© 2014 UTC Fire & Security. All rights reserved. 1 / 4 P/N 501-1776ZE-1-09 • REV 09 • ISS 16APR14
ZP755HA-2 Addressable Omnidirectional
Sounder Installation Sheet
Description
The ZP755HA-2 is an addressable, omnidirectional horn
sounder, designed for use on Ziton analogue addressable fire
detection and alarm systems.
The device includes a volume control, an address-setting
switch, programmable tone settings, and a pair of jumpers to
select the operating power — from the analogue addressable
loop or an external supply. The sounder plugs into a base that
is purchased separately. See Table 1 for a list of model
numbers.
Table 1: Models
Model number Description
Sounder:
ZP755HA-2R
ZP755HA-2P
Addressable, horn sounder, Red
Addressable, horn sounder, Polar white
Base:
SPB-2R
SPB-2P
Plug in-base, Red
Plug in-base, Polar White
Installation
To install the device follow these general steps.
1. Wire the base.
2. Set the operating power.
3. Set the address.
4. Set the mode of operation.
5. Set the tone.
6. Set the volume.
7. Mount the sounder onto the base.
The details of each step are given below.
Wiring the base
Connect the loop wiring for the plug-in base as shown in
Figure 1. There is no wiring between the sounder and plug-in
base.
Figure 1: Loop wiring for the plug-in base
1. Ext. 24 VDC+ IN/OUT
2. Ext. 24 VDC ground IN/OUT
5. Loop+ IN/OUT
6. Loop − IN/OUT
7. Shield
Setting the operating power
The sounder includes a pair of power selection jumpers, J1
and J2. To select the source of the sounder operating power,
position the jumpers as shown in Figure 2.
Figure 2: Power-selection jumper configuration
1. Loop powered 2. External 24 VDC
Note: When using an external power supply, use only one that
is CE and EN 54-4 compliant to power all the sounders on the
same loop.
6
2
5
1
J1 J1J2 J2
21
2 / 4 P/N 501-1776ZE-1-09 • REV 09 • ISS 16APR14
Setting the address
The sounder includes a seven-segment DIP switch (SW1) for
assigning device addresses. Each switch segment represents
the value shown in Figure 3. The address is the sum of all the
switch segments in the ON position. The switch is used to set
the device address in binary code. The switch may be set to
represent any address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Figure 3: Address switch setting
Mode and tone settings
The sounder includes a seven-segment DIP switch (SW2) to
select operating mode, device mode, and tone. See Figure 4.
Figure 4: Mode of operation switch settings
1. Power selection jumpers
2. SW2 configuration switch
3. Tone
4. Device mode
5. Operating mode
Setting the operating mode
The device operates as a dedicated (stand-alone) sounder with
its own unique loop address when SW2-7 is set to ON.
To configure operation as a stand-alone sounder:
1. Set SW2-7 to ON.
2. Navigate to the following menu to tag the sounders as
SAB:
ZP3 Panel Menu/Setup/Sounders/SAB/Add SAB
The Planner can also be used.
3. To map an alert-to-evac function, make the first input type
a fast flash input.
The sounder will sound the alert tone in response to a fast
flash input or an evac tone when the input configured as
steady is triggered, overriding the alert tone.
Setting the device mode
SW2-6 selects whether the loop sounder operates in ZP755
mode or in ZP754 emulation mode as described in Table 2.
Table 2: SW2-6 mode selection switch
Mode SW2-6 Output Signal Requirement
ZP755 OFF User-selectable two-
tone operation and
full monitoring
ZP3 software
v1.18 or later
ZP754
emulation ON Two fixed tones ZP5 panels or
ZP3 panels with
legacy software
Setting the tone
Two different tones can be programmed to operate from the
panel. In ZP755HA mode these tones are selected using SW2-
1, SW2-2, and SW2-3. Refer to Table 3.
Note: In the ZP panel I/O mapping menu, outputs are
programmed as "steady" or "flashing." The link to the table
below is as follows:
• Tone A = Panel setting "fast flash/slow flash.”
• Tone B = Panel setting "steady.”
1
2
34
5
P/N 501-1776ZE-1-09 • REV 09 • ISS 16APR14 3 / 4
Table 3: Tone settings
SW2-6 device mode
switch setting Device mode SW2 switch setting
-1 -2 -3 Mapping input type
Fast flash Steady
Tone type
Tone A primary/alert Tone B secondary/evac
OFF ZP755 0 Intermittent Continuous
OFF ZP755 1 Continuous Intermittent
OFF ZP755 2 Continuous Two-tone
OFF ZP755 3 Two-tone Continuous
OFF ZP755 4 Two-tone Intermittent
OFF ZP755 5 Intermittent Two-tone
OFF ZP755 6 Not used
ON ZP754 7 Intermittent Continuous
Setting the volume
Refer to Figure 5. The sounder has a volume control
potentiometer to adjust the volume.
WARNING: To conform to EN 54 Part 3 sound output levels,
the volume control must be set to the full clockwise position. If
the volume is adjusted for any reason, it must be returned to
the full clockwise position.
Figure 5: Volume control
1. Tone select
2. SW2-6 on
3. SW2-6 off
4. Volume control
Mounting the sounder onto the base
Refer to Figure 6. Align the addressable sounder to the plug-in
base. Push up (A) and turn the sounder until it clicks into place
(B). Push the sounder up once more to engage (C).
Reverse the above procedure to remove the sounder from the
base.
Figure 6: Mounting
1. Addressable sounder
2. Release aid (3X)
3. Release/lock catch
4. Plug-in base
Sounders per loop
The sounder can be powered directly from the loop of a ZP5 or
ZP3 panel. Use Table 4, in conjunction with Figure 7, to
determine the quantity of detectors and sounders that can be
connected to a two-core shielded loop.
1
2
3
123
4
4
3
2
1
A
B
C
4 / 4 P/N 501-1776ZE-1-09 • REV 09 • ISS 16APR14
Figure 7: Detector/sounders per loop
A. Cable length panel to first sounder
B. Cable length first to last sounder
C. Cable length last sounder to panel
1. Detectors and Sounders
Table 4: Maximum detectors and sounders per loop
A B C Quantity allowed [1]
10 m 980 m 10 m 50 detectors and 50 sounders
63 detectors and 42 sounders
100 m 800 m 100 m 45 detectors and 45 sounders
63 detectors and 40 sounders
200 m 600 m 200 m 40 detectors and 40 sounders
63 detectors and 37 sounders
300 m 400 m 300 m 37 detectors and 37 sounders
63 detectors and 35 sounders
[1] Using a two-core shielded loop of 1000 meters cable size 1.5 mm²
Specifications
Operating voltage
External supply
Loop supply, ZP protocol
18 to 30 VDC
19.5 to 20.5 V pulsed, max. 4 V line
loss
Current (line powered)
Quiescent (RMS)
Alarm (RMS)
Alarm (excluding device
address)
Alarm (at device address)
820 µA
6.4 mA
9.4 mA max.
25 mA max.
Current (externally powered)
Quiescent (RMS)
Alarm (RMS)
Maximum number
470 µA
500 µA
50 per 1 km loop (subject to cable
size and sounder spacing)
Sound output
Tone 1
Tone 2
Tone 3
90 dBA (all around)
Continuous 980 Hz
Intermittent 980 Hz (0.5 sec on/off)
Two-tone warble 980 Hz/670 Hz
Sound distribution Wide
CNPP anechoic sound levels See Figure 8
Monitoring
ZP loop
Sound output level
Open and short circuit fault
Self test facility
Compatibility Ziton analogue addressable
systems
Addressing method 7-segment DIP switch
Mounting Surface, with plug-in base
Wiring Two-core loop
Construction
Material
Weight
Dimensions (Ø × D)
Moulded thermoplastic
275 g
127 × 113 mm
Operating environment
Temperature
Relative humidity
−10 to +60°C
10 to 95%, noncondensing
Storage temperature −20 to +70°C
Figure 8: CNPP anechoic sound levels
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information refer to the product Declaration of Performance.
Certification
Certification body 0370
Declaration of
Performance number 360-5201-0399
Year of first CE marking 14
Product Identification ZP755HA-2
Intended use See DoP point 3
Essential characteristics See DoP point 9
Manufacturer Gulf Security Technology Co.,Ltd
80, Changjiang East Road,
QETDZ, Qinhuangdao,
Hebei Province, China 066004
Authorized EU manufacturing
representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
European Union
directives 1999/5/EC (R&TTE directive): Hereby, UTC
Fire & Security declares that this device is in
compliance with the essential requirements
and other relevant provisions of Directive
1999/5/EC.
2002/96/EC (WEEE directive): Products
marked with this symbol cannot be disposed
of as unsorted municipal waste in the
European Union. For proper recycling,
return this product to your local supplier
upon the purchase of equivalent new
equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
Contact information
For contact information, see www.utcfssecurityproducts.eu.
A
C
B
1
165
O
105
O
75
O
45
O
15
O
135
O
dBA 70 75 80 857075808590 90

