Viessmann VITOTRONIC 200 User manual

Operating instructions
for the system user
VIESMANN
Heating system and domestic ventilation system with heat pump control unit
Vitotronic 200, type WO1C
VITOTRONIC 200
5623 540 GB 8/2012 Please keep safe.

2
Please follow these safety instructions closely to
prevent accidents and material losses.
Safety instructions explained
Danger
This symbol warns against the risk of injury.
!Please note
This symbol warns against the risk of material
losses and environmental pollution.
Note
Details identified by the word "Note" contain additional
information.
Target group
These operating instructions are designed for system
users.
This appliance has not been designed to be operated
by individuals (including children) with limited physical,
sensory or mental capacities or who are lacking in the
appropriate experience and/or knowledge, unless they
are supervised by a person with responsibility for their
safety or were instructed by that person in the opera-
tion of this appliance.
!Please note
Children should be supervised.
Ensure that children never play with the appli-
ance.
Danger
Incorrect work on the system can lead to life-
threatening accidents.
Work on electrical equipment must only be car-
ried out by a qualified electrician.
In case of fire
Danger
With fire there is a risk of burning.
■Shut down the system.
■Use a tested fire extinguisher, class ABC.
Installation conditions
!Please note
Incorrect ambient conditions can lead to system
damage and can put safe operation at risk.
Appliances installed inside:
■Ambient temperatures:
–Vitocal 200-A:
Ensure ambient temperatures higher than
5 °C and lower than 30 °C.
–All other Vitocals:
Ensure ambient temperatures higher than
0 °C and lower than 35 °C.
■Avoid air contamination through halogenated
hydrocarbons (e.g. as in paints, solvents and
cleaning agents).
■Avoid continuously high humidity levels (e.g.
through frequent drying of washing).
Appliance installed outside:
■Operate the appliance only at ambient temper-
atures above –20 ºC and below 35 ºC.
Auxiliary components, spare and wearing parts
!Please note
Components that are not tested with the system
may cause system damage, or may affect its
functions.
Installation or replacement work must only be
carried out by qualified personnel.
Safety instructions
For your safety
5623 540 GB

3
1. Introductory information Commissioning ...................................................................................... 6
Terminology ........................................................................................... 6
Your system is preset at the factory ....................................................... 6
Energy saving tips ................................................................................. 7
Tips for greater comfort ......................................................................... 7
2. About the controls Opening the control unit ......................................................................... 9
Programming unit .................................................................................. 9
■"Operating info" ................................................................................... 10
■Symbols .............................................................................................. 10
Standard menu ...................................................................................... 11
Extended menu ...................................................................................... 12
How to use the controls ......................................................................... 12
Operating program ................................................................................. 13
■Operating programs for heating, cooling, DHW, frost protection ........ 13
■Operating programs for ventilation ..................................................... 15
■Special operating programs ................................................................ 15
Time program ........................................................................................ 15
■Setting a time program using central heating/central cooling as an
example .............................................................................................. 16
■Setting the time program efficiently .................................................... 17
■Deleting time phases .......................................................................... 17
3. Start-up/shutdown Starting the heat pump .......................................................................... 18
Stopping the heat pump ......................................................................... 19
■With frost protection ............................................................................ 19
■Without frost protection (shutting down the system) ........................... 19
4. Central heating/central
cooling
Room temperature ................................................................................. 20
■Setting the standard room temperature for heating/cooling ............... 20
■Setting the reduced room temperature for heating/cooling ................ 20
Operating program ................................................................................. 20
■Setting the operating program for heating/cooling .............................. 20
Time program ........................................................................................ 21
■Setting the time program for heating/cooling ...................................... 21
Heating system with heating water buffer cylinder ................................ 21
■Setting the time program for the heating water buffer cylinder ........... 21
Heating curve/cooling curve .................................................................. 22
■Setting the curves for heating/cooling ................................................ 22
Switching off central heating/central cooling .......................................... 23
Comfort function "Party mode" .............................................................. 23
■Setting "Party mode" for heating/cooling ............................................ 23
■Ending "Party mode" ........................................................................... 23
Energy saving function "Economy mode" .............................................. 24
■Setting "Economy mode" for heating .................................................. 24
■Ending "Economy mode" .................................................................... 24
Energy saving function "Holiday program" ............................................ 24
■Setting the "Holiday program" for heating/cooling, ventilation ............ 24
■Cancelling or deleting the "Holiday program" ..................................... 25
5. DHW heating DHW temperatures ................................................................................ 26
■Setting the standard DHW temperature ............................................. 26
■Setting the higher DHW temperature ................................................. 26
Operating program ................................................................................. 26
■Setting the operating program for DHW heating ................................ 26
Time program ........................................................................................ 26
■Setting the time program for DHW heating ......................................... 26
■Setting the start optimisation .............................................................. 27
■Setting the stop optimisation .............................................................. 27
■Setting a time program for the DHW circulation pump ....................... 27
Index
Index
5623 540 GB

