Problems Possible causes You should try this
8. The wall control • TII mode is activated. • If the outside temperature is below -15°C (5°F), then the TII mode is probably
does not work. activated. (See Section 7.)
• The wires may be in • Ensure that the color coded wires have been connected to their
reverse position. appropriate places.
• The wires may be broken. •Inspect every wire and replace any that are damaged.
• There may be a short-circuit. • With the help of a multimeter, check for continuity.
• The wire in the wall OR • Remove the wall control and test it right beside the unit using another
the wall control may shorter wirer. If the wall control works there, change the wire.
be defective. If it does not, change the wall control.
• The circuit board may • If the second wall control does not solve the problem, then replace
be defective. the circuit board.
9. The 20/40/60-minute • The switch • Unplug the unit. Disconnect the main control and the
push-button timer does may be defective. optional control(s) (if need be). Jump the OL and OC
not work OR its indicator terminals. Plug the unit. If the unit switches to high
light does not stay on. speed, replace the switch.
10. The defrost cycle • Ice deposits may be hindering • Remove the ice.
does not work (the the damper operation.
fresh air duct is frozen • The damper rod or the port •Inspect these parts and replace if necessary.
OR the fresh air damper itself may be broken.
distributed is very cold. • The damper actuator • Plug in the unit and select “MIN” or “MAX”. Press the door switch and see if
may be defective. the port damper opens. If it doesn’t open, feed 120 V directly to the damper
actuator. If the port damper still does not open, replace the damper actuator.
• The circuit board may • Unplug the unit. Unplug the defrost sensor wire (see J4 on wiring diagram,
be defective. Section 8). Plug the unit back in. Select “MIN” and make sure the unit is
adjusted for low speed operation (turn all dehumidistats maximum
counterclockwise).Wait 3 minutes.The unit should switch to high speed and
the damper at the fresh air intake port should close (defrost mode). If it does
not happen, then replace the circuit board.
• The thermistor may • If the defrost mode works well after having disconnecting the thermistor wire
be defective. (above test), this means the thermistor is probably defective. You should
replace it.
- CSA, Standard F326, “Residential Mechanical Ventilation Systems”.
- NRCC, “National Building Code” 1995 edition.
- HRAI, “Desing and installation Manual for Residential Mechanical Ventilation Systems”, 1987 edition.
- HRAI, “Installation Manual for Heat Recovery Ventilators”, 1987 edition.
- CSA Standard C444-M887, “Installation requirements for Heat Recovery Ventilators”.
- ASRHAE 1984 Systems Handbook, chapter 11, “Air Distribution Design for Small Heating and Cooling Systems”.
20