Westell Virtual Edge VE-2400 User manual

Section VE1-200-20A
R
Equipment Issue A
030-101556 Rev. C, October 2007
0710IARC
ECopyright 2007 Westell, Inc. All rights reserved.
Westellris a registered trademark and VirtualEdgetis a trademark of Westell, Inc. Page 1 of 6
VE-1200 and VE-2400 Series of VirtualEdgetConnectivity Panels
PART # PAGE #
1. GENERAL 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. INSTALLATION 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. ACCESSORIES 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. CUSTOMER & TECHNICAL SERVICES 5. . . . . . . . .
5. WARRANTY & REPAIRS 5. . . . . . . . . . . . . . . . . . . . . . .
6. SPECIFICATIONS 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. GENERAL
1.1 Document Purpose
This practice describes Westell’s VirtualEdgetConnectivity
Panels, models VE-1200, VE-1212, VE-2400, VE-2424,
VE-2424BNC, and VE-2424SC, shown in Figure 1.
- NOTE -
Hereafter, the WestellrVirtualEdge Connectivity Panels may be
commonly referred to as the panel." The specific model num-
bers will be used where differences apply.
1.2 Document Status
Whenever this practice is updated, the reason will be stated in
this paragraph. Revision C of this practice adds models
VE-2424BNC and VE-2424SC. Revision B added Part 3,
Figure 5, and Figure 6, and updated Paragraph 1.5 and Table 2.
1.3 Product Purpose and Description
The VirtualEdge (VE) connectivity panels are 12-position or
24-position interface panels that are used by the Telco to termi-
nate any 10Base-T, 100Base-T, fiber, or COAX services (or a
combination thereof, or any other services) typically at the CPE
point of demarcation. The service terminated is determined by
the coupler type selected to occupy any one or all of the 12 or 24
positions. The 24-position VE-2424BNC panels come equipped
with BNC couplers (for DS3 services), the 24-position
VE-2424SC panels come equipped with SC couplers (for fiber
services), and the 12-position VE-1212 and 24-position
VE-2424 panels come equipped with CAT 5e couplers for
Ethernet services. The 12-position VE-1200 and 24-position
VE-2400 panels are empty, allowing a variety of individual ter-
minations to be installed in one panel, as needed by the
application or customer. Westell offers a variety of couplers and
cables as orderable options for terminating other services (see
Table 2). A circuit or position designation strip, numbered 1-12
or 1-24, depending on the model ordered, allows installers to
mark the physical position of the circuits terminated at the front
panel. The strip’s magnetic backing allows the installer to easily
remove or position the strip when marking or erasing circuit
numbers during an installation.
VE-1212
(12 positions with
CAT 5e couplers)
Figure 1. Isometric Views of VirtualEdge Connectivity Panel
s
VE-1200
VE-2400
(12 empty positions)
(24 empty positions)
VE-2424
(24 positions with
CAT 5e couplers)
VE-2424BNC
(24 positions with
BNC couplers)
VE-2424SC
(24 positions with
SC couplers)

Section VE1-200-20A 030-101556 Rev. C R
20710IARC
1.4 Product Mounting
The panels can be rack or wall mounted. The included mounting
ears come factory-installed on the panel for flush-mounting in
23" relay racks, but can be easily detached and reversed for 19"
relay racks, or flipped and repositioned at the back of the panel
for wall-mounting. These versatile ears also can be installed in
a ‘set-back’ position on the panel, giving the panel a projected
appearance, and the versatile ears have pre-drilled holes for
mounting in standard EIA racks.
1.5 Applications
1.5.1 To enable a greater variety of service and interface of-
ferings, service providers are putting more fiber into customer
premises, via either Fiber-to-the-Premise or placing more fiber
multiplexers and IP aggregation devices closer to subscribers. In
business markets, the strong demand for Transparent LAN and
Virtual Private Network services, where the customer’s LAN is
extended over the Service Provider Network to provide native
Ethernet service, creates numerous applications for Westell’s
VirtualEdge Enclosure Series.
1.5.2 The panels are intended to be simple, sturdy, and ver-
satile mechanical platforms used to terminate high-speed
Ethernet services in any combination(s). Additional interfaces
can also be installed on a per-circuit basis.
1.6 Product Features
The VirtualEdge connectivity panels offer the following fea-
tures.
