The charge pressure of the expansion vessel (as supplied) is 0.5
bar, which is equivalent to a static head of 5 metres (17 ft). The
charge pressure must not be less than the static head at the
point of connection. See Fig. 16. A Schraider type tyre valve is
fitted to the expansion vessel to allow the charge pressure to be
increased if necessary.
Set the System Pressure.
Fill the system until the pressure gauge shows 2.5 bar (37
lb/ins2) and check for water soundness. Release water from the
system using the pressure relief valve test knob until the System
Design Pressure is obtained up to a maximum of
1.5 bar.
System Design Pressure in bar = Static Head of the System in
bar + 0.3
Note: 1 bar is equivalent 10.2 metres (33.5 ft) of water
Set the movable pointer on the pressure gauge to coincide with
the indicating pointer giving a permanent record of the set
system pressure. See Fig. 16.
If the pressure indicated on the pressure gauge is greater than
2.5 bar when operating at the maximum central heating
temperature, an extra expansion vessel must be fitted to the
system as close to the appliance central heating return
connection as possible.
The appliance (as despatched) can accommodate a system
volume of about 104 litres. Refer to BS 7074 Part 1. If the system
volume is in excess of that accommodated by the expansion
vessel fitted to the appliance then an extra vessel must be fitted
as close as possible to the central heating return connection of
the appliance.
Any extra vessel fitted must be pressurised to the same figure as
the integral vessel. If the expansion vessel fails then the specified
replacement must be fitted.
12.3 PROGRAMMER
Any programmer fitted to the appliance should be set up at this
stage following the instructions sent with the programmer.
12.4 APPLIANCE OPERATION
Check that the electrical supply to the appliance is off.
Turn the room thermostat (if fitted) to maximum.
Set the Operating Switch (or Programmer) to OFF.
In order to thoroughly vent the appliance and system the
appliance may be operated without gas turned on as follows:
Switch on the electricity supply.
Note: Immediately the mains electricity is applied to the
appliance the electronic control board is energised causing the
pump to run on for about five minutes. This occurs whether or
not the controls are calling for heat. The pump will subsequently
only run in the course of the normal operation of the boiler.
Set the Operating switch (or Programmer) to Heating and Water
and the Hot Water thermostat to maximum. The pump will run
but the main burner will not light. Primary water will circulate
around the appliance.
Allow the appliance to operate in this condition for a few
minutes before setting the Hot Water thermostat to the Off
position.
Set the Heating thermostat to maximum and room thermostat (if
fitted) to maximum. The water diverter will open to central
heating and the appliance will operate as previously.
Primary water will now circulate around the central heating
system. Allow the appliance to operate in this condition for a few
minutes. Vent all radiators during this period until air is cleared
from the system.
When the system has been vented sufficiently set the Heating
thermostat to the Off position.
Note: The water diverter valve, in the de-energised condition, is
always open to Hot Water. The controls give priority to reheating
the heatbank following a demand for hot water. If the valve fails
to open when energised to the central heating system, hot water
will still be available.
The valve does not have a manually open position.
Set the Operating Switch (or Programmer) to OFF.
Switch off the electrical supply.
The appliance and central heating system should now be vented.
Continue the appliance operation:
Turn on the gas supply. Check for gas soundness around the gas
valve.
Light the pilot by pressing in the grey button on the gas valve
and operating the red igniter button. When the pilot has lit
continue to hold the grey button for a further 20 seconds and
then release it slowly.
If the pilot does not stay alight, twist the gas valve button anti-
clockwise. Wait for 3 minutes and repeat the operation until the
pilot remains lit.
Test for gas soundness at the joint between the pilot pipe and the
burner with leak detection fluid. See Fig. 20.
Observe the pilot flame. It should be about 20mm (3/4in) long
and envelope the thermocouple tip. See Fig. 20.
Put the Operating Switch (or Programmer) to OFF and disconnect
the electrical supply at the mains.
IMPORTANT: Replace the inner casing cover and reposition the
pressure vessel. See Fig. 16.
Loosen the burner pressure test point screw and connect a
pressure gauge. See Fig. 21.
Hot Water Mode
Set the Operating Switch (or Programmer) to Water. Turn the Hot
Water thermostat to maximum. Turn the Heating thermostat to
Off.
The boiler should light at a burner pressure of between 13.9 and
14.4 mbar (5.6-5.8 in wg). Allow the boiler to fire for at least 10
minutes before checking the gas pressure.
Note: It may be necessary to open a hot tap to maintain the
boiler firing.
If the burner pressure is low check that the supply pressure at
the gas valve is at least 19 mbar (7.6in wg). See Fig. 21.
Hot Water (High) Gas Pressure
The burner (High) pressure is factory set and is NOT adjustable in
the Hot Water mode. If the gas supply pressure is correct but the
correct burner pressure is not achieved, contact Worcester Heat
Systems Service Department.
Check several times the main burner lights smoothly and goes
out, by operating the Hot Water thermostat, before proceeding
to check the Heating (Low) gas pressure.
Note: If the electrical supply to the appliance is interrupted at
the isolation switch or a power failure occurs whilst the burner is
firing, the boiler will normally relight automatically when the
power supply is restored. However, depending upon
circumstances it may be necessary to reset the overheat
thermostat before the appliance will operate.
Close the hot water tap (if necessary). The burner will be
extinguished and the pump will continue running until the
appliance has cooled to a preset temperature.
Set the Operating Switch (or Programmer) to Off.
Central Heating Mode
Check that all the radiator valves are open. Set the room
thermostat, if fitted, to maximum and the Heating thermostat to
maximum. Turn the Hot Water thermostat to Off.
Sealed Systems: Check the system is pressurised and set to the
required pressure as indicated on the gauge. See Fig. 16.
Set the Operating Switch (or Programmer) to Heating and Water.
The boiler should light at a burner pressure of 5.7 mbar. (2.3 in
wg).
Heating (Low) Gas Pressure
The burner (Low) pressure is factory preset to satisfy a central
heating demand of up to 15 kW (51,200 Btu/hr). For different
heating requirements the gas (Low) pressure must be
adjusted to suit the installation.
The output to central heating is adjustable from a minimum
of 8.8 kW (30,000 Btu/hr) to a maximum of 24 kW (82,000
19