Verve VTST-LNV WiSPER User manual

1
INSTALLATION:
This device should be installed and serviced by a qualified technician.
Mount this control ONLY to a grounded metallic box.
1. Caution: HIGH VOLTAGE - Disconnect power supply before
servicing.
2. All wiring must comply with applicable codes and ordinances.
All wiring must have insulation rated 600VAC minimum.
Supply wires must be suitable for at least 105°C.
Suitable for insulated walls.
3. A thorough check-out of the system should be made after
installation is complete.
4. If fan motor is larger than 1/4 HP and/or electric heaters are used
for heating, additional power relays will be required
5. If retrofitting old thermostat, remove old thermostat from the
junction box, carefully noting the wire connections on the old unit.
Record wire color and terminal legends in spaces provided.
Disconnect old thermostat and remove any existing backplate or
mounting plate.
6. Install the mounting bracket to the junction box with the two long
mounting screws provided.
Note: If application involves a double ganged junction box,
abackplate will be required for a complete installation.
Please consult your supplier.
7. From the wire chart found in step 5, assign, according to function,
the cable wire colors to the thermostat wire legend provided below.
Note: The control feed and the load feed will be connected together
for the 4-pipe installation. If this is a new installation, record the cable
wire colors in the thermostat legend provided below.
8. Connect the thermostat wires to the cable wires recorded in step 7.
Be sure to connect green wire to earth ground.
9. Push the wires into the junction box. Tilt
the thermostat so that the bottom of the
thermostat is resting on the mounting tabs
ofthe mounting plate. Push the top of the
thermostat towards the wall and secure into
place with the self-tapping screw as shown
tothe right.
10. Turn power on. At start up, the low fan will automatically run for
three minutes to cycle room air.
If cooling or heating is required, it may become active after the
first 30 seconds of fan run time.
Application:
This thermostat is a line voltage heating and cooling digital temperature
control designed to operate either 2 or 4-pipe fan coil systems, but it
can also be configured to operate line voltage PTHP/PTAC systems.
This thermostat also has the capability to receive and transmit to
EnOcean enabled wireless products. Please see programming
instructions for more details. Switching of load circuits is through relay
contacts (see specifications for applicable load ratings). The fan
cycles on/off with calls for heating or cooling or can be on continuously
in either low or high speed when configured as a heat pump or on
continuously in either low, medium or high speed when configured as
a fan coil. The control can be placed in economy mode or stop mode
with 40°F freeze protection.This thermostat operates at a single
setpoint with automatic changeover.
Specifications:
Temperature Monitor Range: 32.2°F to 99.9°F (0.0°C to 37.7°C)
Setpoint Range: 60.0°F to 85.0°F (15.5°C to 29.5°C)
*Setpoint: 72.0°F (22.0°C)
*Comfort Limits: 65.0°F (18.5°C) cooling
85.0°F (29.5°C) heating
Display Format: Liquid Crystal Display (LCD)
Backlight: EL blue green
Sampling Rate: Every 15 seconds
Accuracy: ± 1°F (0.5°C)
Power Source: 120VAC to 277VAC (102 minimum to 304 maximum)
Load Rating:
*Fan Control:
Fan Coil - Selectable: Auto cycle, Low, Medium, High, Economy, Stop
Heat Pump - Selectable: Auto cycle, Low, High, Economy, Stop
Heat/Cool Control:
Fan Coil: 1 heat and 1 cool circuit
Heat Pump: 2 heat and 1 cool circuit
*Economy Limits:
Maintains room temperature between 60.0°F and 85.0°F
