VentCool Tahoe Series User manual

www.eldcontrols.com
Please retain these instructions after installation.
This device MUST be installed by a qualied agency in accordance with the manufacturer's installation instructions. The denition of
a qualied agency is: any individual, rm, corporation or company which either in person or through a representative is engaged
in, and is responsible for, the installation and operation of HVAC appliances, who is experienced in such work, familiar with all the
precautions required, and has complied with all the requirements of the authority having jurisdiction.
Installation Date:
Installed By: Phone:
P/N 780102000 07/20 Rev F
VentCool®Tahoe Series
WHOLE HOUSE FAN SYSTEMS
MODELS: T2, T3, T4, T5
INSTALLATION MANUAL
ITEMS INCLUDED:
• Fan Assembly with steel support straps, hardware and 20 foot power cord
• Duct Support Straps & hardware
• Acoustic Flex Duct, 7 foot length with collars
• Gravity Damper Assembly
• “Eggcrate” style Inlet Grille (white) with mounting screws
• Wall Mount WTT Control (ON/OFF, 2 Speed and 12-hour timer), white
decora wall plate and 50 foot cable

page 2 of 20P/N 780102000 07/20 Rev F
(THIS PAGE LEFT INTENTIONALLY BLANK)

page 3 of 20
SAFETY CONSIDERATIONS
•
•
Never
Never
operate this fan without a window or door opened.
operate this fan without a window or door opened.
•
•
This fan is meant for general ventilation.
This fan is meant for general ventilation.
It has NOT been designed to ventilate particle laden and/or
It has NOT been designed to ventilate particle laden and/or
explosive mixtures of air and must NOT be used for such.
explosive mixtures of air and must NOT be used for such.
•
•
This fan is NOT for use in kitchens
This fan is NOT for use in kitchens
•
•
Before installing or servicing this fan, switch power o at the home’s electrical panel to reduce the risk
Before installing or servicing this fan, switch power o at the home’s electrical panel to reduce the risk
of damaging circuit boards, re, electrical shock, or injury.
of damaging circuit boards, re, electrical shock, or injury.
•
•
Install this fan in accordance with this manual and all local codes and standards.
Install this fan in accordance with this manual and all local codes and standards.
Some of the principles of safe installation and operation of this product are not immediately obvious.
Some of the principles of safe installation and operation of this product are not immediately obvious.
Read the following safety information before continuing further:
Read the following safety information before continuing further:
Thank you for purchasing a VentCool
®ducted Whole House Fan by Field Controls. This fan has been designed
to provide many years of natural, quiet, and energy-ecient cooling.
Please take a few minutes to read over this manual and its accompanying documents to make sure you are
prepared to install the Whole House Fan system. In particular:
•
•
The homeowner/resident should read the WHERE TO LOCATE section so that the fan will be correctly lo-
The homeowner/resident should read the WHERE TO LOCATE section so that the fan will be correctly lo-
cated to maximize its eectiveness and eciency.
cated to maximize its eectiveness and eciency.
•
•
The VENTILATION REQUIREMENTS section is also particularly important, as it describes the minimum attic
The VENTILATION REQUIREMENTS section is also particularly important, as it describes the minimum attic
ventilation neccessary to operate the fan.
ventilation neccessary to operate the fan.
•
•
The INSTALLATION: GRAVITY DAMPER section contains important information regarding the constraints
The INSTALLATION: GRAVITY DAMPER section contains important information regarding the constraints
within which this fan’s gravity damper must be installed.
within which this fan’s gravity damper must be installed.
The Eggcrate Inlet Grille and Gravity Damper Assemblies come in dierent size openings. Verify which
The Eggcrate Inlet Grille and Gravity Damper Assemblies come in dierent size openings. Verify which
gravity
gravity
damper component design is part of your Whole House Fan Assembly by actual measurement of the gravity
damper component design is part of your Whole House Fan Assembly by actual measurement of the gravity
damper opening section before beginning installation of gravity damper section.
damper opening section before beginning installation of gravity damper section.
Before installing this fan, inspect it and all of its parts for any damage it may have sustained during shipping.
Before installing this fan, inspect it and all of its parts for any damage it may have sustained during shipping.
DO NOT INSTALL DAMAGED EQUIPMENT.
DO NOT INSTALL DAMAGED EQUIPMENT.
If you suspect this fan has been damaged during shipping, contact
If you suspect this fan has been damaged during shipping, contact
Field Controls technical support by phone at 1.800.742.8368, or email at eldtec@eldcontrols.com.
Field Controls technical support by phone at 1.800.742.8368, or email at eldtec@eldcontrols.com.
Whole House Fans are designed to be installed within a home’s attic, which makes them and their sub-
Whole House Fans are designed to be installed within a home’s attic, which makes them and their sub-
components dicult to access once installed.
components dicult to access once installed.
TEST THIS FAN OUTSIDE OF THE ATTIC BEFORE INSTALLING IT
TEST THIS FAN OUTSIDE OF THE ATTIC BEFORE INSTALLING IT
PERMANENTLY.
PERMANENTLY.
P/N 780102000 07/20 Rev F

