SECTION 3A GENERAL REQUIREMENTS (EIRE)
This appliance must be installed by a competent
person in accordance with and defined by, the
Standard Specification (Domestic Gas Installa-
tions) Declaration (I.S. 813).
3A.1 RELATED DOCUMENTS
The installation of this boiler must be in accord-
ance with the relevant requirements of the local
building regulations, the current ETCI National
Rules for Electrical Installations, and the bylaws
of the local water undertaking.
Itshould bein accordancealso withany relevant
requirementsofthelocaland/ordistrictauthority.
3A.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current ETCI
National Rules for Electrical Installations, and
I.S. 813, Annex K.
When an appliance is installed in a room or
internal space containing a bath or shower, the
appliance or any control pertaining to it must not
be within reach of a person using the bath or
shower.
The location chosen for the appliance must per-
mit the provision of a safe and satisfactory flue
andtermination.Thelocationmustalsopermitan
adequate air supply for combustion purposes
and an adequate space for servicing and air
circulation around the appliance. Where the in-
stallation of the appliance will be in an unusual
location special procedures may be necessary,
refer to I.S. 813 for detailed guidance on this
aspect. A compartment used to enclose the
appliance must be designed and constructed
specificallyforthispurpose.Anexistingcompart-
ment/cupboardmay be utilisedprovided thatit is
modified to suit.
This appliance is not suitable for external instal-
lation.
3A.3 GAS SUPPLY
The gas meter - as supplied by the gas supplier
-mustbecheckedtoensurethatitisofadequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with I.S. 813.
Pipe work from the meter to the appliance must
be of adequate size.Pipes of a smaller size than
the appliance gas inlet connection must not be
used.The installation must be tested for sound-
ness in accordance with I.S.813.
Ifthegassupplyservesmorethanoneappliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3A.4 FLUE SYSTEM
Theterminalshouldbelocatedwherethedisper-
sal of combustion products is not impeded and
withdueregardforthedamageanddiscoloration
thatmayoccurtobuildingproductslocatednearby.
Theterminalmustnotbelocatedinaplacewhere
itislikelytocauseanuisance(refertoI.S.813for
guidance on permitted locations and minimum
distances of flue terminals).
Watervapourwillcondenseonleavingthetermi-
nal; the effect of such pluming must be consid-
ered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
RefertoI.S.813,whentheterminalis0.5metres
(or less) below plastic guttering or 1 metre (or
less) below painted eaves.
3A.5 AIR SUPPLY
The following notes are intended for general
guidance only. This appliance is a room-sealed,
fan-flued boiler, consequently it does not require
a permanent air vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not re-
quired.
3A.6 WATER CIRCULATION
Specific recommendations are given in I.S. 813.
Thefollowing notesare forgeneral guidanceonly.
3A.6.1 PIPEWORK
It is recommended that copper tubing be used in
conjunction with soldered capillary joints.
Where possible pipes should have a gradient to
ensureairiscarriednaturallytoairreleasepoints
and that water flows naturally to drain cocks.
Exceptwhereprovidingusefulheat,pipesshould
beinsulatedtoavoidheatlossandinparticularto
avoid the possibility of freezing. Particular atten-
tion should be paid to pipes passing through
ventilatedareas such asunder floors,loft space,
and void areas.
3A.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass.
However it may be necessary to fit an external
bypass should the design of the heating system
require such. In any case, the design of the
system should be such that it prevents boiler
‘cycling’.
3A.6.3 DRAIN COCKS
Thesemust be locatedin accessible positionsto
facilitate draining of the appliance and all water
pipes connected to the appliance.
3A.6.4 AIR RELEASE POINTS
Thesemustbepositionedatthehighestpointsin
thesystem whereairis likelytobe trapped.They
should be used to expel trapped air and allow
complete filling of the system.
3A.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel
to accommodate the increased volume of water