Vostok VOSPAC10KWA User manual

2.9KW SMART PORTABLE
AIR CONDITIONER
(WHITE)
VOSPAC10KWA

2
Safety & Warnings
3
Components
14
Overview
15
Installation
19
Operation
26
Cleaning & Care
30
Troubleshooting
31
Notes
33

3
Warning
• Do not operate in rooms with continuously operating ignition sources (for example:
open flames, gas appliances or electric heaters).
• Do not pierce or burn this appliance.
• Be aware that refrigerants may not contain an odour.
• Appliance must be installed, operated and stored in a room with a floor area larger
than 15m2
MODEL
X(m2)
12000Btu/h, 14000, 16000Btu/h, 18000Btu/h
15
Appliance with R290 Refrigerant Gas.
• When defrosting and cleaning the appliance, do not use any tools other than those
recommended in this guide.
• Do not operate in rooms with continuously operating ignition sources (for example:
open flames, gas appliances or electric heaters).
• Do not pierce or burn this appliance.
• This appliance contains XXg (refer to rating label back of unit) of R290 refrigerant gas.
• R290 is a refrigerant gas that complies with the European directives on the
environment. Do not puncture any part of the refrigerant circuit.
• If the appliance is installed, operated, stored in an unventilated area, the room must be
designed to prevent the accumulation of refrigerant leaks resulting in a risk of fire or
explosion due to ignition of the refrigerant caused by electric heaters, stoves, other
sources of ignition.
• The appliance must be stored in such a way as to prevent any mechanical failure.
• This appliance should only be repaired by a certified tradesperson specified in the use
of flammable refrigerants. Do not dismantle or attempt any repairs yourself.
• Ducts connected to the appliance must not contain a potential ignition source.
SAFETY & WARNINGS
WARNING: Do not install or use your portable air conditioner until you
have read all safety notes and instructions. Retain this user guide for
future reference.

4
General Safety Instructions
• This appliance is for indoor use only.
• Do not use the unit on a socket under repairs or not installed properly.
• Do not use the unit:
o Near a source of fire.
o In an area where oil is likely to splash.
o In an area exposed to direct sunlight.
o In an area where water is likely to splash.
o Near a bath, a laundry, a shower or a swimming pool.
• Never insert your fingers or other objects into the ventilation openings. Ensure children
are explicitly warned to not do this.
• Ensure that the appliance is positioned upright (vertically) during both transport and
storage so that the compressor is correctly positioned.
• Always turn off the appliance before cleaning and unplug it from the wall outlet.
• Switch off the appliance before moving it and unplug it from the wall outlet. Move the
appliance slowly and carefully.
• To a v o i d t h e r i s k o f f i re , d o n o t cover the appliance.
• Do not overload the power outlet by operating the appliance simultaneously with too
many powerful electrical appliances.
• All fan connections must comply with local electrical safety regulations. If necessary,
refer to these regulations.
• If the power cord or plug is damaged, it must be replaced by the manufacturer, an
authorised specialist company or a similarly qualified person.
• Children over the age of 8 and persons with reduced physical, sensory or mental
capabilities or those with a lack of experience and knowledge may only use the
appliance if they are instructed on how to do so by a person responsible for their safety
or if they are supervised and understand the hazards associated with the use of the
appliance. Children may not clean or carry out user maintenance without supervision.
Supervise children so that they do not play with the unit.
• Never drink condensation water that leaks from the appliance.
• The appliance must be installed in accordance with national wiring regulations.
• Do not pull the power cord, deform or modify it or immerse it in water. Incorrect handling
of the power cord may result in damage to the equipment and/or electric shock.
• National gas regulations must be observed. If gas leakage should happen, open the
window for ventilation before running the appliance.
• Do not block the ventilation openings.
• Do not operate the appliance solely by inserting or removing the power plug, as this
may result in electric shock or fire due to heat.

