Warmfloor WF TH1 User manual

TECHNICAL SPECIFICATIONS AND WARRANTY INFORMATION
Wiring Diagram:
ProbeTemperature/Values
Temp°C
Resistance
valuekΩ's
0 27.28
5 22.05
1017.96
1514.69
2012.09
25 10.00
308.31
ADVANCED PROGRAMMING OPTIONS
ADVANCED PROGRAMMING OPTIONS
FICATIONS AND WARRANTY INFORMATION
Technical Specifications:
Input voltage: 230VAC +10% 50/60Hz.
Main Heating Relay: 16amp max.
Auxiliary Heating Relay: 3amp max.
IP21 rated.
Working temperature: 0-50°C.
Storage Temperature: -25-50°C
The accuracy of temperature control +1% °C
Certification: EN60730-2-9/EN50081-1/EN50082-2 (EMC testing standard) and IEC-607-
60730-2-9
Declaration of Conformity may be downloaded from www.warmfloornz.com
Warranty:
Warmfloor warrants this product to be free from workmanship or material defects for a
period of two (2) years from the date of purchase by the consumer. Warmfloor reserves
the right to repair or provide a replacement unit at their discretion. This warranty does
not cover removal or reinstallation costs.
Please visit www.warmfloornz.com for further information relating to common consumer
questions and answers.
5. Technical Specifications and
Warranty Information
If Towel rail heating option has been selected:
Towel rail indicator icon at bottom of screen is displayed when towel rail heating is active.
To turn floor heating off and continue with towel rail heating only:
Press Power button to turn thermostat OFF
Press MODE to toggle Main floor heating from ON to OFF
Press Power button to turn thermostat ON.
If your installer has enabled the Power Indicator option
When your floor heating is running the accumulated power useage is indicated by the display
bottom right of screen.
Altering your running costs:
By changing either the heating periods or the temperature set point it is possible to alter the
running costs.
1. After running your heating for a set period of time view the power usage indicator and
record this value.
2. Alter heating periods and/or temperature set point (see installers programming guide or
visit www.warmfloornz.com.
3. Press CLEAR to reset Power Indicator
Run the heating system for the same time period again. View your power indicator to record
value again. Analyse the power differences.
Please Note: The power indicator is a feature to help best run your system cost effectively, but
is not designed for accurate power metering. This option is available for you to attain the most
economical running costs should you wish.
In some instances, depending on the climate zone, floor construction, and substrate, it may
be desirable to run your heating in the continuous manual mode with a lower temperature
set point.
More information may be available at www.warmfloornz.com
6. Other User Options
Technical Specifications:
Input voltage: 230VAC ±10% 50/60Hz.
Main Heating Relay: 16amp max.
Auxiliary Heating Relay: 3amp max.
IP21 rated.
Working temperature: 0-50°C.
Storage Temperature: -25-50°C
The accuracy of temperature control ±1°C
Certification: EN60730-2-9/EN50081-1/EN50082-2 (EMC testing standard)
and IEC-607-60730-2-9
Declaration of Conformity may be downloaded from www.warmfloornz.com
Warranty:
Warmfloor warrants this product to be free from workmanship or material defects for a period
of two (2) years from the date of purchase by the consumer. Warmfloor reserves the right to
repair or provide a replacement unit at their discretion. This warranty does not cover removal or
reinstallation costs.
Please visit www.warmfloornz.com for further information relating to common consumer
questions and answers.
Programmable Electronic
Heating Thermostat
Installers
Instruction Sheet
Code: WF TH1
For more information or for
Warmfloor technical support, please visit
Visit www.warmfloornz.com
Congratulations on choosing a Warmfloor Heating System
You may visit www.warmfloornz.com to download operating instructions and to view
common questions and answers to help you understand the operation of your thermostat.
OPERATING YOUR THERMOSTAT
Programming should have been completed before using this guide (by your installer.)
Manual Mode:
Turn Power on.
Press MODE button to select Manual icon symbol will appear.
With manual mode your floor will maintain its temperature for a 24 hour period.
Automatic Mode:
Turn Power on.
Press MODE Button to select Automatic icon symbol will appear.
With automatic mode your floor will maintain its temperature according to the heating
periods your installer has programmed.
Note: While floor is heating, the icon appears at bottom left screen.
Programme Day and Time
(WITH THERMOSTAT TURNED ON)
1. Press DAY and view displayed day. Press sor ▼arrows to set the day
2. Press HOUR and view current hour. Press sor ▼arrows to set the hour
3. Press MIN and view current minutes. Press sor ▼arrows to set the minutes
To turn off heating system:
Press power button . The OFF icon will appear.
OWNERS OPERATING INSTRUCTIONS
Congratulations of choosing a Warmfloor Heating System
You may visit www.warmfloor.co.nz to download operating instructions and to view common
questions and answers to help you understand the operation of your thermostat.
OPERATING YOUR THERMOSTAT
Programming should have been completed before using this guide (by your installer.)
Manual Mode:
Turn Power on.
Press MODE button to select Manual icon symbol will appear.
With manual mode your floor will maintain its temperature for a 24 hour period.
Automatic Mode:
Turn Power on.
Press MODE Button to select Automatic icon symbol will appear.
With automatic mode your floor will maintain its temperature according to the heating periods
your installer has programmed.
Note: While floor is heating, the icon appears at bottom left screen.
To turn off heating system:
Press power button
. The
OFF icon will appear.
Owners Operating Instructions
OWNERS OPERATING INSTRUCTIONS
Congratulations of choosing a Warmfloor Heating System
You may visit www.warmfloor.co.nz to download operating instructions and to view common
questions and answers to help you understand the operation of your thermostat
.
OPERATING YOUR THERMOSTAT
Programming should have been completed before using this guide (by your installer.)
Manual Mode:
Turn Power
on.
Press
MODE button to select Manual
icon symbol will appear.
With manual mode your floor will maintain its temperature for a 24 hour period.
Automatic Mode:
Turn Power on.
Press MODE Button to select Automatic icon symbol will appear.
With automatic mode your floor will maintain its temperature according to the heating periods
your installer has programmed.
Note: While floor is heating, the icon appears at bottom left screen.
To turn off heating system:
Press power button
. The
OFF icon will appear.