4
DHW heating outside the time program ................................................. 28
■Activating "1x DHW heating" .............................................................. 28
Stopping DHW heating .......................................................................... 28
6. Heating system with elec-
tric booster heater
.................................................................................................................. 29
7. Active cooling mode Enabling and blocking active cooling mode ........................................... 30
8. Air/water heat pumps .................................................................................................................. 31
9. Ventilation Starting ventilation ................................................................................. 32
Stopping ventilation ............................................................................... 32
■Activating "Standby mode" ................................................................. 32
■Stopping ventilation to change filters .................................................. 32
Operating program ................................................................................. 32
■Setting the operating program for ventilation ...................................... 33
Ventilation without heat recovery ........................................................... 33
■Setting the room temperature for ventilation ...................................... 33
■Setting a minimum temperature for ventilation ................................... 33
Time program ........................................................................................ 33
■Setting a time program for ventilation ................................................. 33
Comfort function "Intensive operation" .................................................. 34
■Setting "Intensive operation" for ventilation ........................................ 34
■Ending "Intensive operation" .............................................................. 34
Energy saving function "Economy mode" .............................................. 34
■Setting "Economy mode" for ventilation ............................................. 34
■Ending "Economy mode" .................................................................... 35
Energy saving function "Holiday program" ............................................ 35
■Setting "Holiday program" for ventilation, heating/cooling .................. 35
■Cancelling or deleting the "Holiday program" ..................................... 35
10. Power from a photovoltaic
system
Own consumption of power ................................................................... 36
11. Further adjustments Setting the display contrast .................................................................... 37
Setting the display brightness ................................................................ 37
Setting names for heating/cooling circuits ............................................. 37
Setting the preferred heating/cooling circuit for the standard menu ...... 38
Setting the time and date ....................................................................... 38
Language selection ................................................................................ 38
Setting the temperature unit (°C/°F) ...................................................... 38
Restoring factory settings ...................................................................... 38
12. Calling up Calling up information ............................................................................ 40
■Calling up the solar energy yield ........................................................ 40
■Daily log .............................................................................................. 40
■Screed drying ..................................................................................... 40
Calling up messages ............................................................................. 41
13. Manual mode .................................................................................................................. 43
14. Special system versions .................................................................................................................. 44
15. What to do if... Rooms are too cold ................................................................................ 45
Rooms are too hot ................................................................................. 46
There is no hot water ............................................................................. 46
The DHW is too hot ............................................................................... 46
" " is flashing and "Note" is displayed ................................................ 47
" " is flashing and "Warning" is displayed ............................................ 47
" " is flashing and "Fault" is displayed ................................................. 47
Index
Index
5623 540 GB

5
"Power-OFF C5" is displayed ................................................................ 47
"Controls locked out" is displayed .......................................................... 47
"Check filter" is displayed ...................................................................... 47
Doors/windows can only be opened with difficulty ................................. 47
Doors/windows bang when opened ....................................................... 48
16. Maintenance Cleaning the heating system ................................................................. 49
■In conjunction with a brine/water or water/water heat pump .............. 49
■In conjunction with an air/water heat pump ........................................ 49
■Vitotronic control unit .......................................................................... 49
Heating system inspection and maintenance ........................................ 49
■DHW cylinder (if installed) .................................................................. 49
■Safety valve (DHW cylinder) ............................................................... 49
■Potable water filter (if installed) .......................................................... 50
■Damaged connecting cables .............................................................. 50
Cleaning the domestic ventilation system .............................................. 50
■Cleaning supply air/extract air valves ................................................. 50
Replacing filters in the extract air valves ............................................... 51
Replacing the ventilation unit filters ....................................................... 51
■Resetting the service display .............................................................. 53
17. Appendix Refrigerant ............................................................................................. 54
Overview extended menu ...................................................................... 54
Calling up options under "Information" .................................................. 54
Terminology ........................................................................................... 57
■Active cooling mode (active cooling) .................................................. 57
■System version ................................................................................... 57
■Operating program ............................................................................. 57
■Operating status ................................................................................. 57
■Own consumption of power from a photovoltaic system .................... 57
■Electric booster heater ........................................................................ 58
■Power-OFF ......................................................................................... 58
■Underfloor heating .............................................................................. 58
■Quieter operation ................................................................................ 58
■Heating mode/cooling mode ............................................................... 58
■Heating curve/cooling curve ............................................................... 59
■Heating/cooling circuits ....................................................................... 61
■Heating circuit pump ........................................................................... 62
■Instantaneous heating water heater ................................................... 62
■Heating water buffer cylinder .............................................................. 62
■Controlled domestic ventilation ........................................................... 62
■Cooling mode ..................................................................................... 64
■Cooling function .................................................................................. 64
■Cooling curve ...................................................................................... 64
■Cooling circuit ..................................................................................... 64
■Ventilation ........................................................................................... 64
■Mixer ................................................................................................... 65
■Room temperature .............................................................................. 65
■Safety valve ........................................................................................ 65
■Secondary pump ................................................................................ 65
■Solar circuit pump ............................................................................... 65
■Cylinder primary pump ....................................................................... 65
■Drinking water filter ............................................................................. 65
■Compressor ........................................................................................ 66
■Weather-compensated heating/cooling mode .................................... 66
■Domestic ventilation ........................................................................... 66
■Time program ..................................................................................... 66
■DHW circulation pump ........................................................................ 66
18. Keyword index .................................................................................................................. 67
Index
Index (cont.)
5623 540 GB

