OIMM – VENTUS PRO
to ensure proper sealing.
through working section and locked to the rewind unit.
Differential pressure switch must be installed and connected to the control panel.
along with the units.
Filters that are shipped separately in the unit should be assembled after cleaning the inner surface by operating
All coils are leak tested and checked prior to assembly. Fins are checked for proper condition. However, they
must be checked once more and combed out if necessary, because they might be damaged during handling and
installation. Do not remove plastic covers from coil pipe connections until the unit is ready for piping connectors.
Connections should be checked according to the project and the leakage should be taken in to account. System
layout should take into consideration of possible coil withdrawal.
heating coil, the hot water pump and water / steam valves should only be opened during the operation of fan.
overheating danger will occur.
Check the concentration ratio of the antifreeze before the start-up of the cooling coil. It should be enough for the
claimed operating temperature range. It should be taken in to account that the increasing concentration ratio of
the antifreeze decreases the performance of the coil.
The minimum temperature of the chilled water should be +20C, at lower temperatures freezing danger will occur.
Antifreeze is a dangerous chemical. The safety regulations of the antifreeze manufacturer should be taken in to
account.
Direct expansion coils will be supplied with a refrigerant distributor suitable for brazed connections. Refrigerant
pipe work must include necessary shut off devices, dehydrators, solenoid valves, oil traps etc. Selection, sizing,
installation and setting of thermostatic expansion valve should be in accordance with the recommendation of
condensing unit manufacturer.
Steam coils: Special care should be taken for collection and disposal of condensate within the coils and to
prevent entry of the condensate in the main into the coil by trapping it independently on a coil bypass. Condensate
connections to the stream trap must be of the same size as the coil outlet.
AIR FILTERS
COIL HEAT EXCHANGERS
3.7.3
3.7.4
!
label.
! If not otherwise stated on the capacity label, maximum operating temperature and pressure:
• for water coils (type:1) : 90ºC, 10 bar,
• for water coils (type:2) : 150ºC, 15 bar,
• for steam coils: 160ºC, 6 bar
!