1. Press PGM button followed by MODE button (a small S symbol appears bottom of screen)
2. Press and hold DAY button until all seven days of the week are displayed
3. Press HOUR and MIN buttons to set first on period
4. Press PGM then HOUR and MIN buttons to set first off period
5. Press PGM then HOUR and MIN buttons to set second on period
6. Press PGM then HOUR and MIN buttons to set second off period
7. Press RETURN to resume normal operation.
Note: To remove a heating period press PGM until time is displayed then press CLEAR.
1. Press TEMP button
2. Press sor ▼keys to set desired temperature.
3. Press RETURN
1. Select MANUAL MODE
2. Press sor ▼keys to set desired temperature.
3. Press RETURN
This completes basic programming
INSTALLERS BASIC PROGRAMMING GUIDE
Programme Day and Time
(WITH THERMOSTAT TURNED ON)
1.
Press DAY and view displayed day. Press sor tarrows to set the day
2.
Press HOUR and view current hour. Press sor tarrows to set the hour
3.
Press MIN and view current minutes. Press sor tarrows to set the minutes
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0800 OFF
Second Heating Period 1800 ON
2130 OFF
To customize time settings
1. Press PGM (first symbol appears) to set First heat up period ON time.
2. Press and hold DAY button until all seven days of the week are displayed.
3. Press HOUR button until first heat up hour is reached
4. Press MINUTE button until first heat up minute is reached
5. Press PGM (second symbol appears) to set First heat up period OFF time.
6. Press HOUR and then MINUTE buttons as above to set first heat up period OFF
time.
7.
Press PGM. Repeat steps 3 to 6 as above to set second heating period.
8.
Press RET to exit programme
Note: If a key is not pressed when setting heat times within 20 seconds, you will need to press programme
button until you reach the heating period you wish to alter (indicated by symbol)
Programme Weekend Times
1. Press PGM.
2. Press DAY button until Saturday is displayed
3. Repeat the process (3 -8 as above) to set 1
st and 2nd heat up periods for Saturday
4. Once Saturday has been programmed press DAY to step to Sunday
and set times
as previous
5.
Press RETURN to exit program.
Note: To remove a heating period press PGM until time is displayed then press CLR.
ADVANCED PROGRAMMING OPTIONS
Alter Sensor Type
(THERMOSTAT TURNED OFF)
•Press TEMP until desired method is indicated as below:
1.
Floor Sensing
2.
Air Sensing
3.
Air Sensing with floor limiting temperature
Setting Maximum and Minimum Temperatures
(THERMOSTAT TURNED OFF)
•Press and hold WATTS button for 3 seconds
•Press MODE to toggle and view temperature
(Note 1 & 2 symbol appears at bottom of screen)
1. Floor Temperature Maximum (default setting 30°C)
2. Floor Temperature Minimum (default setting 5°C)
•Use sand tbuttons to adjust temperature settings
•Press RETURN to exit
Enable/Disable Power Indicator
(THERMOSTAT TURNED ON)
•Press WATTS button to toggle Power Indicator (displayed bottom right) to ON or OFF
•Press CLEAR to delete accumulated value
Programming Cable Size for Power Meter Function
(THERMOSTAT TURNED OFF)
•Press sand tkeys to set to closest Cable Wattage value
Note: This is for indication only to assist achieving lowest consumer running
costs (see owners operating instructions)
Reset to Default
(THERMOSTAT TURNED OFF)
•Press and hold PGM for 15 seconds (OFF flashes)
•Press RETURN within 5 seconds to reset.
To customize time settings
1. Press PGM (first symbol appears) to set First heat up period ON time.
2. Press and hold DAY button until all seven days of the week are displayed.
3. Press HOUR button until first heat up hour is reached
4. Press MINUTE button until first heat up minute is reached
5. Press PGM (second symbol appears) to set First heat up period OFF time.
6. Press HOUR and then MINUTE buttons as above to set first heat up period OFF time.
7. Press PGM. Repeat steps 3 to 6 as above to set second heating period.
8. Press RET to exit programme
Note: If a key is not pressed when setting heat times within 20 seconds, you will need to press
programme button until you reach the heating period you wish to alter (indicated by symbol)