(15.5°C and 29.5°C) when thermostat is in economy (ECON) mode
*Fan Purge Timer: 30 seconds
Anti-short Cycle: 3 minute hold in no call state at all times
*Cycle Rate:
Fan Coil: 8 cycles per hour
Heat Pump: 6 cycles per hour
* Differential: 0.4°F
*Display Mode: Setpoint temperature
* System Function: Heat and Cool
*See Field Programming Instructions
Old thermostat
wire function
Power Feed
Load Feed
Neutral
Heat
Cool
Low Fan
Medium Fan
High Fan
Reverse Valve
Cable
wire color
New Stat Wire
Function
Control Feed
Load Feed
Neutral
Heat
Cool
Low Fan
Medium Fan
High Fan/Reverse Valve
Earth Ground
New Stat Wire
Color
Black
Orange
White
Red
Blue
Yellow
Yellow/Black
Yellow/Red
Green
Cable Wire Color
Standard
Junction
box
Voltage120VAC
1/4HP FLA
Heat/Cool
Pilot Duty
125VA
(1.0A)
5.8A
208VAC 220 - 240VAC
125VA
(0.6A)
125VA
(0.52A)
3.1A
277VAC
125VA
(0.45A)
2.4A2.9A
1/4 HP 3 speed or 2 speed fan motors:
Voltage120VAC
1/6HP FLA
Heat/Cool
Pilot Duty
240VA
(2.0A)
4.4A
208VAC 220 - 240VAC
240VA
(1.15A)
240VA
(1.0A)
2.4A
277VAC
240VA
(0.87A)
1.9A2.2A
Single speed fan motors:
Installation Guide
VTST-LNV WiSPER Thermostat
Line Voltage

2
LINE
VOLTAGE
Y
RELAY
HIGH
BLUE
VALVE
WHITE
FAN
RELAY
FAN
YELLOW W/
RED STRIPE
COMP
SYSTEM COMPONENTS
LOW
RELAY
W2
ORANGE
YELLOW
MECHANICAL
R
GL
CONTROLLER
RV
REVHEAT
RED
YELLOW W/
BLACK STRIPE
THERMOSTAT INTERNAL
MICROPROCESSOR
GH
N
AUX
RELAY
888.8
HEAT PUMP
BLACK
R = CONTROL FEED
N = NEUTRAL
GH = HIGH FAN SPEED
GL = LOW FAN SPEED
W2 = AUXILIARY HEAT
Y = COMPRESSOR
RV = REVERSING VALVE
LINE
VOLTAGE
GL
YELLOW W/
BLACK STRIPE
MECHANICAL
RELAY
GH
YELLOW
YELLOW W/
RED STRIPE
THERMOSTAT INTERNAL
WHITE
R
MICROPROCESSOR
FAN FAN
MEDIUM
BLUE
RED
RELAY
VALVE
ORANGE LF
HT
CL
N
LOW
RELAY
CONTROLLER
SYSTEM
COMPONENTS
GM
888.8
HIGH
FAN
BLACK
Hot pipe
Cool pipe
switch
Aquastat or
season change
2 pipe FAN COIL with aquastat (3 speed fan)
R = CONTROL FEED
N = NEUTRAL
GH = HIGH FAN SPEED
GM = MEDIUM FAN SPEED
GL = LOW FAN SPEED
HT = HEAT VALVE
CL = COOL VALVE
LINE
VOLTAGE
LOW
ORANGE
CL
RELAY
SYSTEM COMPONENTS
MECHANICAL
CLG
CONTROLLER 888.8
RED
YELLOW W/
BLACK STRIPE
VALVE
GL
RELAY
HT
MICROPROCESSOR
FAN
VALVE
R
GH
N
MEDIUM
RELAY
YELLOW W/
RED STRIPE
YELLOW
HTG
BLACK
WHITE
FAN
FAN
GM
THERMOSTAT INTERNAL
BLUE
HIGH
4 pipe FAN COIL (3 speed fan)
R = CONTROL FEED
N = NEUTRAL
GH = HIGH FAN SPEED
GM = MEDIUM FAN SPEED
GL = LOW FAN SPEED
HT = HEAT VALVE
CL = COOL VALVE
Fan Coil Note:
If the mechanical system has only
two fan speeds -
Yellow - low fan
Yellow w/ Black Stripe - high fan
Yellow w/ Red Stripe- not used
NOTE:
Green wire is to be attached to
earth ground.
GREEN
GREEN
GREEN

Installation Notice:
This high performance digital thermostat is designed to provide many
years of superior comfort control when properly installed and maintained
To achieve maximum performance, this device is designed to draw
room air into itself continuously. Reasonable care must therefore be
taken with regard to air quality at the time of installation as well as
during periods of normal use, see operating conditions below.
Operating Conditions:
The electronic mechanisms incorporated within this unit REQUIRE
operating conditions similar to other electronic devices intended for
INDOOR USE ONLY, such as would be acceptable for TV and similar
household appliances. Relative humidity must be less than 95% and
the atmosphere must be non-condensing. Air quality must be main-
tained FREE of heavy dust or debris which may infiltrate the interior of
this device. Installation in any space which is unfinished or under-
going repainting or general rehabilitation is also considered product
abuse. This device should be removed from service during any local
construction activity.
