YOKOGAWA UTAdvanced UP55A User manual

IM 05P02C41-15EN page 1/14
Contents
1. Safety Precautions
2. ModelandSufxCodes
3. How to Install
4. HardwareSpecications
5. HowtoConnectWires
6. TerminalWiringDiagrams
Introduction
ThankyouforpurchasingtheUP55AProgramController.
Thisoperationguidedescribesthebasicoperationsrelatedtothesingle-loopcontrol
functionoftheUP55A.Theguideshouldbeprovidedtotheenduserofthisproduct.
Besuretoreadthisoperationguidebeforeusingtheproductinordertoensure
correct operation.
Fordetailsofeachfunction,refertoUser’sManual.Beforeusingtheproduct,refer
tothetableof Model andSufxCodestomake sure that thedeliveredproductis
consistentwiththemodelandsufxcodesyouordered. Also make surethatthe
followingitemsareincludedinthepackage.
•ProgramController(themodelyouordered) ..........................................x1
• Set of Brackets........................................................................................x1
•UnitLabel(L4502VZ) ..............................................................................x1
•TagLabel(L4502VE) ..............................................................................x1
(Onlywhenordered.)
•TerminalCover(L4502XP) .....................................................................x1
l
TargetReaders
Thisguideisintendedforthefollowingpersonnel;
• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.
• Personnelresponsiblefornormaldailyoperationoftheequipment.
1. Safety Precautions
Thefollowingsymbolisusedontheinstrument.Itindicatesthepossibilityofinjury
totheuserordamagetotheinstrument,andsignies that the usermustreferto
theuser’smanualforspecialinstructions.Thesamesymbolisusedintheuser’s
manualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”
or“CAUTION.”
WARNING
Calls attention to actions or conditions that could cause serious
or fatal injury to the user, and indicates precautions that should be
taken to prevent such occurrences.
CAUTION
Calls attention to actions or conditions that could cause injury to
the user or damage to the instrument or property and indicates pre-
cautions that should be taken to prevent such occurrences.
AC
AC/DC
Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.
Functionalgroundingterminals
(Donotusethisterminalasaprotectivegroundingterminal).
Note
Identiesimportantinformationrequiredtooperatetheinstrument.
nWarning and Disclaimer
(1) YOKOGAWAmakes nowarrantiesregardingthe productexceptthosestated in
theWARRANTYthatisprovidedseparately.
(2) Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilityto
anypersonorentityforanylossordamage,directorindirect,arisingfromthe
useoftheproductorfromanyunpredictabledefectoftheproduct.
nSafety,Protection,andModicationoftheProduct
(1)Inordertoprotectthesystemcontrolledby this product andtheproductitself,
andtoensuresafeoperation,observethesafetyprecautionsdescribedinthe
user’smanual.Useoftheinstrumentinamannernotprescribed herein may
compromise the product's functions and the protection features inherent in the
device.Weassumenoliabilityforsafety,orresponsibilityfortheproduct'squality,
performanceorfunctionalityshouldusersfailtoobservetheseinstructionswhen
operatingtheproduct.
(2)Installationofprotectionand/or safety circuits withrespecttoalightning
protector;protectiveequipmentforthesystemcontrolledbytheproductandthe
productitself;foolprooforfailsafedesignofa process or lineusingthesystem
controlledbytheproductortheproductitself;and/orthedesignandinstallation
ofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthe
customer deems necessary.
(3) Be sureto usethesparepartsapprovedbyYOKOGAWAwhen replacingparts
orconsumables.
(4) This productis not designedor manufacturedtobe usedin criticalapplications
thatdirectlyaffectorthreatenhumanlives.Suchapplicationsincludenuclear
powerequipment,devicesusingradioactivity, railway facilities, aviation
equipment,airnavigationfacilities,aviationfacilities,andmedicalequipment.
Ifsoused,itistheuser’sresponsibilitytoincludeinthesystemadditional
equipmentanddevicesthatensurepersonnelsafety.
(5) Modicationoftheproductisstrictlyprohibited.
(6) This product is intended to be handled by skilled/trained personnel for electric
devices.
(7) This product is ULRecognizedComponent.InordertocomplywithUL
standards,end-productsarenecessarytobedesignedbythosewhohave
knowledgeoftherequirements.
WARNING
l
Power Supply
Ensure that the instrument’s supply voltage matches the voltage
of the power supply before turning ON the power.
lDo Not Use in an Explosive Atmosphere
Do not operate the instrument in locations with combustible
or explosive gases or steam. Operation in such environments
constitutes an extreme safety hazard. Use of the instrument in
environments with high concentrations of corrosive gas (H2S,
SOX, etc.) for extended periods of time may cause a failure.
lDo Not Remove Internal Unit
The internal unit should not be removed by anyone other than
YOKOGAWA's service personnel. There are dangerous high
voltage parts inside. Additionally, do not replace the fuse by
yourself.
lDamage to the Protective Construction
Operation of the instrument in a manner not specified in the
user’s manual may damage its protective construction.
CAUTION
This instrument is an EMC class A product. In a domestic environ-
ment this product may cause radio interference in which case the
user needs to take adequate measures.
2. ModelandSufxCodes
nUP55A
[Style:S2]
Model Sufxcode
Optional
sufx
code
Description
UP55A
ProgramController(providedwith3DIs,and3DOs)
(Powersupply:100-240VAC)
30programpatterns/300programsegments(Max.99
segmentsperpattern)
Fixedcode -NNN Always"-NNN”
Displaylanguage(*1)
-1 English
-2 German
-3 French
-4 Spanish
Casecolor0White(Lightgray)
1Black(Lightcharcoalgray)
Output1(*2)(*3)
-A Analogoutput(current/voltagepulse)
-R Relayoutput(c-contact)
-U Universaloutput(current/voltagepulse/relay)
-T Triac output
-P Position proportional output
Output2(*2)(*3)
AAnalogoutput(current/voltagepulse)
RRelayoutput(c-contact)
UUniversaloutput(current/voltagepulse/relay)
TTriac output
NNone
Retransmissionoutput /RT Retransmissionoutputor15VDCpowersupply
Heaterbreakalarm(*3) /HA Heaterbreakalarm
E1terminalarea(*4)
/R1
Remote(1additionalaux.analog)inputand1additionalDI
/U1 1additionaluniversalinput(TC/RTD/DCV/mA)
/X1 5additionalDIs
/Y1 5additionalDOs
/W1 2additionalDIsand2additionalDOs
E2terminalarea(*4)
/A2 1additionalaux.analoginputand1additionalDI
/X2 5additionalDIs
/Y2 5additionalDOs
/W2 2additionalDIsand2additionalDOs
E3terminalarea(*4)(*5)
/CH3 RS485communication(Max.38.4kbps,2-wire/4-wire)
/CC3 CC-Linkcommunication(withModbusmasterfunction)
/PD3
PROFIBUS-DPcommunication(withModbusmasterfunction)
/DN3
DeviceNetcommunication(withModbusmasterfunction)
/ET3 Ethernetcommunication(withserialgatewayfunction)
/X3 5additionalDIs
/Y3 5additionalDOs
/W3 2additionalDIsand2additionalDOs
E4terminalarea(*4)(*5)
/A4 1additionalaux.analoginputand1additionalDI
/C4 RS485communication(Max.19.2kbps,2-wire/4-wire)
/L4 24VDClooppowersupply
/AC4 1additionalaux.analoginput,1additionalDI,and
RS485communication(Max.19.2kbps,2-wire)
/LC4 24VDClooppowersupplyandRS485communication
(Max.19.2kbps,2-wire)
/X4 5additionalDIs
/Y4 5additionalDOs
/W4 2additionalDIsand2additionalDOs
Power supply /DC Powersupply24VAC/DC
Additionaltreatment(*6) /CT Coating
*1: English,German,French,andSpanishcanbedisplayedastheguidedisplay.
*2: Forheating/coolingoutput,bothOutput1andOutput2shouldbespecified.
Notavailable
whenOutput2is“N”.Forpositionproportionaloutput,specify“-P”forOutput1and“N”forOutput2.
*3: The/HAoptioncanbespecifiedonlywhenthecodeforOutput1and2is“-AN”,“-RN”,“-UN”or“-TN.”
*4: OnlyoneoptionisavailableforeachterminalareaofE1toE4.
*5: The/L4and/LC4optionsforE4terminalareacanbespecifiedonlywhentheE3terminal
areaoptionisnotspecifiedorspecifiedanyof/CH3,/X3,/Y3or/W3.
*6: Whenthe/CToptionisspecified,theUT55Adoesnotconformtothesafetystandards(UL
andCSA)andCEmarking.
nAccessories (sold separately)
Thefollowingisanaccessorysoldseparately.
• LL50AParameterSettingSoftware
Model Sufxcode Description
LL50A -00 ParameterSettingSoftware
• SetofBrackets(Partnumber:L4502TP)
2 pcs for upper and lower sides
•User’sManual(A4size)
Note:User’sManualcanbedownloadedfromawebsite.
• User’sManual(CD-ROM),Model:UTAP003
Note:Containsallmanuals.
• OperationGuideforSingle-loopControl(thisdocument)x7(A3size)
(InstallationandWiring,InitialSettings,Programmings,Operations,andParameters)
3. How to Install
nInstallation Location
Theinstrumentshouldbeinstalledinindoorlocationsmeetingthefollowing
conditions:
• Instrumented panel
Thisinstrumentisdesignedtobemountedinaninstrumentedpanel.Mountthe
instrumentinalocationwhereitsterminalswillnotinadvertentlybetouched.
• Well ventilated locations
Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-
naltemperaturefromrising.
However,makesurethattheterminalportionsarenotexposedtowind.Exposure
to wind may cause the temperature sensor accuracy to deteriorate. To mount mul-
tipleindicatingcontrollers,seetheexternaldimensions/panelcutout dimensions
whichfollow.Ifmountingotherinstrumentsadjacenttotheinstrument,complywith
thesepanelcutoutdimensionstoprovidesufcientclearancebetweentheinstru-
ments.
• Locations with little mechanical vibration
Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.
• Horizontal location
Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationto
therightorleft.
Front panel
of controller Keep this angle
within 30°
Rear of
controller
30°
Note
Iftheinstrumentismovedfromalocationwith low temperatureandlowhumidity
toaplacewithhigh temperatureandhighhumidity, orifthe temperaturechanges
rapidly,condensationwillresult.Moreover,inthe case of thermocoupleinputs,
measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthe
newenvironmentunderambientconditionsformorethan1hourpriortousingit.
Donotmounttheinstrumentinthefollowinglocations:
• Outdoors
• Locations subject to direct sunlight or close to a heater
Installtheinstrumentinalocationwithstabletemperaturesthatremainclosetoan
averagetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlight
orclosetoaheater.Doingsoadverselyaffectstheinstrument.
• Locations with substantial amounts of oily fumes, steam, moisture, dust, or
corrosive gases
Thepresence ofoilyfumes, steam,moisture,dust,orcorrosivegases adversely
affectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyof
thesesubstances.
• Areasnearelectromagneticeldgeneratingsources
Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Ifthe
instrumentisusedinlocationsclosetoastrongelectromagneticeldgenerating
source,themagneticeldmaycausemeasurementerrors.
• Locationswherethedisplayisdifculttosee
TheinstrumentusesanLCDforthedisplayunit,andthiscanbedifculttosee
fromextremelyobliqueangles.Mounttheinstrumentinalocationwhereitcanbe
seenasmuchaspossiblefromthefront.
• Areasclosetoammablearticles
Absolutelydonotplacetheinstrumentdirectlyonam-
mablesurfaces.Ifsuchacircumstanceisunavoidable
andtheinstrumentmustbeplacedclosetoaammable
item,provideashieldforitmadeof1.43mmthickplated
steel or 1.6 mm thick unplated steel with a space of at
least150mmbetweenitandtheinstrumentonthetop,
bottom,andsides.
• Areas subject to being splashed with water
WARNING
Be sure to turn OFF the power supply to the controller before in-
stalling it on the panel to avoid an electric shock.
www.yokogawa.com/ns
YOKOGAWA ELECTRIC CORPORATION
Network Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN
YOKOGAWA CORPORATION OF AMERICA
Head office and for product sales
2 Dart Road, Newnan, Georgia 30265, USA
YOKOGAWA EUROPE B.V.
Headquarters
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation
150 mm150 mm
150 mm
150 mm
150 mm150 mm
150 mm
150 mm
Operation
Guide
IM 05P02C41-15EN
UP55A
Program Controller
Operation Guide for Single-loop Control
This operation guide describes installation, wiring, and other tasks required to make the
controller ready for operation.
2nd Edition : Jan. 2011
Installation and Wiring
nWaste Electrical and Electronic Equipment (WEEE),
Directive 2002/96/EC
ThisisanexplanationofhowtodisposeofthisproductbasedonWasteElectricaland
ElectronicEquipment(WEEE),Directive2002/96/EC.ThisdirectiveisonlyvalidintheEU.
Marking
ThisproductcomplieswiththeWEEEDirective(2002/96/EC)
markingrequirement.
Thismarkingindicatesthatyoumustnotdiscard this electrical/
electronic product in domestic household waste.
Product Category
WithreferencetotheequipmenttypesintheWEEEdirectiveAnnex1,this
productisclassifiedasa“MonitoringandControlinstrumentation”product.
Donotdisposein domestichouseholdwaste.WhendisposingproductsintheEU,
contactyourlocalYokogawaEuropeB.V.ofce.

IM 05P02C41-15EN page 2/14
nMounting the Instrument Main Unit
Provideaninstrumentedpanelsteelsheetof1to10mmthickness.
Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstall
the controller:
1) Insertthecontroller into the opening from the frontofthepanelsothatthe
terminalboardontherearisatthefarside.
2) Setthebracketsinplaceonthetopandbottomofthecontrollerasshowninthe
gurebelow,thentightenthescrewsofthebrackets.Takecarenottoovertighten
them.
Bracket
(top mounting hardware)
Terminal board
Bracket
(bottom mounting hardware)
Panel
Insert a screwdriver into the
brackets to tighten the screws.
Direction to insert the
controller
Appropriate
tightening torque:
0.25 N•m
Insert the controller
into the opening at
the front of the panel.
CAUTION
• Tighten the screws with appropriate tightening torque within 0.25
N•m. Otherwise it may cause the case deformation or the bracket
damage.
•Make sure that foreign materials do not enter the inside of the
instrument through the case’s slit holes.
nExternal Dimensions and Panel Cutout Dimensions
(25)
(53) (2.09)
[(N-1)×96+92]
117 (4.61) min.
145 (5.71)
min.
+0.8
0
+0.8
0
92
“N” stands for the number of controllers to be
installed.
However, the measured value applies if N≥5.
65 (2.56)
20 (0.79)
11
(0.43)
UP55A
1 to 10 mm (0.04 to 0.39 inch) (panel thickness)
Bracket
Bracket
94.6 (3.72)
91.6 (3.61)
105.2 (4.14)
Unit: mm (approx. inch)
96 (3.78)
96 (3.78)
• General mounting • Side-by-side close mounting
Terminal cover
Normal tolerance:
±(value of JIS B 0401-1998 tolerance class IT18)/2
+0.8
0
92
+0.03
0
(3.62 )
(0.98)
+0.03
0
(3.62 )
+0.8
0
92
+0.03
0
(3.62 )
([(N-1)×3.78+3.62] )
+0.03
0
4. HardwareSpecications
WARNING
This instrument is for Measurement Category I (CAT.I). Do not use it
for measurements in locations falling under Measurement Catego-
ries II, III, and IV.
Internal Wiring
Outlet
Entrance IV
Cable
III T
I
II
Category Measurement
category Description Remarks
ICAT.I For measurements performed on circuits not
directlyconnectedtoMAINS. -
II CAT.II For measurements performed on circuits di-
rectlyconnectedtothelow-voltageinstallation.
Appliances,portableequip-
ments, etc.
III CAT.III Formeasurementsperformedinthebuilding
installation.
Distributionboard,circuit
breaker,etc.
IV CAT.IV For measurements performed at the source of
thelow-voltageinstallation.
Overheadwire,cable
systems, etc.
nInputSpecications
●UniversalInput(Equippedasstandard)
• Numberofinputs:1
• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow.
Input Type Instrument Range Accuracy
ºC ºF
Thermo-
couple
K
-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±2%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleK
±1%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF
-200.0to500.0ºC -200.0to1000.0ºF
J-200.0to1200.0ºC -300.0to2300.0ºF
T
-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digit
for400°Cormore
±5%ofinstrumentrange±1digitfor
lessthan400°C
S0.0to1700.0ºC 32to3100ºF ±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF
±0.1%ofinstrumentrange±1digit
±0.25%ofinstrumentrange±1digit
forlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±1.5%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U
-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit
(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor
800°Cormore
Accuracyisnotguaranteedforless
than800°C.
W97Re3-
W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100 -200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100
-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)
-200.0to500.0ºC -300.0to1000.0ºF
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal
0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V
4.00to20.00mA
DCvoltage/current
0.000to2.000V
0.00to10.00V
0.00to20.00mA
-10.00to20.00mV
0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpower
frequencyat50/60Hz.
Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange
between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsampling(control)period:Selectfrom100and200ms
• Burnout detection:
FunctionsatTC,RTD,andstandardsignal.
Upscale,downscale,andoffcanbespecied.
Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4
mAorless.
•Inputbiascurrent:0.05µA(forTCorRTD)
•Measuredcurrent(RTD):About0.16mA
• Input resistance:
TCormVinput:1MΩormore
Vinput:About1MΩ
mAinput:About250Ω
•Allowablesignalsourceresistance:
TCormVinput:250Ωorless
Effectsofsignalsourceresistance:0.1µV/Ωorless
DCvoltageinput:2kΩorless
Effectsofsignalsourceresistance:About0.01%/100Ω
• Allowablewiringresistance:
RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires
shallbeequal.)
Wiringresistanceeffect:±0.1ºC/10Ω
• Allowableinputvoltage/current:
TC,mV,mAandRTDinput:±10VDC
Vinput:±20VDC
mAinput:±40mA
• Noiserejectionratio:
Normalmode:40dBormore(at50/60Hz)
Commonmode:120dBormore(at50/60Hz)
For100-240VAC,thepowerfrequencycanbesetmanually.
Automaticdetectionisalsoavailable.
For24VAC/DC,thepowerfrequencycanbesetmanually.
• Referencejunctioncompensationerror:
±1.0ºC(15to35ºC)
±1.5ºC(-10to15ºCand35to50ºC)
• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
●AuxiliaryAnalogInput
• Use:Remotesetpointsetting,externalcompensatinginput,auxiliaryinputforcom-
putation, etc.
• Numberofinputs:SeethetableofModelandSufxCodes.
• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow.
Input Type Instrument Range Accuracy
Standardsignal 0.400to2.000V ±0.2%ofinstrumentrange±1digit
1.000to5.000V ±0.1%ofinstrumentrange±1digit
DCvoltage 0.000to2.000V ±0.2%ofinstrumentrange±1digit
0.00to10.00V ±0.1%ofinstrumentrange±1digit
DCvoltage
forhigh-input
impedance 0.000to1.250V ±0.1%ofinstrumentrange±1digit
• Inputsampling(control)period:Sameasuniversalinput
• Inputresistance:About1MΩ
However,10MΩormoreforDCvoltageforhigh-inputimpedancerange
•Burnoutdetection:Functionsatstandardsignal
Burnoutisdeterminedtohaveoccurredifitis0.1Vorless.
●UniversalInput(Optionalsufxcode:/U1)
• Numberofinputs:SeethetableofModelandSufxCodes.
• Inputtype,instrumentrange,andmeasurementaccuracy:Sameasthestandard-
equippeduniversalinputexceptthetablebelow.