Programme Weekend Times
1. Press PGM.
2. Press DAY button until Saturday is displayed
3. Repeat the process (3 - 8 as above) to set 1st and 2nd heat up periods for Saturday
4. Once Saturday has been programmed press DAY to step to Sunday and set times as previous
5. Press RETURN to exit program.
Note: To remove a heating period press PGM until time is displayed then press CLR.
2. Installers Basic Programming Guide continued
4. Advanced Programming Options
Alter Sensor Type
(WITH THERMOSTAT TURNED OFF)
• Press TEMP until desired method
is indicated as below:
1. Floor Sensing
2. Air Sensing
3. Air Sensing with floor
limiting temperature
Setting Maximum and Minimum Temperatures
(WITH THERMOSTAT TURNED OFF)
• Press and hold WATTS button for 3 seconds
• Press MODE to toggle and view temperature
(Note 1 & 2 symbol appears at bottom of screen)
1. Floor Temperature Maximum, adjustable from 16°C to 35°C (default setting 30°C)
2. Floor Temperature Minimum, adjustable from 5°C to 20°C (default setting 18°C)
• Use sand ▼buttons to adjust temperature settings
• Press RETURN to exit
Enable/Disable Power Indicator
(WITH THERMOSTAT TURNED ON)
• Press WATTS button to toggle Power Indicator (displayed bottom right) to ON or OFF
• Press CLEAR to delete accumulated value
Programming Cable Size for Power Meter Function
(WITH THERMOSTAT TURNED OFF)
• Press sand ▼keys to set to closest Cable Wattage value
Note: This is for indication only to assist achieving lowest consumer running costs
(see owners operating instructions)
Reset to Default
(WITH THERMOSTAT TURNED OFF)
• Press and hold PGM for
15 seconds (OFF flashes)
• Press RETURN within 5 seconds to reset.
Thermostat Lock/Unlock
• Press power button for 6 seconds to lock.
• Press return for 6 seconds to unlock.
3. Additional Installers Options
Programming Automatic Operating Times
(Factory default – all seven days)
First heat period 00:-- ON
00:-- OFF
Second Heating Period 00:-- ON
00:-- OFF
ADDITIONAL INSTALLERS OPTIONS
HEATED TOWEL RAIL
(To alter factory default on/off times)
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0900 OFF
Second Heating Period 1800 ON
2100 OFF
1. Press PGM button followed by MODE button (a small
S
symbol appears bottom of
screen)
2. Press and hold DAY button until all seven days of the week are displayed
3. Press HOUR and MIN buttons to set first on period
4. Press PGM then HOUR and MIN buttons to set first off period
5. Press PGM then HOUR and MIN buttons to set second on period
6. Press PGM then HOUR and MIN buttons to set second off period
7. Press RETURN to resume normal operation.
Note: To remove a heating period press PGM until time is displayed then press CLEAR.
Programming Temperature Set Point
Default set point 22 Deg Celsius (floor sensing)
1. Press TEMP button
2. Press
s
or
t
keys to set desired temperature.
3. Press RETURN
This completes basic programming
ADVANCED PROGRAMMING OPTIONS
INSTALLERS BASIC PROGRALLERS BASIC PROGRAMMING
GUIDE
ADDITIONAL INSTALLERS OPTIONS
HEATED TOWEL RAIL
(To alter factory default on/off times)
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0900 OFF
Second Heating Period 1800 ON
2100 OFF
1. Press PGM button followed by MODE button (a small
S
symbol appears bottom of
screen)
2. Press and hold DAY button until all seven days of the week are displayed
3. Press HOUR and MIN buttons to set first on period
4. Press PGM then HOUR and MIN buttons to set first off period
5. Press PGM then HOUR and MIN buttons to set second on period
6. Press PGM then HOUR and MIN buttons to set second off period
7. Press RETURN to resume normal operation.
Note: To remove a heating period press PGM until time is displayed then press CLEAR.
Programming Temperature Set Point
Default set point 22 Deg Celsius (floor sensing)
1. Press TEMP button
2. Press
s
or
t
keys to set desired temperature.
3. Press RETURN
This completes basic programming
ADVANCED PROGRAMMING OPTIONS
INSTALLERS BASIC PROGRALLERS BASIC PROGRAMMING
GUIDE
Programming Temperature Set Point (Auto Mode)
Default set point 24 Degrees Celsius (floor sensing)
INSTALLERS BASIC PROGRAMMING GUIDE
Programme Day and Time
(WITH THERMOSTAT TURNED ON)