Cleaning:
This device incorporates a high impact polycarbonate enclosure which
is easily cleaned with a dry cloth or vacuum brush. Occasional soiling
may be cleaned with a soft cloth lightly dampened with water and/or
mild cleaning solution. IN NO CASE should this device be directly
sprayed with or exposed to free flowing liquids, including water, which
could penetrate its interior.
FAILURE TO OBSERVE ANY OF THE ABOVE CONDITIONS OF USE
WILL COMPLETELY VOID THE SUPPLIER WARRANTY.
CAUTION
MAKE SURE UNIT IS PROPERLY CONNECTED. DAMAGE TO THE
DIGITAL CONTROL CAN BE CAUSED BY MISWIRING, WHICH WILL
VOID THE WARRANTY. FOR SAFETY REASONS ALWAYS USE
WIRE NUTS ON ALL WIRE CONNECTIONS!!!
3
User Note: The top of this unit will become warm to the touch. This is a
normal operation. Internal heating is employed to continuously convect
air upward through the thermostat, thereby improving room air temperature
measurement. Direct conflict with a downward ceiling fan or system fan air
flow may result in false temperature reading. Locate thermostat to avoid
interference.
Room
Tem perature
Indicator
Fan
Icons
Mode
Icons
Cool
Icon Heat
Icon
Diagnostic
Indicator
Programming
Icons
Scale Indicator
Setpoint
Indicator
ROOM SETPOINT
AUTO
ECON
PROG
ERASE
DIAG
◦
BASIC FUNCTIONS
Adjust Temperature Setpoint:
Press up button ( ) to raise the temperature (warmer)
Press down button ( ) to lower the temperature (cooler)
Select Fan Operation:
Press fan button ( ) to select the following fan functions
AUTO - auto on/off with automatic speed change
Small fan icon -continuous LOW speed fan
Medium fan icon (if available) - continuous MEDIUM speed fan
Large fan icon - continuous HIGH speed fan
ECo ECON - maintains room temperature between 60.0°F and
85.0°F or 15.5°C and 29.5°C)
Stp - heating and cooling controls are disabled and the
fans are off
Change Scale Units:
Slide the °F/°C switch to the left to display °F
Slide the °F/°C switch to the right to display °C
When the °F/°C switch is invoked, the thermostat will reset and
display the default setpoint in the selected scale.
Cycle Timing: (Anti-short cycle protection)
3 minute (minimum) dwell time in no-call states (both heat and cool).
1minute (minimum) dwell time in call states (both heat and cool).
Temperature is sampled every 15 seconds.
SYSTEM CHECK:
Check Low Fan Function:
Press the fan button until the fan indicator on the LCD moves to
the LOW fan position.
Low speed fan will turn on immediately.
Check Medium Fan Function (if applicable):
Press the fan button until the fan indicator on the LCD moves to
the MEDIUM fan position.
Medium speed fan will turn on immediately.
Check High Fan Function:
Press the fan button until the fan indicator on the LCD moves to
the HIGH fan position.
High speed fan will turn on immediately.
Check Heating:
Press and hold the up button until the heat symbol appears on the
LCD. Within 3 minutes heating will be activated.
Note: Room temperature must be below the Comfort Heating Limit
85.0°F (29.5°C) for heating to become active.
Check Cooling:
Press and hold the down button until the cool symbol appears on
the LCD. Within 3 minutes cooling will be activated.
Note: Room temperature must be above the Comfort Cooling Limit
65.0°F (18.5°C) for cooling to become active.
AUTO
◦
°
F
/°
C
Decrease
temperature
Switches between
°F and °C
Selects
fan
function
Increase
temperature

Trouble Shooting Tests:
All measurements taken with a voltmeter set to read volts AC. One
lead of the voltmeter should be on the neutral (white wire) of the
thermostat. The voltmeter should read 120VAC to 277VAC when the
other lead is connected to the wire colors stated below.
A. Black (control feed): this wire will have power at all times when
power is applied to the thermostat.
B. Orange (load feed): In a two pipe fan coil with aquastat configu-
ration this wire will have power during a heating or cooling call.
Inany other configuration this wire will have power at all times
when power is applied to the thermostat.