6
The commissioning and matching up of the heat pump
control unit to local conditions and to the structural
characteristics of the building, plus the instruction of
the user in operating the system, must be carried out
by your heating contractor.
Note
These operating instructions also describe functions
that are only available on some heat pump models or
only with accessories. These functions are not specifi-
cally identified.
For questions relating to the extent of functions and
accessories for your heat pump and your heating sys-
tem, check with your local heating contractor.
Terminology
To provide you with a better understanding of the func-
tions of your Vitotronic control unit some terminology is
explained.
The terms are marked as follows:
Further information can be found in chapter
"Terminology" in the appendix.
Your system is preset at the factory
Your heating system is preset at the factory and is
therefore ready for operation:
Central heating/Central cooling
■Your home will be heated from 00:00 to 24:00 h to
20 °C "Set room temperature" (standard room tem-
perature).
■If a heating water buffer cylinder is installed, it will be
heated.
■Any electric booster heater installed will be enabled
(see chapter "Enabling electric booster heater").
■Active cooling mode is blocked (see chapter "Ena-
bling and blocking active cooling mode").
DHW heating
■The DHW is heated every day from 00:00 to 24:00 h
to 50 °C "Set DHW temperature".
■Any installed DHW circulation pump is switched off.
■Any electric booster heater installed will be enabled
(see chapter "Enabling electric booster heater").
Frost protection
■Frost protection for your heat pump, DHW cylinder
and any heating water buffer cylinder that may be
installed is ensured.
Note
At temperatures below −15 °C, the frost protection of
the heat pump, the DHW cylinder and the heating
water buffer cylinder is only ensured if an instantane-
ous heating water heater is installed (on site).
Domestic ventilation with Vitovent 300-F
■From 00:00 to 24:00 h: Domestic ventilation in oper-
ating status "Standard".
Wintertime/summertime changeover
■This changeover is automatic.
Date and time
■The date and time were set by your heating contrac-
tor.
Your heating contractor can make further settings for
you during commissioning.
You can change the settings to suit your requirements
at any time.
Power failure
In the case of a power failure, all settings are retained.
Introductory information
Commissioning
5623 540 GB