1.
Press DAY and view displayed day. Press sor tarrows to set the day
2.
Press HOUR and view current hour. Press sor tarrows to set the hour
3.
Press MIN and view current minutes. Press sor tarrows to set the minutes
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0800 OFF
Second Heating Period 1800 ON
2130 OFF
To customize time settings
1. Press PGM (first symbol appears) to set First heat up period ON time.
2. Press and hold DAY button until all seven days of the week are displayed.
3. Press HOUR button until first heat up hour is reached
4. Press MINUTE button until first heat up minute is reached
5. Press PGM (second symbol appears) to set First heat up period OFF time.
6. Press HOUR and then MINUTE buttons as above to set first heat up period OFF
time.
7.
Press PGM. Repeat steps 3 to 6 as above to set second heating period.
8.
Press RET to exit programme
Note: If a key is not pressed when setting heat times within 20 seconds, you will need to press programme
button until you reach the heating period you wish to alter (indicated by symbol)
Programme Weekend Times
1. Press PGM.
2. Press DAY button until Saturday is displayed
3. Repeat the process (3 -8 as above) to set 1st and 2nd heat up periods for Saturday
4. Once Saturday has been programmed press DAY to step to Sunday
and set times
as previous
5.
Press RETURN to exit program.
Note: To remove a heating period press PGM until time is displayed then press CLR.
Programme Day and Time
(WITH THERMOSTAT TURNED ON)
1. Press DAY and view displayed day. Press sor ▼arrows to set the day
2. Press HOUR and view current hour. Press sor ▼arrows to set the hour
3. Press MIN and view current minutes. Press sor ▼arrows to set the minutes
Programming Automatic Operating Times
(Factory default – all seven days)
First heat period 0600 ON
0800 OFF
Second Heating Period 1800 ON
2130 OFF
1. Installers Basic Programming Guide
ADVANCED PROGRAMMING OPTIONS
Alter Sensor Type
(THERMOSTAT TURNED OFF)
•Press TEMP until desired method is indicated as below:
1.
Floor Sensing
2.
Air Sensing
3.
Air Sensing with floor limiting temperature
Setting Maximum and Minimum Temperatures
(THERMOSTAT TURNED OFF)
•Press and hold WATTS button for 3 seconds
•Press MODE to toggle and view temperature
(Note 1 & 2 symbol appears at bottom of screen)
1. Floor Temperature Maximum (default setting 30°C)
2. Floor Temperature Minimum (default setting 5°C)
•Use sand tbuttons to adjust temperature settings
•Press RETURN to exit
Enable/Disable Power Indicator
(THERMOSTAT TURNED ON)
•Press WATTS button to toggle Power Indicator (displayed bottom right) to ON or OFF
•Press CLEAR to delete accumulated value
Programming Cable Size for Power Meter Function
(THERMOSTAT TURNED OFF)
•Press sand tkeys to set to closest Cable Wattage value
Note: This is for indication only to assist achieving lowest consumer running
costs (see owners operating instructions)
Reset to Default
(THERMOSTAT TURNED OFF)
•Press and hold PGM for 15 seconds (OFF flashes)
•Press RETURN within 5 seconds to reset.
ADDITIONAL INSTALLERS OPTIONS
HEATED TOWEL RAIL
(To alter factory default on/off times)
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0900 OFF
Second Heating Period 1800 ON
2100 OFF
1. Press PGM button followed by MODE button (a small
S
symbol appears bottom of
screen)
2. Press and hold DAY button until all seven days of the week are displayed
3. Press HOUR and MIN buttons to set first on period
4. Press PGM then HOUR and MIN buttons to set first off period
5. Press PGM then HOUR and MIN buttons to set second on period
6. Press PGM then HOUR and MIN buttons to set second off period
7. Press RETURN to resume normal operation.
Note: To remove a heating period press PGM until time is displayed then press CLEAR.
Programming Temperature Set Point
Default set point 22 Deg Celsius (floor sensing)
1. Press TEMP button
2. Press
s
or
t
keys to set desired temperature.
3. Press RETURN
This completes basic programming
ADVANCED PROGRAMMING OPTIONS
INSTALLERS BASIC PROGRALLERS BASIC PROGRAMMING
GUIDE
Programming Temperature Set Point (Manual Mode)
Default set point 24 Degrees Celsius (floor sensing)