DTerminates any combination of 10/100Base-T, fiber, COAX
or other services
DMounts on wall or in 19" or 23" relay racks or data cabinets
DOccupies only 1 RU (12-position models) or 2 RUs
(24-position models)
DAdjustable, reversible mounting ears
DStandard BNC couplers
DStandard SC couplers for optical services (accepts optional
LC couplers)
DStandard RJ45/RJ48/CAT5e couplers for Ethernet and T1
services
DEmpty positions/inserts for a variety of individual termina-
tions (VE-1200 and VE-2400 models only)
DMagnetic and removable front-panel, circuit-designation
strip for easy installation and circuit identification
DGround lug
DSteel construction (panel and ears)
DRear steel tray provides cable support and cable tie-downs
for cables coming from the Network/Telco
DRack mounting hardware included
DOptional couplers, cable management tray, cable manage-
ment D-rings, and combination kits available (see Table 2)
2. INSTALLATION
- PRECAUTIONARY STATEMENT -
Never install telephone wiring during a lightning storm.
Never install telephone jacks in wet locations unless the jack
is specifically designed for wet locations.
Never touch uninsulated telephone wires or terminals unless
the telephone line has been disconnected at the network
interface.
Use caution when installing or modifying telephone lines.
- INSPECTION NOTE -
Visually inspect the unit for damages prior to installation. If the
equipment has been damaged in transit, immediately report the
extent of the damage to the transportation company and to West-
ell (see Part 4 for telephone number).
The VirtualEdge panels can be mounted on a wall or in 19" or
23" relay racks with standard EIA 1.75" hole spacing. When rack
mounting, the panel can be installed so the front of it is flush with
the front of the rack, or mounted in a projected position in the
rack. The following paragraphs and Figure 2 provide further de-
tails. Screws to attach the mounting ears to the panel are
provided, as well as screws to mount the panel to a rack.
2.1 Mounting in a 23" Rack
The panels are shipped from the factory pre-assembled with the
mounting ears already attached to the panels in a flush-mount
position for quick and easy installation in a 23" Telco relay rack.
Each panel is equipped with an L-shaped mounting ear. For 23"
rack mounting, the mounting ear’s long flange attaches to the
rack channel.
1. Determine the vertical mounting location in the rack. The
12-position/coupler panels require one vertical Rack Unit
(RU) in a standard Telco relay rack, and the 24-position/
coupler panels require two RUs. Skip the next step if
flush-mounting is desired.
2. If a projected look or orientation in the rack is desired, re-
move the ears from the panel and re-attach them further
back on the panel’s side flange, so that the panel is projected
further forward from the mounting ears. The mounting ears
and the panel’s side flanges have several mounting holes
from which to choose, for the desired amount of projection
in the rack.
3. Once the mounting ears are attached to the panel in the de-
sired orientation or shelf-projection positioning, attach the
long flange of the ears to the rack channels with the screws
provided.
2.2 Mounting in a 19" Rack
The mounting ears can be removed, adjusted, and re-attached
for 19" rack installations.
1. Determine the vertical mounting location in the rack. The
12-position/coupler panels require one vertical Rack Unit
(RU) in a standard Telco relay rack, and the 24-position/
coupler panels require two RUs.
2. Remove the mounting ears from the factory-assembled
panel. Flip and rotate the ears and re-attach them to the

Section VE1-200-20A
030-101556 Rev. C
R
3
0710IARC
Figure 2. Mounting Views of the 12-Position Connectivity Panel
19" Rack Mounting
23" Flush Rack Mounting
Wall Mounting
Attach short ear flange to rack channel
Attach panel to ears
D
D
Attach long ear flange to rack channel
D
Attach panel to ears
D
Attach ears to panel, as shown
D
Mark and pre-drill mounting holes in wall*
D
(brackets reversed/flipped)
Attach panel to wall
D
(Use keyhole-shaped holes)
* Can be mounted vertically, if desired.
Panel is flush against front face of channel**
Long
Flange
(use keyhole-shaped holes)
of Ear
Coupler
(Always insert from the rear, tab up) Short
Flange
of Ear
**For a "projected" appearance, bring or mount the panel further
forward on the ears.
{
{Panel comes factory-shipped with ears attached for 23" rack mounting
panel so the long flange of the ears abuts or is up against the
panels’ side flanges, using the screws provided. If a project-
ed look or orientation in the rack is desired, attach the
mounting ears further back on panels’ side flanges. Several
holes are provided for a choice of projection.
3. Next, lift and place the re-assembled panel between the two
rack channels, attaching the short flanges of the mounting
ears to the rack with the screws provided.