Input Type Instrument Range Accuracy
°C °F
4-wireRTD
JPt100 -200.0to500.0°C -300.0to1000.0°F
±0.5°Cofinstrumentrange±1digit
-150.00to150.00°C -200.0to300.0°F
±0.2°Cofinstrumentrange±1digit
Pt100
-200.0to850.0°C -300.0to1560.0°F
±0.1%ofinstrumentrange±1digit
(Note1)
-200.0to500.0°C -300.0to1000.0°F
±0.5°Cofinstrumentrange±1digit
-150.00to150.00°C -200.0to300.0°F
±0.2°Cofinstrumentrange±1digit
Note1:±0.5°C±1digitintherangebetween-200.0and500.0°C/-300.0and1000.0°F.
• Inputsampling(control)period:Sameasthestandard-equippeduniversalinput.
• Burnoutdetection:Sameasthestandard-equippeduniversalinput.
nAnalogOutputSpecications
• Numberofoutputs:
Controloutput:1
Cooling-sidecontroloutputofHeating/coolingtype:1
• Outputtype:Currentoutputorvoltagepulseoutput
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,
andpowerfrequencyat50/60Hz.
• Voltagepulseoutput:
Use:Timeproportionaloutput
On-voltage:12Vormore/loadresistanceof600Ωormore
Off-voltage:0.1VDCorless
Timeresolution:10msor0.1%ofoutput,whicheverislarger
nStepResponseTimeSpecications
Within500ms(whenthecontrolperiodis100ms)
Within1s(whenthecontrolperiodis200ms)
(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspan
isapplied)
nTriacOutputSpecications
•Contacttypeandnumberofoutput:zerocross;1point
Loadvoltage:75to250VAC
Allowableloadcurrent:0.8Awhentheambienttemperatureis20°C,0.3Awhenthe
ambienttemperatureis50°C.
•Minimumloadcurrent:20mA(*)
*:Unusableforasmallloadof10mAorless.
*:Ifthereisariskofsurgecurrent, connect a current-limitingreactor,acurrent-
limitingfuseorabreakerinseriestotheloadpowersupply.
•Use:Timeproportionaloutput,Alarmoutput
•Timeresolutionofcontroloutput:1/commercialfrequency(s)or 0.1% of output,
whicheverislarger.
nRelayContactOutputSpecications
• Contacttypeandnumberofoutputs:
Controloutput:contactpoint1c;1point
Cooling-sidecontroloutputofHeating/coolingtype:contactpoint1c;1point
Eventoutput:contactpoint1a;3points(commonisindependent)
• Contactrating:
Contactpoint1c(controloutput):250VAC,3Aor30VDC,3A(resistanceload)
Contactpoint1a(eventoutput):240VAC,1Aor30VDC,1A(resistanceload)
• Use:Timeproportionaloutput,eventoutput,alarmoutput,FAILoutput,etc.
• Timeresolutionofcontroloutput:10msor0.1%ofoutput,whicheverislarger
Note:Thiscannotbeusedforasmallloadof10mAorless.
nPositionProportionalOutputSpecications
• Positionsignalinput:
Slideresistance:100Ωto2.5kΩoftotalresistance
100%sideandslideline:withdisconnectiondetection
0%side:withoutdisconnectiondetection
Currentinput:4to20mA(withdisconnectiondetection)
• Samplingperiod:50ms
• Measurementresolution:0.1%ofinputspan
• Position proportional relay output:
Contactpoint1a;2points,250VAC,3Aor30VDC,3A(resistanceload)
Note:Thiscannotbeusedforasmallloadof10mAorless.
n
RetransmissionOutputSpecications
• Numberofoutputs:Retransmissionoutput;1,sharedwith15VDC loop power
supply
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,
andpowerfrequencyat50/60Hz.
n
15VDCLoopPowerSupplySpecications
(Sharedwithretransmissionoutput)
• Powersupply:14.5to18.0VDC
• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)
nContactInputSpecications
• Numberofinputs:SeethetableofModelandSufxCodes.
• Inputtype:No-voltagecontactinputortransistorcontactinput
• Inputcontactrating:12VDC,10mAormore
Useacontactwithaminimumon-currentof1mAormore.
• ON/OFFdetection:
No-voltagecontactinput:
Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact
resistanceof50kΩormoreas“OFF.”
Transistor contact input:
Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust
notexceed100µAwhen“OFF.”
• Minimumstatusdetectionholdtime:Controlperiod+50ms
• Use:PTNO.switch,operationmodeswitch,andeventinput
nTransistorContactOutputSpecications
• Numberofoutputs:SeethetableofModelandSufxCodes.
• Outputtype:Opencollector(SINKcurrent)
• Outputcontactrating:Max.24VDC,50mA
• Outputtimeresolution:Min.100ms
nHeaterBreakAlarmSpecications
• Numberofinputs:2
• Numberofoutputs:2(transistorcontactoutput)
• Use:Measurestheheatercurrentusinganexternalcurrenttransformer(CT)and
generatesaheaterbreakalarmwhenthemeasuredvalueislessthanthebreak
detectionvalue.
• Currenttransformerinputresistance:About9.4Ω
• Currenttransformerinputrange:0.0to0.1Arms(0.12Armsormorecannotbeap-
plied.)
• Heatercurrentsettingrange:OFF,0.1to300.0Arms
Heatercurrentmeasuredvaluedisplayrange:0.0to360.0Arms
Note:TheCTratiocanbeset.CTratiosettingrange:1to3300
• RecommendedCT:CTfromU.R.D.,Ltd.
CTL-6-S-H:CTratio800,measurablecurrentrange:0.1to80.0Arms
CTL-12L-30:CTratio3000,measurablecurrentrange:0.1to180.0Arms
• Heatercurrentmeasurementperiod:200ms
• Heatercurrentmeasurementaccuracy:±5%ofcurrenttransformerinput range
span±1digit(CTerrorisnotincluded.)
• Heatercurrentdetectionresolution:Within1/250ofcurrenttransformerinputrangespan
• BreakdetectionOn-time:Min.0.2second(fortimeproportionaloutput)

IM 05P02C41-15EN page 3/14
n24VDCLoopPowerSupplySpecications
• Use:Powerissuppliedtoa2-wiretransmitter.
• Powersupply:21.6to28.0VDC
• Ratedcurrent:4to20mADC
• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)
■ SafetyandEMCStandards
• Safety:CompliantwithIEC/EN61010-1(CE),approvedbyCAN/CSAC22.2
No.61010-1(CSA),approvedbyUL61010-1.
Installationcategory:CAT.IIPollutiondegree:2
Measurementcategory:I(CAT.I)
Ratedmeasurementinputvoltage:Max.10VDC
Ratedtransientovervoltage:1500V(Note)
Note:ThisisareferencesafetystandardvalueforMeasurementCategoryIofIEC/EN/CSA/
UL61010-1.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.
• EMCConformitystandards:
CEmarking
EN61326-1ClassA,Table2(Foruseinindustriallocations)
EN61326-2-3
EN55011ClassA,Group1
EN61000-3-2ClassA
EN61000-3-3
C-tickmark
EN55011ClassA,Group1
Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%of
therangeduringtesting.
■ Construction,Installation,andWiring
• Dust-proofanddrip-proof:IP56(forfrontpanel)(Notavailableforside-by-side
closemounting.)
• Material:Polycarbonate(Flameretardancy:UL94V-0)
• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)
• Weight:0.5kgorless
• Externaldimensions(mm):96(W)×96(H)×65(depthfromthepanelface)
(Depthexcepttheprojectionontherearpanel)
• Installation:Directpanelmounting;mountingbracket,oneeachforupperand
lowermounting
• Panelcutoutdimensions(mm):92+0.8/0(W)×92+0.8/0(H)
•
Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.
• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
■ PowerSupplySpecicationsandIsolation
• Power supply:
Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz
24VAC/DC(+10%/-15%)(for/DCoption)
• Powerconsumption:18VA(DC:9VA,AC:14VAif/DCoptionisspecied)
• Databackup:Nonvolatilememory
• Powerholduptime:20ms(for100VACdrive)
• Withstandingvoltage
Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute
Betweenprimaryterminals:1500VACfor1minute
Betweensecondaryterminals:500VACfor1minute
(Primary terminals:Power*andrelayoutputterminals;Secondaryterminals:
AnalogI/Osignalterminals,contactinputterminals,communicationterminals
andfunctionalgroundingterminals.)
*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.
• Insulationresistance:Betweenpowersupplyterminalsandagroundingterminal
20MΩormoreat500VDC
• Isolationspecications
PV (universal ) input terminals
Remote (universal) input terminals with direct input / Remote input terminals
Aux. analog (AIN2) input terminals
Control relay (contact point c)/Triac output terminals
PV event-1 relay (contact point a) output terminals
PV event-2 relay (contact point a) output terminals
PV event-3 relay (contact point a) output terminals
Position proportional relay output terminals
Contact input terminals (all)
RS-485 communication terminals (2 ports)
Contact output (transistor) terminals
Ethernet communication terminal
PROFIBUS-DP/DeviceNet/CC-Link communication terminals
Current transformer input terminals
Control, retransmission (analog) output terminals
(not isolated between the analog output terminals)
Valve position (feedback) input terminals
Internal
circuits
Power
supply
The circuits divided by lines are insulated mutually.
Aux. analog (AIN4) input terminals
■ EnvironmentalConditions
NormalOperatingConditions:
• Ambienttemperature:-10to50ºC(-10to40ºCforside-by-sideclosemounting)
FortheCC-Linkoption,0to50ºC(0to40ºCforside-by-sideclosemounting)
• Ambienthumidity:20to90%RH(nocondensationallowed)
• Magneticeld:400A/morless
• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90
minuteseachinthethreeaxisdirections
Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseach
inthethreeaxisdirections
• Short-periodvibration:14.7m/s2, 15 seconds or less
• Shock:98m/s2or less, 11 ms
• Altitude:2000morlessabovesealevel
• Warm-uptime:30minutesormoreafterthepoweristurnedon
• Startuptime:Within10seconds
*:TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.TheLCDhas
acharacteristicthatthedisplayactionbecomeslateatthelowtemperature.However,the
control fuction is not affected.
TransportationandStorageConditions:
• Temperature:-25to70ºC
• Temperaturechangerate:20ºC/horless
• Humidity:5to95%RH(nocondensationallowed)
Effects of Operating Conditions
• Effectofambienttemperature:
VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger
Currentinput:±0.01%ofF.S./ºC
RTDinput:±0.05ºC/ºC(ambienttemperature)orless
Analogoutput:±0.02%ofF.S./ºCorless
• Effectofpowersupplyvoltageuctuation
Analoginput:±0.05%ofF.S.orless
Analogoutput:±0.05%ofF.S.orless
(Eachwithinratedvoltagerange)
5. How to Connect Wires
WARNING
• Wiring work must be carried out by a person with basic electrical
knowledge and practical experience.
•
Be sure to turn OFF the power supply to the controller before wiring
to avoid an electric shock. Use a tester or similar device to ensure
that no power is being supplied to a cable to be connected.
•
As a safety measure, always install a circuit breaker (an IEC
60947-compatible product, 5 A, 100 V or 220 V AC) in an easily
accessible location near the instrument. Moreover, provide indication
that the switch is a device for turning off the power to the instrument.
• Install the power cable keeping a distance of more than 1 cm
from other signal wires.
•
The power cable is required to meet the IEC standards concerned or the
requirements of the area in which the instrument is being installed.
• Wiring should be installed to conform to NEC (National Electrical
Code:ANSI/NFPA-70)orthewiringconstructionstandardsin
countries or regions where wiring will be installed.
• For control relay output, alarm relay output, and power terminal
connections, use heat-resistant cables.
• Since the insulation provided to each relay output terminal
is Functional insulation, provide Reinforced insulation to the
external of the device as necessary. (Refer to the drawing below.)
This product
Functional
insulation
A safety
voltage circuit
A safety
voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional
insulation
A hazardous
voltage circuit
A hazardous
voltage circuit
A safety
voltage circuit
A safety
voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional
insulation
A hazardous
voltage circuit
A hazardous
voltage circuit
A hazardous
voltage circuit
A hazardous
voltage circuit
CAUTION
• When connecting two or more crimp-on terminal lugs to the
single terminal block, bend the crimp-on terminal lugs before
tightening the screw.
•Note that the wiring of two or more crimp-on terminal lugs to the
single high-voltage terminal of the power supply and relay, etc.
does not comply with the safety standard.
CAUTION
• Provide electricity from a single-phase power supply. If the
power is noisy, install an isolation transformer on the primary
side, and use a line filter on the secondary side. When measures
against noise are taken, do not install the primary and secondary
power cables close to each other.
•
If there is a risk of external lightning surges, use a lightning arrester etc.
• For TC input, use shielded compensating lead wires for wiring.
For RTD input, use shielded wires that have low conductor
resistance and cause no significant differences in resistance
between the three wires.
•Since the control output relay has a life span (resistance load of
100,000 times), use the auxiliary relay to perform ON/OFF control.
• The use of inductance (L) loads such as auxiliary relays, motors
and solenoid valves causes malfunction or relay failure; always
insert a CR filter for use with alternating current or a diode for
use with direct current, as a spark-removal surge suppression
circuit, into the line in parallel with the load.
• After completing the wiring, the terminal cover is recommended
to use for the instrument.
● RecommendedCrimp-onTerminalLugs
(A)
(F)
(ød)
5.5 3.3
E4-terminal area
E3-terminal area E2-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
211
212
101
-112
501
-512
401
-412
301
-312
201
-212
ALM
(Equipped
as standard)
Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
PV event-2 output
PV event-3 output
PV event-1 output
Common
Common
Common
UP
104
105
106
107
108
109
PV
PV input
TC input RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(Equipped
as standard)
202
203
201
202
203
202
203
203
204
Factory default: PV input
type is undefined.
OUT
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)
+
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Control output
(Suffix code: Output 1; -A or -U)
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
207
208
207
-208
207
208
Can be used for retransmission output or 15 V DC loop power supply when
current/voltage pulse output is not used for control output.
Current output range can be changed.
In Position proportional type, can be used for retransmission output or 15 V
DC loop power supply.
RET
Retransmission output
4-20 mA DC or
0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV
retransmission
Load resistance 600 Ωor less
Retransmission output
(Optional suffix code /RT)
205
206
205
206
Can be used for 15 V DC loop
power supply when not used for
retransmission output.
VALV
(Suffix code: Output 1=-P)
Position proportional control output
Resistance: 100 Ωto 2.5 kΩ
Feedback input
100%
0%
Relay contact output
HIGH
(direct)
LOW
(reverse)
COM
Contact rating: 250 V AC, 3A
30 V DC, 3 A
(resistance load)
507
508
509
510
511
512
-
Feedback input
Current (mA)
input
When feedback input is current
510
511
512
+
HBA
(Optional suffix code /HA)
Heater break alarm
Heater current detection input
CT1
CT2
COM
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
Heater break alarm-1
output
Heater break alarm-2
output
Common
510
511
512
HAL1
HAL2
COM
UP
507
508
509
112
(24 V AC/DC power supply: Optional suffix code /DC)
Power supply
100-240 V AC power supply
N
L
Allowable range:
100-240 V AC (±10%)
(free voltage)
50/60 Hz shared
110
111
24 V AC/DC power supply
-
+
110
111
112 112
N
L
OUT
(Suffix code:
Output 1; -T)
Control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
101
102
Triac output
103
NO
COM
Contact rating: 75 - 250 V AC
Allowable load current: 0.8 A
OUT
(Suffix code:
Output 1; -R or -U)
OUT2
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12V)
+
-
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Cooling-side control output
Relay contact output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A
(resistance load)
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
511
512
507
508
509
511
512
511
512
507
508
Triac output
509
NO
COM
Contact rating: 75 - 250 V AC
Allowable load current: 0.8 A
Triac
(Suffix code: Output 2; A or U)
(Suffix code: Output 2; R or U) (Suffix code: Output 2; T)
DI (Equipped as standard)
Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI3
DI2
DI1
COM
Common
DI3
DI2
DI1
COM
+5V
+5V
+5V
No-voltage
contact Transistor contact
UP UP
209
210
211
212
209
210
211
212
Function can be changed.
Start of program operation when
DI1 changes from OFF to ON.
Stop of program operation when
DI2 changes from OFF to ON.
Start of local-mode operation when
DI3 changes from OFF to ON.
Wiring direction
6. Terminal Wiring Diagrams
CAUTION
• Do not use an unassigned terminal as the relay terminal.
• Do not use a 100-240 V AC power supply for the 24 V AC/DC
model; otherwise, the instrument will malfunction.
■ UP55A
Recommendedtighteningtorque:0.6N·m
Applicablewiresize:Powersupplywiring1.25mm2or more
Applicable terminal lug Applicable wire size mm2(AWG#) (φd) (A) (F)
M3 0.25to1.65(22to16) 3.3 5.5 4.2
● CableSpecicationsandRecommendedCables
Purpose Name and Manufacturer
Power supply, relay contact outputs 600VGradeheat-resistantPVCinsulatedwires,JISC
3317(HIV),0.9to2.0mm2
Thermocouple Shieldedcompensatingleadwires,JISC1610
RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)
Othersignals(otherthancontactinput/output)
Shielded wires
Othersignals(contactinput/output)
Unshieldedwires
RS-485communication
Shielded wires
Ethernetcommunication
100BASE-TX(CAT-5)/10BASE-T
PROFIBUS-DPcommunication
DedicatedcableforPROFIBUS-DP(Shieldedtwo-wires)
DeviceNetcommunication
DedicatedcableforDeviceNet(Shieldedve-wires)
CC-Linkcommunication
DedicatedcableforCC-Link(Shieldedthree-wires)
PROFIBUS-DP/CC-LinkConnector(wiringside)(Partnumber:A1987JT)
DeviceNetConnector(wiringside)(Partnumber:L4502BW)
Recommendedtighteningtorque:0.5to0.6N·m
External DC power supply
Relay
UP’s contact
Diode
(Mount it directly
to the relay coil
terminal (socket).)
Relay
(Use one with a relay coil rating
less than the UP’s contact rating.)
R
UP55A
DC Relay Wiring AC Relay Wiring
UP55A
R
UP’s contact CR filter
(Mount it directly
to the relay coil
terminal (socket).)
External AC power supply
Relay
(Use one with a relay coil
rating less than the UP’s
contact rating.)

IM 05P02C41-15EN page 4/14
E1-Terminal Area
301-306 E2-Terminal Area
307-312
(Optional suffix code /X1)
Contact input
External contact input
DI11
DI12
DI13
DI14
DI15
COM
Common
DI11
DI12
COM
+5V
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
DI13 +5V
DI14 +5V
DI15 +5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UP UP
301
302
303
304
305
306
301
302
303
304
305
306
Function can be assigned to the terminals with no function.
DI
Contact output
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
DO12
DO11
DO13
DO14
DO15
COM
Common
UP
(Optional suffix code /Y1)
PV event-4 output
PV event-5 output
PV event-6 output
PV event-7 output
PV event-8 output
301
302
303
304
305
306
Function can be assigned to the terminal with no function.
DO (Optional suffix code /U1)
Universal input
TC input RTD input
Voltage (mV, V) input
+
-
+
-
Current (mA) input
+
-
4-wire
302
303
302
303
303
304
RSP
a
B
b
A301
302
303
305
(Optional suffix code /R1)
Remote input / Contact input
External contact input
DI16
COM
Common
DI16
COM
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
UP UP
Start of remote-mode
operation when DI16
switches from OFF to ON.
303
304
303
304
RSP
Remote input
Default: 1-5 V DC
+
-
305
306
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
Contact output
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO22
DO21
DO23
DO24
DO25
COM
Common
UP
(Optional suffix code /Y2)
307
308
309
310
311
312
Function can be changed.
DO
Time event-5 output
Time event-4 output
Time event-3 output
Time event-2 output
Time event-1 output
(Optional suffix code /W1)
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO12
DO11
COM
Common
UP
Contact input / Contact output
External contact input
DI11
DI12
COM
Common
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
UP
301
302
303
304
305
306
DI/DO
Function can be assigned to the terminals with no function.