1. Press PGM button followed by MODE button (a small S symbol appears bottom of screen)
2. Press and hold DAY button until all seven days of the week are displayed
3. Press HOUR and MIN buttons to set first on period
4. Press PGM then HOUR and MIN buttons to set first off period
5. Press PGM then HOUR and MIN buttons to set second on period
6. Press PGM then HOUR and MIN buttons to set second off period
7. Press RETURN to resume normal operation.
Note: To remove a heating period press PGM until time is displayed then press CLEAR.
1. Press TEMP button
2. Press sor ▼keys to set desired temperature.
3. Press RETURN
1. Select MANUAL MODE
2. Press sor ▼keys to set desired temperature.
3. Press RETURN
This completes basic programming
INSTALLERS BASIC PROGRAMMING GUIDE
Programme Day and Time
(WITH THERMOSTAT TURNED ON)
1.
Press DAY and view displayed day. Press sor tarrows to set the day
2.
Press HOUR and view current hour. Press sor tarrows to set the hour
3.
Press MIN and view current minutes. Press sor tarrows to set the minutes
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0800 OFF
Second Heating Period 1800 ON
2130 OFF
To customize time settings
1. Press PGM (first symbol appears) to set First heat up period ON time.
2. Press and hold DAY button until all seven days of the week are displayed.
3. Press HOUR button until first heat up hour is reached
4. Press MINUTE button until first heat up minute is reached
5. Press PGM (second symbol appears) to set First heat up period OFF time.
6. Press HOUR and then MINUTE buttons as above to set first heat up period OFF
time.
7.
Press PGM. Repeat steps 3 to 6 as above to set second heating period.
8.
Press RET to exit programme
Note: If a key is not pressed when setting heat times within 20 seconds, you will need to press programme
button until you reach the heating period you wish to alter (indicated by symbol)
Programme Weekend Times
1. Press PGM.
2. Press DAY button until Saturday is displayed
3. Repeat the process (3 -8 as above) to set 1
st and 2nd heat up periods for Saturday
4. Once Saturday has been programmed press DAY to step to Sunday
and set times
as previous
5.
Press RETURN to exit program.
Note: To remove a heating period press PGM until time is displayed then press CLR.
ADVANCED PROGRAMMING OPTIONS
Alter Sensor Type
(THERMOSTAT TURNED OFF)
•Press TEMP until desired method is indicated as below:
1.
Floor Sensing
2.
Air Sensing
3.
Air Sensing with floor limiting temperature
Setting Maximum and Minimum Temperatures
(THERMOSTAT TURNED OFF)
•Press and hold WATTS button for 3 seconds
•Press MODE to toggle and view temperature
(Note 1 & 2 symbol appears at bottom of screen)
1. Floor Temperature Maximum (default setting 30°C)
2. Floor Temperature Minimum (default setting 5°C)
•Use sand tbuttons to adjust temperature settings
•Press RETURN to exit
Enable/Disable Power Indicator
(THERMOSTAT TURNED ON)
•Press WATTS button to toggle Power Indicator (displayed bottom right) to ON or OFF
•Press CLEAR to delete accumulated value
Programming Cable Size for Power Meter Function
(THERMOSTAT TURNED OFF)
•Press sand tkeys to set to closest Cable Wattage value
Note: This is for indication only to assist achieving lowest consumer running
costs (see owners operating instructions)
Reset to Default
(THERMOSTAT TURNED OFF)
•Press and hold PGM for 15 seconds (OFF flashes)
•Press RETURN within 5 seconds to reset.
To customize time settings
1. Press PGM (first symbol appears) to set First heat up period ON time.
2. Press and hold DAY button until all seven days of the week are displayed.
3. Press HOUR button until first heat up hour is reached
4. Press MINUTE button until first heat up minute is reached
5. Press PGM (second symbol appears) to set First heat up period OFF time.
6. Press HOUR and then MINUTE buttons as above to set first heat up period OFF time.
7. Press PGM. Repeat steps 3 to 6 as above to set second heating period.
8. Press RET to exit programme
Note: If a key is not pressed when setting heat times within 20 seconds, you will need to press
programme button until you reach the heating period you wish to alter (indicated by symbol)
Programme Weekend Times