5
• Immediately unplug the appliance from the wall outlet if it emits strange noises, odours
or smoke.
• Details of type and rating of fuses:T, 250V AC, 3.15A or higher.
• Any person who is involved with working on or breaking into a refrigerant circuit should
hold a current valid certificate from an industry-accredited assessment authority, which
authorizes their competence to handle refrigerants safely in accordance with an
industry recognized assessment specification.
• Servicing shall only be performed as recommended Kogan.com. Maintenance and
repair requiring the assistance of other skilled personnel shall be carried out under the
supervision of the person competent in the use of flammable refrigerants.
• Do not operate or stop the unit by inserting or pulling out the power plug, it may cause
electric shock or fire due to heat generation.
• In the even the unit emits strange sounds, odours or smoke, cease use immediately and
contact help.Kogan.com for support.

6
Impedance Declaration
This appliance can be connected only to a power supply with system impedance no more
than 0.381Ω. If necessary, please consult your local utility authority for system impedance
information.
REPAIR SAFETY NOTES (Professional use only)
Cabling:
Regularly check that cabling is not showing signs of wear, corrosion, excessive pressure,
vibration, sharp edges, any other adverse environmental effects. The check shall also
consider the effects of aging or continual vibration from sources such as compressors or
fans.
Detection of Flammable Refrigerants:
Under no circumstances shall potentially sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used.
Leak Detection Methods:
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants. Electronic leak detectors shall be used to detect flammable
refrigerants, but the sensitivity may not be adequate, may need recalibration. (Detection
equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a
potential source of ignition and is suitable for the refrigerant used.
Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and
shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 %
maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but
the use of detergents containing chlorine shall be avoided as the chlorine may react with
the refrigerant and corrode the copper pipework.
If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of
refrigerant is found which requires brazing, all the refrigerant shall be recovered from the
system, isolated (by means of shut off valves) in a part of the system remote from the leak.
Oxygen free nitrogen (OFN) shall then be purged through the system both before and
during the brazing process.

7
Removal and Evacuation:
When breaking into the refrigerant circuit to make repairs – or for any other purpose –
conventional procedures shall be used. However, it is important that best practice is
followed since flammability is a consideration. The following procedure shall be adhered to
remove refrigerant; purge the circuit with inert gas; evacuate; purge again with inert gas;
open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system
shall be “flushed” with OFN to render the unit safe. This process may need to be repeated
several times. Compressed air or oxygen shall not be used for this task. Flushing shall be
achieved by breaking the vacuum in the system with OFN and continuing to fill until the
working pressure is achieved, then venting to atmosphere, finally pulling down to a vacuum.
This process shall be repeated until no refrigerant is within the system.
When the final OFN charge is used, the system shall be vented down to atmospheric
pressure to enable work to take place. This operation is vital if brazing operations on the
pipework are to take place. Ensure that the outlet for the vacuum pump is not close to any
ignition sources and there is ventilation available.
Charging Procedures:
In addition to conventional charging procedures, the following requirements shall be
followed:
1. Ensure that contamination of different refrigerants does not occur when using
charging equipment. Hoses or lines shall be as short as possible to minimize the
amount of refrigerant contained in them.
2. Cylinders shall be kept upright.
3. Ensure that the refrigeration system is earthed prior to charging the system with
refrigerant.
4. Label the system when charging is complete (if not already).
5. Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system, it shall be pressure tested with OFN. The system shall be
leak tested on completion of charging but prior to commissioning. A follow up leak test shall
be carried out prior to leaving the site.

