VSL3.928.010ASY 1 V1.00
zFeature
Used as an warning device to generate fire
alarm;
Installation and wiring same as detector
base;
Driven by detection circuit, no need for extra
power line.
zDescription
VB-6611S Conventional Alert Base is designed for the application inside a closed room. As an
warning device, the base will generate alarm sound when the detector detects a fire occurred.
Installed as a base, it is compatible with the range of VSAIL conventional detectors. It is usually
installed in hotel room, residential bedroom or other locations that are far away from the audible
and visual alarm.
zTechnical Data
Operating voltage: 15VDC~28VDC
Operating current: Standby current: 0mA Action current: ≤4mA (12V)
Sound level >75dB at 1 meter
Tonal modification cycle 0.6~1.5S
Environment Temperature:-10℃~+55℃Relative humidity≤95%,non-condensing
Weight 67g
Dimension diameter of 102mm, height of 25.5mm
Installation hole distance 73mm
zOutline and Installation Dimension
zInstallation and Wiring
1) The flame resistant twisted-pair ZR-RVS-2×1.0~1.5mm2is recommended to be used for the
wiring.
2) Before the installation, please check whether the shell is intact without any damage, and
whether the label is complete.
3) The terminals of the alert base shall be connected as the following diagram:
Control panel terminal Zone Input+: connected with the alert base’s position “1” or “2”;
VB-6611S ConventionalAlert Base
Beijing VSAIL Fire Protection Equipment Co. Ltd.
Building 32, Huilongsen Technology Park,
No.99 14th Kechuang Street, BDA, Beijing, PRC
nstallation and O
eration Manua
V1.00