1. Press PGM.
2. Press DAY button until Saturday is displayed
3. Repeat the process (3 - 8 as above) to set 1st and 2nd heat up periods for Saturday
4. Once Saturday has been programmed press DAY to step to Sunday and set times as previous
5. Press RETURN to exit program.
Note: To remove a heating period press PGM until time is displayed then press CLR.
2. Installers Basic Programming Guide continued
4. Advanced Programming Options
Alter Sensor Type
(WITH THERMOSTAT TURNED OFF)
• Press TEMP until desired method
is indicated as below:
1. Floor Sensing
2. Air Sensing
3. Air Sensing with floor
limiting temperature
Setting Maximum and Minimum Temperatures
(WITH THERMOSTAT TURNED OFF)
• Press and hold WATTS button for 3 seconds
• Press MODE to toggle and view temperature
(Note 1 & 2 symbol appears at bottom of screen)
1. Floor Temperature Maximum, adjustable from 16°C to 35°C (default setting 30°C)
2. Floor Temperature Minimum, adjustable from 5°C to 20°C (default setting 18°C)
• Use sand ▼buttons to adjust temperature settings
• Press RETURN to exit
Enable/Disable Power Indicator
(WITH THERMOSTAT TURNED ON)
• Press WATTS button to toggle Power Indicator (displayed bottom right) to ON or OFF
• Press CLEAR to delete accumulated value
Programming Cable Size for Power Meter Function
(WITH THERMOSTAT TURNED OFF)
• Press sand ▼keys to set to closest Cable Wattage value
Note: This is for indication only to assist achieving lowest consumer running costs
(see owners operating instructions)
Reset to Default
(WITH THERMOSTAT TURNED OFF)
• Press and hold PGM for
15 seconds (OFF flashes)
• Press RETURN within 5 seconds to reset.
Thermostat Lock/Unlock
• Press power button for 6 seconds to lock.
• Press return for 6 seconds to unlock.
3. Additional Installers Options
Programming Automatic Operating Times
(Factory default – all seven days)
First heat period 00:-- ON
00:-- OFF
Second Heating Period 00:-- ON
00:-- OFF
ADDITIONAL INSTALLERS OPTIONS
HEATED TOWEL RAIL
(To alter factory default on/off times)
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0900 OFF
Second Heating Period 1800 ON
2100 OFF
1. Press PGM button followed by MODE button (a small
S
symbol appears bottom of
screen)
2. Press and hold DAY button until all seven days of the week are displayed
3. Press HOUR and MIN buttons to set first on period
4. Press PGM then HOUR and MIN buttons to set first off period
5. Press PGM then HOUR and MIN buttons to set second on period
6. Press PGM then HOUR and MIN buttons to set second off period
7. Press RETURN to resume normal operation.
Note: To remove a heating period press PGM until time is displayed then press CLEAR.
Programming Temperature Set Point
Default set point 22 Deg Celsius (floor sensing)
1. Press TEMP button
2. Press
s
or
t
keys to set desired temperature.
3. Press RETURN
This completes basic programming
ADVANCED PROGRAMMING OPTIONS
INSTALLERS BASIC PROGRALLERS BASIC PROGRAMMING
GUIDE
ADDITIONAL INSTALLERS OPTIONS
HEATED TOWEL RAIL
(To alter factory default on/off times)
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0900 OFF
Second Heating Period 1800 ON
2100 OFF
1. Press PGM button followed by MODE button (a small
S
symbol appears bottom of
screen)
2. Press and hold DAY button until all seven days of the week are displayed
3. Press HOUR and MIN buttons to set first on period
4. Press PGM then HOUR and MIN buttons to set first off period
5. Press PGM then HOUR and MIN buttons to set second on period
6. Press PGM then HOUR and MIN buttons to set second off period
7. Press RETURN to resume normal operation.
Note: To remove a heating period press PGM until time is displayed then press CLEAR.
Programming Temperature Set Point
Default set point 22 Deg Celsius (floor sensing)
1. Press TEMP button
2. Press
s
or
t
keys to set desired temperature.
3. Press RETURN
This completes basic programming
ADVANCED PROGRAMMING OPTIONS
INSTALLERS BASIC PROGRALLERS BASIC PROGRAMMING
GUIDE
Programming Temperature Set Point (Auto Mode)
Default set point 24 Degrees Celsius (floor sensing)
INSTALLERS BASIC PROGRAMMING GUIDE
Programme Day and Time
(WITH THERMOSTAT TURNED ON)
1.
