GENERAL INFORMATION
1) A qualified electrician, in accordance with IEE wiring regulations should carry out connection
to mains wiring.
2) Ensure that the rated voltage and frequency requirements are compatible with the available
mains supply.
3) Do not carry out high voltage insulation test, i.e. 500/1000v this may damage internal
components.
SPECIFICATION
 9 Port LCM (3 separate groups)
 3 Switch Inputs (latching or retractive switches)
 3 Sensor Inputs (occupancy, absence, presence & constant lux control)
 2 x DALI modes - DALI auto addressing (Broadcast) / DALI Addressable (individual addressing)
 Integral emergency testing and reporting (via smart device app or switch input)
 Corridor Linking
 Bluetooth 4.2 networking Auto discoverable; password security.
 Bluetooth programming via free app (Android & iOS)
TECHNICAL DATA
 Operating Temperature: 0°C to +40°C
 Mains supply: 230Vac +/- 10%; 50Hz
 Mains input: Male socket for Wieland GST18i3 (Black) female connection
 Maximum output per LCM: 6.3A (internally fused) (1450W or 160W per port)
 Isolation: 4kV between mains and sensors control
 Inrush current: 1s time delay between group outputs at power-up
 In-rush current rating of relays: 6.3A
 Output connections:
o Wieland GST18i6 (Blue / Black) x 2
o GST18i5 (Blue) x 7
 Maximum DALI dimming load: 100mA (or 16 DALI devices)
 Sensor inputs: RJ11 connection for 3 sensors (VERVERECPIR / VERVESURPIR)
 Sensor supply: 12Vdc +/- 5%, 30mA
 Switch inputs: 3 pole 5mm pitch plug (0.5 to 2.5mm²)
 Switch input cable: max. 10m; segregated from mains
 Max distance between hubs: 8m
 Max no of hubs: 20 per cluster; multiple clusters
 PC/ABS housing
 Dimensions: 250mm() x 47.5mm(h)
Verve
VERVE
MAY 2021 – Rev 7
Mounting:
ONLY mount in a horizontal orientation
Label MUST face towards the floor
DO NOT vertically mount the hub
Mechanical Installation:
The Verve is designed for surface and drop-rod installation. All mountings are located on the
outside of the enclosure to reduce installation time.
Four M4 mounts are provided at the base of the enclosure for surface mounting.
Drilling out the inner rings of the supports will allow for M8 drop rod mounting to be
used. The unit should be mounted in an orientation, as to provide suitable fixing and
cable access. The LCM must be mounted flat and true to avoid distortion or damage
to the enclosure and/or any internal components.
When securing the LCM in place in a ceiling, ensure that the label of the unit is facing
downward so the status LED is visible. Doing otherwise may affect the communication ability
of the LCM.
The total weight load bearing capabilities of the unit when installed correctly, including plugs
and cabling, is 20kg. Exceeding this may cause damage to the unit. All cables should be
dressed and tied to avoid any unnecessary strain on the sockets.
N.B. Due to the nature of wireless Bluetooth communications, issues may arise with device
pairing if the units are above metal-bonded ceiling tiles.
Input power connection:
Power is applied to the LCM via a 3-pole Wieland GST18i3 female
connector (supplied in box). Input power to the unit must be 230V AC
50Hz ±10%. The input power cable must be a 3-core cable providing
live, neutral and earth to each LCM and should be adequately insulated
and rated for the supply current and voltage.
The total current rating of the device is 6.3A. The total supply current
should not be exceeded, and the unit should be externally fused by
means of a suitably rated Miniature Circuit Breaker (MCB).
Non EM Luminaire ports:
Connection to the luminaires is achieved using a 5 pole Wieland
GST18i5 blue male plug.
At minimum live, neutral and earth pins should be connected between the
LCM and the luminaires.
Dimming is provided via pins 4 (DA+) and 5 (DA-). These cables must in-
turn be connected to the correct terminals on the luminaires.
WLL Part number TB/9295444530 for the 5 pole plug
L N E Da+ Da-
WHITE
RED
BROWN
Y/G
BLUE
BROWN
BROWN
BLUE
Y
/G
RED
WHITE
BROWN
Y/G
BLUE
BROWN
BLUE
Y/G
RED
WHITE
BROWN
Y/G
BLUE
Emergency-enabled Luminaire ports:
The two emergency ports (G1/E&G3/E) require 6 pole Wieland
GST18i6 male plugs to connect to the load.
At minimum live, neutral, earth and the fourth pin (Em) should be
connected between the LCM and the load.
Dimming is provided via pins 5 (DA+) and 6 (DA-). These cables must
in-turn be connected to the correct terminals on the ballast.
WLL Part no TB/9296903581 6 pole plug
Sensor inputs:
The three sensor ports use RJ11 terminations to connect to the
VERVERECPIR or VERVESURPIR sensor and the sensor input
lead is wired like for like on each end.
Switch inputs:
Latching or retractive switches connect to the switch inputs via a 3 pole
5mm pitch plug.
Two-way retractive switches should be wired between Common (terminal
2) and Off/Down (terminal 1) and On/Up (terminal 3).
The switch input may also be configured for use as an emergency test
key switch input.
The switch inputs are volt-free and should not be connected to any
external voltage.
Restrictions and barriers:
Objects made of metal, such as metallic separation walls and metal inserted ceilings, wall
reinforcements and the metal foil of heat insulations, reflect electromagnetic waves and
thus create what is known as radio shadow and are barriers to signal path. Fire-safety walls
(and curtain barriers), elevator shafts, staircase, air ducting (and HVAC units) and RSJ’s
can be considered as barriers, as well as metal pan ceiling tiles
Material range reduction
• Wood, plaster, glass uncoated, without metal 0 - 10%
• Brick, press board 5 - 35%
• Ferro concrete 10 - 90%
• Metal, aluminium lining 70 - 90%
Avoid barriers when installing BLE wireless networks by repositioning the
Bluetooth transmitting and/or receiving unit away from the radio shadow, or by
using a repeater unit either via sensor or repeater node – repeater unit
(VERVERECPIR / VERVESURPIR / W-GS480BLE repeater sensor).
It is recommended to keep a clearance distance around the LCM of >50cm to
ensure the Bluetooth communications are not restricted.
Da
-
Da+ Em N
E
L
WHITE
RED
BROWN
Y/G
BLUE
BROWN

