manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Unico
  6. •
  7. Air Handler
  8. •
  9. Unico M Series User manual

Unico M Series User manual

Other manuals for M Series

4

This manual suits for next models

4

Other Unico Air Handler manuals

Unico M Series User manual

Unico

Unico M Series User manual

Unico M Series User manual

Unico

Unico M Series User manual

Unico M Series User manual

Unico

Unico M Series User manual

Unico V2430 User manual

Unico

Unico V2430 User manual

Unico M Series User manual

Unico

Unico M Series User manual

Popular Air Handler manuals by other brands

Vents VUT 270 V5B EC A14 user manual

Vents

Vents VUT 270 V5B EC A14 user manual

Armstrong Air BCE7S Series installation instructions

Armstrong Air

Armstrong Air BCE7S Series installation instructions

Klimor EVO-S Operation and maintenance manual

Klimor

Klimor EVO-S Operation and maintenance manual

Salda SMARTY XP MOUNTING AND INSTALLATION INSTRUCTION

Salda

Salda SMARTY XP MOUNTING AND INSTALLATION INSTRUCTION

BLAUBERG KOMFORT Roto EC S400 user manual

BLAUBERG

BLAUBERG KOMFORT Roto EC S400 user manual

Trenton TPLP Series installation instructions

Trenton

Trenton TPLP Series installation instructions

Daikin DV PTC 14 Series installation instructions

Daikin

Daikin DV PTC 14 Series installation instructions

Haier HB2400VA1M20 Installation & operation manual

Haier

Haier HB2400VA1M20 Installation & operation manual

Webasto BlueCool A-Series operating instructions

Webasto

Webasto BlueCool A-Series operating instructions

RDZ DA 701 Technical installation manual

RDZ

RDZ DA 701 Technical installation manual

Carrier 39T Installation, Start-Up and Service Instructions

Carrier

Carrier 39T Installation, Start-Up and Service Instructions

Armstrong Air BCE5V Series installation instructions

Armstrong Air

Armstrong Air BCE5V Series installation instructions

Carrier 40MBDAQ Service manual

Carrier

Carrier 40MBDAQ Service manual

TemperZone Econex Pro OPA 1410RLTM4FPQD Installation & maintenance

TemperZone

TemperZone Econex Pro OPA 1410RLTM4FPQD Installation & maintenance

RDZ WHR 200 Technical installation manual

RDZ

RDZ WHR 200 Technical installation manual

AAON H3 Series Installation operation & maintenance

AAON

AAON H3 Series Installation operation & maintenance

Lennox VEOA042N432U Installation & operation instructions

Lennox

Lennox VEOA042N432U Installation & operation instructions

Kemper CleanAirTower operating manual

Kemper

Kemper CleanAirTower operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

The information on the following pages is to help the in-
staller save time, provide the best possible installation and
ensure continuous trouble-free operation.
These instructions apply to the Unico M-Series air han-
dler units. For heat pump coils, refer to Bulletin 30-24 for
additional instructions. Installation instructions for the air
distribution system are covered in Bulletin 30-05. Before
beginning any installation a detailed system layout must
be done in accordance with the System Sizing and Layout
Procedure, Bulletin 40-40 and the Component Layout In-
structions, Bulletin 40-30.
Do not attempt to install or startup unit without first read-
ing and understanding the appropriate sections in this
manual.
Before operating, be sure the unit is properly grounded.
Installation should be in accordance with all local codes
and regulations and with the National Board of Fire Un-
derwriters regulations. In case of conflict, local codes take
precedence.
All electrical wiring should be in accordance with the lat-
est edition of the National Electrical Code and all local
codes and regulations. The unit is safety certified to UL
1995 and listed with ETL.
Always install a secondary drain pan when an overflow of
condensate could cause damage.
This manual does not always include the latest revision
letter when referring to UPC part numbers. Refer to the
latest Price List and Spec Sheets for the current UPC re-
vision letter. For example, in UPC-00xthe ‘x’ indicates
the latest revision.
The Unico System is a complete indoor comfort system
that includes an indoor air handling unit and small duct
system. The air handler and duct system were designed to
operate together to provide the proper airflow in every in-
stallation. The conditioned air is supplied through a series
of 2-inch ducts as a stream of air that entrains and mixes
the room air. This process of aspiration produces a more
even temperature distribution in the room.
The Unico 'M' Modular Series air-handling units consist
of various modules that are easily latched together. The
modules can be arranged in a vertical-up-flow, vertical-
counter-flow and horizontal-flow configuration. They can
be combined as a heating-only, cooling-only, or heating
and cooling air handler unit. See Fig. 1.
