1.1 Flue systems
The following requirements regarding design and installation apply to
flue systems for condensing combustion equipment:
Prior to starting work on the flue system, your heating contractor
should confer with the responsible flue gas inspector [where
applicable].
Gas combustion equipment must be connected to the domestic chim-
ney on the same floor where it is installed (no transition through sep-
arating ceilings).
Here, differentiation is required as to whether the condensing boiler
should be installed in the living space (occupied rooms) or in the non-
living space (installation room).
Siting the Vitodens in the living space is feasible, subject to the flue
inside the living space being routed inside a protective pipe and being
surrounded by ventilation air (balanced flue system, balanced flue
operation).
As a special case, an installation inside the living space is also feasible
for open flue operation, provided a connection piece with secondary
ventilation up to the shaft (operation with interconnected room air sup-
ply) is provided (see page 35).
Structural unit
The aforementioned conditions are generally met when CE-designa-
ted flue systems (accessories) are used together with the Vitodens.
The following Viessmann balanced flue systems for balanced flue
operation are tested to DVGW and are CE-designated as a single
structural unit with the Vitodens:
■ Vertical roof outlet
■ External wall connection
■ Horizontal roof outlet
■ External routing through a coaxial pipe
Advantages of single structural units:
■ No calculated performance verification for flues to EN 13384 is
required for individual cases
■ Simplified visual inspection by the local flue gas inspector every two
years
■ No additional approval certificate by the flue pipe manufacturer is
required
Outside the living space, the flue pipe in the installation room may
also be routed without secondary ventilation. However, the installation
room would then require an adequately sized ventilation air aperture
to the outside (acc. to TRGI 2008).
Rated heating output up to 50 kW:
150 cm2 or 2 × 75 cm2
Rated heating output above 50 kW (e.g. Vitodens 200-W, from
60 kW, or multi boiler systems):
150 cm2 plus 2 cm2 for each kW above 50 kW
aThe country-specific regulations (which may include the TR Gas
and ÖVGW guidelines) apply to the installation of this appliance.
The plain flue must be type approved by the Deutsches Institut für
Bautechnik (DIBt) [Germany] (open flue operation).
The flue available as an accessory is CE-designated and approved in
accordance with EN 14471.
System certification
System certification to EC Gas Appliances Directive 2009/142/EC in
conjunction with PPs flues offered by Skoberne
Vitodens 200-W CE-0085CN0050
Vitodens 222-F CE-0085CN0050
Vitodens 222-W CE-0085CN0050
Vitodens 242-F CE-0085CN0050
Vitodens 300-W CE-0085CM0463
Vitodens 333-F CE-0085CM0463
Vitodens 343-F CE-0085CM0463
Vitosolar 200-F CE-0085CM0184
1.2 Balanced flue operation
Due to the sealed combustion chamber the Vitodens gas condensing
boilers are suitable for balanced flue operation. These boilers are cat-
egorised as equipment type C13x, C33x, C43x, C53x, C63x, C83x or C93x
according to TRGI 2008 ("x" only applies to DE).
With this type of equipment (except C63x) there is a joint approval for
the Vitodens and balanced flue system.
For this type of construction the tightness test (overpressure test) by
the flue gas inspector during commissioning and the verification of
"General Building Regulations approval" by the DIBt may be omitted.
Any approved flue system can be used for type C63x. This flue system
is not tested together with the boilers.
Maintain the dimensions specified on pages 12 to 22. The com-
bustion air is supplied and the flue gas extracted through one concen-
tric coaxial pipe (balanced flue system). The combustion air is supplied
through the annular gap between the external aluminium ventilation
air pipe and the flue pipe. Flue gases are discharged through the inter-
nal plastic pipe (PPs).
For balanced flue systems tested together with the wall mounted gas
boiler there is no requirement for a tightness test during commissioning
by the flue gas inspector.
In such cases we recommend that your heating contractor carries out
a simple tightness test during the commissioning of your system. For
this, it is sufficient to check the CO2 concentration in the combustion
air at the annular gap of the balanced flue pipe. The flue pipe is deemed
to be gas-tight if the CO2 concentration in the combustion air is no
higher than 0.2 % or the O2 concentration is at least 20.6 %.
Check the flue system for tightness by pressure testing if higher CO2
or lower O2 values are established.
In conjunction with the concentric coaxial pipe (balanced flue system),
the surface temperature of the Vitodens or that of the balanced flue
system will never exceed 85 °C. Therefore, clearances to combustible
components according to TRGI are not required.
For boiler types C63x and C43x, the DIBt-approved flue pipes from
Viessmann or alternative DIBt-approved flue pipes by other manufac-
turers may be used.
Use a condensate trap above the boiler flue connection if aluminium
flue pipes are used. Install the connecting pipes (routed horizontally)
with a fall of at least 3° to the boiler. In addition, we recommend using
clips spaced about 1 m apart to support the connection pipe.
The balanced flue system is CE-designated and approved in accord-
ance with EN 14471 (see page 6).
Flue systems
4VIESMANN VITODENS AND VITOSOLAR
1
5414 641 GB