7
Central heating/Central cooling
■Standard room temperature ("Set room tempera-
ture", see page 20):
Never overheat your home. Every degree of room
temperature reduction saves up to 6 % on your heat-
ing bills.
Never set your standard room temperature higher
than 20 °C.
■Time program (see page 21):
Heat your home to the standard room temperature
during the day and the reduced temperature at night
(not suitable for underfloor heating). Set the time pro-
gram for this.
■Operating program:
If you do not require central heating or cooling, select
one of the following operating programs:
–"Only DHW" (see page 26):
If you require no heating for your home in summer,
but you need hot water.
–"Standby mode" (see page 19):
If you don't need to heat your home and don't need
hot water for longer periods.
■Short absence (see page 24):
Reduce the room temperature, for example when
you go shopping (not suitable for underfloor heating
systems). For this, select "Economy mode".
■Holidays (see page 24):
If you are going away, select the "Holiday pro-
gram":
The room temperature will be reduced, and DHW
heating will be turned off. In connection with a venti-
lation unit, a lower ventilation stage will be selected.
■Ventilation/airing:
To air a room, close the thermostatic valves and
briefly open the windows fully (if no domestic ventila-
tion system has been installed).
■Roller shutters:
Close roller shutters (where installed) at dusk.
■Thermostatic valves:
Ensure that thermostatic valves are set correctly.
■Radiators:
Never place things in front of radiators or thermo-
static valves.
DHW heating
■DHW circulation pump (see page 27):
Only activate the DHW circulation pump for periods
in which DHW is regularly drawn off. Set the time
program for this.
■DHW consumption:
Consider showering instead of running a bath. A
shower generally uses less energy than a full bath.
Domestic ventilation (in conjunction with ventila-
tion units)
■Short absence (see pages 32 and 34):
Select a lower ventilation stage, for example when
going shopping. For this, select "Economy mode"
or the "Standard operation" operating program.
■Holidays (see page 35):
If you are going away, select the "Holiday pro-
gram":
A lower ventilation stage will be selected. The room
temperature will be reduced, and DHW heating will
be turned off.
Own consumption of power (in conjunction with a
photovoltaic system)
■Use the power generated by your photovoltaic sys-
tem for your heating system (see page 36).
For additional energy saving functions of the heat
pump control unit, please contact your heating contrac-
tor.
Tips for greater comfort
Central heating/Central cooling
■Standard room temperature ("Set room tempera-
ture", see page 11):
You can select your individual preferred temperature
at any time in the standard menu.
■Preferred heating circuit (see page 38):
If your heating system comprises several heating cir-
cuits, you can input the important settings for a pre-
ferred heating/cooling circuit directly in the standard
menu.
■Time program (see page 21):
Make use of the time program. In the time program,
you can set time phases with different room temper-
atures, for example different temperatures for day
and night time.
■Heating water buffer cylinder (if installed, see
page 21):
Set the time program for the heating water buffer cyl-
inder so there is always sufficient heat for your heat-
ing circuits, for example to bridge power-OFF times
imposed by your local power supply utility.
■Electric booster heater (if installed, see page 29):
Enable the electric booster heater and set up a time
program for it. The electric booster heater starts
automatically if large amounts of heat are suddenly
required.
■"Active cooling mod." (see page 30):
After enabling the active cooling mode, a high cool-
ing capacity will be available for centrally cooling
your home, when required.
Introductory information
Energy saving tips
5623 540 GB

8
■Heating curve/cooling curve (see page 22):
The heating curve enables you to individually adjust
the heating system to the actual heat demand in your
home. If set correctly, your preferred temperature will
be achieved all year round. The same applies to the
cooling curve.
■"Party mode" (see page 23):
Select "Party mode" if you want to heat your home
to a temperature that is different from that dictated by
the time program.
Example: The time program determines that in the
evening, your home is heated to a reduced room
temperature, but you have visitors staying into the
evening.
DHW heating
■Time program (see page 26 and 27):
Use the time program for DHW heating. In the time
program, you can set time phases with different
DHW temperatures, for example higher in the morn-
ings than during daytime.
Use the time program for the DHW circulation pump.
During the selected time phases, DHW will be availa-
ble at the draw-off points at the required tempera-
ture.
■"Start optimisation" (see page 27):
The start optimisation ensures that your DHW cylin-
der will be heated to the selected temperature at the
beginning of any heating phase.
■"Stop optimisation" (see page 27):
The stop optimisation ensures that your DHW cylin-
der will be heated to the selected temperature at the
end of any heating phase.
■Once-only DHW heating (see page 28):
With "1x DHW heating" the heat pump will immedi-
ately heat up the DHW cylinder, independent of any
time program.
■Electric booster heater (if installed, see page 29):
Enable the electric booster heater and set up a time
program for it. The electric booster heater starts
automatically, if the heat pump on its own cannot
heat up the DHW cylinder quickly enough, for exam-
ple during the power-OFF times enforced by the
local power supply utility.
Domestic ventilation (in conjunction with ventila-
tion units)
■"Intensive operation" (see page 34):
During "Intensive operation" you increase the air
change rate in your home, for example when cook-
ing.
Operation of air/water heat pumps
■Quieter operation (see page 31):
Select the time program for quieter operation, for
example in order to reduce the noise level of your
air/water heat pump at night.
Introductory information
Tips for greater comfort (cont.)
5623 540 GB

9
The heat pump control unit may look different depend-
ing on the type of heat pump.
Control unit at the front of the heat pump
14°C 21°C
Fig. 1
Control unit on top of the heat pump
BA
Fig. 2
ATop part of control unit with programming unit
BButton for changing the angle
Control unit mounted on the wall
Fig. 3
Note
Brief operating instructions can be found on the back
of the flap. To open, pull the top edge of the flap for-
ward.
Programming unit
You can change all heat pump control unit settings
centrally at the programming unit.
If remote controls are installed in your rooms, you can
also adjust the settings at these remote controls.
Remote control operating instructions
About the controls
Opening the control unit
5623 540 GB