C. Red (heat): In a heat pump configuration this wire will have power
during an auxiliary heating call.
Ina two pipe fan coil with aquastat configuration this wire will have
power during a heating call if the aquastat is set to heating.
In any other configuration this wire will have power duringaheating
call.
D. Blue (cool/compressor): In a heat pump configuration this wire
will have power during a first stage heating or cooling call.
Ina two pipe fan coil with aquastat configuration this wire will have
power during a cooling call if the aquastat is set to cooling.
In any other configuration this wire will have power during a cooling
call.
E. Yellow (low fan): this wire will have power at all times when the
thermostat is calling for low fan.
F. Yellow with black stripe (medium fan): In a heat pump configuration
this wire will have power at all times when the thermostat is calling
for high fan.
Inany other configuration this wire will have power when the
thermostat is calling for medium fan.
G. Yellow with red stripe (high fan/reverse valve): In a heat pump
configuration this wire will be the reverse valve and will have power
ifthe thermostat is set to a type “O” and in a cooling call or if the
thermostat is set to a type “B” and in a heating call.
Inany other configuration this wire will have power when the
thermostat is calling for high fan and set for three speed operation.
4
Diagnostic Mode:
Press and hold the "up" and "down" buttons
together until "DIAG" appears on the display.
Release the buttons.
Diagnostic mode will alternately display
setpoint and room temperature every 5 seconds.
AUTO
DIAG
◦
ROOM
AUTO
DIAG
◦
The room temperature is displayed "ROOM".
Both setpoint and room temperature displays
will indicate the fan speed activity and "DIAG".
ECON
◦
Diagnostic mode can be deactivated by changing
the °F/°C slide switch.
Room temperature must be below the Comfort Heating Limit
Press “UP” or “DOWN” button to set temperature.
Cooling: Cooling and low fan turn on automatically when
temperature rises 2°F above setpoint. Fan will switch to medium speed
if temperature continues to rise to 2°F above setpoint. Fan will switch
to high speed if temperature continues to rise to 4°F above setpoint.
High fan will turn off when temperature changes to 3°F above setpoint.
Medium fan will turn off when temperature changes to 1°F above
setpoint. Cooling will turn off when temperature drops 0.4°F below
setpoint. After first cooling call, cooling and low fan will turn on
automatically when temperature rises 0.4°F above setpoint. Cooling
will turn off when temperature drops 0.4°F below setpoint.
Heating: Heating and low fan turn on automatically when
temperature drops 2°F below setpoint. Fan will switch to medium
speed if temperature continues to drop to 2°F below setpoint. Fan will
switch to high speed if temperature continues to drop to 4°F below
setpoint. High fan will turn off when temperature changes to 3°F below
setpoint. Medium fan will turn off when temperature changes to 1°F
below setpoint. Heating will turn off when temperature rises 0.4°F
above setpoint. After first heating call, heating and low fan will turn on
automatically when temperature drops 0.4°F below setpoint. Heating
will turn off when temperature rises 0.4°F above setpoint.
Heat Pump: If system is set up to function as a heat pump the reverse
valve (yellow with red stripe wire) will engage with the compressor
during cooling if the thermostat is set to type ”O”. The reverse valve
(yellow with red stripe wire) will engage with the compressor during
heating if the thermostat is set to type “B”.
The reverse valve will de-energize 3 minutes after a compressor call.
Automatic Changeover: When thermostat is currently in cooling mode
and the temperature drops to 2°F plus the differential below the setpoint,
the mode will automatically switch to heating. When thermostat is
currently in heating mode and the temperature rises to 2°F plus the
differential above the setpoint, the mode will automatically switch to
cooling.
Motion Detection: If the thermostat is equipped with an onboard
motion detector or is using a remote motion detector use programming
parameters Setback Ramping (Sbr) to Economy Heating Limit (EH).
See page 3 of programming instructions to set up function and time
delays. If using a motion detector with a door switch, see Entry Door
Switch (Ed) below. Otherwise see Without Entry Door Switch.
Entry Door Switch (Ed): When the door is opened, the thermostat
will go into a temporary occupied mode. If, after a period of time
defined by the Open Door Timer (Odt), no motion is detected the
thermostat will go into unoccupied mode. If Setback Ramping (Sbr)
is disabled, the thermostat will now be controlled by the Economy
Cooling Limit (EC) or the Economy Heating Limit (EH). If Setback
Ramping (Sbr) is enabled, the thermostat will ramp back to the Economy
Cooling Limit (EC) or the Economy Heating Limit (EH). If motion is
detected at any time the thermostat will latch into occupied mode and
remain there until the door is opened again.