Other UTC Fire and Security Horn manuals

UTC Fire and Security Edwards Genesis WG4 Series Assembly instructions

UTC Fire and Security

UTC Fire and Security Edwards Genesis WG4 Series Assembly instructions

Popular Horn manuals by other brands

Vixen Horns VXO4830AB/3318XB installation guide

Vixen Horns

Vixen Horns VXO4830AB/3318XB installation guide

Kleinn Air Horns SDKIT17-230STD installation manual

Kleinn Air Horns

Kleinn Air Horns SDKIT17-230STD installation manual

Tait T02-00004-0201 installation instructions

Tait

Tait T02-00004-0201 installation instructions

Mania MEGAHORN instruction manual

Mania

Mania MEGAHORN instruction manual

Juuko TA3 instruction manual

Juuko

Juuko TA3 instruction manual

Valcom V-1080 Flexhorn installation guide

Valcom

Valcom V-1080 Flexhorn installation guide

Valcom V-1050C brochure

Valcom

Valcom V-1050C brochure

syncrotek Noxaudio HM50 owner's manual

syncrotek

syncrotek Noxaudio HM50 owner's manual

Vixen Horns VXO8210/3114 installation guide

Vixen Horns

Vixen Horns VXO8210/3114 installation guide

Vixen Horns VXO8325/4124C installation guide

Vixen Horns

Vixen Horns VXO8325/4124C installation guide

Vixen Horns VXO8210/1101 installation guide

Vixen Horns

Vixen Horns VXO8210/1101 installation guide

APART EN-H15-G manual

APART

APART EN-H15-G manual

Westfalia 81 34 50 Original instructions

Westfalia

Westfalia 81 34 50 Original instructions

PagePac V-5331210 manual

PagePac

PagePac V-5331210 manual

Altec 31A HF HORNS manual

Altec

Altec 31A HF HORNS manual

Vixen Horns VXO8325/3114 installation guide

Vixen Horns

Vixen Horns VXO8325/3114 installation guide

Wheelock SA-H5-B installation instructions

Wheelock

Wheelock SA-H5-B installation instructions

Vixen Horns VXS9200B installation guide

Vixen Horns

Vixen Horns VXS9200B installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.