DI11
DI12
COM
+5V
+5V
UP
301
302
303
(Optional suffix code /X2)
Contact input
External contact input
DI21
DI22
DI23
DI24
DI25
COM
Common
DI21
DI22
COM
+5V
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
DI23 +5V
DI24 +5V
DI25 +5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UP UP
307
308
309
310
311
312
307
308
309
310
311
312
Function can be assigned
to the terminals with no
function.
DI
(Optional suffix code /W2)
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO22
DO21
COM
Common
UP
Contact input / Contact output
External contact input
DI21
DI22
COM
Common
DI21
DI22
COM
+5V
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
UP UP
307
308
309
307
308
309
310
311
312
DI/DO
Function can be
assigned to the
terminals with no
function.
(Optional suffix code /A2)
Aux. analog input
Default: 1-5 V DC
+
-
Aux. analog input / Contact input
External contact input
DI26
COM
Common
DI26
COM
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
UP UP
309
310
309
310
311
312
Function can be assigned to the terminals with no function.
AIN2
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
PV event-4 output
PV event-5 output
Time event-1 output
Time event-2 output
E3-Terminal Area
401-412 E4-Terminal Area
501-506
(Optional suffix code /ET3)
Ethernet communication (with gateway function)
10BASE-T/100BASE-TX
RJ45 connector
Color
Lit
Unlit
Amber
100M bps
10M bps
Green
Linked
Active
Link failure
Color
Lit
Blink
Unlit
Upper side LED (baud rate)
Lower side LED (link activity)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
ETHR
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication
(Optional suffix code /CH3)
407
408
409
410
411
RS485
Contact input
External contact input
DI41
DI42
DI43
DI44
DI45
COM
DI41
DI42
COM
+5V
+5V
DI43 +5V
DI44 +5V
DI45 +5V
UP UP
(Optional suffix code /X4)
Common
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Bit-0 of
program pattern number
Bit-1 of
program pattern number
Bit-2 of
program pattern number
Bit-3 of
program pattern number
Bit-4 of
program pattern number
501
502
503
504
505
506
501
502
503
504
505
506
Function can be changed.
DI
(Optional suffix code /X3)
Contact input
External contact input
DI31
DI32
DI33
DI34
DI35
COM
Common
DI31
DI32
COM
+5V
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
DI33 +5V
DI34 +5V
DI35 +5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UP UP
407
408
409
410
411
412
407
408
409
410
411
412
DI
Function can be assigned to the terminals with no function.
Contact output (Optional suffix code /Y3)
DO
External contact output
DO32
DO31
DO33
DO34
DO35
COM
Time event-6 output
Time event-7 output
Time event-8 output
Time event-9 output
Time event-10 output
Common
UP
407
408
409
410
411
412
Transistor contact rating: 24 V DC, 50 mA Function can be changed.
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication
501
502
503
504
505
RS485
(Optional suffix code /C4)
RS-485
RSB(+)
RSA(-)
SG
RS
-
485 communication/24 V DC loop power supply
+
24 V DC loop power supply
21.6-28.0 V DC
(Max. 30 mA DC) -
501
502
503
505
506
RS485/LPS24
(Optional suffix code /LC4)
+
24 V DC loop power supply
21.6-28.0 V DC
(Max. 30 mA DC) -
24 V DC loop power supply
505
506
LPS24
(Optional suffix code /L4)
Aux. analog input/Contact input
(Optional suffix code /A4)
AIN4
Aux. analog input
Default: 1-5 V DC
+
-
External contact input
DI46
COM
DI46
COM
+5V
UP UP
Common
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
503
504
503
504
505
506
Function can be assigned to the
terminals with no function.
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
(Optional suffix code /PD3)
PROFIBUS-DP communication (with Modbus master)
Pin
1
2
Signal name Description
VP
RxD/TxD-P
3 RxD/TxD-N
4DGND
5SHIELD
+5V bus power
Data signal
(positive data receive/transmit)
Data signal
(negative data recive/transmit)
Signal ground
Shield ground
RS-485
RSB(+)
RSA(-)
SG
407
408
409
PROF
If the UP is located at the
end of a segment for the
PROFIBUS
communication wiring,
terminating resistors are
separately needed.
These are to be prepared
by users. (390 Ω: 2 pcs.
220 Ω: 1 pc., or an active
terminator.)
VP
RxD/TxD-P
Data
line
Data
line
390Ω
220Ω
390Ω
RxD/TxD-N
DGND
LED
CHK
(red)
RDY
(green)
Lit Unlit
ERR
(red)
User profile error
CHK
RDY
ERR
1
2
3
4
5
Normal
Normal
Not connected, or
communication
failure (flashing)
Normal.
Communicating
successfully
No electricity, or
communication
failure
Contact output
External contact output
DO42
DO41
DO43
DO44
DO45
COM
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Common
UP
(Optional suffix code /Y4)
501
502
503
504
505
506
DO
Transistor contact rating: 24 V DC, 50 mA Function can be assigned to the
terminals with no function.
(Optional suffix code /W4)
Contact input / Contact output
DI/DO
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO42
DO41
COM
Common
UP
External contact input
DI41
DI42
COM
Common
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
UP
501
502
503
504
505
506
Function can be assigned to the terminals with no function.
DI41
DI42
COM
+5V
+5V
UP
501
502
503
RS-485 communication / Aux. analog input / Contact input
(Optional suffix code /AC4)
External contact input
DI46
COM
Common
DI46
COM
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
UP UP
Factory default: No function
503
504
503
504
AIN4/RS485 Aux. analog input
Default: 1-5 V DC
+
-
505
506
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
RS-485
RSB(+)
RSA(-)
SG
501
502
503
Program pattern number
1 2 3 4 5 6 7 8 9 10 11 12
DI41 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
DI42 OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF
DI43 OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON
DI44 OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON
DI45 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
(Suffix code: Type 3=5,
except Type 2=3)
DeviceNet communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
DNET
If the UP is located at
the end of a segment
for the DeviceNet
communication wiring,
terminating resistors
are separately needed.
These are to be
prepared by users.
(121 Ω: 1 pc.)
CAN_H
CAN_L
121Ω
LED
CHK
(red)
RDY
(green/
red)
Lit/flashing Unlit
User profile error Normal
Pin
1
2
Signal name Description
CAN_H
CAN_L
3
V+
4
V-
5
DRAIN
RX/TX + signal
RX/TX - signal
Shield/Drain wire
DeviceNet power supply 24V
DeviceNet power supply common
Normal. Communicating
successfully (green, lit).
Not connected (green, flashing).
Critical link failure (red, lit).
Communication timeout (red,
flashing)
At power-on/Communication
faulted (green/red, flashing)
No electricity
CHK
MNS
1
2
3
4
5
(Suffix code: Type 3=3,
except Type 2=3)
CC-Link communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
CC-L
If the UP is located at
the end of a segment
for the CC-Link
communication wiring,
terminating resistors
are separately needed.
These are to be
prepared by users.
(110 Ω: 1 pc.)
DA
DB
110Ω
LED
CHK
(red)
L ERR
(red)
L RUN
(green)
Lit Unlit
User profile error Normal
Normal
Pin
1
2
Signal name Description
DA
DB
3 DG
4
SLD
5
FG
RX/TX - signal
RX/TX + signal
Frame ground
TX/RX signal ground
Shield
Normal
Communicating successfully
Communication failure
(CRC error)
No carrier
detected/
Connection
timeout
CHK
L RUN
L ERR
1
2
3
4
5
Function can be assigned to the terminals with no function.
(Optional suffix code /W3)
Contact input / Contact output
External contact input
DI31
DI32
COM
Common
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
UP
407
408
409
DI/DO
DI31
DI32
COM
+5V
+5V
UP
407
408
409
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO32
DO31
COM
Common
UP
410
411
412
Time event-6 output
Time event-7 output
A program pattern is selected with the combination of ON and OFF of a
contact input.
In the case of a pattern 5, ON (1) of "DI45 to DI41" and OFF (0) is
represented as a binary number "00101": it is "5" decimally.
The pattern 13 or later can be selected similarly.
Bit-0 of
program pattern number
Bit-1 of
program pattern number
E4-terminal area
E3-terminal area
E2-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
211
212
101
-112
501
-512
401
-412
301
-312
201
-212
112
■ UP55A(Continuedfrompage3) [ Operations 13. Troubleshooting ] nErrors at Power On
Theerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual.
PV display
(Operation
Display)
Setpoint display
(Operation Display)
Status indicator
(Operation Display)
Parameter that displays error
details Error description Cause and diagnosis Remedy
Indication off Indication off — — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty.
Contactusforrepair.
ERR
SYS-----
—
— System data error System data is corrupted. Faulty.
Contactusforrepair.
PAR0004
(foruserdefaultvalueerroronly)
Setupparameter(PA.ER)
User(parameter)defaultvalue
error
Userparameteriscorrupted.
Initializedtofactorydefaultvalue.
Checkandreconguretheinitialized
settingparameters.Errorindicationis
erased when the power is turned on
again.
PAR0010
(forsetupparametererroronly)
Setup parameter error Setup parameter data is corrupted.
Initializedtouserdefaultvalue.
PAR0020
(foroperationparametererroronly)
Operationparametererror Operationparameterdataiscorrupted.
Initializedtouserdefaultvalue.
PAR0040
(forprogrampatternerroronly)
Programpatternerror Programpatterndataiscorrupted.
Allprogrampatternsaredeleted.
SLOT0017
(0017:Erroroccurstoall
hardwareofE1toE4-terminal
areas.)
Setupparameter(OP.ER)
Nonrespondinghardwareof
extendedfunction(E1toE4-
terminalareas)
Inconsistence of system data and
hardwareofextendedfunction.
Nonrespondingcommunicationbetween
hardwareofextendedfunction(E1toE4-
terminalareas).
Faulty.
Contactusforrepair.
Normal
indication Normalindication
Rightmostdecimalpoint
onPVdisplayblinks. Setupparameter(PA.ER)
Calibrationvalueerror
Initializedtocalibrateddefaultvaluebecause
ofcorruptedfactorydefaultvalue.
Faulty.
Contactusforrepair.
Rightmostdecimalpoint
onSymboldisplayblinks.
FaultyFRAM
Datawriting(storing)toFRAMisimpossible.
Normal
indication Normalindication LADDERlampblinks Setupparameter(LA.ER) Corruptedladderprogram Ladderprogramiscorrupted.
Operateswithoutladderprogram. Downloadtheladderprogramagain.
Normal
indication
0.00000000
(Decimalpointontheleftof
theSymboldisplayblinks)
—Setupparameter(OP.ER) Userproleerror Userproleiscorrupted. Downloadtheuserproleagain.
[ Operations 13. Troubleshooting ] nErrors during Operation
Theerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual.
PV display
(Operation
Display)
Setpoint display
(Operation Display)
Status indicator
(Operation Display)
Parameter that displays
error details Error description Cause and diagnosis Remedy
AD.ERR Normalindication(Note) —Setupparameter(AD1.E)
AnaloginputterminalADCerror
•PVinput
•RSPinput(E1-terminalarea)
•AIN2input(E2-terminalarea)
•AIN4input(E4-terminalarea)
AnaloginputterminalADvalueerror Faulty.
Contactusforrepair.
RJC.E
(DisplaysRJC.
EandPV
alternately.)
Normalindication(Note) —Setupparameter(AD1.E)
UniversalinputterminalRJCerror
•PVinput
•RSPinput(E1-terminalarea)
UniversalinputterminalRJCerror
Faulty.
Contactusforrepair.
SettheparameterRJCtoOFFtoerase
error indication.
B.OUT Normalindication(Note) —
Setupparameter(AD1.E)
Analoginputterminalburnouterror
•PVinput
•RSPinput(E1-terminalarea)
•AIN2input(E2-terminalarea)
•AIN4input(E4-terminalarea)
Analoginputterminalsensorburnout
Checkwiringandsensor.
Errorindicationiserasedinnormal
operation.
Setupparameter(PV1.E/PV2.E) PVinputburnouterror(Loop1,
Loop2) BurnoutofanaloginputconnectedtoPV
Checkwiringandsensorofconnected
analoginputterminals.
Errorindicationiserasedinnormal
operation.
OVER
-OVER Normalindication —Setupparameter(PV1.E/PV2.E)
PVinputover-scale
PVinputunder-scale
(PVvaluesoutof-5to105%)(Loop
1,Loop2)
PVinputisoutof-5to105%.Alsooccurs
whenthedataoutofrangewhichisthe
ladder calculation result is input.
Checkanaloginputvalueorladder
program.
Normal
indication Normalindication —Setupparameter(PV1.E) RSPinputburnouterror(Loop1) BurnoutofanaloginputconnectedtoRSP Checkwiringandsensor.Error
indication is erased in normal operation.
Normal
indication RSPB.OUT —Setupparameter(PV1.E) BurnouterrorwhenRSPinputis
usedforcontrol(Loop1)
BurnoutofanaloginputconnectedtoRSP
whenRSPisusedforcontrolcomputation
Checkwiringandsensor.Error
indication is erased in normal operation.
Normal
indication OUT----- —Setupparameter(AD2.E) Feedbackinputresistor/current
burnout Feedbackinputburnout
Checkwiringoffeedbackinputresistor/
current.Errorindicationiserasedin
normal operation.
Normal
indication
Normalindication LADDERlampblinks Setupparameter(LA.ER)
Laddercalculationoverow Floatingpointcomputationforladder
calculationisinnite. Checktheladderprogram.
Loadfactorover100%
Computationdoesnotendwithinthe
controlperiod.(Whentheloadfactoris
100%ormore,andthecomputationdoes
notendwithinthecontrolperiod.)
Changethecontrolperiodorreduce
thenumberofstepsfortheladder
program.
Loadfactorover200%
(Forcedend)
Computationdoesnotendwithinthecontrol
period(loadfactoris200%ormore).
Changethecontrolperiodorreducethe
numberofstepsfortheladderprogram.
Ladderprogramerror Ladderprogramiscorrupted.
Downloadtheladderprogramagain.If
the error indication is still not erased,
thereisafault.Contactusforrepair.
0.00000000
(Decimalpointontheleftof
theSymboldisplayblinks)
—Setupparameter(OP.ER) Peer-to-peercommunicationerror Peer-to-peercommunicationerror
Checkthatthetargetdevicesare
connected correctly.
Recoveryatnormalreceipt.
AT.E Normalindication —Setupparameter(PV1.E/PV2.E) Auto-tuningtime-out
(Loop1,Loop2)
Auto-tuningdoesnotendevenwhen24
hourshaveelapsedafterthestartoftuning.
Checktheprocess.Holddownanykeyto
erase the error indication
VAT.E Normalindication —Setupparameter(AD2.E) Valvepositionautomatic
adjustmenterror
Fully-closedvalvepositionisequaltoorlarger
thanthefully-openvalvepositionafterautomatic
valvepositionadjustmentisperformed.
Checkwiringandvalve.Holddownany
key to erase the error indication.
Normal
indication
0.00000000
(Decimalpointontheleftof
theSymboldisplayblinks)
—Setupparameter(OP.ER) Communicationerror
(RS-485communication)
Framingparityerror
Bufferoverow
Inter-charactertime-out
Checksumerror(PClinkcommunicationwith
checksum)
CRCcheckerror(Modbus/RTU)
LRCcheckerror(Modbus/ASCII)
Checkthecommunicationparameters.
Recoveryatnormalreceipt.
Holddownanykeytostopblinking.
Normal
indication
0.00000000
(Decimalpointontheleftof
theSymboldisplayblinks)
—Setupparameter(OP.ER) Userproleerror Userproleiscorrupted. Downloadtheuserproleagain.
Normal
indication Normalindication
Rightmostdecimalpointon
Symboldisplayblinks.
Setupparameter(PA.ER) FaultyFRAM
Writing(storing)datatoFRAMisimpossible.
Faulty.Contactusforrepair.
Undened Undened — — FaultyMCU/DCU
(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.
Note:WhenanerroroccursininputshowninAnaloginputdisplay(Operationdisplay),SetpointdisplayshowsthesamesymbolasthePVdisplay.

IM 05P02C41-15EN page 5/14
Contents
1. NamesandFunctionsofDisplayParts
2. Setup Procedure
3. QuickSettingFunction(SettingofInputandOutput)
4.
AdjustingValvePositionAutomatically(foraPositionProportionalTypeControllerOnly)
5. SettingAlarmType
6. SettingAlarmSetpoint
1. Names and Functions of Display Parts
(2) + (3) + (4) : Setpoint display
(1)
(9)
(2)
(10)
(11)
(12)
(13)
(4)
(3)
(5)
(6)
(7)
(8)
No.ingure Name Description
(1) PVdisplay
(whiteorred)
DisplaysPV.
Displaysanerrorcodeifanerroroccurs.
DisplaysthescrollingguideintheMenuDisplayandParameter
SettingDisplaywhentheguidedisplayON/OFFissettoON.
(2)
Groupdisplay(pattern
number)
(green)
1to30representpatternnumbersintheOperationDisplay.
Displaysagroupnumber(1to8orR)andterminalarea(E1toE4)
intheParameterSettingDisplay.
(3)
Symboldisplay(orange)
Displaysaparametersymbol.
(4) Datadisplay(orange) Displaysaparametersetpointandmenusymbol.
(5)
Bar-graphdisplay
(event,alarm)
(orange)
DisplaystheeventstatusandthesegmentpositionintheOperation
Display.(Defaultvalues:Timeeventstatus,Alarmstatus)
Displayscontroloutputvalue(OUT)andmeasuredinputvalue(PV).
Thedatatobedisplayedcanbesetbytheparameter.
(6) Eventindicator
(orange)
LitwhenthePVeventsoccur.
Eventdisplayscanbesetbytheparameter.
(7) Keynavigationindica-
tor(green)
LitorblinkswhentheUp/DownorLeft/Rightarrowkeyoperation
ispossible.
(8) Parameterdisplaylevel
indicator(green)
Displaysthesettingconditionsoftheparameterdisplaylevelfunc-
tion.
Parameter display level EASY PRO
Easysettingmode Lit Unlit
Standardsettingmode Unlit Unlit
Professionalsettingmode Unlit Lit
(9) Programmonitor
(green)
Displaysthestatusofincrement,constancy,anddecrementofthe
programsetpoint.
:Litwhenaprogramsetpointisincreasing.
:Litwhenaprogramsetpointisconstant.
:Litwhenaprogramsetpointisdecreasing.
(10) Status indicator
(greenandred)
Displaystheoperatingconditionsandcontrolstatus.
Indicator Description
HLD Litwheninholdmode(HLD).
CAS Litwhenincascademode(CAS).
PRG
Litwheninprogramoperationmode(PRG).
LitwhiletheStartingtimeofprogramoperation
(S.TM)isavailable.
RST Litwheninresetmode(RST).
MAN Litwheninmanualmode(MAN).
Blinksduringauto-tuning.
(11) Securityindicator(red) Litifapasswordisset.Thesetupparametersettingsarelocked.
(12) Ladderoperation
indicator(green)
Litwhiletheladderprogramoperationisexecuted.
(13)
Loop2indicator
(LP2lamp)
(green)
LitwhenthecontrolmodeisCascadecontrol.
IntheOperationDisplay,theLP2lampislitwhiletheLoop-2data
is displayed on Setpoint display.
IntheParameterSettingDisplay,theLP2lampindicatesthe
loopofdisplayedmenusymbolorparametersymbol.TheLP2
lampislitwhiletheLoop-2menusymbolorparametersymbolis
displayed.
(4)
(5)
(1)
(2)
(3)
No.ingure Name Description
(1) DISPLAYkey
UsedtoswitchtheOperationDisplays.
PressthekeyintheOperationDisplaytoswitchtheprovided
OperationDisplays.
PressthekeyintheMenuDisplayorParameterSettingDisplay
toreturntotheOperationDisplay.
(2) PARAMETERkey
Holddownthekeyfor3secondstomovetotheOperation
ParameterSettingDisplay.