10
14 °C 21 °C
Fig. 4
Takes you to the previous step in the menu or
cancels a setting you have started to input.
Cursor keys
Scroll through the menu or set values.
OK Confirms your selection or saves the setting.
Calls up "Operating info" (see following chapter)
or additional information on the selected menu.
Calls up the extended menu.
Two control levels are available:
■The standard menu: See page 11.
■The extended menu: See page 12.
Note
The screen saver is activated if you have not made
any adjustments on the programming unit for a few
minutes (see page 12).
"Operating info"
Displays brief instructions on how to operate the
device.
How to call up the "Operating info":
■If the screen saver is active (see page 12):
Press .
■From anywhere in the menu:
Keep pressing the key until the standard menu is
shown (see page 11).
Press .
Symbols
These symbols are not always displayed, but appear
subject to the system version and the operating state.
Indicators:
Frost protection enabled
Central heating to standard room temperature
Central heating with reduced room temperature
Party mode is active for central heating
Economy mode is active for central heating
In conjunction with a solar thermal system:
Solar circuit pump is running
Compressor is running
For brine/water or water/water heat pumps:
Primary pump is running
For air/water heat pumps:
Fan is running
Instantaneous heating water heater is active (elec-
tric booster heater)
In conjunction with a cooling circuit:
Cooling mode is active
In conjunction with a photovoltaic system:
Own consumption of power is active
Heating/cooling circuits:
HC... Heating circuit ...
or
Heating/cooling circuit ...
SKK Separate cooling circuit
Operating programs:
■Operating programs for heating, cooling, DHW:
, , , :
For explanation of the symbols, see page 13
■Operating programs for ventilation:
Ventilation stages
0
to
4
subject to the selected
operating program, see page 15
Ventilation stages (in conjunction with a ventilation
unit):
0
No ventilation
1
Minimum air flow rate
2
Reduced air flow rate
3
Standard air flow rate
4
Maximum air flow rate
2
Frost protection for the ventilation unit is active.
Symbol using fan stage 2 as an example
About the controls
Programming unit (cont.)
5623 540 GB

11
2
Preheater bank for the ventilation unit is active, if
installed. Symbol using fan stage 2 as an exam-
ple
Ventilation unit was switched off at the ON/OFF
switch
Messages:
Fault
Warning
Note
Standard menu
In the standard menu, you can make and call up the
following settings for the preferred heating/cooling cir-
cuit (D):
■Set room temperature
■Operating program
How to call up the standard menu:
■If the screen saver is active (see page 12):
Press OK.
■If you are in the extended menu (see page 12):
Keep pressing the button until the standard menu
appears.
B
C
A
40°CFlow temperature
14°C 21°C
HC1
D
Fig. 5
AOperating program for the preferred heating/cool-
ing circuit (D)
BCurrent outside temperature
CSet room temperature for the preferred heating/
cooling circuit (D)
DPreferred heating/cooling circuit (see page 38)
Not shown if only one heating/cooling circuit is
installed.
Note
■In the case of special system versions, the standard
menu may differ from the display shown here (see
chapter "Special system versions", page 44).
■The settings for the preferred heating/cooling circuit
can also be made in the extended menu (see
page 12).
■The settings for any other connected heating/cooling
circuits can only be made in the extended menu.
■The settings for ventilation (if installed) can only be
made in the extended menu.
■Your heating contractor can block the operation of
the standard menu. In such cases, you will not be
able to make adjustments either in the standard
menu or in the extended menu (see page 47).
Setting the standard room temperature for the pri-
ority heating/cooling circuit
Press the following keys:
/ for the required value.
OK to confirm.
Setting the operating program for the priority heat-
ing/cooling circuit
Press the following keys:
/ for the required operating program.
OK to confirm.
About the controls
Programming unit (cont.)
5623 540 GB

12
In the extended menu, you can adjust and call up all
settings from the heat pump control unit's range of
functions, such as inputting settings for the holiday
program and time programs.
The menu overview can be found on page 54.
How to call up the extended menu:
■If the screen saver is active:
Press OK and then .
■From anywhere in the menu:
Press .
Note
Your heating contractor can block the operation of the
extended menu. In this case, you can only call up
messages (see page 41) and, in exceptional cases,
activate manual mode (see page 43).
Menu
Manual mode
Continue with
System
DHW
Heating/cooling
OK
F
i
Fig. 6
FDialogue line
How to use the controls
The screen saver is activated if you have not made
any adjustments on the programming unit for a few
minutes. The display brightness is reduced.
Screen saver
14 °C 21 °C
B
C
Fig. 7
BCurrent outside temperature
CSet room temperature
1. Press OK. This takes you to the standard menu
(see page 11).
2. Press . This takes you to the extended menu
(see page 12).
The selected menu option is highlighted in white.
The dialogue line F (see diagram on page 12)
then shows the necessary actions.
You can input the central heating/central cooling set-
tings for every heating/cooling circuit. It is therefore
necessary to select the required heating/cooling circuit
prior to inputting the settings (e.g. room temperature).
The following diagram shows how to input settings,
using the set room temperature setting as an example.
The diagram shows the setting with and without select-
ing the heating circuit, as well as various dialogue
lines.
About the controls
Extended menu
5623 540 GB