Press DAY and view displayed day. Press sor tarrows to set the day
2.
Press HOUR and view current hour. Press sor tarrows to set the hour
3.
Press MIN and view current minutes. Press sor tarrows to set the minutes
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0800 OFF
Second Heating Period 1800 ON
2130 OFF
To customize time settings
1. Press PGM (first symbol appears) to set First heat up period ON time.
2. Press and hold DAY button until all seven days of the week are displayed.
3. Press HOUR button until first heat up hour is reached
4. Press MINUTE button until first heat up minute is reached
5. Press PGM (second symbol appears) to set First heat up period OFF time.
6. Press HOUR and then MINUTE buttons as above to set first heat up period OFF
time.
7.
Press PGM. Repeat steps 3 to 6 as above to set second heating period.
8.
Press RET to exit programme
Note: If a key is not pressed when setting heat times within 20 seconds, you will need to press programme
button until you reach the heating period you wish to alter (indicated by symbol)
Programme Weekend Times
1. Press PGM.
2. Press DAY button until Saturday is displayed
3. Repeat the process (3 -8 as above) to set 1st and 2nd heat up periods for Saturday
4. Once Saturday has been programmed press DAY to step to Sunday
and set times
as previous
5.
Press RETURN to exit program.
Note: To remove a heating period press PGM until time is displayed then press CLR.
Programme Day and Time
(WITH THERMOSTAT TURNED ON)
1. Press DAY and view displayed day. Press sor ▼arrows to set the day
2. Press HOUR and view current hour. Press sor ▼arrows to set the hour
3. Press MIN and view current minutes. Press sor ▼arrows to set the minutes
Programming Automatic Operating Times
(Factory default – all seven days)
First heat period 0600 ON
0800 OFF
Second Heating Period 1800 ON
2130 OFF
1. Installers Basic Programming Guide
ADVANCED PROGRAMMING OPTIONS
Alter Sensor Type
(THERMOSTAT TURNED OFF)
•Press TEMP until desired method is indicated as below:
1.
Floor Sensing
2.
Air Sensing
3.
Air Sensing with floor limiting temperature
Setting Maximum and Minimum Temperatures
(THERMOSTAT TURNED OFF)
•Press and hold WATTS button for 3 seconds
•Press MODE to toggle and view temperature
(Note 1 & 2 symbol appears at bottom of screen)
1. Floor Temperature Maximum (default setting 30°C)
2. Floor Temperature Minimum (default setting 5°C)
•Use sand tbuttons to adjust temperature settings
•Press RETURN to exit
Enable/Disable Power Indicator
(THERMOSTAT TURNED ON)
•Press WATTS button to toggle Power Indicator (displayed bottom right) to ON or OFF
•Press CLEAR to delete accumulated value
Programming Cable Size for Power Meter Function
(THERMOSTAT TURNED OFF)
•Press sand tkeys to set to closest Cable Wattage value
Note: This is for indication only to assist achieving lowest consumer running
costs (see owners operating instructions)
Reset to Default
(THERMOSTAT TURNED OFF)
•Press and hold PGM for 15 seconds (OFF flashes)
•Press RETURN within 5 seconds to reset.
ADDITIONAL INSTALLERS OPTIONS
HEATED TOWEL RAIL
(To alter factory default on/off times)
Programming Automatic Operating Times
(Factory default –all seven days)
First heat period 0600 ON
0900 OFF
Second Heating Period 1800 ON
2100 OFF
1. Press PGM button followed by MODE button (a small
S
symbol appears bottom of
screen)
2. Press and hold DAY button until all seven days of the week are displayed
3. Press HOUR and MIN buttons to set first on period
4. Press PGM then HOUR and MIN buttons to set first off period
5. Press PGM then HOUR and MIN buttons to set second on period
6. Press PGM then HOUR and MIN buttons to set second off period
7. Press RETURN to resume normal operation.
Note: To remove a heating period press PGM until time is displayed then press CLEAR.
Programming Temperature Set Point
Default set point 22 Deg Celsius (floor sensing)
1. Press TEMP button
2. Press
s
or
t
keys to set desired temperature.
3. Press RETURN
This completes basic programming
ADVANCED PROGRAMMING OPTIONS
INSTALLERS BASIC PROGRALLERS BASIC PROGRAMMING
GUIDE
Programming Temperature Set Point (Manual Mode)
Default set point 24 Degrees Celsius (floor sensing)