8
Decommissioning:
Before carrying out this procedure, it is essential that the technician is completely familiar
with the equipment and all its detail. It is recommended good practice that all refrigerants
are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall
be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential
that electrical power is available before the task is commenced.
• Become familiar with the equipment and its operation.
• Isolate system electrically.
• Before attempting the procedure ensure that: mechanical handling equipment is
available, if required, for handling refrigerant cylinders; all personal protective
equipment is available and being used correctly; the recovery process is always
supervised by a competent person; recovery equipment and cylinders conform to the
appropriate standards.
• Pump down refrigerant system, if possible.
• If a vacuum is not possible, make a manifold so that refrigerant can be removed from
various parts of the system.
• Make sure that cylinder is situated on the scales before recovery takes place.
• Start the recovery machine and operate in accordance with manufacturer's
instructions.
• Do not overfill cylinders. (No more than 80 % volume liquid charge).
• Do not exceed the maximum working pressure of the cylinder, even temporarily.
• When the cylinders have been filled correctly and the process completed, make sure
that the cylinders and the equipment are removed from site promptly and all isolation
valves on the equipment are closed off.
• Recovered refrigerant shall not be charged into another refrigeration system unless it
has been cleaned and checked.
Labelling:
Equipment shall be labelled stating that it has been de-commissioned and emptied of
refrigerant. The label shall be dated and signed. Ensure that there are labels on the
equipment stating the equipment contains flammable refrigerant.

9
Recovery:
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely. When transferring
refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are
employed. Ensure that the correct number of cylinders for holding the total system charge
are available. All cylinders to be used are designated for the recovered refrigerant and
labelled for that refrigerant (i.e., special cylinders for the recovery of refrigerant). Cylinders
shall be complete with pressure relief valve and associated shut-off valves in good working
order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery
occurs.
The recovery equipment shall be in good working order with a set of instructions concerning
the equipment that is at hand and shall be suitable for the recovery of flammable
refrigerants. In addition, a set of calibrated weighing scales shall be available and in good
working order. Hoses shall be complete with leak-free disconnect couplings and in good
condition. Before using the recovery machine, check that it is in satisfactory working order,
has been properly maintained and that any associated electrical components are sealed to
prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery
units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated
to an acceptable level to make certain that flammable refrigerant does not remain within
the lubricant. The evacuation process shall be carried out prior to returning the compressor
to the suppliers. Only electric heating to the compressor body shall be employed to
accelerate this process. When oil is drained from a system, it shall be carried out safely.

10
COMPETENCE OF SERVICE PERSONNEL
General:
Special training additional to usual refrigerating equipment repair procedures is required
when equipment with flammable refrigerants is affected. In many countries, this training is
carried out by national training organizations that are accredited to teach the relevant
national competency standards that may be set in legislation. The achieved competence
should be documented by a certificate.
Training:
Training should include the following:
• Information about the explosion potential of flammable refrigerants to show that
flammables may be dangerous when handled without care.
• Information about potential ignition sources, especially those that are not obvious, such
as lighters, light switches, vacuum cleaners, electric heaters.
Information about the different safety concepts:
Unventilated – Safety of the appliance does not depend on ventilation of the housing.
Switching off the appliance or opening of the housing has no significant effect on the safety.
Nevertheless, it is possible that leaking refrigerant may accumulate inside the enclosure and
flammable atmosphere will be released when the enclosure is opened.
Ventilated enclosure – Safety of the appliance depends on ventilation of the housing.
Switching off the appliance or opening of the enclosure has a significant effect on the
safety. Care should be taken to ensure a sufficient ventilation before.
Ventilated room – Safety of the appliance depends on the ventilation of the room.
Switching off the appliance or opening of the housing has no significant effect on the safety.
The ventilation of the room shall not be switched off during repair procedures. Information
about the concept of sealed components and sealed enclosures according to IEC 60079-
15:2010.
Information about the correct working procedures:
a) Commissioning
• Ensure that the floor area is sufficient for the refrigerant charge or that the ventilation
duct is assembled in a correct manner.
• Connect the pipes and carry out a leak test before charging with refrigerant.
• Check safety equipment before putting into service.