page 4 of 20
GRAVITY DAMPER INFORMATION
ELECTRICAL REQUIREMENTS
The VentCool PSC Tahoe Series Whole-House Fan Systems require a 115 volt electrical power supply of mini-
mum 15A ampacity and maximum 15 Amp circuit overcurrent protection. We strongly recommend providing
a dedicated circuit for this fan system.
All electrical components, whether included with the VentCool system or supplied by others, must be rated for
the fan system’s electrical load requirements; please refer to the VentCool Tahoe Series specications table for
the electrical load requirements of the specic model to be installed.
All wiring and connections must be made according to this manual and all applicable electrical
wiring codes and standards. All applicable electrical codes must be followed to the satisfaction of the local
authority having jurisdiction.
VentCool Tahoe Series Whole House Fan Systems are shipped with a pre-wired 20 foot 115VAC power cord
with Nema 5-15P plug and fan control module (FC3JF) prewired and installed on the fan assembly. The fan
assembly directly connects to the Ventcool digital wall control (WTT) system via 50 foot Plug&Play (P&P) cable.
The P&P cable is equipped with RJ12 connectors that plug directly into the fan assembly control module
and backside of the wall control display. The wall control display is mounted in the living space and is used
for fan control (on/o, timer operation or temperature operation) of the whole house fan system. Refer to
INSTALLATION: Wiring & Controls section for wiring and connection diagrams for the Ventcool Tahoe Series
Whole House Fan (Generation 4) product line.
The Ventcool Tahoe Series Whole House Fan Systems have dierent gravity damper sizes,
The Ventcool Tahoe Series Whole House Fan Systems have dierent gravity damper sizes,
depending on the specic model to be installed. Verify which gravity damper size is provided with your
depending on the specic model to be installed. Verify which gravity damper size is provided with your
system prior to beginning installation of the product.
system prior to beginning installation of the product.
The VentCool Tahoe Series fan systems include gravity-closed gravity damper doors that are opened by air
pressure created by fan operation. The dampers serve to block entry of air from the attic into the living space, and
are provided with foam sealing and insulating material in the doors to reduce heat transfer from the attic space.
P/N 780102000 07/20 Rev F

page 5 of 20
VENTILATION REQUIREMENTS
It is very important that the attic be suciently ventilated for the fan system to operate properly. Without
adequate ventilation, hot air exhausted from the home cannot easily escape from the attic, which creates
back-pressure that will substantially reduce the fan’s performance. Operating this fan in an attic with less net
free ventilation area than recommended will decrease its airow and energy eciency.
If subject to the California Title 24 requirements for whole-house fan ventilation, the fan system must be installed
If subject to the California Title 24 requirements for whole-house fan ventilation, the fan system must be installed
to the minimum ventilation requirements as found in the standard.
to the minimum ventilation requirements as found in the standard.
In the absence of applicable local code regarding whole-house ventilation, we recommend a minimum of 1
In the absence of applicable local code regarding whole-house ventilation, we recommend a minimum of 1
square
square
foot of “net free” ventilation area per 500 cfm at a fan’s highest speed for proper operation.
foot of “net free” ventilation area per 500 cfm at a fan’s highest speed for proper operation.
Refer to specication
Refer to specication
table for required Net Free Ventilation Area in Attic at HVI fan rating.
table for required Net Free Ventilation Area in Attic at HVI fan rating.
Net
Net
Free Ventilation Area
Free Ventilation Area
can be provided by any combination of gable, eyebrow, roof cap, sot, or ridge
can be provided by any combination of gable, eyebrow, roof cap, sot, or ridge
vents, or any other method of ventilating the attic space. The openings of most vents are partially obstructed
vents, or any other method of ventilating the attic space. The openings of most vents are partially obstructed
by grilles, louvers, and/or screens. A vent’s “net free” ventilation area is the surface area of its opening minus the
by grilles, louvers, and/or screens. A vent’s “net free” ventilation area is the surface area of its opening minus the
surface area of any grilles, louvers, or screening covering it. Dierent types of vents have dierent ratios of net free
surface area of any grilles, louvers, or screening covering it. Dierent types of vents have dierent ratios of net free
area to total area.
area to total area.
While most properly constructed homes have adequately ventilated attics, not all do. Because sucient
While most properly constructed homes have adequately ventilated attics, not all do. Because sucient
ven
ven
tilation is a very strong factor in this fan’s performance, it is important that the home’s existing ventilation be
tilation is a very strong factor in this fan’s performance, it is important that the home’s existing ventilation be
veried before it is installed.
veried before it is installed.
Manufacturers typically publish their vents’ net free ventilation areas and/or ratios in their products’
Manufacturers typically publish their vents’ net free ventilation areas and/or ratios in their products’
specication documents. If this information is unavailable, a ratio of 50% net free area to total area is usually a good
specication documents. If this information is unavailable, a ratio of 50% net free area to total area is usually a good
rule of thumb. A notable exception to this rule of thumb are ridge vents. The industry standard net free ventilation
rule of thumb. A notable exception to this rule of thumb are ridge vents. The industry standard net free ventilation
area for ridge vents is 13% of the vent’s length in feet.
area for ridge vents is 13% of the vent’s length in feet.
Since most attics have multiple vents, often of dierent types, it is necessary to count each vent, noting its type
Since most attics have multiple vents, often of dierent types, it is necessary to count each vent, noting its type
and size. Apply the appropriate ratio to the dimensions of each vent to nd its net free area, and sum these
and size. Apply the appropriate ratio to the dimensions of each vent to nd its net free area, and sum these
values to nd the attic’s total ventilation. An example of how these calculations are made is given in the
values to nd the attic’s total ventilation. An example of how these calculations are made is given in the
table below:
table below:
Vent Type Dimensions Total Area
Net Free Area Ratio
(“NFA”)
Net Free Ventilation Area
(=Total Area x NFA)
Two Louvers 24” x 24” 24” x 24”/ 144 = 4 ft.250% 2 x 4 ft.2x .50 = 4 ft.2
Ridge 32 feet n/a 13% 32 feet x .13 = 4.16 ft.2
Round Sot 10” diameter 3.14 x 5” x 5” / 144 = .55 ft.250% .55 ft.2 x .50 = 0.28 ft.2
Total Net Free Ventilation Area: 8.44 ft.2
Please consult a roong professional if the attic’s net free ventilation area remains uncertain. Additional ventilation
may be required for proper operation of the fan system.
P/N 780102000 07/20 Rev F
Refer to specication table for required minimum Open Window Ventilation Area in square feet when operating
Refer to specication table for required minimum Open Window Ventilation Area in square feet when operating
whole house fan. Without adequate Open Window Ventilation Area, the quantity of cooler air pulled into the home
whole house fan. Without adequate Open Window Ventilation Area, the quantity of cooler air pulled into the home
to be exhausted to the attic may substantially reduce the fans overall performance.
to be exhausted to the attic may substantially reduce the fans overall performance.