HolddownthekeyandtheLeftarrowkeysimultaneouslyfor3
secondstomovetotheSetupParameterSettingDisplay.
PressthekeyintheParameterSettingDisplaytoreturntothe
MenuDisplay.Pressthekeyoncetocanceltheparameterset-
ting(setpointisblinking).
(3)
SET/ENTERkey
Up/Down/Left/Right
arrow keys
SET/ENTERkey
PressthekeyintheMenuDisplaytomovetotheParameter
SettingDisplayoftheMenu.PressthekeyintheParameter
SettingDisplaytotransfertotheparametersettingmode
(setpointisblinking),andtheparametercanbechanged.
Pressthekeyduringparametersettingmodetoregisterthe
setpoint.
Up/Down/Left/Rightarrowkeys
PresstheLeft/RightarrowkeysintheMenuDisplaytoswitch
theDisplays.
PresstheUp/Down/Left/RightarrowkeysintheParameter
SettingDisplaytoswitchtheDisplays.
PresstheUp/Downarrowkeysduringparametersettingmode
(setpointisblinking)tochangeasetpoint.
PresstheLeft/Rightarrowkeysduringparametersettingmode
(setpointisblinking)tomovebetweendigitsaccordingtotheparameter.
(4) Light-loaderinterface
Itisthecommunicationinterfacefortheadaptercableusedwhen
settingandstoringparametersfromaPC.TheLL50AParameter
SettingSoftware(soldseparately)isrequired.
(5)
RUNkey
RSTkey
MODEkey
PTNkey
RUNkey:PresstheRUNkeyfor1secondwhileanoperation
displayisshownstartstheprogrampatternoperation.
RSTkey:PresstheRSTkeyfor1secondwhileanoperation
displayisshownstopstheprogrampatternoperation.
MODEkey:PresentsadisplayforswitchingbetweentheHOLD,
ADVANCE,PROG,RESET,LOCAL,REMOTEand
AUTO/MAN.Inordertochangetheoperationmode,
presstheSET/ENTERkeywhilethesetpointisblinking.
PTNkey:Aprogrampatternnumbercanbeselectedduringthe
operationexcepttheprogrampatternoperation.(The
programpatternnumberdisplayedontheGroupdisplay
blinks.)WhenthePTNkeyispressedwhiletheprogram
patternnumberisblinking,theblinkingstops.
Userscanassignfunctionstothekeyusingparameters.
Note: Thecommunicationconnector(maintenanceport)forLL50AParameterSettingSoftwareis
on the top of the unit.
2. Setup Procedure
ThefollowingowchartshowsthesetupprocedureforUP55A.
Install and wire a controller.
Monitoring and control of regular operations
Adjust PID using auto-tuning or manually for PID control.
Other setup
Operation
NO
NO NO
YES
YES YES
Control mode: Single-loop control only
Set the other parameters as needed.
Programming Set the program pattern.
PID tuning
Input setup
Output setup
Installation
and wiring
Power ON
Control mode setup
Control type setup
Control type setup
Input/output setup
Valve position
adjustment
Use
Quick setting
function?
Position
proportional
type?
Position
proportional
type?
For Position proportional type
3.
Quick Setting Function (Setting of Input and Output)
TheQuicksettingfunctionisafunctiontoeasilysetthebasicfunctionofthecontrol-
ler.
TurnonthecontrollertostarttheQuicksettingfunction.
Thisfunctionallowsyoutoeasilysetthecontroltype,input,andoutput,andquickly
start the control action.
Theitems(parameters)tobesetbyQuicksettingfunctionareasfollows.
(1)Controltype(PIDcontrol,Heating/coolingcontrol,etc.)
(2)Inputfunction(PVinputtype,range,scale(atvoltageinput),etc.)
(3)Outputfunction(controloutputtypeandcycletime)
Afterturningonthecontroller,rstdecidewhetherornottousetheQuicksettingfunc-
tion.
TheQuicksetting functioncan beusedonly whenthecontrol modeisSingle-loop
control.Forothercontrolmodes,setthefunctionswithout using the Quicksetting
function.
Operation in Initial Display
· PresstheSET/ENTERkeywhileYESisdisplayedtostarttheQuicksettingfunction.
· IfyouchangeYEStoNOandpresstheSET/ENTERkey,OperationDisplay will
appearwithoutstartingtheQuicksettingfunction.
Operation
Guide
Initial Settings
This operation guide describes basic settings and operations of the UP55A.
For details of each function, see User’s Manual.
The scrolling guide is displayed on PV display in the Parameter Setting Display.
This guide can be turned on/off with the MODE key.
UP55A
Program Controller
Operation Guide for Single-loop Control
Operation for Setting
· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrow
keytomovetothenextparameter.
· Tochangeandset theparametersetting, presstheSET/ENTER keytostartthe
setpointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).
UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/EN-
TERkeytoregisterthesetting.
■Making Settings Using Quick Setting Function
Example: SettingtoPIDcontrol,thermocoupletypeK(rangeof0.0to
500.00C), and current control output
Forthedetailedprocedureandswitchingofdisplays,see "Flow of Quick Setting
Function"below.Fortheparameterstoset,seethenextpage.
(1)PresstheSET/ENTERkeywhileYESforQSM(Quicksettingmode)isdisplayed.
(2)Setthecontroltypeparameter(CNT)toPID(PIDcontrol).
(3)SetthePVinputtypeparameter(IN)toK1(-270.0to1370.00C).
(4)SetthePVinputunitparameter(UNIT)toC(DegreeCelsius).
(5)SetthemaximumvalueofPVinputrangeparameter(RH)to500.0.
(6)SettheminimumvalueofPVinputrangeparameter(RL)to0.0.
(7)Settheoutputtypeselectionparameter(OT)toOUTterminals(current).
(8)Finally,EXITisdisplayed.ChangeNOtoYESandpresstheSET/ENTERkeyto
completethesetup.OperationDisplayappears.
■ FlowofQuickSettingFunction
InQuicksettingmode,theparameterguideappearsonPVdisplay.
Thisguidecanbeturnedon/offwiththeMODEkey.
First, the control type parameter
(CNT) is displayed.
Initial value: PID (PID control)
H/C (Heating/cooling control) for
Heating/cooling type unit.
The PV input type
parameter (IN) is
displayed.
Initial value: OFF
OFF blinks.
Blinking allows you to
change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum
value of PV input range) has been
changed to 500.0.
The setpoint for the parameter
RH has been registered.
The PV input unit parameter
(UNIT) is displayed.
Initial value: C (Degree
Celsius)
Press the SET/ENTER key
while YES is displayed to start
the Quick setting. Select NO with the Down
arrow key and press the
SET/ENTER key.
Select NO to return to
the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
The upper limit value of the
setting range is displayed for the
parameter RH (maximum value
of PV input range).
Change the setpoint using the Up/Down
arrow keys to increase and decrease the
value and the Left/Right arrow keys to
move between digits.
Finally, EXIT is displayed.
Press the SET/ENTER key to swtich to the setting mode.
Change NO to YES and press the SET/ENTER key to
complete the setup of the basic function.
Operation Display appears.
The Quick setting function continues in the NO state.
Displays the measured
input value (PV).
Displays the starting
target setpoint (SSP).
Follow the same procedure to set RL to 0.0 and
OT to 00.02.
Set other parameters as needed.
Quick setting starts
Power-on
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
12.
7.
[YES]
Operation Display
[NO]
First, the control type parameter
(CNT) is displayed.
Initial value: PID (PID control)
H/C (Heating/cooling control) for
Heating/cooling type unit.
The PV input type
parameter (IN) is
displayed.
Initial value: OFF
OFF blinks.
Blinking allows you to
change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum
value of PV input range) has been
changed to 500.0.
The setpoint for the parameter
RH has been registered.
The PV input unit parameter
(UNIT) is displayed.
Initial value: C (Degree
Celsius)
Press the SET/ENTER key
while YES is displayed to start
the Quick setting. Select NO with the Down
arrow key and press the
SET/ENTER key.
Select NO to return to
the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
The upper limit value of the
setting range is displayed for the
parameter RH (maximum value
of PV input range).
Change the setpoint using the Up/Down
arrow keys to increase and decrease the
value and the Left/Right arrow keys to
move between digits.
Finally, EXIT is displayed.
Press the SET/ENTER key to swtich to the setting mode.
Change NO to YES and press the SET/ENTER key to
complete the setup of the basic function.
Operation Display appears.
The Quick setting function continues in the NO state.
Displays the measured
input value (PV).
Displays the starting
target setpoint (SSP).
Follow the same procedure to set RL to 0.0 and
OT to 00.02.
Set other parameters as needed.
Quick setting starts
Power-on
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
12.
7.
[YES]
Operation Display
[NO]

IM 05P02C41-15EN page 6/14
■ Parameterstobeset
Control Type
Parameter Symbol Name of Parameter Setting Range
CNT Controltype
PID:PIDcontrol
ONOF:ON/OFFcontrol(1pointofhysteresis)
ONOF2:ON/OFFcontrol(2pointsofhysteresis)
H/C:Heating/coolingcontrol
Note: Somesetpointsmaynotbedisplayeddependingonthemodelandsuffixcodes.
Input Function
Parameter Symbol Name of Parameter Setting Range
IN PVinputtype
OFF:Disable
K1:-270.0to1370.00C/-450.0to2500.0 0F
K2:-270.0to1000.00C/-450.0to2300.0 0F
K3:-200.0to500.00C/-200.0to1000.0 0F
J:-200.0to1200.00C/-300.0to2300.0 0F
T1:-270.0to400.00C/-450.0to750.0 0F
T2:0.0to400.00C/-200.0to750.0 0F
B:0.0to1800.00C/32to3300 0F
S:0.0to1700.00C/32to3100 0F
R:0.0to1700.00C/32to3100 0F
N:-200.0to1300.00C/-300.0to2400.0 0F
E:-270.0to1000.00C/-450.0to1800.0 0F
L:-200.0to900.00C/-300.0to1600.0 0F
U1:-200.0to400.00C/-300.0to750.0 0F
U2:0.0to400.00C/-200.0to1000.0 0F
W:0.0to2300.00C/32to4200 0F
PL2:0.0to1390.00C/32.0to2500.0 0F
P2040:0.0to1900.00C/32to3400 0F
WRE:0.0to2000.00C/32to3600 0F
JPT1:-200.0to500.00C/-300.0to1000.0 0F
JPT2:-150.00to150.000C/-200.0to300.0 0F
PT1:-200.0to850.00C/-300.0to1560.0 0F
PT2:-200.0to500.00C/-300.0to1000.0 0F
PT3:-150.00to150.000C/-200.0to300.0 0F
0.4-2V:0.400to2.000V
1-5V:1.000to5.000V
4-20:4.00to20.00mA
0-2V:0.000to2.000V
0-10V:0.00to10.00V
0-20:0.00to20.00mA
-1020:-10.00to20.00mV
0-100:0.0to100.0mV
UNIT PVinputunit -:Nounit,C:DegreeCelsius
-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit
RH Maximumvalueof
PVinputrange
Dependsontheinputtype.
-Fortemperatureinput-
Setthetemperaturerangethatisactuallycontrolled.
(RL<RH)
-Forvoltage/currentinput-
Settherangeofavoltage/currentsignalthatisapplied.
Thescaleacrosswhichthevoltage/currentsignalis
actuallycontrolledshouldbesetusingthemaximumvalue
ofinputscale(SH)andminimumvalueofinputscale(SL).
(Inputisalways0%whenRL=RH.)
RL Minimumvalueof
PVinputrange
SDP
PVinputscale
decimal point
position
0:Nodecimalplace
1:Onedecimalplace
2: Two decimal places
3: Three decimal places
4: Four decimal places
SH Maximumvalueof
PVinputscale -19999to30000,(SL<SH),|SH-SL|≤30000
SL Minimumvalueof
PVinputscale
Note1:SDP,SH,andSLaredisplayedonlyforvoltage/currentinput.
Note2:W:W-5%Re/W-26%Re(HoskinsMfg.Co.),ASTME988
Output Function
Parameter Symbol Name of Parameter Setting Range
OT
Outputtypeselection
Uppertwodigits
Lowertwodigits
ControloutputorHeating-
sidecontroloutput(Lower
twodigits)
00:OFF
01:OUTterminals(voltage
pulse)
02:OUTterminals(current)
03:OUTterminals(relay/
triac)
04:OUT2terminals(voltage
pulse)
05:OUT2terminals(current)
06:OUT2terminals(relay/
triac)
Cooling-sidecontroloutput
(Uppertwodigits)
00:OFF
01:OUTterminals(voltage
pulse)
02:OUTterminals(current)
03:OUTterminals(relay/
triac)
04:OUT2terminals(voltage
pulse)
05:OUT2terminals(current)
06:OUT2terminals(relay/
triac)
CT
Controloutputcycle
time
Heating-sidecontrol
output cycle time
(inHeating/cooling
control)
0.5to1000.0s
CTc
Cooling-sidecontrol
output cycle time
4.
Adjusting Valve Position Automatically
(for a Position Proportional Type Controller Only)
Thefollowingoperatingproceduredescribeshowtoinputfeedbacksignalsfromthe
controlvalveandadjustthefully-openandfully-closedpositionsofthecontrolvalve
automatically.Thefully-openandfully-closedpositionsofthevalvecanbeadjusted
automaticallybyinputtingfeedbacksignalsfromthevalve.Toadjustthevalveposi-
tion,youneedtocarryouttheconnectionandbringthecontrollerintomanualmode.
Fortheconnection,see“6.TerminalWiringDiagrams”in"InstallationandWiring",
andforthemanualmode,see“5.SwitchingbetweenAUTOandMAN”in"Opera-
tions."Theautomaticadjustmentcanbedoneinprogrampatternoperation,local
operation, and remote operation.
CTL menu is displayed.
+
OUT menu is displayed.
OFF blinks.
1.
2.
3.
4.
5.
6.
7.
Show the Operation Display.
MAN
is lit
* When a password is set, PASS is displayed.
If the correct password is not entered, setup
parameters cannot be changed.
Hold down the keys for 3 seconds.
Press the Right arrow key until OUT menu
appears.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter V.AT (automatic valve
position adjustment) is displayed.
Press the Up arrow key.
ON is displayed.
Blinks during the change.
ON has been registered and the automatic
adjustment of the valve position starts.
V.AT blinks during the automatic
adjustment.
After the adjustment is completed, press
the DISPLAY key or DISP key once to
return to the Operation Display.
● When the adjustment is completed normally, the indication
automatically returns to OFF.
● When VAT.E appears on PV display, it indicates an error.
Check the wiring for feedback input and perform the automatic
adjustment again. To perform a valve adjustment manually, see
User’s Manual.
5. Setting Alarm Type
Thefollowingoperatingprocedureshowsanexampleofchangingthealarm-1type
(factorydefault:PVhighlimitalarm)toPVlowlimitalarm(setpoint:02).(These
alarmsworkirrespectiveoftheoperationmode.)
MODE menu is displayed.
ALRM menu is displayed.
1.
2.
3.
4.
5.
6.
Symbol
Show the Operation Display.
Hold down the key for 3 seconds.
Press the Right arrow key until ALRM menu appears.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter AL1 (alarm-1 type) is
displayed.
The last digit of the setpoint blinks.
Change the setpoint using the Up/Down arrow keys
to increase and decrease the value and the
Left/Right arrow keys to move between digits.
The alarm-1 type setpoint 02 (PV low limit) is
registered.
After the setup is completed, press the DISPLAY
key once to return to the Operation Display.
Stand-by action
Energized/De-energized
Latch action
● To change the alarm type, change the last 2 digits of the
5-digit value.
● Stand-by action and excitation are turned on or off by
selecting 1 or 0. (See “Setting Display of Alarm Type.”)
● For the latch action, see User’s Manual.
Press the Up/Down arrow keys to display the
parameter needs to be changed.
MODE menu is displayed.
ALRM menu is displayed.
1.
2.
3.
4.
5.
6.
Symbol
Show the Operation Display.
Hold down the key for 3 seconds.
Press the Right arrow key until ALRM menu appears.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter AL1 (alarm-1 type) is
displayed.
The last digit of the setpoint blinks.
Change the setpoint using the Up/Down arrow keys
to increase and decrease the value and the
Left/Right arrow keys to move between digits.
The alarm-1 type setpoint 02 (PV low limit) is
registered.
After the setup is completed, press the DISPLAY
key once to return to the Operation Display.
Stand-by action
Energized/De-energized
Latch action
● To change the alarm type, change the last 2 digits of the
5-digit value.
● Stand-by action and excitation are turned on or off by
selecting 1 or 0. (See “Setting Display of Alarm Type.”)
● For the latch action, see User’s Manual.
Press the Up/Down arrow keys to display the
parameter needs to be changed.
Hysteresis
Alarm setpoint PV, RSP, AIN2
or AIN4
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation
setpoint
PV
Hysteresis Hysteresis
Open
(unlit)
Closed
(lit)
SP or Target SP
PV
Deviation setpoint
Hysteresis
- -
SP or Target SP
PV
Hysteresis Hysteresis
Deviation
setpoint
Open
(unlit)
SP or
Target SP
Alarm setpoint
Hysteresis
SP or
Target SP
Hysteresis
Alarm setpoint
Alarm setpoint
Output
Hysteresis
Closed
(lit)
Hysteresis
Alarm setpoint
Output
Alarm setpoint
Hysteresis
PV, RSP, AIN2
or AIN4
Hysteresis
Alarm setpoint PV, RSP, AIN2
or AIN4
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation
setpoint
PV
Hysteresis Hysteresis
SP or Target SP
PV
Deviation setpoint
Hysteresis
SP or Target SP
PV
Hysteresis Hysteresis
Deviation
setpoint
Closed
(unlit)
SP or
Target SP
Alarm setpoint
Hysteresis
SP or
Target SP
Hysteresis
Alarm setpoint
Alarm setpoint
Hysteresis
PV, RSP, AIN2
or AIN4
Alarm setpoint
Output
Hysteresis
Hysteresis
Alarm setpoint
Output
Setting Display of Alarm Type Stand-by Action
Energized (0) / De-energized (1)
Alarm type
Without (0) or With (1)
Stand-by action
Latch action (0/1/2/3/4)
See User’s Manual.
PV low limit
alarm setpoint
Treated
as normal
ºC
Power-on Time
The alarm output does not turn on
in this region even if the PV valule
is below PV low limit alarm setpoint.
Normal Abnormal
The alarm output
turns on.
No alarm (00)
Alarm Action (De-energized)
PV high limit (01)
Analog input PV high limit (19)
Analog input RSP high limit (21)
Analog input AIN2 high limit (23)
Analog input AIN4 high limit (25)
PV low limit (02)
Analog input PV low limit (20)
Analog input RSP low limit (22)
Analog input AIN2 low limit (24)
Analog input AIN4 low limit (26)
SP high limit (03)
Target SP high limit (09)
SP low limit (04)
Target SP low limit (10)
Deviation high limit (05)
Target SP deviation high
limit (11)
Deviation low limit (06)
Target SP deviation low limit (12)
Deviation high and low
limits (07)
Target SP deviation high and
low limits (13)
Deviation within high and low
limits (08)
Target SP deviation within high
and low limits (14)
Control output high limit (15)
Cooling-side control output
high limit (17)
Control output low limit (16)
Cooling-side control output
low limit (18)
Feedback input high limit (27)
Feedback input low limit (28)
PV velocity (29)
Fault diagnosis alarm (30)
FAIL (31)
Alarm Type (Alarm Setpoint) Alarm Action (Energized)
Open
(unlit)
Open
(unlit)
Open
(lit)
Closed
(lit) Open
(unlit)Open
(lit)Closed
(unlit)
Closed
(
unlit
)
Open
(lit)
Closed
(unlit) Closed
(unlit)
Open
(lit)
Open
(lit)
Closed
(lit) Closed
(lit)
Closed
(lit)
Closed
(lit)
Closed
(lit)
Closed
(lit)
Closed
(lit)
Closed
(lit)
Open
(unlit)
Open
(unlit)
Open
(unlit)
Open
(unlit)
Open
(unlit)
Open
(unlit)
Open
(lit)
Open
(lit)
Open
(lit)
Open
(lit)
Open
(lit)
Open
(lit)
Closed
(unlit)
Closed
(unlit)
Closed
(unlit)
Closed
(unlit)
Closed
(unlit)
Closed
(unlit)
Burnout of PV input, RSP remote input, or AIN2/AIN4 auxiliary
analog input. ADC failure, RJC error.