Popular Controllers manuals by other brands

Toro NO FOUND TMC-424E user guide

Toro

Toro NO FOUND TMC-424E user guide

BECS BECSys3 115VAC Installation and technical manual

BECS

BECS BECSys3 115VAC Installation and technical manual

Botex DMX DC-2448 user manual

Botex

Botex DMX DC-2448 user manual

Graco P20-VM instructions

Graco

Graco P20-VM instructions

Niles WVC100K Installation & operation guide

Niles

Niles WVC100K Installation & operation guide

Gardena Flex Operator's manual

Gardena

Gardena Flex Operator's manual

CBI Astute Series instruction manual

CBI

CBI Astute Series instruction manual

WiSilica Lumos Controls Radiar AFD1 manual

WiSilica

WiSilica Lumos Controls Radiar AFD1 manual

Coulisse RC-XSA32 Assembly manual

Coulisse

Coulisse RC-XSA32 Assembly manual

AUMA SA 25.1 operating instructions

AUMA

AUMA SA 25.1 operating instructions

Carlisle Ransburg Service manual

Carlisle

Carlisle Ransburg Service manual

ActronAir QTW-1000 Installation and commissioning manual

ActronAir

ActronAir QTW-1000 Installation and commissioning manual

SIGOR 9057001 quick start guide

SIGOR

SIGOR 9057001 quick start guide

Nordson ValveMate 7197PCP-2K operating manual

Nordson

Nordson ValveMate 7197PCP-2K operating manual

CYP CR-CS2 Operation manuals

CYP

CYP CR-CS2 Operation manuals

Blaupunkt IVSC-5502 manual

Blaupunkt

Blaupunkt IVSC-5502 manual

Canon imagePASS-B2 INSTALLATION PROCEDURE

Canon

Canon imagePASS-B2 INSTALLATION PROCEDURE

Cumberland SPRKT2415 Operation and installation manual

Cumberland

Cumberland SPRKT2415 Operation and installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.