page 6 of 20
• Locate this fan in a central location, away from windows that will be opened during
its operation. Installing this fan centrally promotes an even replacement of air through-
out the home, and the longer the path of air travels from an open window to the fan,
the greater the cooling eect.
• The damper provided with this fan can only be installed in a horizontal orientation,
thereby requiring the unit to be installed in the ceiling.
• Locate this fan at the highest point possible. This exploits natural convection and helps
the fan exhaust the hottest indoor air from the home.
• Typically, the ideal location for this fan in a two-story home is in the open area at the
top of the stairs.
• Avoid locating this fan in a narrow space or over hard ooring as sound reecting o
of hard surfaces can amplify its perceived noise.
• Even though the Tahoe series fan systems are engineered to be extremely quiet, we
specically recommend against installing it in a bedroom as humans’ perception of
noise is far greater when the surrounding environment is quiet (such as within a bed-
room at night).
By running this fan through the night, homeowners can extract the maximum possible amount of heat from their
home’s structure and contents. This essentially “pre-cools” the home ahead of the rise in temperature the next
day, which can reduce or even eliminate the need for air conditioning. This VentCool Whole House Fan has
been designed specically for quiet and ecient operation. As such, we strongly recommend homeowners run
this fan through the night to reduce their energy expense.
With these principles of operation in mind, adhere to the following guidelines when choosing a location for
this fan:
WHERE TO LOCATE THIS FAN
The best location for this fan is determined by an under-
standing of its theory of operation: As a home heats up
during the day, a large amount of heat is retained in its
structure and contents. These materials give up their heat
slowly and, in doing so, continue to heat the home’s inte-
rior even though the outdoor temperature may, in fact, be
very comfortable in the evening and at night. Thus, home-
owners are forced to either endure the hot conditions in-
side of their homes or turn on their air conditioners and
bear the expense thereof.
When operated properly, this whole house fan can resolve
this dilemma by forcing the hot air inside a home out and
drawing cool air from outside in. The illustration to the right
depicts how this fan exhausts hot air into the attic and
draws cool air into the house from outdoors through open
windows and/or doors.
P/N 780102000 07/20 Rev F

page 7 of 20
The ideal orientation of unit’s gravity damper is in a level position. If necessary, however, the damper can be in-
stalled at a slight angle. TIP: before beginning the installation, make sure that the fan assembly is undamaged,
and that the fan blade rotates freely. Brace or clamp the fan assembly to a secure object, and temporarily plug
in the fan’s power cord into a grounded power outlet to verify smooth and correct operation.
Be aware that the fan is quite powerful and will draw in loose objects or de
Be aware that the fan is quite powerful and will draw in loose objects or de
bris, and will blow dirt, debris
bris, and will blow dirt, debris
and other objects with force!
and other objects with force!
Use eye protection when operating the fan to avoid injury from blowing sand or debris! Keep hands and
Use eye protection when operating the fan to avoid injury from blowing sand or debris! Keep hands and
other objects away from the rotating fan blade!
other objects away from the rotating fan blade!
TIP: Before beginning the installation, verify that the damper assembly is undamaged, and that the damper doors
operate freely, opening and closing fully without binding or restriction.
INSTALLATION: GRAVITY DAMPER
GRAVITY DAMPER ORIENTATION NOTE
1. From consideration of the principles of whole-house fan
operation, determine the best general area for installation
of the gravity damper assembly. The damper assembly is to
be mounted in the attic with its bottom edge opening into
and ush with the ceiling of the living space. The eggcrate
inlet grille is to be mounted on the ceiling of the living
space, covering and engaging with the opening of the
damper assembly.
2. Using the cardboard from the fan system’s packaging, or
other suitable material, make a rectangular template for the
rough opening of the damper assembly to these dimensions
(making sure all sides are at right angles to each other):
a. Tahoe T2 and T3 models: 14-1/4” wide, 22-1/4” long
b. Tahoe T4 and T5 models: 14-1/4” wide, 30-1/4”long FIGURE 1 - TEMPLATE
3. Take the template into the attic, above the general area for installation, and determine the exact desired
location for the rough opening for installation of the damper assembly. There must be at least 36” of
vertical clearance above the damper assembly location, and the damper assembly must be fastened to
secure framing (ceiling joist, roof truss, or additional framing) along at least one long side or both short
sides of the damper assembly! Add additional framing as required to support the weight of the damper
assembly and duct.
a. For existing construction, the anges surrounding the opening of the damper assembly may be
removed for clearance (as with 16” on-center framing) and/or to allow the side or sides of the
damper assembly to make direct contact with the framing used to support the damper assembly.
Leave anges in place if they will not be fastened to framing, if possible. Additional framing
may be added after the damper assembly is placed into the rough opening, so the anges can
remain in place if space allows.
b. For new construction, before the ceiling drywall is hung, frame in a rough opening for
installation of the damper assembly from below. Leave the assembly anges in place and
simply attach the damper assembly to the bottom of the framing using appropriate fasteners
installed through the anges. Skip all following steps regarding cutting the rough opening
into the ceiling and proceed with installation of the duct and fan assembly.
P/N 780102000 07/20 Rev F

