12
Fit the appropriate flashing plate to the roof and
insert the vertical flue terminal through the flash-
ingplatefromtheoutside,ensuringthatthecollar
on the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropri-
ate type and quantity of fixing should be used to
ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall,
mount the appliance onto the bracket.
IMPORTANT
The vertical flue terminal is 1.0 metre in length
andcannotbecut;thereforeitmaybenecessary
toadjustthe heightoftheappliance tosuitoruse
a suitable extension.
Connecttheverticalflueassemblytotheboilerflue
spigot using the 60mm & 100mm clips, gaskets &
screws (supplied), ensuring the correct seal is
made. The flue support bracket (supplied with the
vertical flue kit) can now be fitted.
If the vertical flue requires extension/s or addi-
tional bend/s, connect the required number of
flue extensions or bends (up to the maximum
equivalent flue length) between the boiler and
vertical flue assembly (see fig. 8).
Ensure that any horizontal sections of the flue
system have a minimum 1º fall back to the boiler
(17mm per 1000mm).
NOTE
Whencutting anextensiontotherequired length,
you must ensure that the excess is cut from the
plain end of the extension (see fig. 8). Remove
any burrs, and check that any seals are located
properly.
You must ensure that the entire flue system is
properly supported and connected.
4.5.3 TWIN FLUE SYSTEM
TheVokeratwinfluesystemenablesgreaterflue
distances to be achieved (see 4.4.2) than that of
a concentric flue system. It can be used for
horizontal or vertical applications, however the
twin flue system must be converted to the dedi-
cated concentric flue kit for termination. It is
essential that the installation of the twin flue
system be carried out in strict accordance with
these instructions.
GUIDANCE NOTES ON TWIN FLUE INSTAL-
LATION
●The flue must have a fall back of 1º back to the
appliancetoallowanycondensatethatmayform
in the flue system to drain via the condensate
drain. Consideration must also be given to the
factthatthereisthepossibilityofasmallamount
of condensate dripping from the terminal.
●Ensurethattheentirefluesystemisadequately
supported, use at least one bracket for each
extension.
●The entire flue system must be adequately
insulated to maintain heat within the flue sys-
temtherebyreducingthepossibilityofconden-
sate production.
●As the exhaust outlet pipe can reach very high
temperatures it must be protected to prevent
persons touching the hot surface.
●The condensate drainpipe must be connected
in accordance with local building regulations
that are in force.
MOUNTING THE BOILER
The fixing holes for the wall-mounting bracket
should now be drilled and plugged, an appropri-
ate type and quantity of fixing should be used to
ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall,
mount the appliance onto the bracket.
Part No. Description Min-Max Length
0225805 Horizontal flueterminal 1.0 metre
0225810 Verticalflue terminal 1.0metre
430 Twin adapterkit N/A
0225770 Pitched roofflashing plate N/A
0225765 Flatroof flashingplate N/A
0225815 Condensatedrain kit N/A
0225820 0.25 m extension (pair) 250 mm
0225825 0.5m extension(pair) 500mm
0225830 1.0m extension(pair) 1000mm
0225835 2.0m extension(pair) 2000mm
0225840 45ºbend (pair) N/A
0225845 90ºbend (pair) N/A
0225850 Twin bracket (5) N/A
0225855 Singlebracket(5) N/A
Twin flue accessories
Bend Reduction in maximum flue length for each bend
45ºbend 1.0 metre
90ºbend 1.0 metre
Reduction for bends
FLUE RESTRICTOR RING (vertical flue)
To ensure maximum efficiency of the appliance,
it may be necessary to fit one of the supplied
flue restrictor rings to the appliance flue outlet
(see tables below).
Total flue length Restrictor required
Lessthan 2.0 metre 82.5mmdiameter
Less than 4.0 metres 88mm diameter
Less than 5.5 metres notrequired
25
Total flue length Restrictor required
Less than 2.8 metres 84mm diameter
Less than 5.0 metres notrequired
29
Total flue length Restrictor required
Less than 2.7 metres notrequired
35
FLUE RESTRICTOR RING (vertical flue)
To ensure maximum efficiency of the appliance,
itmaybenecessary tofit oneof theflue restrictor
rings (supplied with the twin adaptor kit) to the
appliance flue outlet (see tables below).
Total flue length Restrictor required
Lessthan 7.0 metre 40mmdiameter
Lessthan 13.5metres 45mm diameter
Lessthan 19.5metres notrequired
25
Total flue length Restrictor required
Less than 5.0 metres 45mm diameter
Lessthan 12.0metres notrequired
29