13
Vv
or
OK
Ú
OK
OK
Heating circuit 1
Economy mode
ÙÚ
Party mode
HC1 Htg circuit selection ÙÚ
HC2
Was selected
Heating circuit 2
Set room temperature HC1
20 °C
Change with (
Set room temperature HC1
22 °C
Adopt with OK
Set room temperature HC1
22 °C
Adopted
ê
ê
ÙÚ
HC1
Heating circuit 2
Economy mode
ÙÚ
Party mode
HC1
Continue with OK
ê
ê
ÙÚ
HC2
Set red. room temp
Set red. room temp
Set room temperature
Set room temperature
Vv
or
OK
Set room temperature HC2
20 °C
Change with (
Set room temperature HC2
22 °C
Adopt with OK
Set room temperature HC2
22 °C
Adopted
OK / /
v v
Heating circuit 1
Economy mode
Party mode
HC1
Continue with OK
ê
ê
Set red. room temp
Set room temperature
/
v v
OK
OK
40 °CFlow temperature
HC1
14 °C 21 °C
Menu
DHW
Continue with OK
Manual mode
System
Heating/cooling
i
Select with (
Fig. 8
Operating program
Operating programs for heating, cooling, DHW, frost protection
Heating/cooling
circuits
System version with DHW heating System version without DHW heating
Symbol Operating program Symbol Operating program
Heating circuit
"HC1", "HC2",
"HC3"
"Standby mode" "Standby mode"
"Only DHW" — —
"Heating and DHW"
(Factory setting)
"Htg"
Heating/cooling cir-
cuit
"HC1", "HC2",
"HC3"
"Standby mode" "Standby mode"
"Only DHW" — —
"Heating/cooling and DHW"
(Factory setting)
"Heating/cooling"
About the controls
How to use the controls (cont.)
5623 540 GB

14
Heating/cooling
circuits
System version with DHW heating System version without DHW heating
Symbol Operating program Symbol Operating program
Separate cooling
circuit
"SKK"
"Standby mode" "Standby mode"
"Only DHW" — —
"Cooling and DHW"
(Factory setting)
"Coolng"
Symbol Operating program Function
Central heating/central cooling and DHW heating
"Heating and DHW" ■The rooms of the selected heating circuit are
heated in accordance with the specified room
temperature and time program settings (see
chapter "Central heating/central cooling").
■DHW is heated in accordance with the specified
DHW temperature and time program settings
(see chapter "DHW heating").
"Heating/cooling and DHW" ■The rooms of the selected heating/cooling circuit
are heated/cooled in accordance with the speci-
fied room temperature and time program settings
(see chapter "Central heating/central cooling").
■DHW is heated in accordance with the specified
DHW temperature and time program settings
(see chapter "DHW heating").
"Cooling and DHW" ■The rooms supplied by the separate cooling cir-
cuit are constantly cooled (no time program can
be set).
■DHW is heated in accordance with the specified
DHW temperature and time program settings
(see chapter "DHW heating").
DHW heating
"Only DHW" ■DHW is heated in accordance with the specified
DHW temperature and time program settings
(see chapter "DHW heating").
■No central heating/central cooling.
■Frost protection of the heating water buffer cylin-
der (if installed) is active.
Central heating/central cooling
"Htg" ■The rooms of the selected heating circuit are
heated in accordance with the specified room
temperature and time program settings (see
chapter "Central heating/central cooling").
"Heating/cooling" ■The rooms of the selected heating/cooling circuit
are heated/cooled in accordance with the speci-
fied room temperature and time program settings
(see chapter "Central heating/central cooling").
"Coolng" ■The rooms supplied by the separate cooling cir-
cuit are constantly cooled (no time program can
be set).
Frost protection
"Standby mode" ■No central heating/central cooling.
■No DHW heating.
■Frost protection for the heat pump, the DHW cyl-
inder and the heating water buffer cylinder (if in-
stalled) is active.
About the controls
Operating program (cont.)
5623 540 GB