For the factory default, the contact output is turned ON in normal operation,
OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF
Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2: Positive setpoint, Negative setpoint
Hysteresis
Alarm setpoint PV, RSP, AIN2
or AIN4
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation
setpoint
PV
Hysteresis Hysteresis
Open
(unlit)
Closed
(lit)
SP or Target SP
PV
Deviation setpoint
Hysteresis
- -
SP or Target SP
PV
Hysteresis Hysteresis
Deviation
setpoint
Open
(unlit)
SP or
Target SP
Alarm setpoint
Hysteresis
SP or
Target SP
Hysteresis
Alarm setpoint
Alarm setpoint
Output
Hysteresis
Closed
(lit)
Hysteresis
Alarm setpoint
Output
Alarm setpoint
Hysteresis
PV, RSP, AIN2
or AIN4
Hysteresis
Alarm setpoint PV, RSP, AIN2
or AIN4
SP or Target SP
Hysteresis
PV Deviation setpoint
SP or Target SP
Deviation
setpoint
PV
Hysteresis Hysteresis
SP or Target SP
PV
Deviation setpoint
Hysteresis
SP or Target SP
PV
Hysteresis Hysteresis
Deviation
setpoint
Closed
(unlit)
SP or
Target SP
Alarm setpoint
Hysteresis
SP or
Target SP
Hysteresis
Alarm setpoint
Alarm setpoint
Hysteresis
PV, RSP, AIN2
or AIN4
Alarm setpoint
Output
Hysteresis
Hysteresis
Alarm setpoint
Output
Setting Display of Alarm Type Stand-by Action
Energized (0) / De-energized (1)
Alarm type
Without (0) or With (1)
Stand-by action
Latch action (0/1/2/3/4)
See User’s Manual.
PV low limit
alarm setpoint
Treated
as normal
ºC
Power-on Time
The alarm output does not turn on
in this region even if the PV valule
is below PV low limit alarm setpoint.
Normal Abnormal
The alarm output
turns on.
No alarm (00)
Alarm Action (De-energized)
PV high limit (01)
Analog input PV high limit (19)
Analog input RSP high limit (21)
Analog input AIN2 high limit (23)
Analog input AIN4 high limit (25)
PV low limit (02)
Analog input PV low limit (20)
Analog input RSP low limit (22)
Analog input AIN2 low limit (24)
Analog input AIN4 low limit (26)
SP high limit (03)
Target SP high limit (09)
SP low limit (04)
Target SP low limit (10)
Deviation high limit (05)
Target SP deviation high
limit (11)
Deviation low limit (06)
Target SP deviation low limit (12)
Deviation high and low
limits (07)
Target SP deviation high and
low limits (13)
Deviation within high and low
limits (08)
Target SP deviation within high
and low limits (14)
Control output high limit (15)
Cooling-side control output
high limit (17)
Control output low limit (16)
Cooling-side control output
low limit (18)
Feedback input high limit (27)
Feedback input low limit (28)
PV velocity (29)
Fault diagnosis alarm (30)
FAIL (31)
Alarm Type (Alarm Setpoint) Alarm Action (Energized)
Open
(unlit)
Open
(unlit)
Open
(lit)
Closed
(lit) Open
(unlit)Open
(lit)Closed
(unlit)
Closed
(
unlit
)
Open
(lit)
Closed
(unlit) Closed
(unlit)
Open
(lit)
Open
(lit)
Closed
(lit) Closed
(lit)
Closed
(lit)
Closed
(lit)
Closed
(lit)
Closed
(lit)
Closed
(lit)
Closed
(lit)
Open
(unlit)
Open
(unlit)
Open
(unlit)
Open
(unlit)
Open
(unlit)
Open
(unlit)
Open
(lit)
Open
(lit)
Open
(lit)
Open
(lit)
Open
(lit)
Open
(lit)
Closed
(unlit)
Closed
(unlit)
Closed
(unlit)
Closed
(unlit)
Closed
(unlit)
Closed
(unlit)
Burnout of PV input, RSP remote input, or AIN2/AIN4 auxiliary
analog input. ADC failure, RJC error.
For the factory default, the contact output is turned ON in normal operation,
OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF
Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2: Positive setpoint, Negative setpoint
NotethattheSPinreset-modeisSSP(Startingtargetsetpoint).
6. Setting Alarm Setpoint
Thefollowingoperatingprocedureshowsanexampleofsettingthealarm-1setpoint
to180.0.(Thesealarmsworkirrespectiveoftheoperationmode.)
Beforesettingthealarmsetpoint,checkthealarmtype.
Tochangethealarmtype,see“5.SettingAlarmType.”
Display the parameter that need to
be changed.
Blinks during the change.
1.
2.
3.
4.
5.
6.
Show the Operation Display.
Display MODE menu with the same procedure as described in
Setting Alarm Type.
Press the Right arrow key.
AL menu is displayed.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter A1 is displayed.
A1 to A8 represent the alarm-1 to -8
setpoints.
Each parameter can be changed in the
Parameter Setting Displays of alarms using
arrow keys.
Up/Down arrow keys: changing parameters
The setpoint has been registered.
After the setup is completed, press
the DISPLAY key once to return to
the Operation Display.
Change the setpoint using the Up/Down
arrow keys to increase and decrease the
value and the Left/Right arrow keys to
move between digits.

IM 05P02C41-15EN page 7/14
Contents
1. OverviewofProgramPatterns
2. CreatingProgramPatterns
3. ProgramPatternSetupCharts
1. Overview of Program Patterns
Theprogrammingexamplegivenheredemonstrateshowto do the tasksoutlined
below.
1) Program the controller to start program operation at 50.0°C and raise the
temperature up to 100.0°C in 50 minutes.
2) When the temperature reaches 100.0°C, keep it at this level for 30 minutes.
3) Raise the temperature up to 200.0°C in 60 minutes.
4) When the temperature reaches 200.0°C, keep it at this level for 30 minutes.
5) Lower the temperature to 50.0°C in 50 minutes.
6) When the temperature reaches 50.0°C, keep it at this level for 30 minutes.
PVinputrangesarefollowing:
MaximumvalueofPVinputrange:250.0°C
MinimumvalueofPVinputrange:0.0°C
PVinputunit:C
ZonePIDselection(ZON):SegmentPIDselection(0)
Segmentsettingmethod(SEG.T):Segmenttimesetting(TIME)
Programtimeunit(TMU):hour.minute(HH.MM)
Seg.1 Seg.2 Seg.3 Seg.4 Seg.5 Seg.6
321
PV event 1
Segment time
TIME
Segment PID number
S.PIDN
100.0ºC
50.0ºC
200.0ºC
Time event 1
Time event 2
4 5 6
60 min.30 min.50 min. 30 min. 50 min. 30 min. Time
Setpoint
TSP
TSP
TSP
The display symbols of the parameters, TSP (Final target setpoint), TIME (Segment
time setting), and S.PID (Segmet PID number selection) are the same in each
segment. However, the segment can be recognized by the number displayed on the
Symbol display.
TSP
SSP
TSP
Dev. high (5ºC)
PV high (110ºC)
On
On On On
OnOff
Off Off Off
Off Off Off Off OffOn
Dev. high (5ºC)
PV high (210ºC)
Dev. low (5ºC)
PV low (10ºC)
SeeUser'sManualfortheWaitandRepeatactions, Zone PID, Startofprogram
operation(Startcode),Changingoperationmodeat segment switching(Junction
code),Localmode,andRemotemode.
Operation
Guide
Programming
UP55A
Program Controller
Operation Guide for Single-loop Control
This operation guide describes basic program settings of the UP55A.
For details of each function, see User’s Manual.
The scrolling guide is displayed on PV display in the Parameter Setting Display.
This guide can be turned on/off with the MODE key. (The scrolling guide is OFF when
displaying the Program parameter setting display first.)
2. Creating Program Patterns
Thefollowingoperatingproceduredescribesan example ofcreatingtheprogram
discussedin“1.OverviewofProgramPatterns.”
CAUTION
Note that the program patterns are all deleted if the settings change
after creating program patterns.
Be sure to check the PV input range, Program time unit (TMU), and
Segment setting method (SEG.T) before creating.
PTNO.=1
SEGNO.=0
1.
2.
3.
4.
5.
Set the common parameter of the specified pattern.
When SEGNO.=0, set the common parameter for
the pattern specified.
When SEGNO.=1 to 99, set the parameter for the
segment specified.
6.
7.
Starting target setpoint=50.0°C
STC=SSP (Starting target setpoint)
8.
Segment 1
Set the final target setpoint.
9.
10.
11.
Final target setpoint=100.0°C
Set the segment time.
Keep the initial value.
Pattern number
RST lamp is lit.
Hold down the keys for 3 seconds.
Show the Operation Display.
MODE menu is displayed.
PROG menu is displayed.
Press the Right arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Press the Down arrow key.
Set the final target setpoint.
Continues the TSP of segment 1.
12.
Set the segment PID number.
Keep the initial value.
Keep the initial value.
Set the junction code.
Segment time=50 minutes
13.
14.
15.
16.
Time event-2 starts from the Off state.
There is no the Off time.
Set the On time.
PV event-1 type=Deviation high limit
Set the PV event-1 type.
Set the PV event-1 setpoint.
17.
18.
PV event-1 setpoint=5.0°C
25. Set the segment time.
19.
20.
21.
On time=25 minutes
22.
23.
24.
Segment 2
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the Up/Down arrow keys to move the
parameters for segment-1 and the Left/Right
arrow keys to move between each segmets.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TIM1 appears.)
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Time event-1 starts from the Off state.
● Settings for the segment 3 to 6 can be done similarly.
● For programming and the settings for Wait and Repeat actions,
see User's Manual.
Set the junction code.
In this case, the former segment is left unchanged.
PV event-1 type=PV high limit
Set the PV event-1 type.
26.
Segment time=30 minutes
Segment PID number=2
27.
29.
30.
Set the segment PID number.
Set the PV event-1 setpoint.
32.
31.
28.
Start condition of time event 2=ON start
33.
PV event-1 setpoint=110.0°C
35. Set the time event 2.
34.
36.
37. Press the DISPLAY key once to return to the
Operation Display.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key. (until TIM2 appears.)
Press the Down arrow key (until TIM1 appears.)
Change the Up/Down arrow keys to move the
parameters for segment-1 and the Left/Right
arrow keys to move between each segmets.
Press the Down arrow key.
Time event-1 starts from the Off state.
PTNO.=1
SEGNO.=0
1.
2.
3.
4.
5.
Set the common parameter of the specified pattern.
When SEGNO.=0, set the common parameter for
the pattern specified.
When SEGNO.=1 to 99, set the parameter for the
segment specified.
6.
7.
Starting target setpoint=50.0°C
STC=SSP (Starting target setpoint)
8.
Segment 1
Set the final target setpoint.
9.
10.
11.
Final target setpoint=100.0°C
Set the segment time.
Keep the initial value.
Pattern number
RST lamp is lit.
Hold down the keys for 3 seconds.
Show the Operation Display.
MODE menu is displayed.
PROG menu is displayed.
Press the Right arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Press the Down arrow key.
Set the final target setpoint.
Continues the TSP of segment 1.
12.
Set the segment PID number.
Keep the initial value.
Keep the initial value.
Set the junction code.
Segment time=50 minutes
13.
14.
15.
16.
Time event-2 starts from the Off state.
There is no the Off time.
Set the On time.
PV event-1 type=Deviation high limit
Set the PV event-1 type.
Set the PV event-1 setpoint.
17.
18.
PV event-1 setpoint=5.0°C
25. Set the segment time.
19.
20.
21.
On time=25 minutes
22.
23.
24.
Segment 2
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the Up/Down arrow keys to move the
parameters for segment-1 and the Left/Right
arrow keys to move between each segmets.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TIM1 appears.)
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Time event-1 starts from the Off state.
● Settings for the segment 3 to 6 can be done similarly.
● For programming and the settings for Wait and Repeat actions,
see User's Manual.
Set the junction code.
In this case, the former segment is left unchanged.
PV event-1 type=PV high limit
Set the PV event-1 type.
26.
Segment time=30 minutes
Segment PID number=2
27.
29.
30.
Set the segment PID number.
Set the PV event-1 setpoint.
32.
31.
28.
Start condition of time event 2=ON start
33.
PV event-1 setpoint=110.0°C
35. Set the time event 2.
34.
36.
37. Press the DISPLAY key once to return to the
Operation Display.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key. (until TIM2 appears.)
Press the Down arrow key (until TIM1 appears.)
Change the Up/Down arrow keys to move the
parameters for segment-1 and the Left/Right
arrow keys to move between each segmets.
Press the Down arrow key.
Time event-1 starts from the Off state.
PTNO.=1
SEGNO.=0
1.
2.
3.
4.
5.
Set the common parameter of the specified pattern.
When SEGNO.=0, set the common parameter for
the pattern specified.
When SEGNO.=1 to 99, set the parameter for the
segment specified.
6.
7.
Starting target setpoint=50.0°C
STC=SSP (Starting target setpoint)
8.
Segment 1
Set the final target setpoint.
9.
10.
11.
Final target setpoint=100.0°C
Set the segment time.
Keep the initial value.
Pattern number
RST lamp is lit.
Hold down the keys for 3 seconds.
Show the Operation Display.
MODE menu is displayed.
PROG menu is displayed.
Press the Right arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Press the Down arrow key.
Set the final target setpoint.
Continues the TSP of segment 1.
12.
Set the segment PID number.
Keep the initial value.
Keep the initial value.
Set the junction code.
Segment time=50 minutes
13.
14.
15.
16.
Time event-2 starts from the Off state.
There is no the Off time.
Set the On time.
PV event-1 type=Deviation high limit
Set the PV event-1 type.
Set the PV event-1 setpoint.
17.
18.
PV event-1 setpoint=5.0°C
25. Set the segment time.
19.
20.
21.
On time=25 minutes
22.
23.
24.
Segment 2
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the Up/Down arrow keys to move the
parameters for segment-1 and the Left/Right
arrow keys to move between each segmets.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TIM1 appears.)
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key (until TSP appears.)
Press the Down arrow key.
Time event-1 starts from the Off state.
● Settings for the segment 3 to 6 can be done similarly.
● For programming and the settings for Wait and Repeat actions,
see User's Manual.
Set the junction code.
In this case, the former segment is left unchanged.
PV event-1 type=PV high limit
Set the PV event-1 type.
26.
Segment time=30 minutes
Segment PID number=2
27.
29.
30.
Set the segment PID number.
Set the PV event-1 setpoint.
32.
31.
28.
Start condition of time event 2=ON start
33.
PV event-1 setpoint=110.0°C
35. Set the time event 2.
34.
36.
37. Press the DISPLAY key once to return to the
Operation Display.
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key. (Blinks during the change.)
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value and the
Left/Right arrow keys to move between digits.
Change the setpoint using the Up/Down arrow
keys to increase and decrease the value.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key. (until TIM2 appears.)
Press the Down arrow key (until TIM1 appears.)
Change the Up/Down arrow keys to move the
parameters for segment-1 and the Left/Right
arrow keys to move between each segmets.
Press the Down arrow key.
Time event-1 starts from the Off state.

IM 05P02C41-15EN page 8/14
3. Program Pattern Setup Charts
Youcanregistermax.99programsegmentswith the UP55A controller.Createas
many copies of the chart as necessary.
System name
ProgramNo.
Programname
Model
SerialNo.
Thefollowingparametersarenecessarytobesetbeforeprogrammings.
NotethattheprogramisdeletedifTMUorSEG.Tischangedaftercreating pro-
grams.
Forthesettingrange,see"Parameters."
< Setup Parameters >
Parametersymbol Parameter name Usersettings
TMU Programtimeunit
SEG.T Segmentsettingmethod
ZON ZonePIDselection
PT2.G Programpattern-2retransmission
Thefollowingparametersarecommonparametersfortheprogrampatternspecied.
Forthesettingrange,see"Parameters."
< Program Pattern Data (common parameter) >
Parametersymbol Parameter name Usersettings
SSP Startingtargetsetpoint
SSP Startingtargetsetpoint(forprogrampattern-2retransmission)
STC Start code
WT.SW1 WaitfunctionON/OFF1
WZ.UP1 Upper-sidewaitzone1
WZ.LO1 Lower-sidewaitzone1
WT.TM1 Waittime1
WT.SW2 WaitfunctionON/OFF2
WZ.UP2 Upper-sidewaitzone2
WZ.LO2 Lower-sidewaitzone2
WT.TM2 Waittime2
WT.SW3 WaitfunctionON/OFF3
WZ.UP3 Upper-sidewaitzone3
WZ.LO3 Lower-sidewaitzone3
WT.TM3 Waittime3
WT.SW4 WaitfunctionON/OFF4
WZ.UP4 Upper-sidewaitzone4
WZ.LO4 Lower-sidewaitzone4
WT.TM4 Waittime4
WT.SW5 WaitfunctionON/OFF5
WZ.UP5 Upper-sidewaitzone5
WZ.LO5 Lower-sidewaitzone5
WT.TM5 Waittime5
R.CYCL Numberofrepeatcycles
R.STRT Repeatcyclestartsegmentnumber
R.END Repeatcycleendsegmentnumber
Error Indication at Program Pattern Creation and Editing
Errorcode Errorinformation Causeoferror
ERR01
Patterncreationorediting
isdisableduringprogram
operation.
Deletingorcopyingoftheprogrampattern,orinserting
ordeletingofthesegmentwasexecutedduringprogram
operation.
ERR22 Segmentwriteerror Thetotalnumberofsegmentsexceeded300.
ERR23 Segmentinserterror Newsegmentcannotbeinsertedbecausethenumberof
segmentsinapatternexceeded99.
ERR32 Pattern source
specicationerror Nopatternexistsinthesource.
ERR33 Pattern destination
specicationerror Patternsalreadyexistinthedestination.
ERR41 Pattern delete error Thepatterntobedeleteddoesnotexist.
Excepttheaboveerrors,therearesomeerrorcodesincommunication.Fordetails,
seeUser'sManual.
< Program Pattern Data (parameters for segments) >
MaximumvalueofPVinputrange/MaximumvalueofPVinputscale
()
Unit()
Aprogrampatterncanbedrawnintherighttable.