TECHNICAL SPECIFICATIONS AND WARRANTY INFORMATION
Wiring Diagram:
ProbeTemperature/Values
Temp°C
Resistance
valuekΩ's
0 27.28
5 22.05
1017.96
1514.69
2012.09
25 10.00
308.31
ADVANCED PROGRAMMING OPTIONS
ADVANCED PROGRAMMING OPTIONS
FICATIONS AND WARRANTY INFORMATION
Technical Specifications:
Input voltage: 230VAC +10% 50/60Hz.
Main Heating Relay: 16amp max.
Auxiliary Heating Relay: 3amp max.
IP21 rated.
Working temperature: 0-50°C.
Storage Temperature: -25-50°C
The accuracy of temperature control +1% °C
Certification: EN60730-2-9/EN50081-1/EN50082-2 (EMC testing standard) and IEC-607-
60730-2-9
Declaration of Conformity may be downloaded from www.warmfloornz.com
Warranty:
Warmfloor warrants this product to be free from workmanship or material defects for a
period of two (2) years from the date of purchase by the consumer. Warmfloor reserves
the right to repair or provide a replacement unit at their discretion. This warranty does
not cover removal or reinstallation costs.
Please visit www.warmfloornz.com for further information relating to common consumer
questions and answers.
5. Technical Specifications and
Warranty Information
If Towel rail heating option has been selected:
Towel rail indicator icon at bottom of screen is displayed when towel rail heating is active.
To turn floor heating off and continue with towel rail heating only:
Press Power button to turn thermostat OFF
Press MODE to toggle Main floor heating from ON to OFF
Press Power button to turn thermostat ON.
If your installer has enabled the Power Indicator option
When your floor heating is running the accumulated power useage is indicated by the display
bottom right of screen.
Altering your running costs:
By changing either the heating periods or the temperature set point it is possible to alter the
running costs.
1. After running your heating for a set period of time view the power usage indicator and
record this value.
2. Alter heating periods and/or temperature set point (see installers programming guide or
visit www.warmfloornz.com.
3. Press CLEAR to reset Power Indicator
Run the heating system for the same time period again. View your power indicator to record
value again. Analyse the power differences.
Please Note: The power indicator is a feature to help best run your system cost effectively, but
is not designed for accurate power metering. This option is available for you to attain the most
economical running costs should you wish.
In some instances, depending on the climate zone, floor construction, and substrate, it may
be desirable to run your heating in the continuous manual mode with a lower temperature
set point.
More information may be available at www.warmfloornz.com
6. Other User Options
Technical Specifications:
Input voltage: 230VAC ±10% 50/60Hz.
Main Heating Relay: 16amp max.
Auxiliary Heating Relay: 3amp max.
IP21 rated.
Working temperature: 0-50°C.
Storage Temperature: -25-50°C
The accuracy of temperature control ±1°C
Certification: EN60730-2-9/EN50081-1/EN50082-2 (EMC testing standard)
and IEC-607-60730-2-9
Declaration of Conformity may be downloaded from www.warmfloornz.com
Warranty:
Warmfloor warrants this product to be free from workmanship or material defects for a period
of two (2) years from the date of purchase by the consumer. Warmfloor reserves the right to
repair or provide a replacement unit at their discretion. This warranty does not cover removal or
reinstallation costs.
Please visit www.warmfloornz.com for further information relating to common consumer
questions and answers.
Programmable Electronic
Heating Thermostat
Installers
Instruction Sheet
Code: WF TH1
For more information or for
Warmfloor technical support, please visit
Visit www.warmfloornz.com
Congratulations on choosing a Warmfloor Heating System
You may visit www.warmfloornz.com to download operating instructions and to view
common questions and answers to help you understand the operation of your thermostat.
OPERATING YOUR THERMOSTAT
Programming should have been completed before using this guide (by your installer.)
Manual Mode:
Turn Power on.
Press MODE button to select Manual icon symbol will appear.
With manual mode your floor will maintain its temperature for a 24 hour period.
Automatic Mode:
Turn Power on.
Press MODE Button to select Automatic icon symbol will appear.
With automatic mode your floor will maintain its temperature according to the heating
periods your installer has programmed.
Note: While floor is heating, the icon appears at bottom left screen.
Programme Day and Time
(WITH THERMOSTAT TURNED ON)
1. Press DAY and view displayed day. Press sor ▼arrows to set the day
2. Press HOUR and view current hour. Press sor ▼arrows to set the hour
3. Press MIN and view current minutes. Press sor ▼arrows to set the minutes
To turn off heating system:
Press power button . The OFF icon will appear.
OWNERS OPERATING INSTRUCTIONS
Congratulations of choosing a Warmfloor Heating System
You may visit www.warmfloor.co.nz to download operating instructions and to view common
questions and answers to help you understand the operation of your thermostat.
OPERATING YOUR THERMOSTAT
Programming should have been completed before using this guide (by your installer.)
Manual Mode:
Turn Power on.
Press MODE button to select Manual icon symbol will appear.
With manual mode your floor will maintain its temperature for a 24 hour period.
Automatic Mode:
Turn Power on.
Press MODE Button to select Automatic icon symbol will appear.
With automatic mode your floor will maintain its temperature according to the heating periods
your installer has programmed.
Note: While floor is heating, the icon appears at bottom left screen.
To turn off heating system:
Press power button
. The
OFF icon will appear.
Owners Operating Instructions
OWNERS OPERATING INSTRUCTIONS
Congratulations of choosing a Warmfloor Heating System
You may visit www.warmfloor.co.nz to download operating instructions and to view common
questions and answers to help you understand the operation of your thermostat
.
OPERATING YOUR THERMOSTAT
Programming should have been completed before using this guide (by your installer.)
Manual Mode:
Turn Power
on.
Press
MODE button to select Manual
icon symbol will appear.
With manual mode your floor will maintain its temperature for a 24 hour period.
Automatic Mode:
Turn Power on.
Press MODE Button to select Automatic icon symbol will appear.
With automatic mode your floor will maintain its temperature according to the heating periods
your installer has programmed.
Note: While floor is heating, the icon appears at bottom left screen.
To turn off heating system:
Press power button
. The
OFF icon will appear.
Table of contents
Popular Thermostat manuals by other brands

ritetemp
ritetemp 8045 Operation guide

Computherm
Computherm q3rf operating instructions

Neptronic
Neptronic EVCB14NIT2S Specification and installation instructions

Carel
Carel ir33 smart operating instructions

SBC
SBC Q.RCU-A Series Hardware installation guide

Honeywell
Honeywell TRADELINE T874 quick start guide

Honeywell Home
Honeywell Home evohome THR092 quick start guide

Bryant
Bryant LEGACY T2-PAC installation instructions

Moehlenhoff
Moehlenhoff Standard manual

Johnson Controls
Johnson Controls TCN-890x Specifications

Salus
Salus VS20WRF Installer's/user's manual

Honeywell
Honeywell Lyric Round TH8732WFH-5002/U Professional install guide