Bulletin 30-20 —Page 2
© Copyright 2014, Unico, Inc.
All insulated Unico System modules feature closed-cell
insulation for improved sound attenuation. There is no ex-
posed fiberglass insulation.
Each module is available in four sizes: 2430, 3036, 3642,
and 4860. There are three basic modules: a blower mod-
ule, a cooling module, and a heating module. The blower
module includes the blower wheel, blower housing, mo-
tor, and electrical control box. The cooling module in-
cludes a cooling-only refrigerant coil, a heat pump coil, or
a chilled water coil. The heating module is supplied as an
empty cabinet with room for a slide-in hot water coil.
The modules can be arranged to provide only the options
needed as shown in Figure 1 (with details on pages 26 and
27). Heating-only systems require the blower module, the
heating module, and a hot water coil. Cooling-only sys-
tems include the blower module and a cooling module.
For heating and cooling all the modules are combined
with coils. The system may even be used for ventilation-
only, using just the blower module.
Unico designed and built blowers feature direct drive mo-
tors or EC motors and are located in the air stream. Each
blower wheel is balanced to Unico specifications. The
blowers feature a quick twist-and-lock motor mount for
easy maintenance (see page 16). The motorized blower
assembly consists of the motor, which is mounted to the
inlet ring, and the wheel, which is mounted to the motor
shaft.
Other options and modules are also available to add addi-
tional features or to simplify installation. These include an
electric duct heater, multiple return plenum, and a vertical
plenum stand. Please refer to the latest Unico Catalog for
information on these and other options.
All modules are inspected prior to shipping and are care-
fully packaged in individual cartons. Inspect all cartons
prior to unpacking. Notify carrier of any damage.
Open each carton to remove the modules. Inspect unit for
visible signs of concealed damage and notify carrier of
any such damage.
All materials are sold FOB Factory and it is the responsi-
bility of the consignee to file any claims with the deliver-
ing carrier for materials received in damaged condition.
Locate the air handler to minimize the number of plenum
elbows and fittings while keeping the supply duct runs as
short as possible. (See Bulletin 40-30, Component Duct
Layout Design). Provide minimum clearance on both
sides for servicing the unit as shown in Fig. 2.
Heating and Cooling
Horizontal
Flow
Vertical
Counter-Flow
Vertical
Up-Flow
IL00010d.CVN
Heating Only Cooling Only
Normal Air Inlet/Outlet Optional Air Inlet
Blower Module`
Spacer Module
Cooling Module
Vertical Plenum
Module (with Hot
Water Coil)
Vertical Plenum
Module (without Hot
Water Coil)
Spacer Module
Heating Module
(with Hot Water Coil)
Heating and Cooling (M4860)
Bulletin 30-20 —Page 3
© Copyright 2014, Unico, Inc.
If installing the unit in an attic, avoid placing the unit
above a bed. The ideal location is above a central hall, a
closet, a bathroom, or any normally unoccupied space.
The unit can also be installed in a closet, crawlspace, or
basement. If the local codes allow, the unit may be in-
stalled in the garage provided the ductwork is well sealed,
especially the return duct. Although the unit is not de-
signed for outdoor use, it may be located outside provided
adequate weather protection is used; typically a roof in-
stallation requires mounting on blocks with a sheet metal
cover or cap to protect the unit from rain and extreme
weather conditions.
Be sure to position the return air box and filter near the
unit allowing at least one 90° bend in the return duct for
proper acoustical performance (refer to figure 3 for a typ-
ical horizontal attic installation). The section on Return
Air Ducts in the manual provides more details.
All modules except the 4860 cooling module are designed
to fit through a 14-inch (356 mm) opening, typical of a
joist spaced at 16-inch (406 mm) center distance. The
4860 module requires an 18.5-inch (470 mm) opening. If
no access is provided, an opening must be cut. It is sug-
gested to use the opening required for the return air box,
especially in an attic installation. The opening for the re-
turn air box is listed in Table 1. If the joists or studs are
less than 16-inches (406-mm) center-to-center or running
the wrong direction it will be necessary to cut and header
the joists.
The Unico EC motor includes an electronic circuit board
that is sensitive to overheating if the air temperatures sur-
rounding the motor are above a certain value. The motor
will not function above its maximum operating tempera-
ture and will have some reduction in motor life between
the maximum operating temperature and the recom-
mended temperature limit. Depending on the application,
this may or may not be acceptable.
38
 