MinimumvalueofPVinputrange/MinimumvalueofPVinputscale
()
Parameter
symbol Parameter name Segments
1234567 8 9 10 11 12 13 14 15 16 17 18 19 20
TSP Finaltargetsetpoint
TSP
FinaltargetsetpointforProgrampattern-2retransmission
TIME Segmenttimesetting
TM.RT Segmentramp-ratesetting
S.PID SegmentPIDnumberselection
JC Junction code
PV.TY1 PVevent-1type
PV.EV1 PVevent-1setpoint
PV.TY2 PVevent-2type
PV.EV2 PVevent-2setpoint
PV.TY3 PVevent-3type
PV.EV3 PVevent-3setpoint
PV.TY4 PVevent-4type
PV.EV4 PVevent-4setpoint
PV.TY5 PVevent-5type
PV.EV5 PVevent-5setpoint
PV.TY6 PVevent-6type
PV.EV6 PVevent-6setpoint
PV.TY7 PVevent-7type
PV.EV7 PVevent-7setpoint
PV.TY8 PVevent-8type
PV.EV8 PVevent-8setpoint
TME1 Startconditionoftimeevent1
T.ON1 Ontimeoftimeevent1
T.OF1 Offtimeoftimeevent1
TME2 Startconditionoftimeevent2
T.ON2 Ontimeoftimeevent2
T.OF2 Offtimeoftimeevent2
TME3 Startconditionoftimeevent3
T.ON3 Ontimeoftimeevent3
T.OF3 Offtimeoftimeevent3
TME4 Startconditionoftimeevent4
T.ON4 Ontimeoftimeevent4
T.OF4 Offtimeoftimeevent4
TME5 Startconditionoftimeevent5
T.ON5 Ontimeoftimeevent5
T.OF5 Offtimeoftimeevent5
TME6 Startconditionoftimeevent6
T.ON6 Ontimeoftimeevent6
T.OF6 Offtimeoftimeevent6
TME7 Startconditionoftimeevent7
T.ON7 Ontimeoftimeevent7
T.OF7 Offtimeoftimeevent7
TME8 Startconditionoftimeevent8
T.ON8 Ontimeoftimeevent8
T.OF8 Offtimeoftimeevent8
TME9 Startconditionoftimeevent9
T.ON9 Ontimeoftimeevent9
T.OF9 Offtimeoftimeevent9
TME10 Startconditionoftimeevent10
T.ON10 Ontimeoftimeevent10
T.OF10 Offtimeoftimeevent10
TME11 Startconditionoftimeevent11
T.ON11 Ontimeoftimeevent11
T.OF11 Offtimeoftimeevent11
TME12 Startconditionoftimeevent12
T.ON12 Ontimeoftimeevent12
T.OF12 Offtimeoftimeevent12
TME13 Startconditionoftimeevent13
T.ON13 Ontimeoftimeevent13
T.OF13 Offtimeoftimeevent13
TME14 Startconditionoftimeevent14
T.ON14 Ontimeoftimeevent14
T.OF14 Offtimeoftimeevent14
TME15 Startconditionoftimeevent15
T.ON15 Ontimeoftimeevent15
T.OF15 Offtimeoftimeevent15
TME16 Startconditionoftimeevent16
T.ON16 Ontimeoftimeevent16
T.OF16 Offtimeoftimeevent16

IM 05P02C41-15EN page 9/14
Contents
1. Monitoring-purposeOperationDisplaysAvailableduringOperation
2. Performing/CancelingAuto-tuning
3. SelectingProgramPatternNumber(PT.No)
4. SwitchingbetweenRUNandRESET
5. SwitchingbetweenAUTOandMAN
6. ManipulatingControlOutputinManualMode
7. Enabling/DisablingHold-mode(HOLD)ofProgramOperation
8. ChangingProgramSetpointswheninHold-mode(HOLD)
9. Executing“Advance”(ADV)Function
10.SwitchingtoLocal-mode(LOCAL)Operation
11.ChangingSetpointsduringLocal-mode(LOCAL)Operation
12.SwitchingtoRemote-mode(REMOTE)Operation
13.Troubleshooting
1. Monitoring-purpose Operation Displays Available during Operation
■
Operation Display Switching Diagram
SP Display
TSP Display
Remaining Segment-time Display
Segment Number Display
Remaining Repetition Display
Program Pattern Display
OUT Display / Heating/cooling OUT Display
Displays the target setpoint (SP) on Setpoint display.
Displays "SSP" during reset-mode.
Displays "L.SP" during local-mode operation.
Displays "R.SP" during remote-mode operation.
Displays the final target setpoint (TSP) on Setpoint display
only during program operation.
Displays the remaining segment time (R.TIM) on Setpoint
display during program operation.
Displays the segment number (SEG.N) for which operation is
in progress, the number of segments included in the selected
program pattern.
Displays the number of remaining repetitions (R.CYC) on
Setpoint display. This display is displayed only when the
repeat function is set and the operation mode is PROG.
Displays the program pattern (overview) on Setpoint display.
Program pattern display can be scrolled using
Up/Down/Left/Right arrow keys.
Soak and ramp can be displayed.
Displays the measured input value on PV display.
Displays the control output value (OUT) on Setpoint display.
Displays the control output values (C.H.) of heating and
cooling sides on Setpoint display (C.H. can be changed in
manual mode).
AftershowingtheProgramPatternDisplay,presstheDISPLAYkeytoshowthefol-
lowingdisplaysconditionally.
Fordetails,seeUser’sManual.
Standard, Position Proportional, and Heating/Cooling Types
• SELECTDisplays1to5(whichappearwhenregistered)
• AnalogInputDisplay(displayonly)(factorydefault:non-display)
• PositionProportional Computation Output Display(display only) (factorydefault:
non-display)
• PIDNumberDisplay(displayonly)(factorydefault:non-display)
• Alarm-5to-8StatusDisplay(whichappearwhenregistered)
•
HeaterBreakAlarm-1CurrentDisplay(displayonly)(forheaterbreakalarmoptiononly)
•
HeaterBreakAlarm-2CurrentDisplay(displayonly)(forheaterbreakalarmoptiononly)
■
Event Display
Timeevent(TME),PVevent(PVE)andalarm(AL)aredisplayedontheBar-graph
displayandtheEventIndicator.(factorydefaultsetting)
PV event 1 to 8
Time event 1 to 16
Alarm 1 to 4
■
Operation Display Switching Diagram
*1: For another operation, when select
ADV=ON and starts program
operation. In this case, the segment
is advanced.
(1) Press RUN key for 1 s.
(2) Press RST key for 1 s.
(3) Press MODE key, select HOLD=ON and press SET/ENT key.
(4) Press MODE key, select HOLD=OFF and SET/ENT key.
(5) Press MODE key, select LOC=ON and press SET/ENT key.
(6) Press MODE key, select REM=ON and press SET/ENT key.
Reset
Remote-mode
operation
Local-mode
operation
Program
operation
Hold-mode
operation
(*1)
(1)
(1)
(2)
(2)
(2)
(2)
(3)
(1) (4)
(5)
(5)
(5)
(5)
(6)
(6)
(6)
(6)
(1)
2. Performing/Canceling Auto-tuning
Auto-tuningshouldbeperformedaftersettingaprogrampattern.
Makesurethatthecontrollerisinautomaticmode(AUTO)andinrunmode(RUN)
beforeauto-tuning.ForsettingtoAUTO,see “5. SwitchingbetweenAUTOand
MAN,”andforsettingtoRUN,see“4.SwitchingbetweenRUNandRESET.”
Ifthesetpointisknowninadvanceorauto-tuningdoesnotndanyappropriatePID
constants,setthePIDmanually.ForsettingthePIDmanually,seeUser’sManual.
CAUTION
Do not perform auto-tuning for the following processes.
Tune PID manually.
• Processes with fast response such as flow rate control and pres-
sure control.
•Processes which do not allow the output to be turned on and off
even temporarily.
• Processes which prohibit severe output changes at control
valves (or other actuators).
• Processes in which product quality can be adversely affected if
PV values fluctuate beyond their allowable ranges.
1.
2.
3.
4.
OFF blinks.
Blinks during the change.
The MAN lamp goes off, which means that
the auto-tuning completed normally.
5.
6.
7.
8.
Show the Operation Display.
Hold down the PARAMETER key for 3 seconds
to display MODE menu.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter HOLD (Pause/cancel release
of program operation) is displayed (during
program operation.)
Press the Down arrow key until the parameter AT appears.
The parameter AT (auto-tuning switch) is displayed.
Press the Up/Down arrow keys to display the required setpoint.
The setting range is 1 to 8 (represent group numbers) or R.
To perform auto-tuning for the PID of group 1, set the parameter AT to 1.
To quit the auto-tuning, set the parameter to OFF.
The setpoint has been registered.
This starts auto-tuning.
The limiter can be set to the output during
auto-tuning.
For details, see User’s Manual.
During auto-tuning,
• The MAN lamp blinks.
• The OUT symbol appears.
• The output values at 100.0% and 0%
appear alternately.
1.
2.
3.
4.
OFF blinks.
Blinks during the change.
The MAN lamp goes off, which means that
the auto-tuning completed normally.
5.
6.
7.
8.
Show the Operation Display.
Hold down the PARAMETER key for 3 seconds
to display MODE menu.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter HOLD (Pause/cancel release
of program operation) is displayed (during
program operation.)
Press the Down arrow key until the parameter AT appears.
The parameter AT (auto-tuning switch) is displayed.
Press the Up/Down arrow keys to display the required setpoint.
The setting range is 1 to 8 (represent group numbers) or R.
To perform auto-tuning for the PID of group 1, set the parameter AT to 1.
To quit the auto-tuning, set the parameter to OFF.
The setpoint has been registered.
This starts auto-tuning.
The limiter can be set to the output during
auto-tuning.
For details, see User’s Manual.
During auto-tuning,
• The MAN lamp blinks.
• The OUT symbol appears.
• The output values at 100.0% and 0%
appear alternately.
3.
Selecting Program Pattern Number (PT.No)
Programpatternnumberselectioncanbeperformedusinganyofthefollowing:(1)
key,(2)Parameter,(3)Contactinput,and(4)Communication.
Thefollowingshowsanexampleofchangingtheprogrampatternnumber(PTNO.)
to1usingthekey.
ProgrampatternnumbercanbeselectedwhenthecontrollerisinaRESETmode.
1.
2.
3.
4.
RST lamp
is lit.
PTNO. has been changed to 1.
Blinks during the change.
Show the Operation Display.
Press the SET/ENTER key.
Press the PTN key.
Press the Up/Down arrow keys
to display the required setpoint.
Operation
Guide
This operation guide describes key entries for operating the UP55A.
For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams”
in “Installation and Wiring.”
If you cannot remember how to carry out an operation during setting, press the
DISPLAY key once. This brings you to the display (Operation Display) that appears at
power-on.
The scrolling guide is displayed on PV display in the Parameter Setting Display.
This guide can be turned on/off with the MODE key.
UP55A
Program Controller
Operation Guide for Single-loop Control
Operations
4.
Switching between RUN and RESET
RUNandRESETswitchingcanbeperformedusinganyofthefollowing:(1)key,(2)
Contactinput,(3)Parameter,and(4)Communication.
Thefollowingshowsanexampleofswitchingusingthekey.
Fordetailsofotherswitchingmethodsandthedisplayappearingwhentheoperation
isstarted,seeUser’sManual.
Display in RUN mode
Starting target setpoint
RST lamp is lit.
Display in RESET mode
Current segment number and symbol (SP)
PRG lamp is lit.
Program setpoint
Press RUN key for 1 s.
Symbol SSP
The number of segments included in the selected
program pattern.
The segment number for which operation is in progress.
The figure below is displayed while the right arrow key is held down.
Press RST key for 1 s.
Whenthecontrollerisstopped,inputandoutputsareasfollows:
PVinput DisplaysthePVvalue.
Controloutput WhenthezonePIDselectionparameter(ZON)issettosegment
PIDselection,thepresetoutputvalueforthePIDgroupnumber1
isoutput.WhenthezonePIDselectionparameter(ZON)issetto
otherthansegmentPIDselection,thepresetoutputvalueforthe
PIDgroupnumberforwhichzonecontrolisperformedisoutput.
Eventoutput Turnstheoutputoffincaseofanevent.
Alarmoutput Turns the output on in case of an alarm.
5. Switching between AUTO and MAN
AUTOandMANswitchingcanbeperformedusinganyofthefollowing:(1)MODE
key,(2)Contactinput,(3)Contactinput,and(4)Communication.
ThefollowingshowsanexampleofswitchingusingtheMODEkey.
WhenAUTOandMANswitchingfunctionisassignedtothecontactinput, and the
contactinputisON,theswitchingbykeyoperationcannotbeperformed.
Fordetails,seeUser’sManual.
Displays ”MODE MAN” in AUTO mode.
Displays ”MODE AUTO” in MAN mode.
1.
2.
3.
Press MODE key several times.
Show the Operation Display.
4.
MAN lamp is lit in MAN mode.
Press the SET/ENTER key.
WhenAUTOisswitchedintoMAN,thecontroloutputvalueinAUTOmodeisheld.
Thecontrollercanbeoperatedmanuallyfromtheholdvalue.
Ifthemanualpresetoutputisset(MPONparameter≠OFF),the controller can be
operatedmanuallyfromthearbitraryoutputvalue(MPO1toMPO5parameters).

IM 05P02C41-15EN page 10/14
6.
Manipulating Control Output in Manual Mode
NOTE
Inmanualmode,controloutputismanipulatedbyoperatingthekeys(thevalueis
changedusingtheUp/Downarrowkeys,thenoutputtedasitis).
EveniftheSET/ENTERkeyisnotpressed,the control outputvaluechangesac-
cordingtothedisplayedvalue.
Instopmode(whentheRSTlampislit),controloutputcannotbemanipulated.
MAN lamp is lit.
Up arrow key: increases control output.
Down arrow key: decreases control output.
In Position proportional control:
Up arrow key; opens the valve.
Down arrow key; closes the valve.
Output; only while pressing a key.
OUT; valve opening (0-100%)
Output manipulation in Position proportional control
is not restricted from output limiters (OH, OL).
Manual operation in Heating/cooling control
Symbol of cooling side
Program pattern (PTNO.) number
Symbol of heating side
Heating-side control output
Cooling-side control output
Uparrowkey:concurrentlydecreasescooling-sidecontroloutputandincreases
heating-sidecontroloutput.
Downarrowkey:concurrentlyincreasescooling-sidecontroloutput and decreases
heating-sidecontroloutput.
(Eithernoneoftheheating-sideandcooling-sideoutputsarepresented,orbothof
themarepresentedaccordingtothedeadbandsetting.)
Actual output (%)
DB=24.8
Dead band: Operation parameter DB
Control computation output Control computation output
12.40-12.4
Manipulated output change
when a dead band is positive (+)
Actual output (%)
100
DB= -24.8
12.40-12.4
Manipulated output change
when a dead band is negative (-)
100
Cooling-side
manipulated output
Heating-side
manipulated output
Heating-side
manipulated output
Cooling-side
manipulated output
7.
Enabling/Disabling Hold Mode of Program Operation
Enabling/disablingholdmodeofprogramoperationcanbeperformedduringpro-
gramoperationusinganyofthefollowing:(1)MODEkey,(2)Parameter,(3)Contact
input,and(4)Communication.
ThefollowingshowsanexampleofswitchingusingtheMODEkey.
1.
2.
3.
4.
Show the Operation Display.
Press the MODE key.
The number of segments included
in the selected program pattern.
The segment number for which
operation is in progress.
The figure below is displayed while the right
arrow key hold down.
Displays ”HOLD ON” in PROG mode.
Displays ”HOLD OFF” in HOLD mode.
HLD lamp is lit in HOLD mode.
Press the SET/ENTER key.
The parameter HOLD (Pause/cancel release
of program operation) is displayed (during
program operation.)
1.
2.
3.
4.
Show the Operation Display.
Press the MODE key.
The number of segments included
in the selected program pattern.
The segment number for which
operation is in progress.
The figure below is displayed while the right
arrow key hold down.
Displays ”HOLD ON” in PROG mode.
Displays ”HOLD OFF” in HOLD mode.
HLD lamp is lit in HOLD mode.
Press the SET/ENTER key.
The parameter HOLD (Pause/cancel release
of program operation) is displayed (during
program operation.)
Otheroperatingproceduresfordisablingtheholdmode:
(1)PresstheRUNkeyfor1secondduringhold-modeoperation. In this case, the
controllerresumesprogramoperation.
(2)Execute the “Advance“functionduringhold-mode operation.Inthis case, the
segmentisadvanced.
8.
Changing Program Setpoints when in Hold Mode
Thefollowingoperatingprocedureschangesaprogram setpointofsoaksegment
duringHold-modeoperation.
Theprogramoperationisstartedwhenreleasing the Holdafterchangingthepro-
gramsetpoint.
1.
2.
Set program operation in hold mode.
3.
4.
Blinks during the change.
Blinks during the change.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up/Down arrow keys to display the required setpoint.
9.
Executing “Advance” Function
“Advance”canbeperformedduringprogramoperationusinganyofthefollowing:(1)
MODEkey,(2)Parameter,(3)Contactinput,and(4)Communication.
ThefollowingshowsanexampleofswitchingusingtheMODEkey.
Whenexecutingthe“Advance”functionduringhold-modeoperation,theholdmode
isdisabled.
1.
2.
3.
4.
The segment is advanced.
Press the SET/ENTER key.
Show the Operation Display.
Press the MODE key.
The ADV (Advance of segment) is displayed (during
program operation.)
10.
Switching to Local-mode (LOCAL) Operation
Switchingtolocal-modecanbeperformedusinganyofthefollowing:
(1)MODEkey(userfunctionkey),(2)Parameter,(3)Contactinput,and(4)Commu-
nication.
ThefollowingshowsanexampleofswitchingusingtheMODEkey.
1.
2.
3.
4.
“LSP” is displayed when in
local-mode operation.
Press the SET/ENTER key.
Show the Operation Display.
Press the MODE key several times.
The LOC (local operation) is displayed.
11.
Changing Setpoints during Local-mode Operation
Thefollowingoperatingprocedureschangessetpointsduringlocal-modeoperation.
1.
2.
3.
4.
“LSP” is displayed when in local-mode operation.
Press the SET/ENTER key.
Press the SET/ENTER key.
Blinks during the change.
Blinks during the change.
Press the Up/Down arrow keys to display the required setpoint.
13. Troubleshooting
■
Remedies if Power Failure Occurs
during Operations
• Instantaneouspowerfailurewithin20ms.
Apowerfailureis not detected. Normal
operation continues.
• Powerfailureforlessthanabout5seconds,
orforabout5secondsormore.
Affectsthe"settings"and"operationsta-
tus."
Fordetails,seeUser'sManual.
NOTE
Writedownthesettingsofparametersfora
repairrequest.
■FortheErrorsatPowerOn
and the Errors during Op-
eration, see “Installation”
in this manual.
12.
Switching to Remote-mode (REM) Operation
Switchingtoremote-modecanbeperformedusinganyofthefollowing:
(1)MODEkey(userfunctionkey),(2)Parameter,(3)Contactinput,and(4)Commu-
nication.
ThefollowingshowsanexampleofswitchingusingtheMODEkey.
1.
2.
3.
4.
“R.SP” is displayed when in
remote-mode operation.
Press the SET/ENTER key.
Show the Operation Display.
Press the MODE key several times.
The REM (remote operation) is displayed.
■TroubleshootingFlow
IftheOperationDisplaydoesnotappearafterturningonthecontroller’spower,checktheproceduresinthefollowingowchart.
Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.
Is the controller
defective?
Contact us for repair.
Problem solved.
No communication
capability
Completely
inactive?
Yes
Yes
Yes
No
No
No
Key
operation
failure?
Yes
No
Yes
Check wiring of the
power terminals.
Check the key lock
setting.
Display
failure?
*
Yes
No
Turn off power, and
then turn it on again.
I/O signal
failure?
Yes
No
Check the
supply voltage.
Check the
specifications and polarity
of connected devices .
Check the communication-
related parameters.
Check the specifications
of communication
devices.
Check the
communication wiring.
Communication
failure?
No
With
communi-
cation?
Yes
Yes
Normal?
Is the
key locked?
Check the specifications
of the controller.
Yes
No Correct?
Correct the error(s).
Cancel the setting.
Check the I/O specifications
of the controller.
* The LCD (a liquid crystal display) is used for
a display portion of this product.
The LCD has a characteristic that the display action
becomes late at the low temperature.
Additionally, the luminance and contrast degradation
are caused due to aged deterioration.
However, the control function is not affected.

IM 05P02C41-15EN page 11/14
Operation Parameters / Program Parameters
HolddownthePARAMETERkeyfor3secondstomovefromtheOperationDisplayto
theOperationParameterSettingDisplay.PresstheDISPLAYkeyoncetoreturntothe
OperationDisplay.
Menu
DISPLAY
key key key
key key
The parameter groups can be switched using , keys.