15
Operating programs for ventilation
Operating program Operating status Air flow rate Ventilation
stage
"Standby mode" —No ventilation
0
"Standard operation" —Minimum air flow rate
1
"Ventilation program" "Reduced" Reduced air flow rate
2
"Standard" Standard air flow rate
3
"Intensive" Maximum air flow rate
4
Special operating programs
Display in the standard menu
40 °CFlow temperature
HC1
14 °C 21 °C
Screed drying
E
Fig. 9
Special operating programs E:
■"Screed drying"
This function is activated by your heating contractor.
Your screed is dried in line with a set time program
suitable for the building material (temperature:time
profile). Your settings for central heating/central cool-
ing have no effect for the duration of screed drying.
■"External hook-up"
Your heat pump control unit is regulated by a higher
ranking control unit.
■"External program"
The operating program was changed by a communi-
cations interface (e.g. Vitocom 100).
■"Holiday program"
See page 24.
Note
In the extended menu, you can call up the set operat-
ing program under "Information" (see page 40).
Time program
The following explains how to input the settings for a
time program. The special features of each individual
time program are assigned to the relevant chapters.
You can set up a time program for the following func-
tions:
■Central heating/central cooling (see page 21)
■Heating the heating water buffer cylinder (see
page 21)
■DHW heating (see page 26)
■DHW circulation pump (see page 27)
■Electric booster heater (see page 29)
■Quieter operation of air/water heat pumps (see
page 31)
■Domestic ventilation (in conjunction with a ventilation
unit, see page 33)
In the time program, divide the day into sections.
These are called time phases. It is for you to decide
what happens in these time phases. For example, they
could specify when your rooms will be heated to stand-
ard room temperature. To do this, you will need to set
an operating status.
■You can set the time program individually, to be the
same for every day of the week or different.
■You can select up to 8 time phases per day.
■For each time phase you select the start and end
points.
The selected time phase is illustrated by a white bar
on the time chart. The length of the bar reflects the
length of time.
About the controls
Operating program (cont.)
5623 540 GB

16
■The individual operating status is displayed by bars
of different heights on the time chart.
Where several time phases overlap, the operating
status with the highest bar takes priority.
■In the extended menu, you can call up the time pro-
grams under "Information" (see page 40).
Setting a time program using central heating/central cooling as an example
Extended menu:
1.
2. "Heating/cooling"
3. If necessary, / for the required heating/cooling cir-
cuit.
4. "Time proghtg/cooling"
5. Select part of the week or a day.
6. Select a time phase ! to (. The selected time
phase is illustrated by a white bar on the time chart.
7. Set the start and end points for the relevant time
phase. The length of the white bar in the time dia-
gram is adjusted accordingly.
8. Select the required operating status "Reduced",
"Standard" or "Fixd value". The individual operat-
ing status is displayed on the time chart by bars of
different heights.
9. Press to exit the menu.
Note
If you want to terminate a time phase setting process
prematurely, keep pressing until the required dis-
play appears.
Example of operating status and time phases in
the time program for central heating
Heating/cooling Mo-Su
?08:30 - 12:10 u
Select with
Normal
(
!00:00 - 08:30 u
0 2 4 6 8 10 12 14 16 18 20 22 24
Reduced
?!
HC1
§ $ %
Fig. 10
■Time program for the part of the week "Monday–
Sunday" ("Mo-Su")
■Time phase !:
00:00 to 08:30 h: "Reduced"
■Time phase ?:
08:30 to 12:10 h: "Standard"
■Time phase §:
13:00 to 18:30 h: "Reduced"
■Time phase $:
20:00 to 22:00 h: "Fixd value"
■Time phase %:
22:00 to 24:00 h: "Reduced"
Between the time phases, operating status "Standby"
is active, in the example shown from 12:10 to 13:00 h
and from 18:30 to 20:00 h.
About the controls
Time program (cont.)
5623 540 GB

17
Setting the time program efficiently
Example: You want to set the same time program for
every day except Monday:
1. Select the "Monday–Sunday" part of the week and
input the time program settings.
Heating time program
Monday
Saturday-Sunday
Monday-Friday
Monday-Sunday
ê
ê
ê
ç
HC1
Select with (
Fig. 11
Note
The tick is always set at the sections of the week
with identical time phases.
Factory setting: Same for all days of the week,
therefore "Monday-Sunday" is ticked.
2. Then select "Monday" and adjust the time program
for that day.
Note
The "Saturday-Sunday" part of the week is ticked
because the set time phases correspond only to this
part of the week.
Heating time program
Monday
Saturday-Sunday
Monday-Friday
Monday-Sunday
ê
ê
ê
ç
HC1
Select with (
Fig. 12
Deleting time phases
■Set the time for the end point to the same time that
was set for the start point.
or
■For the start point, select a time prior to 00:00 h.
The display shows the selected time phase as
"- - : - -".
HC1
Change with (
- -:- - - -:- - u
0 2 4 6 8 10 12 14 16 18 20 22 24
---
Mo-Su
Heating/cooling
?08:30 - 12:10 uNormal
!
Fig. 13
About the controls
Time program (cont.)
5623 540 GB