38

12

38

12

38

12

38

12

Cooling
Module
(MCxxxxx)
Blower
Module
(MBxxxxx)
Heating
Module
(MHxxxxx)Return Air Adapter
(UPC 104-xxxx)Band (supplied with return air box)
Return Air Duct
(UPC-04-xx-1)
Return Air Box
(UPC-01-xxxx-1)
Plenum
Adapter
(UPC 61-xxxx)
Isolation
Pads
Secondary
Drain Pan
(UPC 20 or 24)
Platform
Typical 10 foot (3.6 m) Return Duct
Use at least one 90° bend.
IL00039c.CVS
Control
Box
Band
Bulletin 30-20 —Page 4
© Copyright 2014, Unico, Inc.
For maximum
motor life, we recommend that the Unico EC motor be
limited to applications with less than 130°F (54°C) air
temperature. Therefore, the Unico EC motor can be used
with all heat pump and electric heating applications with-
out problem. It may also be installed with a hot water coil
with air temperature leaving the coil less than 130°F
(54°C). This is generally with water temperature less than
135°F (57°C) but it depends on the water and air flow.
Consult the hot water coil specifications to determine air
temperatures based on water flow and air flow rate.
The abso-
lute limit for the motor is 158°F (70°C) air temperature at
which point the motor will automatically begin to slow
down. The motor may be used in applications with air
temperature around the motor between 130 to 150°F (54
to 65°C), typical for boiler systems with water tempera-
tures between 135 and 160°F (57 to 70°C). However, ex-
pect the life of the motor to be reduced by as much as
50%. In most applications, with unit operating intermit-
tently, the amount of time that the motor operates in heat-
ing is very small so the reduction in motor life will not be
significant. Only for extended continuous heating appli-
cations, will the reduction be noticeable. The reduction in
motor life can be minimized by using setback boiler tem-
peratures while operating with maximum airflow at the
highest water temperatures.
The units may be assembled either horizontally or verti-
cally. Refer to Fig. 1 for your particular flow arrangement.
Assemble the units’two modules at a time. If you use a
refrigerant coil, the anti-frost switch wires must be routed
to the control box as you connect the modules.
Remove the coil access
panel and unravel the anti-frost switch wires. If you use a
heating module, feed the wires under the hot water coil
support channel. Then feed the wires through the bushing
in the motor partition panel. After routing the wires
through each module, connect the modules together.
To fasten the modules
together tilt the units to insert the connection flange over
the mating flange as shown in Fig. 4. It may be necessary
to squeeze the units together as you are inserting the
flange to compress the rubber gaskets. If the hook flange
has a small gap, use a large flat bladed screwdriver to pry
the gap apart. Secure the modules together with the
latches, compressing the gasket further.
Most systems are installed in the horizontal configuration,
with the air going from right to left when looking at the
connections (as shown in figure 1). All the modules are
factory set for horizontal airflow. It is not recommended
to flip the cooling module to reverse the flow direction of
the air. When connecting the modules be sure to arrange
the heating module on the inlet (return) side of the cooling
module.
The 4860 cooling module also includes a spacer module
which has a small drip shelf (shipped loose) that must be
installed on the air exit side of the drain pan (shown in
figure 5).
When installing the heat module or return air plenum
module upstream of the cooling module, it is necessary to
first install a hook flange to the bottom of the cooling coil
(Figure 6).
IL00009.CVS
Bulletin 30-20 —Page 5
© Copyright 2014, Unico, Inc.
Figure 6. Hook flange location.
As shown in figure 1, the modular system can also be con-
figured for vertical up-flow or down-flow. The arrange-
ment of modules is different so be sure to follow these
instructions.
In most cases connecting the modules is straight forward
–just use the arrangement shown in figure 1. However, if
you are using a 2430, 3036 or 3642 cooling module, the
top access panel of the cooling module will need to be
repositioned as shown in figure 7.
For vertical up-flow the return air may enter through the
bottom or side return opening of the 2430, 3036 or 3642
cooling module although the bottom opening is preferred.
The 4860 cooling only has one return opening for either
horizontal or vertical applications. The 4860 drain pan is
‘L’ shaped and will work properly when the module is
turned 90 degrees.