2.3 Mounting on a Wall
The mounting ears can be removed, adjusted and re-attached
for wall mounting.
1. Determine the mounting location on the wall. The 24-posi-
tion/coupler panels require more vertical space than the
12-position panels. In addition, the panels can be mounted
in a vertical position, if desired.
2. Remove the ears from the factory-assembled panel. Re-ori-
ent and re-attach the ears to the panel so the short flange
of the ears will be flush against the wall and the long ear
flange abuts or connects to the side wall of the panel.
3. Next, lift and place the re-assembled panel on the wall in the
desired final position and mark the mounting holes to be
drilled in the wall with a marking utensil.
4. Set aside the panel and drill the holes. Do not make the
holes too big.
5. Again lift the panel and align the holes in the mounting ears
with the drilled holes in the wall, then insert and tighten the
mounting screws (not provided).
- GROUNDING NOTE -
Always follow local safety precautions and standard operating proce-
dures for grounding the equipment when installing, upgrading, repairing
or maintaining equipment. Any instructions or information contained
herein is subordinate to local codes, operating procedures or practices.
2.4 Making Ground Connections
2.4.1 The Westell VE panels are shipped from the factory
with a ground lug capable of accepting #6 ground wire for wall-
mount applications. The installer should remove the
factory-installed hex-nut and washer from the post on the rear
of the panel and install the provided ground lug to this post, un-
der the washer and the hex-nut. Make the ground connection to
the ground lug using a #6 ground wire and then ground the panel
to an earth ground or according to local installation procedures
for grounding and bonding Network equipment.
2.4.2 If the VE panel is installed in a relay rack, the #6
ground lug is not required, but a bond wire may be used to con-
nect the VE panel’s chassis to the common ground or bond for
the relay rack or cabinet, per local procedures.
2.5 Making Installer Connections
After the panel is mounted, installer connections can be made
to the panel. The VE-1212, VE-2424, VE-2424BNC, and
VE-2424SC models come equipped with couplers pre-installed.

Section VE1-200-20A 030-101556 Rev. C R
40710IARC
Figure 3. Inserting Couplers into VE-1200/2400 Panels
Insert coupler from
the rear of the panel.
Depress tab and
insert into hole until
it snaps/locks into place.
Panels accept a variety of couplers, including LC, SC, BNC, and Cat5e. See Table 2.
To install couplers of a different type or to install couplers on the
VE-1200 and VE-2400 models, see Paragraph 2.5.1 below.
- CAUTION -
Use care when installing and removing couplers - do not force
into place. If a coupler resists insertion, remove it and check
for debris in or near the coupler or hole. Then gently re-insert
the coupler.
2.5.1 Installing Couplers (VE-1200 & VE-2400 models only)
The VE-1200 and VE-2400 models come without couplers
installed in the panel (the positions are empty), to enable the
technician to install the coupler(s) of choice, depending on the
application or service desired. Follow the steps below to insert
the coupler(s) of choice.
1. Call Westell to order the coupler(s) of choice for the ap-
plication (see Table 2).
2. Insert the coupler of choice from the rear of the panel and
orient the coupler in the proper position before insertion.
Each coupler has a top tab (similar to a phone plug) and a
front and rear connector of identical service type and gen-
der. The coupler should be inserted from the rear of the
panel halfway through and into the hole or space provided.
The top tab should face up and must be depressed while
gently but firmly inserting the coupler into the hole, then re-
leased when it snaps into place, for a firm fit. In this final
position, the tab remains on the back side of the panel, for
a clean front-panel appearance.
2.5.2 Connecting Network/Telco Cables
Network/Telco connections are made to the connector at the
back of the installed coupler(s), at the back of the panel on all
models. Figure 4 shows both a BNC and SC coupler, 24 of which
are provided with the VE-2424BNC and VE-2424SC models,
respectively.
1. Remove the protective connector insert or cover from the
back of the coupler in the first coupler position.
2. Run the cable of choice to the first coupler and insert the
cable’s connector into the back of the coupler.
Figure 4. Pre-installed Couplers in VE-2424 Panels
Make Customer cable connections at the front of the panel, Network at the rear.
SC coupler
BNC coupler
VE-2424BNC
VE-2424SC
Couplers are factory-installed on models VE-1212, VE-2424, VE-2424BNC, and VE-2424SC.
(cap removed)
(cap removed)
3. Leave enough cable slack so as not to strain the cable, then
use a cable tie (provided) to secure the cable to the cable tie-
down provided near the coupler hole on the rear shelf of the
panel.