18
The heat pump control unit may look different depend-
ing on the type of heat pump.
Control unit at the front of the heat pump
14°C 21°C
CBA
Fig. 14
AFault indicator (red)
BON indicator (green)
CON/OFF switch
Control unit on the heat pump
AB C
Fig. 15
AFault indicator (red)
BON indicator (green)
CON/OFF switch
Control unit mounted on the wall
14°C 21°C
B
C
A
Fig. 16
AFault indicator (red)
BON indicator (green)
CON/OFF switch
1. Switch ON the power supply, e.g. at a separate
MCB/fuse or a mains isolator.
2. Turn the ON/OFF switch ON.
Start-up/shutdown
Starting the heat pump
5623 540 GB

19
After a short time, the standard menu is displayed
(see page 11) and the green ON indicator illumi-
nates. Your heat pump and, if installed, your remote
control units are now ready for operation.
Stopping the heat pump
With frost protection
Select the operating program "Standby mode" for
every heating/cooling circuit.
For the priority heating/cooling circuit
Standard menu
1. / for the operating program "Standby mode"
(frost protection).
2. OK to confirm.
For all heating/cooling circuits
Advanced menu
1.
2. "Heating"
3. If necessary, press / for the required heating/cool-
ing circuit.
4. "Operating program"
5. "Standby mode" (frost protection)
■At temperatures below −15 °C, frost protection for
the heat pump, the DHW cylinder and the heating
water buffer cylinder is only ensured if an electric
booster heater is installed.
■The circulation pumps are briefly started every 24
hours to prevent them from seizing up.
■If a ventilation unit is connected to your heat pump
control unit, this unit will continue to run with the
selected operating program (e.g. "Ventilation pro-
gram").
Ending the operating program "Standby mode"
Select another operating program.
Without frost protection (shutting down the system)
1. Switch the ON/OFF switch OFF.
2. Isolate the heat pump from the power supply, e.g.
at a separate MCB/fuse or a mains isolator.
!Please note
If outside temperatures below 3 °C are
expected, take appropriate measures to pro-
tect the heat pump and the heating system
from frost.
If necessary, contact your heating contractor.
Note
If a ventilation unit is connected to your heat pump
control unit, this unit will continue to run with minimum
air flow rate (
1
).
Information on a prolonged shutdown
■Circulation pumps may seize up, as they are not
supplied with power.
■It may be necessary to reset the date and time (see
page 38).
Start-up/shutdown
Starting the heat pump (cont.)
5623 540 GB

20
Further information can be found in chapter
"Terminology" in the appendix.
Setting the standard room temperature for heating/cooling
Factory setting: 20 °C
For the priority heating/cooling circuit
Standard menu
1. / for the required value.
2. OK to confirm.
For all heating/cooling circuits
Advanced menu
1.
2. "Heating" or "Heating/cooling"
3. If necessary, press / for the required heating/cool-
ing circuit.
4. "Set room temperature"
5. Set the required value.
Note
■Central heating to this temperature:
Active in the time program in operating status
"Standard" (see page 21).
■In conjunction with a ventilation unit:
Set the room temperature for ventilation up to 4 °C
lower than the room temperature for heating/cooling.
This will ensure that the bypass functions correctly.
Setting the reduced room temperature for heating/cooling
Factory setting: 16 °C
Note
No set reduced room temperature can be specified for
a separate cooling circuit.
Advanced menu
1.
2. "Heating" or "Heating/cooling"
3. If necessary, press / for the required heating/cool-
ing circuit.
4. "Set red. room temp"
5. Set the required value.
Central heating to this temperature:
■Active in the time program in operating status
"Reduced" (see page 21).
■In the holiday program (see page 24).
Operating program
Further information can be found in chapter
"Terminology" in the appendix.
Setting the operating program for heating/cooling
For the preferred heating/cooling circuit
Standard menu
1. / for the operating program:
For example "Heating and DHW".
For further possible operating programs, see
page 14.
2. OK to confirm.
For all heating/cooling circuits
Extended menu
1.
2. "Heating" or "Heating/cooling"
3. If necessary, / for the required heating/cooling cir-
cuit.
4. "Operating program"
5. For example "Heating and DHW".
For further possible operating programs, see
page 14.
Central heating/central cooling
Room temperature
5623 540 GB
Other manuals for VITOTRONIC 200
15
Table of contents
Other Viessmann Network Router manuals
Popular Network Router manuals by other brands

Patton electronics
Patton electronics ONSITE 2603 quick start guide

Advantech
Advantech ICR-2041 user manual

ZyXEL Communications
ZyXEL Communications IES-1000 - ANNEXE 7 Hardware installation guide

Technicolor
Technicolor DGA4130 Setup and user guide

TP-Link
TP-Link Archer AX75 user guide

D-Link
D-Link DSL-2540U user manual