GUARDS AND WATER
SHIELDS FOR
XT1 SPRINKLERS
TECHNICAL DATA
Form No. F_021319 20.10.06 Rev 20.2
Page 1 of 8
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
T
elephone:
269-945-9501
T
echnical
Services:
877-384-5464
Fax:
269-818-1680
Email:
[email protected]Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
Viking Model XG Sprinkler Guards and XWU Water Shields are used in conjunction
with Viking XT1 style sprinklers where allowed by the approvals. (Refer to the
Approval Charts) The guards are hard-wire cages designed to encase the
sprinklers and protect them from mechanical damage. They are recommended for
areas where sprinklers are installed at a low elevation and/or near a high degree
of human or mechanical activity.
Water shields protect the sprinkler’s heat-sensing operating element from water
spray discharge from sprinklers located at a higher elevation. Viking XT1 style
sprinklers with Model XWU or F-1 Water Shields and/or XG Guards are converted
to intermediate level/rack storage sprinklers. They may be used in any application
where water shielding is required, such as in-rack sprinkler systems, under grating,
on pilot sprinklers for deluge systems, and outdoors as a weather shield.
NOTE:Sprinkler water shields and guards are not designed to be used on
sprinklers installed in recessed escutcheons.
2. LISTINGS AND APPROVALS
FM Approved: Class 2091
cULus Listed: Category VNIV
XG Guard is approved for use with the following sprinklers:
VK1001, VK1021, VK3001, VK3021, VK2002, VK2022, VK3502, VK3522,
VK2001, VK2021, VK3501, and VK3521
XWU Water Shield is approved for use on XT1 Upright sprinklers with XG Guards:
VK1001, VK3001, VK2002, VK3502, VK2001, and VK3501
F-1 Water Shield is approved for use with XT1 Pendent sprinklers:
VK1021, VK3021, VK2022, VK3521, VK2021, and VK3522
Refer to the Approval Charts for more information.
3. TECHNICAL DATA
Specifications: See Table 2.
Material Standards:
XG Sprinkler Guard: UNS-G10100 Bright Basic Steel Wire or JIS G3141 SPCF
XWU Water Shield: UNS-G10080 Cold Rolled Steel or JIS G3141 SPCF
F-1 Water Shield: UNS-G10080 Cold Rolled Steel
TABLE 1: ORDERING INFORMATION AND DIMENSIONS
Guards and water shields must be ordered separately. See below for details.
Refer to the approval charts in this document as well as the appropriate sprinkler Technical Data Page.
Part Number Description Size
NPT BSPT
22931 Model XG Sprinkler Guard 1/2” or 3/4” 15 mm or 20mm
22937 Model XWU Upright Water Shield (must be used with Model XG Guard) -- --
10323 Model F-1 Pendent Water Shield 1/2” 15 mm
10324 Model F-1 Pendent Water Shield 3/4” 20mm
XG Sprinkler Guard
XWU Water Shield
F-1 Water Shield
Replaces Form No. F_021319 Rev 20.1
(Removed pre-assembled options and wrench .)