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
Parameter
END
PROG
PTNO.
SEGNO.
END
Menu END
END
Menu Display
and Parameter
Setting Display
are changed in a
circular pattern.
Hold down PARAMETER key for 3 sec.
SET/ENTER key
1 to 30
SET/ENTER key
SET/ENTER
key
PARAMETER
key
PARAMETER
key
PARAMETER
key
0, 1 to 99
Parameter
Parameter
END
Move to the Setup Parameter Setting Display:
Hold down the PARAMETER key and the Left arrow key simultaneously for 3 sec.
Operation for Setting
· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrow
keytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-
pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).Usethe
Up/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeyto
registerthesetting.
Notethattherearesomeparameterswhicharenotdisplayeddependingonthemodel
andsufxcodes,controlmode(CTLM),controltype(CNT),etc.
The parameters for pro-
fessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.
nOperation Mode
Menusymbol: (MODE)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(HOLD)
Pause/cancelreleaseof
programoperation
Displayduringprogramoperation.
ON:Pause
OFF:Cancelrelease(Programopera-
tionrestart)
OFF
EASY
(ADV) Advanceofsegment
Displayduringprogramoperation.
Setas“ADV=ON”toadvancefrom
thecurrentsegmenttothenextseg-
ment.
OFF
(MODE) Operationmode
RESET:Stopofprogramoperation
PROG:Startofprogramoperation
LOCAL:Startoflocal-modeoperation
REM:Startofremote-modeoperation
RESET
(A.M) AUTO/MANswitch AUTO:Automaticmode
MAN:Manualmode MAN
(PTNO.)
Programpatternnumber
selection
0:Notselectprogrampattern
1to30 0
(SST)
Start-of-programseg-
mentnumber
1to99
Thesettingvaluereturnsto“1”when
theprogramoperation(PROG)
changesintoRESET,LOCAL,or
REM.
1
(P.FWD)
Fast-forwardingof
programoperation
1:Normal,2:Twice,5:Fivetimes,
10:Tentimes
*Usethisfunctionwhenchecking
theprogrampatternsetting.Only
SegmenttimeandTimeeventcan
befaster.
*Theoperationreturnstothenormal
speedafterfast-forwarding.
1
(AT) AUTO-tuningswitch
OFF:Disable
1to8:Performauto-tuning.Tuning
resultisstoredinthespecied
numberedPID.
R:TuningresultisstoredinthePID
forreferencedeviation.
OFF
(PID) PIDnumber
ThePIDgroupnumberbeingselected
is displayed.
1to8,R:PIDgroupforreferencedeviation
1
nSELECT Parameter
Menusymbol: (CS)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
Registeredpa-
rametersymbol
SELECTparameter
10to19
Settingrangeofaregisteredparameter.
Fordetails,seeUser'sManual.
—Table
below EASY
Parameter n=10 n=11 n=12 n=13 n=14 n=15 n=16 n=17 n=18 n=19
CSn
FortheregistrationofSELECTparameters,seeUser'sManual.
nProgram Setting Parameter
Menusymbol:( PROG> PTNO.(=01to30)> SEGNO.(=00))
Parameter symbol Name of
Parameter Setting Range Initial
value
User
setting
Display
level
(SSP)
Startingtarget
setpoint
0.0to100.0%ofPVinputrange(EU)
(Settingrange:P.RLtoP.RH) P.RL
EASY
(STC) Start code
SSP:Programoperationbeginswith
thestartingtargetsetpoint.
RAMP:Ramp-prioritizedPVstart
TIME:Time-prioritizedPVstart
LSP:Local-modestart
RSP:Remote-modestart
*STC=TIMEcannotbeselectedwhen
theparameterSEG.TisTM.RT.
SSP
to
(WT.SW1toWT.SW5)
Waitfunction
ON/OFF1to5
OFF:Disable
ON:Enable OFF
STD
to
(WZ.UP1toWZ.UP5)
Upper-sidewait
zone1to5
0.0to10.0%ofPVinputrange(EU)
0.5%
ofPV
input
range
to
(WZ.LO1toWZ.LO5)
Lower-sidewait
zone1to5
0.5%
ofPV
input
range
to
(WT.TM1toWT.TM5)
Waittime1to5
OFF:Nofunction
0.00to999.59(“hour.minute”or“minute.second”)
*Availableonlyforthewaittimeatthesegment
switching.
*UsetheparameterTMUtosetthetimeunit.
(Commonintheinstrument.)
OFF
(R.CYCL)
Numberof
repeat cycles
0to999,CONT(limitlessnumberof
times) 0
(R.STRT)
Repeatcycle
startsegment
number 1to99
1≤R.STRT≤R.END≤99
1
(R.END)
Repeatcycle
endsegment
number
1
Whentheprogrampattern-2retransmissionisselected(PT2.G=ON),thesecondloopisalsodisplayedfortheparameterSSP.(LP2lampislit.)
Wait-function-relatedparametersaredisplayedinorderofthe1stgroup(WT.SW1,WT.TM1,WZ.UP1,Z.LO1),the2ndgroup,the3rdgroup,andsoon.
nProgram Setting Parameter
Menusymbol:( PROG> PTNO.(=01to30)> SEGNO.(=01to99))
Parameter
symbol
Name of
Parameter Setting Range Initial
value
User
setting
Display
level
(TSP)
Finaltarget
setpoint
0.0to100.0%ofPVinputrange(EU)(Setting
range:P.RLtoP.RH) P.RL
See
"Pro-
gram-
ming"
in this
manual.
EASY
(TIME)
Segmenttime
setting
-:Unregistered
0.00to999.59(“hour.minute”or“minute.second”)
*
SettingavailablefortheparameterSEG.T=TIME.
*UsetheparameterTMUtosetthetimeunit.
(Commonintheinstrument.)
*Ifthesettingis0.00,TSPchangesinstepwise
after one control period.
-
(TM.RT)
Segment
ramp-rate
setting
-:Unregistered
Ramp:0.0to100.0%ofPVinputrangespan
(EUS)/1houror1minute
Soak:0.00to999.59(“hour.minute”or“minute.second”)
*
SettingavailablefortheparameterSEG.T=TM.RT
*UsetheparameterTMUtosetthetimeunit.
(Commonintheinstrument.)
Per1hour:TMU=HH.MM,Per1minute:TMU=MM.SS
*Ifitissetto0.0%oftheinputrangespan,or
thesegmenttime0.00,theprogrammovesto
thenextsegmentafteronecontrolperiod.
-
(S.PID)
SegmentPID
numberselection
1to8
*PIDnumbercanbesetwhentheparameter“ZON=0.”
1
(JC) Junction code
CONT:Switchingforcontinuation
HOLD:Hold-onswitching(thecontrollerholdstheend-of-
segmentsetpointwhenthesegmentiscompleted,to
performcontrol).
LOCAL:Local-modeswitching(thecontrollerswitchestoa
localsetpointwhenthesegmentiscompleted).
REM:Remote-modeswitching(thecontrollerswitchestoa
remotesetpointwhenthesegmentiscompleted).
W.SW1toW.SW5:Waitduringswitchingbetweensegments.
W.IV1toW.IV5:Waitwithinasegmentinterval.
W.SL1toW.SL5:Segmentswitching(thecontrollerswitches
toalocalsetpointwhenthesegmentiscompletedafter
release.)(5groups)
W.SR1toW.SR5:Segmentswitching(thecontrollerswitches
toaremotesetpointwhenthesegmentiscompleted
afterrelease.)(5groups)
PLK.1toPLK.30:Linkedtopatterns1to30.
INS.:Allowsasegmenttobeaddedtotheendofaspecied
segment.
DEL.:Allowsaspeciedsegmenttobedeleted.
CONT
See
"Pro-
gram-
ming"
in this
manual.
STD
Whentheprogrampattern-2retransmissionisselected(PT2.G=ON),thesecondloopisalsodisplayedforthe
parameterSSP.(LP2lampislit.)
nProgram Setting Parameter
Menusymbol:( PROG> PTNO.(=1to30)> SEGNO.(=1to99))
Parameter
symbol
Name of
Parameter Setting Range Initial
value
User
setting
Display
level
to
(PV.TY1to
PV.TY8)
PVevent-1to-8
type
OFF:Disable
(Energized)
1:PVhighlimit,2:PVlowlimit,
3:SPhighlimit,4:SPlowlimit,
5:Deviationhighlimit,
6:Deviationlowlimit,
7:Deviationhighandlowlimits,
8:
Deviationwithinhighandlowlimits,
9:TargetSPhighlimit,
10:TargetSPlowlimit,
11:TargetSPdeviationhighlimit,
12:TargetSPdeviationlowlimit,
13:
TargetSPdeviationhighandlowlimits,
14:
TargetSPdeviationwithinhighandlowlimits,
15:OUThighlimit,16:OUTlowlimit,
17:Cooling-sideOUThighlimit,
18:Cooling-sideOUTlowlimit
*Add100for"de-energized".Forexample,
whenthePVhighlimitisde-energized,the
settingis101.
OFF
See
"Pro-
gram-
ming"
in this
manual.
STD
to
(PV.EV1to
PV.EV8)
PVevent-1to-8
setpoint
SetadisplayvalueofsetpointofPValarm,SP
alarm,deviationalarm,oroutputalarm.
-19999to30000(Setavaluewithintheinput
range.)
Decimalpointpositiondependsontheinput
type.
0
to
(TME1to
TME16)
Start condition of
timeevent1to16
ON:StartONstate
OFF:StartOFFstate OFF
to
(T.ON1to
T.ON16)
Ontimeoftime
event1to16
-:Unregistered
0.01to999.59(“hour.minute”or“minute.
second”)
*Availableonlywithinthesegmenttime.
*OFFwhentheoperationmodeischanged
tothemodeexcepttheprogramoperation.
*
UsetheparameterTMUtosetthetimeunit.
(Commonintheinstrument.)
-
to
(T.OF1to
T.OF16)
Offtimeoftime
event1to16 -
PVeventandTimeeventareavailableonlyduringtheprogramoperation.
PVeventparametersaredisplayedinorderofPVevent1(PV.TY1,PV.EV1),PVevent2,PVevent3,andsoon.
TimeeventparametersaredisplayedinorderofTimeevent1(TME1,T.ON1,T.OF1),Timeevent2,Timeevent3,
and so on.
nLocal Setting Parameter
Menusymbol: (LOC)
Parameter
symbol
Name of
Parameter Setting Range Initial
value
User
setting
Display
level
(LSP)
Localtarget
setpoint
0.0to100.0%ofPVinputrange(EU)(Setting
range:P.RLtoP.RH) P.RL
EASY
(L.PID)
PIDnumberse-
lectionforlocal-
mode operation
SetaPIDgroupnumbertouse.
1to8
*
AvailableonlyfortheL.PIDwhenZON=0or5.
*Ifsetto“LocalPIDselection,”localPIDisse-
lectedirrespectiveoftheoperationmodes.
1
to
(L.TY1to
L.TY8)
Localevent-1to
-8type
OFF:Disable
(Energized)
1:PVhighlimit,2:PVlowlimit,
3:SPhighlimit,4:SPlowlimit,
5:Deviationhighlimit,
6:Deviationlowlimit,
7:Deviationhighandlowlimits,
8:
Deviationwithinhighandlowlimits,
9:TargetSPhighlimit,
10:TargetSPlowlimit,
11:TargetSPdeviationhighlimit,
12:TargetSPdeviationlowlimit,
13:
TargetSPdeviationhighandlowlimits,
14:
TargetSPdeviationwithinhighandlowlimits,
15:OUThighlimit,16:OUTlowlimit,
17:Cooling-sideOUThighlimit,
18:Cooling-sideOUTlowlimit
*Add100for"de-energized".Forexample,
whenthePVhighlimitisde-energized,the
settingis101.
OFF
STD
to
(L.EV1to
L.EV8)
Localevent-1to
-8setpoint
SetadisplayvalueofsetpointofPValarm,SP
alarm,deviationalarm,oroutputalarm.
-19999to30000(Setavaluewithintheinput
range.)
Decimalpointpositiondependsontheinputtype
0
Whentheprogrampattern-2retransmissionisselected(PT2.G=ON),thesecondloopisalsodisplayedforthe
parameterLSP.(LP2lampislit.)
LocaleventparametersaredisplayedinorderofLocalevent1(L.TY1,L.EV1),Localevent2,Localevent3,
and so on.
nAlarm Setpoint Setting Parameter
Menusymbol: (AL)
Parameter
symbol
Name of
Parameter Setting Range Initial
value
User
setting
Display
level
to
(A1toA8)
Alarm-1to-8
setpoint
Thesealarmsworkirrespectiveoftheoperation
mode.
SetadisplayvalueofsetpointofPValarm,SPalarm,
deviationalarm,outputalarm,orvelocityalarm.
-19999to30000(Setavaluewithintheinputrange.)
Decimalpointpositiondependsontheinputtype
0Table
below EASY
UsethefollowingtabletorecordSPandalarmsetpoints.
Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8
An
nSP-related Setting Parameter
Menusymbol: (SPS)
Parameter
symbol Name of Parameter Setting Range Initial value User
setting
Display
level
(RMS) Remoteinputmethod
RSP:Viaremote(auxiliaryanalog)input
COM:Viacommunication RSP
STD
(RFL) Remoteinputlter OFF,1to120s OFF
(RT) Remoteinputratio
SP=RemoteinputxRT+Re-
moteinputbias
0.001to9.999
1.000
(RBS) Remoteinputbias -100.0to100.0%ofPVinput
rangespan(EUS)
0.0%ofPV
inputrange
span
(SPT) SPtrackingselection
Trackingisperformedwhenthe
modechangesfromProgramor
RemotetoLocal.(Thelocalset-
pointkeepstrackoftheprogram
orremotesetpoint.)OFF,ON
OFF
(S.TM)
Startingtimeofprogram
operation
0.00to999.59(“hour.minute”or
“minute.second”(commonuseof
instrument)
*UsetheparameterTMUtoset
the time unit.
0.00
(PNC)
Programpatternnumber
clearance
OFF:Notcleared.
ON:Cleared.
(SettheprogramNo.before
restartprogramoperation)
*Thecontrollerresets(clears)
theprogrampatternnumberon
theoperatingdisplayto“0”atthe
endofprogramoperation.
OFF
nAlarm Function Setting Parameter
Menusymbol: (ALRM)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
to
(EHY1to
EHY8)
Event-1to-8hysteresis
ThehysteresissetpointofPVeventor
Localeventissettotheparcentageof0.0
to100.0%.
Thesettingvalue(%)isforthePVinput
rangespanoroutputspan.
0.5 STD
to
(AL1toAL8)
Alarm-1to-8type
Example:Alarm-1
Stand-by
action
Latch action
Energized/
De-energize
Alarm
type
Thesealarmsworkirrespectiveofthe
operation mode.
Seta5-digitvalueinthefollowing
order.
[Alarmtype:2digits(seebelow)]+
[Without(0)orWith(1)Stand-byac-
tion]+[Energized(0)orDe-energized
(1)]+[Latchaction(0/1/2/3/4)]
Forlatchaction,seeUser'sManual.
AL1,
AL3:
PVhigh
limit(01)
Without-
Stand-
by
action
(0)
Energi-
zed(0)
Latch
action
(0)
AL2,
AL4:
PVlow
limit(02)
Without
Stand-
by
action
(0)
Energi-
zed(0)
Latch
action
(0)
AL5to
AL8:
not
displayed
for
factory
default
Table
below
EASY
Alarmtype:2digits
00:Disable
01:PVhighlimit
02:PVlowlimit
03:SPhighlimit
04:SPlowlimit
05:Deviationhighlimit
06:Deviationlowlimit
07:Deviationhighandlowlimits
08:
Deviationwithinhighandlowlimits
09:TargetSPhighlimit
10:TargetSPlowlimit
11:TargetSPdeviationhighlimit
12:TargetSPdeviationlowlimit
13:
TargetSPdeviationhighandlowlimits
14:TargetSPdeviationwithinhigh
and low limits
15:OUThighlimit
16:OUTlowlimit
17:Cooling-sideOUThighlimit
18:Cooling-sideOUTlowlimit
19:AnaloginputPVhighlimit
20:AnaloginputPVlowlimit
21:AnaloginputRSPhighlimit
22:AnaloginputRSPlowlimit
23:AnaloginputAIN2highlimit
24:AnaloginputAIN2lowlimit
25:AnaloginputAIN4highlimit
26:AnaloginputAIN4lowlimit
27:Feedbackinputhighlimit
28:Feedbackinputlowlimit
29:PVvelocity
30:Faultdiagnosis
31:FAIL
to
(VT1toVT8)
PVvelocityalarmtime
setpoint1to8 0.01to99.59(minute.second) 1.00
to
(HY1toHY8)
Alarm-1to-8hysteresis
Setadisplayvalueofsetpointof
hysteresis.
-19999to30000(Setavaluewithin
theinputrange.)
Decimalpointpositiondependsonthe
inputtype.Whenthedecimalpointposi-
tionfortheinputtypeissetto"1",the
initialvalueofthehysteresisis"1.0".
10
to
(DYN1toDYN8)
Alarm-1to-8On-delay
timer
AnalarmoutputisONwhenthedelay
timerexpiresafterthealarmsetpoint
is reached.
0.00to99.59(minute.second)
0.00
STD
(AMD) Alarmmode
0:Alwaysactive
1:NotactiveinRESETmode
2:NotactiveinRESETorMANmode
0
Forthealarmfunctionsettingparameter,4alarmsaredisplayedforthefactorydefault.Thenumberofalarms
canbechangedbythesetupparameterALNO.(numberofalarms).Tochangethenumberofalarms,see
User'sManual.
Operation
Guide
Yokogawa Electric Corporation
Parameters
This operation guide describes the functions of parameters briefly. The parameter
symbols listed are in the order shown on the display in each group of menu symbols.
In addition, each parameter table has a “User Setting” column, where you can record
your setpoints when setting them in the controller. The scrolling guide is displayed on
PV display in the Parameter Setting Display. This guide can be turned on/off with
the MODE key.
UP55A
Program Controller
Operation Guide for Single-loop Control

IM 05P02C41-15EN page 12/14
Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8
EHYn
ALn
VTn
HYn
DYNn
n:alarmnumber
nPV-related Setting Parameter
Menusymbol: (PVS)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(BS) PVinputbias -100.0to100.0%ofPVinputrange
span(EUS)
0.0%of
PVinput
range
span EASY
(FL) PVinputlter OFF,1to120s OFF
nPID Setting Parameter
Menusymbol: (PID)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(P)
Proportionalband
Heating-sideproportion-
alband(inHeating/cool-
ingcontrol)
0.0to999.9%
When0.0%isset,itoperatesas
0.1%.
Heating-sideON/OFFcontrolapplies
when0.0%inHeating/coolingcontrol
5.0%
EASY
(I)
Integraltime
Heating-sideintegraltime
(inHeating/coolingcontrol)
OFF:Disable
1to6000s 240s
(D)
Derivativetime
Heating-sidederivativetime
(inHeating/coolingcontrol)
OFF:Disable
1to6000s 60s
(OH)
Controloutputhighlimit
Heating-sidecontrol
outputhighlimit(in
Heating/coolingcontrol)
-4.9to105.0%,(OL<OH)
InHeating/coolingcontrol:0.1to
105.0%(OL<OH)
100.0%
(OL)
Controloutputlowlimit
Heating-sidecontrol
outputlowlimit(inHeat-
ing/coolingcontrol)
-5.0to104.9%,(OL<OH),SD:Tight
shut
InHeating/coolingcontrol:0.0to
104.9%(OL<OH)
0.0%
(MR) Manual reset
EnabledwhenintegraltimeisOFF.
Themanualresetvalueequalsthe
outputvaluewhenPV=SP.