4. Repeat for each coupler. Excess cable can be routed to ei-
ther or both sides for neat cable management.
If using a VE-1212, VE-2424, VE-2424BNC, or VE-2424SC
panel (fully-loaded with couplers in each position), the installer
can connect the appropriate service-type connectorized cable to
any desired circuit position and route the cable to the Network
equipment. When the Network equipment is activated, signals
from the Network equipment should be present at the VE front
panel where the end-user or customer equipment can be con-
nected.
2.5.3 Connecting End-User or Customer Cables
Customer connections are made to the connector at the front of
coupler(s), at the front of the panel.
1. Remove the protective connector insert or cover from the
front of the coupler in the first coupler position.
2. Run the cable of choice to the first coupler and insert the
cable’s connector into the front of the coupler.
3. Repeat for each coupler.
2.5.4 Labelling Circuit Positions
A detachable, magnetic-backed, circuit-position label is pro-
vided for indicating and identifying each circuit or position. The
magnetic backing allows this label to be removed for easier
marking or writing on a larger horizontal surface, then re-at-
tached for quick and easy future reference.

Section VE1-200-20A
030-101556 Rev. C
R
5
0710IARC
3. ACCESSORIES
3.1 Couplers
Westell’s VirtualEdge panel accepts multiple coupler types that
can be used or interchanged within the panel(s), including LC
type fiber couplers. Couplers can be purchased separately using
the part numbers shown in Table 2.
3.2 Cable Management Tray
To facilitate cable management at the front of the panel(s),
Westell offers a metallic Cable Management Tray (Figure 5).
This tray attaches to the panels as shown in Figure 5. The tray is
designed to allow jumpers and cables to cross in front of the pan-
el without putting unnecessary downward force or strain on the
couplers, when installed. The tray also has bridge-forms or cable
ties to allow technicians to dress cables to the tray, if desired. The
tray can be mounted to the panels at two different depths to al-
low customization based on the amount of cables and jumpers
running across the panels. Use alone or with one or more D-
rings described in Paragraph 3.3 for a customized, cable
management solution.
3.3 Cable Management D-Rings
Optional, metallic D-rings (Figure 6), installed at either or both
ends of a VirtualEdge panel, provides guidance and support of
the cables that run across the front of the panel to the couplers.
A diagonal slit in the front of the ring allows existing or newly-
installed cables/jumpers to be easily inserted into the ring,
without re-feeding or re-routing, and the 3" ring depth easily ac-
commodates up to 24 or more cables. Use one or more D-rings
alone or with the tray described in Paragraph 3.2 for a custom-
ized cable-management solution.
3.4 24-Position Panel Kits
Kits which contain two D-rings, a cable management tray, and
a 24-position panel equipped with either BNC or SC-type cou-
plers are available from Westell. If desired, the factory-installed
couplers in these kits can be replaced with other coupler types,
such as LC couplers. See Table 2 for ordering information.
4. CUSTOMER & TECHNICAL SERVICES
4.1 Customer Service & Technical Assistance
If technical or customer assistance is required, contact Westell
by calling or using one of the following options:
Voice: (800) 377-8766
email: [email protected]
Visit the Westell World Wide Web site at http://www.Westell.com
for additional information about Westell.
4.2 Part Numbers
This equipment is identified by a product number
(A90-VE1200), which consists of three parts: the issue letter of
the equipment (A), the assembly type (90), and the specific mod-
el number (VE1200). Each time a change is made to the product
which changes the form, fit, or function of the product, the issue
letter is incremented or advanced by one. Be sure to indicate the
issue level as well as the model number when making inquiries
about the equipment.
5. WARRANTY & REPAIRS
5.1 Warranty
Westell warrants this product to be free of defects at the time of
shipment. Westell also warrants this product to be fully function-
al for the time period specified by the terms and conditions
governing the sale of the product. Any attempt to repair or
1. Decide which holes in the panel ear to use to mount the tray; this will
determine the tray depth or projection from the front of the panel.
2. Align the tray’s mounting tab hole(s) with the corresponding panel
ear hole(s) and insert provided screws, from the
outside, through the tray’s tab hole and through
the panel’s ear hole. Tighten screw.
3. Place cables on the tray in the desired
arrangement and secure with cable
ties to the cable
tie−downs.