For vertical up-flow installations, we recommend using
the vertical return plenum module (MV module). The
spacer shown in figure 1 is included with the MV module
(except for the 4860 unit, where it is included with the
cooling module). If you are not using the MV module for
the 2430, 3036 or 3642, you will need to use the vertical
conversion kit, which includes the extra panels needed.
You will also need to provide a field fabricated mount for
the unit.
The vertical plenum module includes a filter and a space
for a hot water coil. If the unit is installed in an area where
water may cause damage, be sure to set the unit inside a
drain pan.
The return air opening for the vertical plenum module is
in the front. If connecting to a flexible duct, you will need
the return air adapter. The return air adapter attaches to
the front of the return plenum module using latches,
which need to be moved from the top to the sides as shown
below.
IL00302.CNV
Reposition Latches
to sides of Module
UPC-104-xxxx
Return Air
Adapter
Airflow
Cooling Module Return Air
Plenum
or
Heating-
Module
Hook Flange
(shipped loose with MR or MH unit)
Latch Hook
(shipped loose with MR module)
IL00220a.CNV
Filler Panel
(Item A)
Install first
IL00301d.CNV
1
Remove
Latches
Move
1Top panel
Remove
Bottom panel
Remove
Drip Plate
Install new
Panel
MV Vertical Heat
Module
AIRFLOW
UPC-104
Return Air Adapter
Typical Vertical
System Layout
Gasket Tape
(Shipped Loose)
IL00303.CNV
Bulletin 30-20 —Page 6
© Copyright 2014, Unico, Inc.
Position the base, either the vertical module or a field fab-
ricated unit, where desired. Then set the cooling module
on top of the base as shown in Figure 9. Use gasket tape
under the cooling cabinet to prevent air leaks.
Then set the spacer section on top of the coil, securing it
with the corner brackets as shown in Figure 10. The
blower module goes on top. The blower module can be
turned 180 degrees to position the motor to the other side,
or top position the blower discharge towards the front.
Heating-Only Systems For heating-only systems, the
installation is similar to the cooling-only or heating-and-
cooling system, except that the cooling module is re-
moved from the system.
For the 2430, 3036 and 3642 systems, use a vertical spacer
kit such that the spacer overhangs the back of the vertical
plenum and the filter access is not covered over.
Blower
Module
Return Air
Adapter
Airflow
Corner
Bracket
(2 plcs)
Attach
both
corner
brackets
(not used
on 4860)
Vertical
Heating
Module
ReturnAir
Adapter
Airflow
Latches
(shipped
loose)
Note: Attach Latches and Latch keepers to appropriate
modules on opposite side (not shown)
Gasket Tape
(applied to top
of MV module)
Cooling
Module
Latch Keeper
(shipped loose)
Blower
Module
ReturnAir
Adapter
Airflow
Bulletin 30-20 —Page 7
© Copyright 2014, Unico, Inc.
The control box is shipped
with the blower module. It can be installed on either the
discharge side of the blower cabinet, on top, or on the bot-
tom of the blower cabinet, depending on what is most con-
venient.
To install, first remove the two knockouts on the side or
top of the cabinet, where it will be installed. Mount the
control box using four (4) sheet metal screws as shown in
Figure 12. Connect the wiring as required in the wiring
section and the control box manual.
Figure 12. Mounting the Control Box.
Where an over-
flow of condensate could cause water damage, a second-
ary drain pan MUST BE INSTALLED. Place the drain
pan on the mounting base, platform or angle iron support
frame. Be sure to allow enough room for the drain line
and connection (refer to Table 3). The assembled unit
should be placed over the secondary drain pan supported
by rails with rubber pads for isolation to raise the unit
above the 1.5-inch (38mm) sides of the secondary drain
pan.
Table 2 shows the secondary drain pans to be used for
horizontally mounted modules. For vertical up-flow ar-
rangements that use the cooling module, the 2-module
drain pans can be used where space permits and the return
air is entering from the side. These pans would be over-
sized compared to the footprint of the cooling module. If
a smaller drain pan is necessary it should be fabricated to
be at least ½-inch (12.7 mm) larger on each side of the
bottom module.
For vertical down flow (counter flow) arrangements it is
difficult to provide a secondary drain pan because of the
blower discharge at the bottom. The secondary drain pan
must be fabricated with an opening for the blower dis-
charge and plenum adapter and still provide a sealed drain
pan.