page 8 of 20
7. Using a drywall saw or other appropriate device, carefully cut out the rough opening into the ceiling. Use
care to avoid damaging the surrounding areas of the ceiling that will not be covered by the edges of the
eggcrate inlet grille.
8. Place the fan assembly, exible duct, and damper assembly in the attic space. If necessary, the fan and
damper assemblies may be passed through the rough opening into the attic. It may be necessary to
detach the exible duct from the fan assembly to allow passage of the fan and duct into the attic space. It is
recommended to pre-attach the ex ductwork to fan assembly prior to placing unit in attic.
9. Move the damper assembly into place in the rough opening, with the bottom edge of the assembly
protruding into the opening. If more than two anges were removed from the damper assembly for
installation clearance, make sure that the bottom edge of the damper assembly does not protrude below
the surface of the ceiling.
10. Attach the damper assembly to the framing by installing drywall screws (as supplied) or wood screws
through the inside wall(s) of the damper assembly into the framing. If addition framing is to be added, place
the framing over the damper assembly anges and fasten in place.
If using fasteners long enough to penetrate through the framing, use extreme caution
If using fasteners long enough to penetrate through the framing, use extreme caution
to avoid drilling into
to avoid drilling into
hidden wiring, plumbing, or other building elements of concern!
hidden wiring, plumbing, or other building elements of concern!
11. From below, install drywall screws through the ceiling and through the anges of the damper assembly, and
into any addition framing positioned above the anges. Use care to avoid installing screws outside of the area
that will be covered by the eggcrate inlet grille!
12. Hold the eggcrate grille in position on the ceiling, and install the included white screws through the holes in the
ange of the grille, through the ceiling, and into the damper assembly anges and/or framing above.
Make sure that the eggcrate grille mounting screws penetrate into either the damper box anges or framing
Make sure that the eggcrate grille mounting screws penetrate into either the damper box anges or framing
above, and that the grille is securely fastened in place!
above, and that the grille is securely fastened in place!
FIGURE 2 - DAMPER BOX INSTALLATION
4. Make sure that the exact location chosen
for the rough opening will allow installation
of the eggcrate inlet grille, and will not
interfere with any lighting xtures, smoke
alarms, or other objects installed in the
ceiling.
5. Remove any insulation from the area of
the exact chosen location, and make sure
that no wiring, plumbing, bracing or other
building elements will interfere with the
damper assembly installation.
6. With the template laying on top of the
ceiling in the exact chosen location, mark the
outline of the template onto the ceiling. If the
ceiling hole is to be cut from below, drill or
punch a small hole at each corner of the tem-
plate, and mark the outline of the template
from below the ceiling.
P/N 780102000 07/20 Rev F