11
b) Maintenance
• Portable equipment shall be repaired outside or in a workshop specially equipped for
servicing units with flammable refrigerants.
• Ensure sufficient ventilation at the repair place.
• Be aware that malfunction of the equipment may be caused by refrigerant loss and
refrigerant leak is possible.
• Discharge capacitors in a way that won’t cause any spark. The standard procedure to
short circuit the capacitor terminals usually create sparks.
• Reassemble sealed enclosures accurately. If seals are worn, replace them.
• Check safety equipment before putting into service.
c) Repair
• Portable equipment shall be repaired outside or in a workshop specially equipped for
servicing units with flammable refrigerants.
• Ensure sufficient ventilation at the repair place.
• Be aware that malfunction of the equipment may be caused by refrigerant loss and a
refrigerant leak is possible.
• Discharge capacitors in a way that won’t cause any spark.
• When brazing is required, the following procedures shall be carried out in the right order
o Remove the refrigerant. If the recovery is not required by national regulations,
drain the refrigerant to the outside. Take care that the drained refrigerant will
not cause any danger. In doubt, one person should guard the outlet. Take
special care that drained refrigerant will not float back into the building.
o Evacuate the refrigerant circuit.
o Purge the refrigerant circuit with nitrogen for 5 min.
o Evacuate again.
o Remove parts to be replaced by cutting, not by flame.
o Purge the braze point with nitrogen during the brazing procedure.
o Carry out a leak test before charging with refrigerant.
• Reassemble sealed enclosures accurately. If seals are worn, replace them.
• Check safety equipment before putting into service.

12
d) Decommissioning
• If the safety is affected when the equipment is out of service, the refrigerant charge
shall be removed before decommissioning.
• Ensure sufficient ventilation at the equipment location.
• Be aware that malfunction of the equipment may be caused by refrigerant loss and a
refrigerant leak is possible.
• Discharge capacitors in a way that won’t cause any spark.
• Remove the refrigerant. If the recovery is not required by national regulations, drain the
refrigerant to the outside. Take care that the drained refrigerant will not cause any
danger. In doubt, one person should guard the outlet. Take special care that drained
refrigerant will not float back into the building.
• Evacuate the refrigerant circuit.
• Purge the refrigerant circuit with nitrogen for 5 min.
• Evacuate again.
• Fill with nitrogen up to atmospheric pressure.
• Put a label on the equipment that the refrigerant is removed.
e) Disposal
• Ensure sufficient ventilation at the working place.
• Remove the refrigerant. If the recovery is not required by national regulations, drain the
refrigerant to the outside. Take care that the drained refrigerant will not cause any
danger. In doubt, one person should guard the outlet. Take special care that drained
refrigerant will not float back into the building.
• Evacuate the refrigerant circuit.
• Purge the refrigerant circuit with nitrogen for 5 min.
• Evacuate again.
• Cut out the compressor and drain the oil.

13
Transportation, marking and storage for units that employ flammable refrigerants
6. Transport of equipment containing flammable refrigerants:
Attention is drawn to the fact that additional transportation regulations may exist with
respect to equipment containing flammable gas. The maximum number of pieces of
equipment or the configuration of the equipment, permitted to be transported together will
be determined by the applicable transport regulations.
7. Marking of equipment using signs:
Signs for similar appliances used in a work area generally are addressed by local regulations
and give the minimum requirements for the provision of safety and/or health signs for a
work location.
All required signs are to be maintained and employers should ensure that employees
receive suitable and sufficient instruction and training on the meaning of appropriate safety
signs and the actions that need to be taken in connection with these signs.
The effectiveness of signs should not be diminished by too many signs being placed
together. Any pictograms used should be as simple as possible and contain only essential
details.
8. Disposal of equipment using flammable refrigerants:
See national regulations.
9. Storage of equipment/appliances:
The storage of equipment should be in accordance with the manufacturer’s instructions.
Storage of packed (unsold) equipment.
Storage package protection should be constructed such that mechanical damage to the
equipment inside the package will not cause a leak of the refrigerant charge.
The maximum number of pieces of equipment permitted to be stored together will be
determined by local regulations.