Like the modules, all the secondary drain pans except
UPC-24C, D will fit through the return air opening. For
these drain pans it will be necessary to fold the pans in
order to pass through the return opening. If you are unable
to use the UPC-24Dbecause of space limitations, use the
UPC-24B under the cooling and heating modules. In this
case the blower module will extend beyond the secondary
drain pan and should be supported with blocks or an angle
iron frame.
The modules come factory-ready for horizontal airflow
applications and may be modified for vertical airflow ar-
rangements (see Fig. 1) with the addition of the vertical
heat module (with or without the heating coil) and the ver-
tical spacer module.
Mount the unit hori-
zontally when vertical height is limited such as in an attic
or crawl space. It is easiest to mount the unit on a platform
but care must be taken to assure proper drain line pitch.
* See Table 3
The platform height must allow for proper pitch of the
condensate drain lines —at least ¼ inch drop per lineal
IL00332.CNV
Bulletin 30-20 —Page 8
© Copyright 2014, Unico, Inc.
foot (20 mm per meter). The platform can be built from a
sheet of ½ inch (13 mm) plywood and stud frame. Table
3 lists the maximum horizontal drain line run for various
framing materials and still provide adequate drainage.




The platform size must allow for the number of modules
being used. For dimensions for minimum platform size
see Fig. 13.
Place secondary drain pan on platform and unit on top of
isolation pads inside of secondary drain pan. Be sure that
the unit is raised above the height of the drain pan side to
allow duct connections.
The modules can
also be suspended from the ceiling or rafters. A typical
suspension method is shown in Fig. 14. Screw four (4) “J”
hooks into rafters. Suspend four (4) chains from “J” hooks
and attach eyebolts to chains. Secure angle iron to eye-
bolts and place secondary drain pan on top. Put isolation
pads in drain pan, making sure unit sits above sides of
drain pan.
As an alternative, rest the unit on the angle iron supports
and hang the secondary drain pan from the same supports.
As above, install “J” hooks, chains, and angle iron. Secure
angle iron to eyebolts and put isolation padding on angle
iron.
Adjust the length of the eyebolts and chains so there is
slight pitch towards the drain end.
Figure 14. Typical Suspended Mounting
Vertical Mounting. Because the units are top heavy, it
is not recommended to suspend a vertical unit. It should
be mounted on either a platform or a floor. Unico makes
a module specifically for vertical installations (refer to
previous section). If only a blower and heating module are
being installed, fabricate a return plenum for the unit to
sit upon.
Although the modules may be assembled without a spacer
module, this can severely restrict the airflow; especially if
the blower needs to achieve its maximum airflow. There-
fore, always use the spacer module for any vertical con-
figuration.
The main duct (or ple-
num) can be round, square or rectangular, provided it
meets the pressure drop requirements of the application.
Adapters are available for the standard sizes for both
round and square ducts.
Figure 15. Round Supply Plenum Adapter Dimensions
Figure 16. Square Supply Plenum Adapters
To attach the plenum adapter, first install the restrictor
plate, if required. Then install the adapter with eight (8)
sheet metal screws as shown in Fig. 17. Sheet metal
screws for installing both are provided with the blower.
Figure 17. Supply Plenum Adapter Installation
B
A
D
L
1 (25)
crimped
AIRFLOW
Model, UPC-61-
1218 2430
10 (254)
3642 4860
7.16 (182) 10.13 (257)
18 (457)
9 (229)
A
B
Dimension,
inch (mm)
6.5 (165) 6 (152)
3.25 (83) 6.38 (162)
D
L
7 (178)
12 (305)
3036
7.16 (182)
9 (229)
A2.0 (51)
Part No.
A, inch (mm)
UPC-62-2430
UPC-62-3036
8.50 (216)
10.50 (267)
A
UPC-62-4860
11.50 (292)
UPC-62-3642
10.50 (267)
Blower
Module
Restrictor
Plate
Plenum Adapter
Plenum