page 9 of 20
INSTALLATION: FAN & DUCT
NOTES:
• The fan assembly must be soundly supported by attachment to structurally sound framing. Provide
additional framing with minimum 2-by-4 lumber as needed for fan support.
• The fan assembly should be positioned with at least 24” of free space in front of the fan, for air to be freely
blown into the attic by the fan.
• Position the fan with a slight upward angle and in a direction minimizing disturbance to attic insulation.
• The acoustical duct should be installed with a gentle bend of close to 90 degrees, from vertical to nearly
horizontal, to minimize fan sound inside the living space. It must not be kinked or bent sharply, especially
where leading into the fan.
• The acoustical duct must be installed with the air ow direction arrow (as marked on the duct) pointing
downstream (towards the fan).
1. Lay the fan assembly on top of the ceiling
joists, within a few feet of the damper assembly
and underneath the area where the fan will be
suspended in place.
2. Rotate and brace the fan assembly so that the
electrical handy-box on the fan is in the 12-o’clock
position (on the top of the fan). This is important
to avoid twisting the duct, while having the fan’s
electrical handy-box within the 10- to 2-o’clock
position once installed.
3. Adjust the exible duct collar on the upstream end
of the duct to be as loose as possible. Squeeze
and position the exible acoustic duct collar over
the oval-shaped collar on the damper box, and attach
using 3 of the screws provided, or other suitable
screws. Note that twisting the duct will cause the
fan to try to roll out of position. Seal the joint with
approved duct tape, mastic, or other approved means.
4. Lift and support the fan assembly into position beneath the rafters, truss structure or other framing to be
used to support the fan, with the electrical handy box at approximately the twelve-o-clock position.
Attach both ends of the metal fan support strap to the framing using a minimum of two screws for each
end of the strap. 1” drywall screws and large washers are supplied; other fasteners of appropriate
strength may also be used.
5. Using the black woven poly strapping, support the acoustic ex duct by attaching the strapping to
attic framing as shown. Fold each end over a large washer 2-3 times and fasten to the framing by driving
the supplied 1” drywall screws or other appropriate fasteners through the washer and into the framing.
The strapping may be cut to length with ordinary scissors if desired.
6. Replace the insulation around and over the damper assembly. Additional insulation may be added to
further reduce heat transfer and fan noised from the attic to the living space.
FIGURE 3: FAN & DUCT STRAPS DETAIL
P/N 780102000 07/20 Rev F

page 10 of 20
INSTALLATION: WIRING & CONTROLS
The VentCool PSC Tahoe Series Whole-House Fan Systems require a 115 volt electrical power supply of
The VentCool PSC Tahoe Series Whole-House Fan Systems require a 115 volt electrical power supply of
minimum 15A ampacity and maximum 15 Amp circuit overcurrent protection.
minimum 15A ampacity and maximum 15 Amp circuit overcurrent protection.
All electrical components, whether included with the VentCool system or supplied by others, must be rated
All electrical components, whether included with the VentCool system or supplied by others, must be rated
for the fan system’s electrical load requirements; please refer to the VentCool Tahoe Series specications
for the fan system’s electrical load requirements; please refer to the VentCool Tahoe Series specications
table for the electrical load requirements of the specic model to be installed.
table for the electrical load requirements of the specic model to be installed.
All wiring and connections must be made according to this manual and all applicable electrical wiring
All wiring and connections must be made according to this manual and all applicable electrical wiring
codes and standards. All applicable electrical codes must be followed to the satisfaction of the local
codes and standards. All applicable electrical codes must be followed to the satisfaction of the local
authority having jurisdiction.
authority having jurisdiction.
A dedicated circuit is strongly recommended for this fan system.
A dedicated circuit is strongly recommended for this fan system.
P/N 780102000 07/20 Rev F
STANDARD WHF WALL CONTROLL INSTALLATION USING WTT PRODUCT
1. Install a dedicated 115VAC, 15 amp power outlet with in 15 foot of fan assembly
location. Verify power voltage and terminal orientation.
2. In living area (upstairs living space), install a PLASTIC RETROFIT SINGLE GANG BOX
roughly 5 feet o the oor for the whole house fan wall controller to be mounted in
(Refer to FIGURE 4).
DO NOT INSTALL METAL GANG BOX.
DO NOT INSTALL METAL GANG BOX.
Select a location that will
best sense the temperature for the living space. Do not install box in a location
where the temperature will be inuenced such as in direct sunlight, on an exterior
wall, etc…
Note:
Note: The wall controller kit comes standard with 50 feet of cable to connect
between plastic box and the fan assembly. The maximum allowable cable
length is 100 feet using a connector and two 50 foot cables. Contact Field
Controls to purchase additional 50 foot cable and connector, if necessary.
FIGURE 4 - PLASTIC
RETROFIT GANG BOX
FIGURE 5 - PLUG CABLE TO FAN CONTROL MODULE
3. Route the 50 foot plug&play cable between the plastic box and fan assembly. Refer to DIAGRAM 1 for cable
connections. Plug the cable into the fan assembly fan control module (FC3JF) (Refer to FIGURE 5). Extend the
cable out of the plastic retrot box (refer to FIGURE 6).
FIGURE 6 - EXTEND CABLE
The Ventcool Tahoe series whole house fan is supplied pre-wired with fan control module (FC3JF) installed
The Ventcool Tahoe series whole house fan is supplied pre-wired with fan control module (FC3JF) installed
on fan assembly. Refer to Diagram 1 for the interconnection cable diagram. Refer to Diagram 2 for the fan
on fan assembly. Refer to Diagram 1 for the interconnection cable diagram. Refer to Diagram 2 for the fan
assembly electrical wiring diagram.
assembly electrical wiring diagram.