14
Carefully unpack all components and ensure all accessories are included before proceeding
with installation.
Exhaust hose
Housing
adaptor
Window
connector
Remote
controller
Window fitting kit
(optional)
Dowel (x2)
(optional)
Water pipe
Batteries
(x2)
COMPONENTS

15
1
Control panel
2
Air outlet
3
Castor
4
Power cord
5
Drainage outlet
6
Air inlet
7
Exhaust hose opening
OVERVIEW

16
Control Panel
1. Full indicator
Illuminates when the water tray is full and needs to be emptied.
2. High Fan Speed indicator
Illuminates when the fan is set to high speed.
3. Low Fan Speed indicator
Illuminates when the fan is set to low speed.
4. Timer indicator
Illuminates when the timer function is enabled.
5. Cooling Mode indicator
Illuminates when the cooling function is enabled.
6. Dehumidification Mode indicator
Illuminates when the dehumidification function is enabled
7. Fan Mode indicator
Illuminates when the fan function is enabled.
8
9
10
11
12
13
14
15

17
8. Wi-Fi indicator
Indicates the connectivity status of the unit.
9. POWER button
Press this button to switch the air conditioning on and off.
10. TEMP + button
Press this button to raise the temperature.
11. TEMP - button
Press this button to lower the temperature.
12. Signal receiver
Receives signals from remote controller.
13. MODE button
Press this button to cycle through the three modes: COOL (cooling mode), FAN
and DRY (dehumidification mode).
14. SPEED button
Press this button to cycle through the two different fan speeds HIGH and LOW.
15. TIMER button
Press this button in standby mode to set the start time.
Press this button in the timer start mode to set the timer end time.

18
Remote Control
1. POWER button
Press this button to switch the air
conditioning on and off.
2. TIMER button
Press this button in standby mode to
set the start time.
Press this button in the timer start
mode to set the timer end time.
3. MODE button
Press this button to select one of the
modes: COOL (cooling mode), FAN
and DRY (dehumidification mode).
Reverse cycle model also has HEAT
(heating mode).
4. TEMP - button
Press this button to lower the
temperature.
5. TEMP + button
Press this button to raise the
temperature.
6. SPEED button
Press this button to set the fan to
high or low speed level.
7. SLEEP button
Press this button to enable sleep
mode.
8. SWING button
Press this button on the remote
control to set the swing function.
Note:
• Do not drop the remote controller.
• Do not place the remote controller in a location exposed to direct sunlight.

19
Installation position
• Place the appliance on a level surface near a window.
• Ensure the appliance is positioned a minimum distance of 30cm from walls.
• Do not install in wet location, such as the laundry room.
INSTALLATION

20
Temporary installation
1. Attach the housing adaptor and the window connector to the ends of the exhaust
hose.
2. Insert the housing adaptor into the outlet on the rear of the air conditioner, taking
care to align the clips.
3. Place the other end of the exhaust hose on the windowsill.
(Rotate clockwise)
Table of contents
Other Vostok Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Hitachi
Hitachi RAS-S18CPA installation manual

Carrier
Carrier 42QN series owner's manual

Panasonic
Panasonic S-15MK2E5B installation instructions

Thermocore Systems
Thermocore Systems T1-PACH-14 owner's manual

Haier
Haier HSU-07RS03/R2, HSU-09RS03/R2, Operation manual

Hitachi
Hitachi RAK-18PPA instruction manual

Sanyo
Sanyo SAP-K181AA Technical & service manual

Guzzanti
Guzzanti GZ-902 instruction manual

Heat Controller
Heat Controller BG-81J owner's manual

Johnson Controls
Johnson Controls DSH installation instructions

Mitsubishi Electric
Mitsubishi Electric MSZ-DM35VA MSZ-DM35VA-ER1 operating instructions

Sanyo
Sanyo KS3032 Service manual