Insulation Wrap IL00308.CVX
Bulletin 30-20 —Page 9
© Copyright 2014, Unico, Inc.
Restrictor Plate (single-speed motors only). The
single speed (non-ECM) blower include a restrictor plate
to fine-tune the airflow. The purpose of the restrictor plate
is to eliminate objectionable outlet noise because the
blower is delivering more air than required. In most cases
where the maximum airflow is required, the restrictor may
be omitted.
The restrictor plate is used to set the system airflow (see
Fig. 18). The full open position corresponds to the highest
airflow the installed duct system will allow. Set the re-
strictor plate to the full open position and measure the sys-
tem airflow. The required system airflow is 200-250 CFM
per nominal ton (27-34 L/s per nominal kW). Measure the
motor amperage and use this to ensure the 200-250 CFM
per nominal ton (27-34 L/s per nominal kW) has been
achieved. If elevated sound levels are noticed at the out-
lets with more than 250 CFM per nominal ton (34 L/s per
nominal kW), the airflow may be reduced with the restric-
tor plate. Always measure the system airflow by the motor
amperage (see Table 4). Refer to the airflow-amperage
charts provided with the blower.
Figure 18. Restrictor Setting
Note: Do not use restrictor plate to adjust
plenum static pressure. Adjust the restrictor
to the proper amperage. This will assure
proper airflow.
Table 4. Approximate Amperages at Given Airflows
Unit Size
Airflow,
CFM (L/s)
MBxxxxL
Amps
@230V †*
MBxxxxL+CB
Amps
@230V †
4860
1250 (590)
4.1
4.1
1000 (470)
3.5
3.3
800 (380)
3.1
2.8
3036
3642
1000 (470)
3.9
3.7
900 (420)
3.6
3.4
800 (380)
3.2
3.2
700 (330)
3.0
2.9
600 (280)
2.8
2.7
2430
600 (280)
2.2
1.9
500 (240)
2.0
1.6
400 (190)
1.8
1.4
* multiply by 1.1 if 208V
†for more exact airflow use the chart included with the blower
Attach main duct. Attach the plenum to the adapter by
inserting it over the supply adapter. If using sheet metal
duct, use three (3) or four (4) equally spaced sheet metal
screws or nails to secure the duct to the supply adapter.
Then tape around the seam with UL 181A aluminum tape.
Then wrap the outside of the plenum adapter with the sup-
plied blanket insulation and secure the insulation seams
with UL 181A tape.
Return Air Duct. Unico supplies a return duct system
but any return duct system is acceptable provided the
pressure loss does not exceed 0.15 inches of water (37 Pa),
including filters. The return duct should have at least one
90° bend between the unit and filter box to reduce sound
transmission directly from the unit.
The Unico Return Duct system has a single return that in-
cludes the return air box with filter, the return duct, and
the return air adapter (refer to Fig. 3). Multiple returns or
extra-long returns are possible so long as the maximum
pressure loss is not exceeded. For vertical installations or
tight spaces it may be necessary to fabricate a return duct
system from duct board or lined metal.
The typical return duct is 10-foot (3 m) in length so it may
have to be cut to avoid bunching if the distance to the unit
is significantly less than 100-inches. The minimum length
should be 7-feet (2 m). When given a choice, the shorter
distances should be avoided as this may increase sound
transmission from the unit.
Cut an opening for the return box as specified in Table 1.
For the 2430, 3036 and 3642 if the joists or studs are on
16-inch (410mm) centers, there is no need to build a frame
to hold the return air box. Otherwise, it will be necessary
to construct a frame around the opening. For the 4860 re-
turn, it will almost always be necessary to cut and header
at least one joist.
Center the return air box so the filter frame flange covers
all the gaps and make sure the flange is flush against the
wall or ceiling. Install the return air box against the frame
using nails or screws.
Screw holes are provided in the return air box. Use the
holes nearest the corners. The other holes are for mount-
ing the filter grille. See Fig. 19.