page 11 of 20
4. Connect the cable to the wall control (WTT). Plug the cable into the “RED” RJ12 Connector on the back
side of WTT. Refer to FIGURE 7 and DIAGRAM 1 for cable connections.
5. Attach the wall control (WTT) and cover plate to the plastic retrot box (refer to FIGURE 8).
FIGURE 7 - PLUG CABLE TO WALL CONTROL FIGURE 8 - ATTACH WALL
CONTROL AND COVER PLATE
6. Verify the number of fan speeds is set to two (2) speed operation on the wall control (WTT) to match2
speed motor.
Note:
Note:
The wall control (WTT) is factory set for two (2) speed motor operation from the factory.
a. Apply 115VAC power to fan assembly. The LCD on the wall control will lite up indicating power is
applied to the system and cable interconnections are made.
b. Press and hold the MODE button for about 7 seconds until STimer is displayed.
i. Press and hold the MODE button again to display the number of speeds.
ii. Press and hold the ARROW UP or ARROW DOWN button to increase/decrease # of fan
speed to 2 speeds.
FIGURE 9 - WALL CONTROL WITH PLATE
FUNCTIONAL SYSTEM CHECK
1. Verify fan power cord is plugged into dedicated 115VAC,
15 AMP outlet.
2. Turn ON dedicated fan assembly power outlet. LCD on
wall control should lite up.
3. Verify fan blade rotation.
a. Press
ON/OFF
ON/OFF button on WTT to start whole house
fan assembly.
b. Listen for fan to start.
4. Verify wall control is set to two (2) speed motor
operation. Refer to item 6 in Installation: Wiring and
Controls section to verify/modify number of fan speeds.
5. Return wall control to Temperature Control
a. Press
MODE
MODE button on WTT then press
DOWN
DOWN
ARROW
ARROW button to select
TEMPERATURE CONTROL.
TEMPERATURE CONTROL.
6. Press
ON/OFF
ON/OFF button on WTT to turn o the whole
house fan, if fan is still running.
P/N 780102000 07/20 Rev F

page 12 of 20
DIAGRAM 1: For T2-T5 Models with 2 Speed Wall Control (WTT) and Fan Motor Control (FC3JF)
DIAGRAM 2: For T2-T5 Models Fan Motor Wiring
P/N 780102000 07/20 Rev F
P/N: 780302502 RevA P/N: 780302504 RevB

page 13 of 20 P/N 780102000 07/20 Rev F
FIGURE 10 : STANDARD WALL CONTROL SYSTEM
(SPEED TEMPERATURE OR TIME)
OPERATION
Before starting this fan for the rst time, verify that:
Before starting this fan for the rst time, verify that:
• All wiring and connection have been made according to this manual and all applicable wiring codes and
• All wiring and connection have been made according to this manual and all applicable wiring codes and
standards.
standards.
• No tools or construction debris have been left in, on or around the fan.
• No tools or construction debris have been left in, on or around the fan.
• Dedicated 115VAC, 15 AMP power outlet has been properly installed and plug terminal outlet orientation is
• Dedicated 115VAC, 15 AMP power outlet has been properly installed and plug terminal outlet orientation is
correct.
correct.
• Wall control is installed properly. Plug&Play cable is installed and connected properly between wall control and
• Wall control is installed properly. Plug&Play cable is installed and connected properly between wall control and
fan assembly.
fan assembly.
• Open windows to allow for outside air to enter space.
• Open windows to allow for outside air to enter space.
• Verify that Functional Check in INSTALLATION:
• Verify that Functional Check in INSTALLATION:
WIRING & CONTROLS
WIRING & CONTROLS
section has been completed prior to home
section has been completed prior to home
owner use.
owner use.
• Verify grille is installed below damper assembly.
• Verify grille is installed below damper assembly.
1. Verify fan power cord is plugged into dedicated 115VAC, 15 AMP outlet.
2. Turn ON dedicated fan assembly power outlet. LCD on wall control should lite up.
3. Press
ON/OFF
ON/OFF button on WTT to turn ON the whole house fan.
The wall control can operate in two dierent modes of operation: Temperature or Timer Control
Temperature control will allow the homeowner to set the indoor temperature at which the whole house fan system
will turn o once temperature is reached. Timer control will allow the homeowner to set how much time in hours
the whole house fan will operate before turning o.

page 14 of 20
Switching wall control between Temperature and Timer Control Modes:
Switching wall control between Temperature and Timer Control Modes:
1. Switch wall control to Temperature Control from Timer Control mode:
a. Press
MODE
MODE button on WTT then press
DOWN ARROW
DOWN ARROW button to select
TEMPERATURE CONTROL.
TEMPERATURE CONTROL.
2. Switch wall control to Timer Control from Temperature Control mode:
a. Press
MODE
MODE button on WTT then press
UP ARROW
UP ARROW button to select
TIMER CONTROL.
TIMER CONTROL.
FIGURE 11- WTT DISPLAY IN
TEMPERATURE CONTROL MODE
FIGURE 12- WTT DISPLAY IN
TIMER CONTROL MODE
Temperature Control Mode:
Temperature Control Mode: (refer to FIGURE 11)
Turn the FAN ON:
Turn the FAN ON:
By pressing
ON/OFF
ON/OFF button. The fan will run until the indoor temperature drops below the
Set To
Set To
Temperature
Temperature
on the WTT display. By pressing the
ON/OFF
ON/OFF button while fan is operating will turn the
fan OFF.
Adjusting the Temperature:
Adjusting the Temperature:
Press and hold the
ARROW UP
ARROW UP or
ARROW DOWN
ARROW DOWN buttons individually to change the
Set To
Set To
Temperature
Temperature
setting.
When the
Set To Temperature
Set To Temperature
is lower than the indoor temperature, the fan is ON and running (ON
is blinking). When the
Set To Temperature
Set To Temperature
is above the indoor temperature, the fan is not running
and ON is not blinking.
Safety Feature in Temperature Control Mode:
Safety Feature in Temperature Control Mode: The WTT
ON/OFF
ON/OFF button is pressed to turn the fan ON.
In addition, the WTT has a built-in safety timer that will automatically turn the fan OFF after 8 hours
of continuous operation in case the homeowner forgets the fan is running.
Adjust the Safety Feature Timer Hour Setting:
Adjust the Safety Feature Timer Hour Setting:
Press and hold
MODE
MODE button for about 7 seconds until STimer is displayed. Press the
ARROW UP
ARROW UP or
ARROW DOWN
ARROW DOWN button to adjust the safety timer hours from 1 to 12 hours.
Adjusting Speed Control Setting:
Adjusting Speed Control Setting:
Press the SPEED button then press the
ARROW UP
ARROW UP or
ARROW DOWN
ARROW DOWN button to adjust the fan speed.
Timer Control Mode:
Timer Control Mode: (refer to FIGURE 12)
Switch wall control to Timer Mode.
Turn the FAN ON:
Turn the FAN ON:
By pressing
ON/OFF
ON/OFF button. The fan will run for Timer Interval on WTT display. By pressing the
ON/
ON/
OFF
OFF button while fan is operating will turn the fan OFF.
P/N 780102000 07/20 Rev F

