSHA requirements for cristobalite
dust, similar to 95. Contact IOSH at:
1-800-356-4676 or on the web at
www.cdc.gov/niosh for latest recommendations.
2. Wear long sleeved, loose fitting clothing,
gloves and eyes protection.
3. Assure adequate ventilation.
4. Wash with soap and water after contact.
5. Wash potentially contaminated clothes sepa-
rately from other laundry and rinse washing
machine thoroughly.
6. Discard used insulation in an air tight plastic
bag.
Niosh Stated First Aid:
Eye/Skin: Immediately irrigate
Breathing: Clean fresh air
WARNING
Handling of reviously Fired Combustion Chamber Insulation
Revised 2/25/15 2012-06 Solo 110_ Excellence_ atural to LP Conversion
Table 2: Torque Specifications
Assembly Screws
Torque Specifications
Min.
Inch- Pounds
Max.
Inch- Pounds
Si ht Glass 11 13
Burner Head 27 31
I niter 27 31
Gas Valve Couplin s 27 31
Blower - Outlet 27 31
Venturi to Gas Valve 31 35
Venturi to Blower 31 35
Burner Plate 44 59

Other TriangleTube Rack & Stand manuals

TriangleTube PSSTND06 User manual

TriangleTube

TriangleTube PSSTND06 User manual

TriangleTube PSRKIT39 User manual

TriangleTube

TriangleTube PSRKIT39 User manual

TriangleTube S08C User manual

TriangleTube

TriangleTube S08C User manual

TriangleTube PSSTND03 User manual

TriangleTube

TriangleTube PSSTND03 User manual

TriangleTube S08 User manual

TriangleTube

TriangleTube S08 User manual

Popular Rack & Stand manuals by other brands

RACING COCKPITS SPORT TRIPLE manual

RACING COCKPITS

RACING COCKPITS SPORT TRIPLE manual

NeoMounts SELECT NM-HUB2LIFT instruction manual

NeoMounts

NeoMounts SELECT NM-HUB2LIFT instruction manual

AOC AS110D0 installation manual

AOC

AOC AS110D0 installation manual

Sony UNI-MDB3 Installation and operation instructions

Sony

Sony UNI-MDB3 Installation and operation instructions

Novus NVB-5000CA user manual

Novus

Novus NVB-5000CA user manual

CHIEF WP2XS installation instructions

CHIEF

CHIEF WP2XS installation instructions

Deltaco Gaming GAM-173 instruction manual

Deltaco Gaming

Deltaco Gaming GAM-173 instruction manual

HUANUO HNWSS1 manual

HUANUO

HUANUO HNWSS1 manual

Yaesu MMB-90 - MOUNTING BRACKET manual

Yaesu

Yaesu MMB-90 - MOUNTING BRACKET manual

Sherpa C Assembly instructions

Sherpa

Sherpa C Assembly instructions

peerless-AV FS-MIS38426 manual

peerless-AV

peerless-AV FS-MIS38426 manual

Shelfology Yuri install guide

Shelfology

Shelfology Yuri install guide

Vivo STAND-V102K instruction manual

Vivo

Vivo STAND-V102K instruction manual

DETAIL K2 TMC201 manual

DETAIL K2

DETAIL K2 TMC201 manual

Sheffield SCS9 Assembly instructions

Sheffield

Sheffield SCS9 Assembly instructions

IBM Netfinity Rack Monitor Compartment installation instructions

IBM

IBM Netfinity Rack Monitor Compartment installation instructions

Workrite Ergonomics CONF-ACC-1EXT-S Assembly/installation instructions

Workrite Ergonomics

Workrite Ergonomics CONF-ACC-1EXT-S Assembly/installation instructions

HUANUO HNCM12-1 instruction manual

HUANUO

HUANUO HNCM12-1 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.