Figure 19. Return Air Box and Filter
Bulletin 30-20 —Page 10
© Copyright 2014, Unico, Inc.
Install filter frame into the return air box using four nails
or screws. Use the holes furthest from the corners. Insert
filter and hold in place by rotating metal clips. Close grille
and secure with clips.
Refer to Table 5 for correct Return Duct Adapter selec-
tion. Attach the proper return duct adapter to either the
Heating or Cooling Module. Then attach the return duct
to the adapter and to the return air box using the Q-bands
and Q-clips.
The return air adapter ships with an insulation blanket that
must be wrapped around the adapter. Tape the seams with
UL 181A aluminum tape.
Table 5. Return Duct Adapter
Unit Size
Blower Module +
Cooling Module
Heating Module
+ Cooling Module
4860
UPC-59-4860
UPC-104-4860
3642
UPC-59-3642
UPC-104-3642
3036
UPC-59-3036
UPC-104-3036
2430
UPC-59-2430
UPC-104-2430
Multiple Returns. If more than one return is desired,
Unico has designed a return plenum (MR) module. The
MR module is available in two sizes: 2430 and 3660, and
it includes a central filter. The MR module is easily fitted
to the air handling unit and multiple return openings may
be cut in the top back or sides of the box. Refer to Bulletin
20-20.6, Return Plenum Module, for additional infor-
mation.
PIPING
All piping must be in accordance with all local codes and
ordinances.
Condensate Lines. The primary drain pan condensate
connection is a ¾-inch (19mm) female pipe thread fitting
and the secondary drain pan connection is a ¾-inch
(19mm) PVC socket fitting.
Elevate the unit so the condensate lines are pitched at
least ¼-inch per lineal foot (20 mm per meter).
Trap the condensate line near the unit using U-trap
A00924-G05 as shown in Figure 20.
In some cases it may be necessary to wrap the conden-
sate line near the unit with insulation to prevent water
condensation on the outside of the pipe.
In some climates or locations it may be necessary to
protect trap from freezing in the winter.
Do not trap the secondary drain line and do not termi-
nate line into the primary drain line.
Figure 20. Typical Condensate Trap
The standard trap that ships with the cooling coil includes
a float switch to shut off the system if the drain is plugged
up. Run secondary drain line so that any drainage will be
immediately known without causing damage to property.
A typical location is to terminate the secondary drain line
above a windowsill so that the drainage splashes on the
window. This will serve as an indicator that there is a
problem with the primary drain. In cases where a second-
ary drain line cannot be run, add a float switch or a micro
switch with a paper fuse.
Refrigerant Connections. All refrigerant coils have
two refrigerant lines: a liquid (small tube) and a vapor
(large tube). The connections are either sweat or flare as
listed in table 6, depending on what type of outdoor unit
the cooling module is matched to.
Table 6. Refrigerant Line and Connection Size
Outdoor unit
Liquid line
Vapor line
1 or 2-stage
3/8 (9.5 mm)
ODF sweat
7/8 (22 mm)
ODF sweat
“iSeries”
Variable-stage
1/4 Flare (2430)
3/8 Flare (3036)
1/2 Flare (2430)
5/8 Flare (3036)
The refrigerant coils are equipped with a Schrader valve
port to relieve the pressure and for factory testing pur-
poses. It can also be used to check for leaks prior to in-
stallation. Unscrew the Schrader cap and press the de-
pressor.
If pressure is present, then go
ahead and relieve the pressure in the coil be continuing to
press on the depressor. When all the pressure is removed
cut the ends of the connections off if brazing the lines.
Otherwise, just remove the flare caps.
Note
All refrigerant coils are shipped from our
factory pressurized with nitrogen. They
do not contain any refrigerant.
WARNING
To prevent injury to eyes, face away from
the Schrader valve when releasing nitro-
gen gas.
5 3/8
(137 mm)
2 1/4
(57 mm)
Pitch ¼ inch per foot
(2 cm per m)
U-TRAP (A00924-G05)
(shipped with cooling module)