page 15 of 20
IMPORTANT OPERATING TIPS
The following important tips for operating this fan have also been provided.
• NEVER operate this fan without also opening a window or door. Doing so can excessively depressurize the
home.
• Only operate this fan when the outdoor air temperature is cooler than the indoor temperature.
• Make sure the home’s air conditioner and furnace are OFF before turning on this fan. Running either of
these together with this whole house fan wastes money because the fan will force expensively conditioned
or heated air out of the home.
• We recommend running this fan through the night. The goal of using a whole house fan is to cool the entire
home, not just the air inside it. Once heated, the home’s structure and contents continue to radiate heat
until reaching the temperature of the surrounding air. Running this fan through the night speeds up this cool
ing process and can then further “pre-cool” the home, reducing or eliminating the need to use air conditioning
the next day.
• If the home has a basement, extra cooling can be achieved by drawing in air through the basement
windows.
• This fan’s cooling eect can be increased or concentrated in particular areas by adjusting the location of
open windows. Visualize the path air will travel from the windows to your fan’s opening. Generally, the
longer the path, the more cooling.
Adjusting the Timer Setting:
Adjusting the Timer Setting:
Press and hold the
ARROW UP
ARROW UP or
ARROW DOWN
ARROW DOWN buttons individually to adjust current
Timer Interval
Timer Interval
setting.
Note: If fan is operating, the new
T
imer Interval
imer Interval
setting adjustment is temporary. Once time period times
out, Timer Interval will revert back to original
Timer Interval
Timer Interval
setting. But if fan is OFF and you adjust the
Timer Interval
Timer Interval
, the new
Timer Interval
Timer Interval
is saved as the permanent setting.
Adjusting Speed Control Setting:
Adjusting Speed Control Setting:
Press the
SPEED
SPEED button then press the
ARROW UP
ARROW UP or
ARROW DOWN
ARROW DOWN button to adjust the fan speed.
P/N 780102000 07/20 Rev F

page 16 of 20
P/N 780102000 07/20 Rev F
Speed Settings: 3 (OFF/LOW/HIGH) - 2 Speed Motors
Gravity Damper Rough
Opening Dimensions:
T2 & T3: 14.3 inches X 22.3 inches
T4 & T5: 14.3 inches X 30.3 inches
Grille Construction: Aluminum Cube Core, Steel frame with White Powder Coat
Fan Diameter: T2, T3: 18.75 inches
T4: 20.75 inches
T5: 22.75 inches
Duct Length: 7 feet
Duct Diameter: T2: 16 inches
T3: 18 inches
T4 & T5: 20 inches
Electrical: 115VAC, 60 Hz, 15 Amp dedicated power
Fan Motor: (HP/FLA) T2: 1/3 HP / 4.9
T3: 1/3 HP /4.9
T4: 1/2 HP / 6.5
T5: 1/2 HP / 6.5
Damper Door Insulation: R5 (compiled)
Installation: Installs easily on 24 inches or 16 inches O.C. framing
Attic Net Free Ventilation Area (Sq ft) ** T2: 3.86
T3: 5.52
T4: 7.28
T5: 8.25
Open Window Ventilation Area (Sq ft)** T2: 7.73
T3: 11.04
T4: 14.56
T5: 16.49
SPECIFICATIONS*
*Due to our continual product improvement eorts, performance ratings and specications are subject to change without notice.
**Attic Net Free Ventilation and Open Window Ventilation Areas are listed as minimum requirements.
Actual lower ventilation areas may reduce fans overall performance at high speeds.
MAINTENANCE & TROUBLESHOOTING
Make sure the appropriate circuit breaker(s) at the homes’ electrical panel are turned OFF before servicing your
whole house fan product(s).
Verify the fan assembly is securely mounted and straps are not wearing prematurely. Repair and replace as
applicable.
Blocking of fan exhaust can cause it to fail prematurely and/or reduce the amount of air the fan can move. Keep
the area in front of the fan exhaust unobstructed. No object should be closer than 24 inches to the face of the fan
grille.
This fan has been factory tested. If problems are encountered, please take a few moments to run through the fol-
lowing troubleshooting procedures before calling for assistance:
• If the fan does not turn on and wall control (WTT) display is blank, check power to the unit and the
verify that fan power cord is plugged in to active 115VAC outlet.

