
Bulletin 30-30 —Page 2
© Copyright 2007 Unico, Inc.
cabinet. Coil must be fully inserted to assure that the
cover plate can be installed after coil is piped.
4. Pipe coil following instructions in “Piping” section
that follows below. Be sure system is filled with wa-
ter, bled of air and checked for leaks.
5. The insulation from Step 2 is to be used to insulate
the copper tubes of the coil. Notch the insulation for
the Water IN and Water OUT lines and position it in
the original opening over the coil tubing.
6. Install the coil cover plate supplied with the coil over
the insulation. Maneuver the plate so notches fit
around the water lines. Screw the cover plate in place
using screws removed from the access plate.
7. Caulk around the Water IN and OUT lines to assure
no air leakage. Also check around the edges of the
cover plate for air leaks with blower operating.
Caulk edges or seal with UL181A-P aluminum foil
tape.
Figure 1. Hot Water Coil with Cover Plate
For horizontal applications the heating module will be
installed upstream of the cooling module. For this config-
uration the hook-flange provided (loose) with the MH unit
must be attached to the cooling module (see Figure 2). In
hydronic heating only applications, use the hook-flange
on the blower module to attach the MH unit.
Cooling Module
or
Blower Module
(Hydronic heat only)
Heating
Module
Hook Flange
(shipped loose with MH unit)
Latch Hook
IL00389.CVX
Figure 2. Hook-flange Location
Piping
All piping must be in accordance with all local codes and
ordinances. Pipe sizing and pump selection must be de-
signed to match, allowing for the pressure loss in the coil
and all other fittings. Refer to ASHRAE Fundamentals
Handbook for design guidelines.
The Unico System Hot Water Coil can be piped as a sin-
gle zone or in a multi-zone system. In either system, the
water flow may either be continuous or intermittent.
In a continuous flow system, the fan is simply cycled on
and off by the thermostat. In an intermittent flow system,
water is circulated through the coil only when heat is re-
quired. The fan can run continuous or at the same time as
the water. The intermittent system will use either pump
on/off control, or mixing or isolation valves to control the
water flow.
An optional aquastat can be installed with the intermittent
system to prevent blowing of cold air by delaying the fan
until the water in the coil is hot.
M2430, and M3660 connections are 7/8-inch (22 mm)
sweat connections. M1218 connections are 5/8 inch (15.8
mm). Solder or braze the water connections, and then fill
the system. Bleed the air from the coil by backing off the
screw inside the bleed valve for venting. Water pressure
drops through the coil can be found in Bulletin 20-20.4
for the M2430 and M3660 and 20-18 for the M1218.
A secondary drain pan must be used under unit if installed
where a water leak could cause damage. Unico has avail-
able secondary drain pans for horizontal applications. For
vertical unit applications it will be necessary to fabricate a
drain pan which should provide at least ½-inch (12.7mm)
clearance around all sides at the bottom.
For vertical upflow arrangements where the air enters the
bottom of the unit, use the vertical plenum (MV) module
for the M2430 and M3660. Coil installation is identical to
the MH installation instructions and shown in Figure 1.
Detailed specifications for the MV unit are available in
Bulletin 20-20.5.
For vertical downflow (counterflow) installations it is
difficult to provide a secondary drain pan because of the
blower discharge at the bottom. If a secondary drain pan
is needed it must be fabricated with an opening for the
blower discharge and still provide a sealed drain pan.
Freeze Protection
If unit is in an unconditioned space below freezing, care
must be taken not to freeze the water in the coil. There are
two methods of freeze protection. The easiest is continu-
ously or intermittently circulate the water. Another meth-
od is to use a glycol-water antifreeze solution with a