4.1.1.Receiving Checklist
Complete the following checklist immediately after receiving unit shipment to detect possible shipping
damage.
Inspect individual crates before accepting.
Check for rattles, bent crates corners, or
other visible indications of shipping
damage.
If a unit appears damaged, inspect it
immediately before accepting the
shipment. Make specific notations
concerning the damage on the freight bill.
Do not refuse delivery.
Inspect the unit for concealed damage
before it is stored and as soon as possible
after delivery. Report concealed damage
to the freight line within the allotted time
after delivery. Check with the carrier for
their allotted time to submit a claim.
Do not move damaged material from the
receiving location. It is the receiver’s
responsibility to provide reasonable
evidence that concealed damage did not
occur after delivery.
Do not continue unpacking the shipment if
it appears damaged. Retain all internal
packing, cartons, and crate. Take photos
of damaged material if possible.
Notify the carrier’s terminal of the damage
immediately by phone and mail. Request
an immediate joint inspection of the
damage by the carrier and consignee.
Notify your VTS representative of the
damage and arrange for repair. Have the
carrier inspect the damage before making
any repairs to the unit.
Compare the electrical data on the unit
nameplate with the ordering and shipping
information to verify the correct unit is
received.
NOTICE! Any damages caused by
improper transportation, unloading or
storage are not covered by the Warrantee
and any claims laid by way of
aforementioned issues will not be
examined by VTS.
4.2. Installation Preparation
The Ventus Compact air-handling can be
installed as well as inside the building as the
outside. Units can be installed and work on the
external air with temperature from -40°C to
+60°C.
AHUs installed outside the building should be
equipped with roof and air intake and outlet
equipment. The unit operated outdoor should
be regularly cleaned from the snow. Such units
should have barrier for protect against the
snow, and base frame should be placed on the
level not lower than height of snow level in that
region.
In condition of the low temperatures, increase
the heat lost, what can needs more reserve of
the heating capacity of the heaters. The heat
node of the heating capacity regulation, three
way valves, water pumps, thermo-
manometers, valves, as well as frequency
converters should be placed in the room with
temperature higher than +5°C.
If the unit operate with the low inlet
temperature of the air it is recommended to
use the mixture of the glycol (up to 45%) as the
heating medium. All installation pipes of the
water heating, condensate drying, hydraulic
valves should be well isolated. The best is use
the pre-heater before the heat recovery
section.
The air damper actuators should be protected
from the atmospheric conditions. If the outdoor
temperature is lower than -20°C, the air
dampers actuators must be equipped with
heating. All equipment and components
operating outside the unit must have the
required IP.
Units, periodically stopped during periods of
low outdoor temperatures, require special
attention.
They should be equipped with an automation
system that supports the flow of the liquid
through water heaters to prevent it from
freezing during AHU downtime. If it is possible
that temperature in the fan section fall below -
30°C or lower, the sections should be
equipped with an internal heating system to
ensure reliable start of the motors after
shutdown and downtime.