
OPERATION PRECISION 8
8
Connections - Location and Description
AC Power Connection
• 120V, 60 Hz AC power only. (consult factory for other options)
• Always maintain an earth ground connection - DO NOT use isolators.
• Use delayed 0.5A fuses. NEVER use a replacement fuse of higher value.
1 Signal Ground Lift. Signal ground is isolated from earth ground in the LIFT
position. This switch will normally be in the grounded (down) position. See
“TROUBLESHOOTING” section for usage tips.
2 Balanced Output connections. Two styles of output connection are
provided: a DB25 eight-channel connector (see Figure 1) and individual
TRS 1/4" connectors (tip is +, ring is -, sleeve is shield). Both outputs may
be used simultaneously to connect to Line Inputs on mixing consoles,
recorders, etc. If both outputs are used, care should be taken to avoid
system ground loops. See “TROUBLESHOOTING” section for tips on
avoiding hum caused by grounding problems.
3 Dual-Purpose Input Connectors. Insert XLR microphone connector for
normal operation (pin 2 is +, pin 3 is -, pin 1 is shield). Insert 1/4" phone
plug for use as Direct Input for instruments. NOTE: Use only tip-sleeve
(unbalanced) phone plug for DI connection. DO NOT insert 1/4" tip-ring-
sleeve (TRS) plug here as DI will not operate properly.
4 Mid-Side microphone inputs. When using Channels 1 and 2 in the M/S
mode, the Mid mic (normally a cardioid) is connected to MIC 1 input. The
FIRE RISK
Replace with same type fuse only
M
Di
BALANCED OUT
1
2
3
4
5
6
7
8
120VAC, 60 Hz, 44 W
LIFT
WARNING- SHOCK HAZARD. Do not
open. Service should be performed by
qualified personnel. Do not expose to
rain or moisture. Do not defeat AC
ground connection.
1-8
(4-40)
S/N
A product of Sunrise Engineering
Tucson, Arizona
1 2
MIC 1MIC 2MIC 3MIC 4MIC 5MIC 6
MIC 7MIC 8
Direct In
Direct In MS
PIN 2 +
PIN 3 -
3 4