page 17 of 20
Optional Upgrade Components for Controlling your Ventcool Summit Series Whole House Fan (Generation 4):
Optional Upgrade Components for Controlling your Ventcool Summit Series Whole House Fan (Generation 4):
Contact Field Controls Sales team for purchasing any of the following optional Upgrade components. These
new products will be available in 2021.
Wireless Remote Control Kit (WLM-RTT)
Wireless Remote Control Kit (WLM-RTT) – p/n: 580011704
The Remote Control Kit is designed to work in conjunction with the wall control (WTT) product. The Remote
Control provides wireless control of the whole house fan from anywhere in the home using the remote con-
trol. The kit includes a wireless plug in module (WLM), remote control (RTT) and set of batteries. The wireless
plug in module connects directly to the backside of wall control (WTT) printed circuit board.
WiFi Plug-In Module (WFM)
WiFi Plug-In Module (WFM)
– p/n: 580011705
The WiFi Plug-In Module is designed to work in conjunction with the wall control (WTT) product. The WiFi
Plug-In Module provides WiFi control of the whole house fan from anywhere using a smart phone, tablet or
PC. The smart phone, tablet or PC is provided by owner. This control requires access to a wireless network
within the home to communicate with a cloud based program on the smart device. The WiFi plug in module
connects directly to the backside of wall control (WTT) printed circuit board.
WiFi Module (iM3)
WiFi Module (iM3) – p/n: 580011703
The WHF WiFi module is designed to work with the fan control module (FC3JF) installed on the fan assem-
bly. The wall control (WTT) will be disconnected when the WiFi Module (iM3) is installed. The WiFi Module
provides WiFi control of the whole house fan from anywhere using a smart phone, tablet or PC. The smart
phone, tablet or PC is provided by owner. This control requires access to a wireless network within the home
to communicate with a cloud based program on the smart device. The WiFi module connects directly to the
plug & play cable from fan assembly.
P/N 780102000 07/20 Rev F
• If the damper doors ap during operation, verify that appropriate windows are open in the home and
that there is enough attic exhaust free space available. Either or both conditions will reduce whole
house fan performance air ow.
• If the damper doors do not open or close, visually inspect the damper for any debris obstructing their
movement. Inspect fan exhaust for obstruction.
• If Wall Control (WTT) display does not lite up. Verify fan power cord is plugged in to active 115VAC
outlet. Verify 50 foot plug&play cable is completely plugged into fan control module and“red” RJ
connector on back side of wall control device.
• The Wall Control (WTT) display indicates ON but the fan is not running. If ON is blinking and the WTT
is in Temperature Control mode, make sure the Set To Temperature is a few degrees lower than indoor
temperature. ON will blink when the fan is running.
• Fan is running but damper doors are not opening. If you feel some air but not a lot of air where the
damper doors open slightly, verify fan assembly is operating. Check outlet power to fan assembly.
• The Wall Control (WTT) only allows for 1 or 3 speed operation and your system is a 2 speed system.
Refer to Step 6 Set the Number of Fan Speeds in the INSTALLATION: WIRING AND CONTROL section to
change number of fan speeds of the wall control (WTT) device.
If the suggestions above do not work, contact Field Controls technical support at 800.742.8368 or by email
at eldtec@eldcontrols.com for further assistance. Technical manuals are available on our website at
www.eldcontrols.com.

page 18 of 20P/N 780102000 07/20 Rev F
(THIS PAGE LEFT INTENTIONALLY BLANK)

page 19 of 20 P/N 780102000 07/20 Rev F
FIGURE 13: VENTCOOL TAHOE REPLACEMENT PARTS
P/N 780800200, Rev B

© Field Controls, LLC
This manual may be downloaded and printed from the Field Controls website (www.eldcontrols.com)
This manual may be downloaded and printed from the Field Controls website (www.eldcontrols.com)
WARRANTY
WARRANTY
For warranty information about this or any Field Controls product, visit:
For warranty information about this or any Field Controls product, visit:
www.eldcontrols.com/ventCool
www.eldcontrols.com/ventCool
Field Controls Technical Support
Field Controls Technical Support
1.800.742.8368
1.800.742.8368
eldtec@eldcontrols.com
eldtec@eldcontrols.com
P/N 780102000 07/20 Rev F
Phone: 252.522.3031 • Fax: 252.522.0214
www.fieldcontrols.com
This manual suits for next models
4
Table of contents
Other VentCool Fan manuals
Popular Fan manuals by other brands

Hubbell
Hubbell Progress Lighting P250018 installation manual

Greenheck
Greenheck ERS-MD Installation, operation and maintenance manual

Stadler Form
Stadler Form Peter Leatherette P-014 operating instructions

Vortice
Vortice Nordik HVSL Super Blade Instruction booklet

Avtec
Avtec ecoarch Operator's manual

Hunter
Hunter 21880 Parts guide