Tray
Flange with
hole for mounting
to panel’s ear
Screw
Panel Mounting Ear
Cable tie-down
Attach to
ear
here
Figure 5. Installing Cable Management Tray to the Panel
side of
Figure 6. Installing Cable Management D-Rings to the Panel
D-ring
D-ring also
can be mounted
here
1. Decide which set of holes in the panel ear to use
to mount the D-ring.
2. Insert the provided peg/insert into the bottom hole
of the D-ring; this will prevent circular rotation of
the D-ring when installed.
3. Align top D-ring hole(s) with corresponding panel
ear hole(s) and insert provided screw, from the
back side, through the panel ear hole and through
the top hole of the D-ring. Tighten screw.
4. Route cables through slit in the front side of the D-
ring.
Insert peg here
(provides rotational stability)
Slit for
cable access
Panel Mounting Ear

Section VE1-200-20A 030-101556 Rev. C R
60710IARC
modify the equipment by anyone other than an authorized Wes-
tell representative will void the warranty.
5.2 Repair and Return
Westell will repair or replace any defective Westell equipment
without cost during the warranty period if the unit is defective
for any reason other than abuse, improper use, or improper
installation. Before returning the defective equipment, first re-
quest a Return Material Authorization (RMA) number from
Westell. Once an RMA number is obtained, return the defective
unit, freight prepaid, along with a brief problem description, to:
Westell, Inc.
ATTN: R.G.M. Department
750 N. Commons Drive
Aurora, IL 60504-7940
Replacements will be shipped in the fastest manner consistent
with the urgency of the situation. Westell will continue to repair
or replace faulty equipment beyond the warranty period for a
nominal charge. Contact Westell for details.
6. SPECIFICATIONS
6.1 Physical Specifications
The physical specifications are shown in Table 1.
6.2 Ordering Specifications
To order units, call the telephone number shown in Paragraph
4.1 and please specify a specific part number shown in Table 2.
All Models U.S. Metric
Width, w/o ears 15.5 inches 39.4 cm
Width, w/ears 19 or 23 inches 48.3 or 58.4 cm
Depth, minimum 4 inches 10.2 cm
Depth, maximum 6 inches 15.2 cm
Operating Temp. -40°to 149°F -40°to 65°C
Humidity 0 to 95% (non-condensing)
VE-1200/1212 U.S. Metric
Height 1.75 inches (1 RU) 4.45 cm
Weight (VE-1200) 25 ounces 709 g
Weight (VE-1212) 33.5 ounces 950 g
VE-2400/2424 U.S. Metric
Height 3.5 inches (2 RU) 8.9 cm
Weight (VE-2400) 30.5 ounces 865 g
Weight (VE-2424) 47.4 ounces 1344 g
Table 1. Physical Specifications
Part # Description
A90-VE1200 Model VE-1200 − 12-position, 1 RU high, VirtualEdge
Connectivity Panel with 12 empty coupler termination
positions.
A90-VE1212 Model VE-1212 − Same as VE-1200 but equipped with
12 CAT 5e couplers.
A90-VE2400 Model VE-2400 − 24-position, 2 RU high, VirtualEdge
Connectivity Panel with 24 empty coupler termination
positions.
A90-VE2424 Model VE-2424 − Same as VE-2400 but equipped with
24 CAT 5e couplers.
A90-VE2424BNC Model VE-2424BNC − Same as VE-2424 but equipped
with 24 BNC couplers.
A90-VE2424SC Model VE-2424SC − Same as VE-2424 but equipped
with 24 SC couplers.
Panel Accessories and Options*
A90-VECMTRAY Cable management tray (front projection)
A90-VECMRING3 Cable management
D-ring (Qty = 1)
A90-VECPL5E10 CAT 5e Keystone style
coupler (Qty = 10)
A90-VECPL5EIDC10 CAT 5e coupler with IDC termination on Network side
(Qty = 10)
A90-VECPLBNC10 BNC COAX coupler
(Qty = 10)
A90-VECPLSC1 Fiber coupler with SC
connectors (Qty = 1)
A90-VECPLLC1 Fiber coupler with LC
connectors (Qty = 1)
A90-VEBLNK100 Blank Inserts (100 per package)
A99-VE2424BNC Kit which contains a 24-position panel, 24 BNC
couplers, a cable management tray, 2 D-rings, kit
assembly hardware, and rack mounting hardware.
A99-VE2424SC Same as A99-VE2424BNC but with SC couplers.
*A variety of cables and fiber jumpers also are available. Call Westell for details.
Table 2. Ordering and Option Information
This manual suits for next models
1
Table of contents