Without Door Switch: If, after a period of time defined by the Ramping
Setback Timer (rSt), no motion is detected the thermostat will go into
unoccupied mode. If the Setback Ramping (Sbr) is disabled, the
thermostat will now be controlled by the Economy Cooling Limit (EC)
or the Economy Heating Limit (EH). If Setback Ramping (Sbr) is
enabled, the thermostat will ramp back to the Economy Cooling Limit
(EC) or the Economy Heating Limit (EH). If motion is detected at any
time the thermostat will return to occupied mode.

5
9510-1236 Rev -
9-15-14
Pipe Sensor:
A pipe sensor can be used to determine whether there is hot or cold
water in a two pipe system. To activate the pipe sensor, install as
shown and then see programming instructions.
Mount the pipe sensor to the water pipe. The best location is to be as
close to the main pipe as possible and attached before the water valve
connection.
Water
Main Valve
Sensor Wire
Ties
Refer to the programming instructions for selecting the pipe sensor
function, temperature changeover settings, output configurations, purge
frequency and purge time duration. The thermostat will monitor pipe
temperature every 5 seconds. For a valveless systems, select the
2Pn configuration setting since this will bypass the valve purge
functions and provide heating or cooling based on pipe temperature
alone.
The 2PS and 2PE configurations operate with a valve purge function
to prevent incorrect temperature readings from static or standing water
in the pipe. The valve purge operates on a programmed interval
(purge frequency) for a programed duration (purge time duration)
in the event of low activity over an extended period of time.
If the heat or cool call has lasted for more than three minutes, the
pipe temperature heat or cool mode is rechecked to verify proper
operating mode.
Pipe Sensor
Blue/white wire
Green wire
Contains FCC ID: SZV-STM300U
Contains IC: 5713A-STM300U
The enclosed device complies with Part 15 of the
FCC Rules.
Operation is subject to the following two conditions:
(i.) this device may not cause harmful interference
and (ii.) this device must accept interference received,
including interference that may cause undesired
operation.
Verve LS & PSG Controls, Inc.
LIMITED WARRANTY POLICY
PSG Controls, Inc. (Hereinafter referred to as "PSG") warrants the following:
Only cataloged products sold to distributors are warranted to the original purchaser, to
conform with specifications furnished or approved by PSG, and to be free from defects in
material and workmanship, for a period of one (1) year from the date of purchase, unless
specified in writing for a different period.
Any PSG product that proves defective within the above described warranty period will
be repaired or replaced (at PSG's option) free of any charge if returned to the PSG
factory at 1225 Tunnel Road, Perkasie, PA. 18944 with transportation charges prepaid.
Prior to returning this product to PSG, the purchaser shall give PSG notice in writing
stating how this product fails to fulfill this warranty. No product shall be accepted for
repair or replacement without a required written notice and without prior written
authorization and shipping instructions having been received by the purchaser from
PSG. Only PSG's factory is authorized to perform services under this warranty.
This warranty does not extend to any product that has been subjected to misuse, abuse,
neglect, accidents, alterations, improper installation or use in violation of the printed
instructions furnished by PSG. This warranty neither applies to batteries nor
deterioration of, nor damage to the product caused by the use of faulty batteries. Final
determination as to whether any product is actually defective rests solely with PSG.
This warranty is expressly in lieu of all other agreements and warranties, expressed,
implied, or statutory and PSG has no other obligations or liabilities in connection with this
product. In no event shall PSG's obligation or liability hereunder exceed the purchase
price of this product. PSG SHALL NOT IN ANY EVENT BE LIABLE FOR ANY
INCIDENTAL OR CONSEQUENTIAL DAMAGES. This warranty gives you specific legal
rights, and you also have other rights which vary from state to state. Some states do not
allow the exclusion or limitation of incidental or consequential damages, or implied
warranties, so the above limitations or exclusion may not apply to you.
Toll free technical assistance is available
via our technical hotline: 1-800-523-2558
Mon-Fri, 8:00 A.M. to 4:30 P. M . Eastern Standard Time
RPSG Controls, Inc.
Table of contents
Other Verve Thermostat manuals