Veris HWS Series User manual

Installation Guide
Humidity
Z204453-0E Page 1 of 4 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TM
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed byVeris Industries for any consequences arising out of the
use of this material.
Product Identification
Product Overview
The HWS analog series measures humidity of the air inside a room. Devices are designed for use in hospital rooms,
laboratories, and other spaces that require precise environmental control. The keypad allows control of setpoint
values. The slide switch position determines the output type (amp or volt). To maintain accuracy, keep vents clear
of dust, debris, etc. The HWS is warranted for period of ve years.
HWS Series
LCD Wall Mount with Analog Setpoints,
Humidistat Control
SetpointAccuracy NIST
= Analog1 = 1%
2 = 2%
3 = 3%
5 = 5%
HWS
N = NIST (1 & 2% only)
X = No (2, 3, 5% only)
S
= CE
A
Specifications
Input Power 15 to 30VDC/24VAC, 100mA max.
Outputs Switch-selectable amp or volt
If volt is selected, the configuration menu allows selection
between 0-5V or 0-10V
RH Sensor* Digitally profiled thin-film capacitive (32-bit mathematics)
U.S. Patent 5,844,138
RH Accuracy at 25°C from 10-80% RH**
(Multi-point Calibration NIST traceable)
±2%, 3%, or 5% models, ±1% at 20-50% RH
Reset Rate*** 24 hours
Stability ±1% @ 20°C (68°F) annually, for two years
Hysteresis 1.5% (typical)
Linearity Included in Accuracy spec.
Operating Humidity Range 0-100% RH (non-condensing)
Temperature Coefficient ± 0.1%RH/ °C above or below 25°C (typical)
Operating Temperature Range 10° to 35°C (50° to 95°F)
Analog Output Scaling 0-100% RH
Calibration Offset Adjustable ±9.9% in 0.1% increments
Setpoint Range 10-80% RH in 1% increments
* The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.
** Accuracy is specified with 24 VDC supplied power with rising humidity.
*** Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.
One side of the transformer secondary is connected to the signal common, so an isolation transformer or
dedicated power supply may be required.
RTD/Thermistors in wall packages are not compensated for internal heating of the product.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper
surge protection (EN 61000-6-1:2007 specification requirements).

Z204453-0E Page 2 of 4 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HWSSeries TM
Dimensions
1.2"
(29 mm)
3.5"
(89 mm)
4.75"
(121 mm)
- +
Installation Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Locate the tab at the top of the sensor housing. Using only the minimum required force, press this tab down and pull the cover
outward from the top. Set the cover aside.
Housing, Top View
Tab
2. Remove the backplate by unfastening the sensor from the bottom of the backplate and pivoting the sensor outward.
3. Punch out wire opening in the backplate.
4. Position the backplate vertically on the wall, 4 ½ feet (1.4 m) above the oor. Locate away from windows, vents, and other
sources of draft.

Z204453-0E Page 3 of 4 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HWSSeries TM
5. Mount the backplate onto the wall using the screws provided.
Five screwholes available; use a minimum
of two for secure mounting.
6. Wire the backplate.
POWER SOURCE
15 to 30VDC or 24VAC
DIGITAL CONTROL
RH Input
RH Setpoint Input
-
-
-
+
RH Output
GND
RH Setpoint Output
7. Install and congure the sensor.
RH
SENSOR
RH
YES
AMPVOLT
NO
RUN
CAL
–
Minus Select Plus
+
RUN/CAL Jumper:
CAL Mode - allows full access to all features.
RUN Mode - allows access to setpoint ONLY.
RH YES/NO Jumper:
YES - allows user to change RH setpoint
NO - user can NOT change RH setpoint
NOTICE
RISK OF EQUIPMENT DAMAGE
Ensure that the output selection is correct before applying power.
Failure to follow these instructions may result in permanent
equipment damage.
8. When the installation is complete, replace the cover and snap it into position.
Installation (cont.)

Z204453-0E Page 4 of 4 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02141
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HWSSeries TM
1. To calibrate, move the RUN/CAL jumper to the CAL position.
2. Relative humidity allows for a calibration oset of ±9.9% RH, at the user’s discretion.
Calibration
Instructions
O U T P U T
0 - 1 0 V
C A L R H
+ 0 . 0 %
4 5 . 5 % R H
S E T P O I N T
4 5 % R H
CONFIG/CAL MODE
(Enter by any keypress when
Run/Cal jumper is in Cal position)
NORMAL MODE
Press +/- to change, press Select button to select.
Press +/- to change, press Select button to select.
Press +/- to change, press Select button to select.
Press +/- to change, press Select button to select.
Only if switch is in
Volts position
SETPOINT MODE
(Enter by any keypress when
RH Yes/No jumper is in Yes position)
Menu Options
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Disconnect power to the unit.
2. Remove the faceplate.
3. Remove the HS element by gently pulling from the pin connector.
4. Place a new HS element onto the pin connector. Orient as shown, or the unit will not function. Ensure that the four HS pin holes
are inserted fully onto the unit pin connectors.
Top
Side
Bottom
Side
5. Replace the faceplate.
Replacing the
HSElement
- +
Display screen
Scroll down
Select
Scroll up