-5.0to105.0%
50.0%
(HYS)
Hysteresis(inON/OFF
control or Position
proportionalcontrol)
Heating-sideON/OFF
controlhysteresis(in
Heating/coolingcontrol)
InON/OFFcontrol:0.0to100.0%of
PVinputrangespan(EUS)
InHeating/coolingcontrolorPosition
proportionalcontrol:0.0to100.0%
In
ON/OFF
control:
0.5%of
PVinput
range
span
In
Heating/
cooling
control or
Position-
proportional
control:
0.5%
(HY.UP)
Upper-sidehysteresis
(inON/OFFcontrol)
0.0to100.0%ofPVinputrange
span(EUS)
0.5%
ofPV
input
range
span
(HY.LO)
Lower-sidehysteresis
(inON/OFFcontrol)
0.5%
ofPV
input
range
span
(DR)
Direct/reverseaction
switch
RVS:Reverseaction
DIR:Directaction RVS STD
(Pc)
Cooling-sidepropor-
tionalband
0.0to999.9%
(Cooling-sideON/OFFcontrolap-
plieswhen0.0%inHeating/cooling
control)
5.0%
EASY
(Ic)
Cooling-sideintegral
time
OFF:Disable
1to6000s 240s
(Dc)
Cooling-sidederivative
time
OFF:Disable
1to6000s 60s
(OHc)
Cooling-sidecontrol
outputhighlimit 0.1to105.0%,(OLc<OHc) 100.0%
(OLc)
Cooling-sidecontrol
output low limit 0.0to104.9%,(OLc<OHc) 0.0%
(HYSc)
Cooling-sideON/OFF
control hysteresis 0.0to100.0% 0.5%
(DB)
Outputdeadband(in
Heating/coolingcontrol
or Position proportional
control)
InHeating/coolingcontrol:-100.0to
50.0%
InPositionproportionalcontrol:1.0
to10.0%
3.0%
(PO)
Preset output
Heating-sidepreset
output(inHeating/cool-
ingcontrol)
InRESETmode,xedcontroloutput
canbegenerated.InPositionpropor-
tionalcontrol,Valveopeningcanbe
set;-5.0to105.0%
0.0%
(POc)
Cooling-sidepreset
output
InRESETmode,cooling-sidexed
controloutputcanbegenerated.
-5.0to105.0%
0.0% EASY
IfyouareusingtwoormoregroupsofPIDparameters,usethefollowingtabletorecordtheirsettingvalues.
Parameter n=2 n=3 n=4 n=5 n=6 n=7 n=8 R
P
I
D
OH
OL
MR
HYS
HY.UP
HY.LO
DR
Pc
Ic
Dc
OHc
OLc
HYSc
DB
PO
POc
n:groupnumber
nTuning Parameter
Menusymbol: (TUNE)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(SC) Super function
OFF:Disable
1:Overshootsuppressingfunction
(normalmode)
2:Huntingsuppressingfunction
(stablemode)
Enablestoanswerthewider
characteristicchangescompared
with response mode.
3:Huntingsuppressingfunction
(responsemode)
Enablesquickfollow-upandshort
convergingtimeofPVforthe
changedSP.
4:Overshootsuppressingfunction
(strongsuppressingmode)
Note:Setpoints2and3mustbe
usedinPIDcontrolorPIcontrol.
Disabledinthefollowingcontrols:
1)ON/OFFcontrol,2)PDcontrol,
3)Pcontrol,4)Heating/cooling
control.
Donotusethefunctionforthe
control processes with response
suchasoworpressurecontrol.
OFF EASY
(AT.TY)
Auto-tuningtype
0:Normal
1:Stability 0 STD
(AR)
Anti-resetwindup
(excessintegration
prevention)
AUTO,50.0to200.0% AUTO
STD
(OPR) Outputvelocitylimiter OFF:Disable
0.1to100.0%/s OFF
(MPON)
Manual preset output
numberselection
SelecttheoutputusedinMANmode
whenswitchedfromAUTOtoMAN
mode.
OFF:HoldthecontroloutputinAUTO
mode(bumpless)
1:Usemanualpresetoutput1(outputbump)
2:Usemanualpresetoutput2(outputbump)
3:Usemanualpresetoutput3(outputbump)
4:Usemanualpresetoutput4(outputbump)
5:Usemanualpresetoutput5(outputbump)
OFF
to
(MPO1toMPO5)
Manual preset output 1
to 5
-5.0to105.0%
However,outputislimitedtothe
outputhighlimitandlowlimit.
0.0% Table
below
Usethefollowingtabletorecordthemanualpresetoutputsettingvalue.
Parameter n=1 n=2 n=3 n=4 n=5
MPOn
nZone Control Parameter
Menusymbol: (ZONE)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
to
(RP1toRP7)
Referencepoint1to7
Set reference points at which switch-
ingiscarriedoutbetweengroupsof
PIDconstantsaccordingtothegiven
temperaturezone.
0.0to100.0%ofPVinputrange(EU)
(RP1≤RP2≤RP3≤RP4≤RP5≤
RP6≤RP7)
100.0%
ofPV
input
range
Table
below STD
(RHY)
ZonePIDswitching
hysteresis
Hysteresiscanbesetforswitchingat
a reference point.
0.0to10.0%ofPVinputrangespan
(EUS)
0.5%
ofPV
input
range
span
STD
(RDV) Referencedeviation
SetadeviationfromSP.ThePIDfor
referencedeviationisusedifthere
isalargerdeviationthanthepreset
referencedeviation.
OFF:Disable
0.0+1digitto100.0%ofPVinput
rangespan(EUS)
OFF STD
ForZonecontrol,setthesetupparameterZON(zonePIDselection)toZonePIDselection.
Usethefollowingtabletorecordthereferencepointsettingvalue.
Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7
RPn
nP Parameter (for Ladder Program)
Menusymbol: (PPAR)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
to
(P01toP10)
P01toP10parameter
-19999to30000(Setadecimalpoint
positionusingLL50AParameterSet-
tingSoftware.)
0Table
below STD
Parameter n=01 n=02 n=03 n=04 n=05 n=06 n=07 n=08 n=09 n=10
Pn
n10-segment Linearizer-1, -2 Setting Parameter
Menusymbol: (PYS1) (PYS2)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(PYS)
10-segmentlinearizer
selection
OFF:Disable
PV:PVanaloginput
RSP:RSPanaloginput
AIN2:AIN2analoginput
AIN4:AIN4analoginput
PVIN:PVinput
OUT:OUTanalogoutput
OUT2:OUT2analogoutput
RET:RETanalogoutput
PV
(CTLM
:
SGL)
STD
(A1)
10-segmentlinearizer
input 1
-66.7to105.0%ofinputrange(EU)
Outputlinearizer:-5.0to105.0% 0.0%
(B1)
10-segmentlinearizer
output 1
10-segmentlinearizerbias:-66.7to
105.0%ofinputrangespan(EUS)
10-segmentlinearizerapproximation:
-66.7to105.0%ofinputrange(EU)
Outputlinearizer:-5.0to105.0%
0.0%
to ,
to
(A2toA11,B2to
B11)
10-segmentlinearizer
input 2 to 11
10-segmentlinearizer
output 2 to 11
SameasA1andB1
Same
asA1
and
B1
(PMD)
10-segmentlinearizer
mode
0:10-segmentlinearizerbias
1:10-segmentlinearizerapproxima-
tion
0
Usethefollowingtabletorecordthe10-segmentlinearizerinputandoutputsettingvalues.
Parameter n=2 n=3 n=4 n=5 n=6 n=7 n=8 n=9 n=10 n=11
An
Bn
Setup Parameters
HolddownthePARAMETERkeyandLeftarrowkeysimultaneouslyfor3secondsto
movefromtheOperationDisplayorOperationParameterSettingDisplaytotheSetup
ParameterSettingDisplay.
PresstheDISPLAYkeyoncetoreturntotheOperationDisplay.
Menu
key key key
key key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
Parameter
END
Menu
END
Menu END
END
Menu Display and
Parameter
Setting Display
are changed in a
circular pattern.
Hold down PARAMETER key and
Left arrow key simultaneously for 3 sec.
DISPLAY key
PARAMETER key
SET/ENTER key
Move to the Operation Parameter Setting Display: Hold down the PARAMETER key for 3 sec.
Operation for Setting
· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrow
keytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-
pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).Usethe
Up/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeyto
registerthesetting.
NotethattherearesomeparameterswhicharenotdisplayeddependingontheModel
andSufxcodes,controlmode(CTLM),controltype(CNT),etc.Theparameters for
professionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’s
Manual.
nControl Function Setting Parameter
Menusymbol: (CTL)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(CTLM) Controlmode
Whenusingthecontrolsotherthan
Single-loopcontrol,seeUser's
Manual.
SGL STD
SGL:Single-loopcontrol
CAS1:Cascadeprimary-loopcontrol
CAS:Cascadecontrol
PVSW:
LoopcontrolwithPVswitching
PVSEL:LoopcontrolwithPVauto-
selector
(CNT) Controltype
PID:PIDcontrol
ONOF:ON/OFFcontrol(1pointof
hysteresis)
ONOF2:ON/OFFcontrol(2pointsof
hysteresis)
H/C:Heating/coolingcontrol
PID
or
H/C
(for
Heating/
Cooling
type)
EASY
(ZON) ZonePIDselection
0:SegmentPIDselection
1:
ZonePIDselection(selectionbyPV)
2:ZonePIDselection(selectionby
targetSP)
4:
ZonePIDselection(selectionbySP)
5:LocalPIDselection
*Ifsetto“SegmentPIDselection,”
allowsPIDconstantstobeselected
foreachsegments.
*Ifsetto“ZonePIDselection,”
automaticallyselectsPIDconstants
accordingtotherangesetinthe
Referencepoint.
*Ifsetto“LocalPIDselection,”local
PIDisselectedirrespectiveofthe
operation modes.
1STD
(SEG.T) Segmentsettingmethod
TIME:Segmenttimesetting
TM.RT:Segmentramp-ratesetting
*Note:Achangeofsettingdeletesa
programpattern.
TIME
EASY
(TMU) Programtimeunit HH.MM: hour.minute
MM.SS: minute.second HH.MM
(PT2.G)
Programpattern-2
retransmission
OFF:Notused.
ON:used.
*
Thecontrollercanserveasaprogram
patterngenerator.
*Retransmissionoutputtypes(RTS,
O1RS,orO2RS)needtobesetto
SP2.
OFF
STD
(SMP)
Inputsamplingperiod
(controlperiod) 100:100ms,200:200ms 200
nPV Input Setting Parameter
Menusymbol: (PV)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(IN) PVinputtype
OFF:Disable
K1:-270.0to1370.0
0
C/-450.0to2500.0
0
F
K2:-270.0to1000.0
0
C/-450.0to2300.0
0
F
K3:-200.0to500.0
0
C/-200.0to1000.0
0
F
J:-200.0to1200.00C/-300.0to2300.0 0F
T1:-270.0to400.0
0
C/-450.0to750.0
0
F
T2:0.0to400.0
0
C/-200.0to750.0
0
F
B:0.0to1800.00C/32to3300 0F
S:0.0to1700.00C/32to3100 0F
R:0.0to1700.00C/32to3100 0F
N:-200.0to1300.0
0
C/-300.0to2400.0
0
F
E:-270.0to1000.0
0
C/-450.0to1800.0
0
F
L:-200.0to900.0
0
C/-300.0to1600.0
0
F
U1:-200.0to400.0
0
C/-300.0to750.0
0
F
U2:0.0to400.00C/-200.0to1000.0 0F
W:0.0to2300.00C/32to4200 0F
PL2:0.0to1390.0
0
C/32.0to2500.0
0
F
P2040:0.0to1900.0
0
C/32to3400
0
F
WRE:0.0to2000.00C/32to3600 0F
JPT1:-200.0to500.00C/-300.0to1000.0 0F
JPT2:-150.0to150.0
0
C/-200.0to300.0
0
F
PT1:-200.0to850.0
0
C/-300.0to1560.0
0
F
PT2:-200.0to500.0
0
C/-300.0to1000.0
0
F
PT3:-150.00to150.00
0
C/-200.0to300.0
0
F
0.4-2V:0.400to2.000V
1-5V:1.000to5.000V
4-20:4.00to20.00mA
0-2V:0.000to2.000V
0-10V:0.00to10.00V
0-20:0.00to20.00mA
-1020:-10.00to20.00mV
0-100:0.0to100.0mV
OFF
EASY
(UNIT) PVinputunit
-:Nounit,C:DegreeCelsius,
-:Nounit,--:Nounit,---:Nounit,
F:DegreeFahrenheit
C
(RH)
MaximumvalueofPV
inputrange
Dependsontheinputtype.
-Fortemperatureinput-
Setthetemperaturerangethatis
actuallycontrolled.(RL<RH)
-Forvoltage/currentinput-
Settherangeofavoltage/cur-
rentsignalthatisapplied.
Thescaleacrosswhichthevoltage
/currentsignalisactuallycontrolled
shouldbesetusingthemaximum
valueofinputscale(SH)andmini-
mumvalueofinputscale(SL).
(Inputisalways0%whenRL=RH.)
Depends
on the
input type
(RL)
MinimumvalueofPV
inputrange
Depends
on the
input type
(SDP)
PVinputscaledecimal
point position
0:Nodecimalplace
1:Onedecimalplace
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type

IM 05P02C41-15EN page 13/14
(SH)
MaximumvalueofPV
input scale -19999to30000,(SL<SH),
|SH-SL|≤30000
Depends
on the
input type
EASY
(SL)
MinimumvalueofPV
input scale
Depends
on the
input type
(BSL)
PVinputburnoutaction
OFF:Disable
UP:Upscale
DOWN:Downscale
Depends
on the
input type
STD
(A.BS)
PVanaloginputbias
-100.0to100.0%ofPVinputrange
span(EUS)
0.0%of
PVinput
range
span
(A.FL)
PVanaloginputlter
OFF,1to120s
OFF
W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988,WRE:W97Re3-W75Re25
nRSP Input Setting Parameter (E1-terminal Area)
Menusymbol: (RSP)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(IN) RSPremoteinputtype
0.4-2V:0.400to2.000V
1-5V:1.000to5.000V
0-2V:0.000to2.000V
0-10V:0.00to10.00V
0-125:0.000to1.250V
Foroption/DR,RSPremoteinput
typeissameasPVinputtype
1-5V
EASY
(UNIT) RSPremoteinputunit
-:Nounit,C:DegreeCelsius,
-:Nounit,--:Nounit,---:Nounit,
F:DegreeFahrenheit
C
(RH)
MaximumvalueofRSP
remoteinputrange
Dependsontheinputtype.
-Fortemperature(/DRoption)input-
Setthetemperaturerangethatis
actuallycontrolled.(RL<RH)
-Forvoltage/current(/DRoption)input-
Settherangeofavoltage/current
signalthatisapplied.
Thescaleacrosswhichthevoltage
/currentsignalisactuallycontrolled
shouldbesetusingthemaximum
valueofinputscale(SH)andmini-
mumvalueofinputscale(SL).
(Inputisalways0%whenRL=RH.)
Depends
on the
input type
(RL)
MinimumvalueofRSP
remoteinputrange
Depends
on the
input type
(SDP)
RSPremoteinputscale
decimal point position
0:Nodecimalplace
1:Onedecimalplace
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
(SH)
MaximumvalueofRSP
remote input scale -19999to30000,(SL<SH),
|SH-SL|≤30000
Depends
on the
input type
(SL)
MinimumvalueofRSP
remote input scale
Depends
on the
input type
(BSL)
RSPremoteinputbum-
out action
OFF:Disable
UP:Upscale
DOWN:Downscale
Depends
on the
input type
STD
(RTD.S) RTDwiringsystem
3-W:3-wiresystem
4-W:4-wiresystem
(TheLL50AParameterSettingSoft-
wareisrequiredtouseRSPterminals
inputasPV.)
3-W
nAIN2/AIN4 Aux. Analog Input Setting Parameter
(E2/E4-terminal Area)
Menusymbol: (AIN2) (AIN4)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(IN)
AIN2/AIN4aux.analog
input type
0.4-2V:0.400to2.000V
1-5V:1.000to5.000V
0-2V:0.000to2.000V
0-10V:0.00to10.00V
0-125:0.000to1.250V
1-5V
EASY
(UNIT)
AIN2/AIN4aux.analog
input unit
-:Nounit
C:DegreeCelsius
-:Nounit
--:Nounit
---:Nounit
F:DegreeFahrenheit
C
(RH)
MaximumvalueofAIN2/
AIN4aux.analoginput
range
Dependsontheinputtype.
Settherangeofavoltagesignalthat
is applied.
Thescaleacrosswhichthevoltage
signalisactuallycontrolledshouldbe
setusingthemaximumvalueofinput
scale(SH)andminimumvalueof
inputscale(SL).
(Inputisalways0%whenRL=RH.)
Depends
on the
input type
(RL)
MinimumvalueofAIN2/
AIN4aux.analoginput
range
Depends
on the
input type
(SDP)
AIN2/AIN4aux.analog
input scale decimal point
position
0:Nodecimalplace
1:Onedecimalplace
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
(SH)
MaximumvalueofAIN2/
AIN4aux.analoginput
scale -19999to30000,(SL<SH),
|SH-SL|≤30000
Depends
on the
input type
(SL)
MinimumvalueofAIN2/
AIN4aux.analoginput
scale
Depends
on the
input type
(BSL)
AIN2/AIN4aux.analog
inputburnoutaction
OFF:Disable
UP:Upscale
DOWN:Downscale
Depends
on the
input type
STD
nInput Range, SP Limiter Setting Parameter
Menusymbol: (MPV)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(P.UNI) ControlPVinputunit
-:Nounit
C:DegreeCelsius
-:Nounit,--:Nounit,---:Nounit
F:DegreeFahrenheit
Same
asPV
input
unit
STD
(P.DP)
ControlPVinputdecimal
point position
0:Nodecimalplace
1:Onedecimalplace
2: Two decimal places
3: Three decimal places
4: Four decimal places
1
(P.RH)
Maximumvalueof
controlPVinputrange -19999to30000,(P.RL<P.RH),
|P.RH-P.RL|≤30000
Depends
on the
input type
(P.RL)
Minimumvalueofcontrol
PVinputrange
Depends
on the
input type
(SPH) SPhighlimit
0.0to100.0%ofPVinputrange(EU),
(SPL<SPH)
Placelimitsontheprogramsetpoints
or the local setpoints when the con-
trollerisinprogramoperation.
*Placesthelimitontheprogram
setpoint, local setpoint, or remote
setpointduringprogramoperation.
*WhenLP2lampison,SPHand
SPLlimittheprogramsetpointfor
programpattern2retransmission.
100.0%
ofPV
input
range
(SPL) SP low limit
0.0%
ofPV
input
range
nOutput Setting Parameter
Menusymbol: (OUT)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(OT)
Outputtypeselection
Upper two
digits Lower two
digits
ControloutputorHeating-sidecontrol
output(Lowertwodigits)
00:OFF
01:OUTterminals(voltagepulse)
02:OUTterminals(current)
03:OUTterminals(relay/triac)
04:OUT2terminals(voltagepulse)
05:OUT2terminals(current)
06:OUT2terminals(relay/triac)
Cooling-sidecontroloutput(Uppertwodigits)
00:OFF
01:OUTterminals(voltagepulse)
02:OUTterminals(current)
03:OUTterminals(relay/triac)
04:OUT2terminals(voltagepulse)
05:OUT2terminals(current)
06:OUT2terminals(relay/triac)
Standard
type:
00.03
Heating/
cooling
type:
06.03
EASY
(CT)
Controloutputcycletime
Heating-sidecontrol
outputcycletime(in
Heating/coolingcontrol) 0.5to1000.0s
30.0s
(CTc)
Cooling-sidecontrol
output cycle time 30.0s
(V.AT)
Automaticvalveposition
adjustment
OFF:Stopautomaticadjustment
ON:Startautomaticadjustment OFF
(V.RS)
Valvepositionsetting
reset
SettingV.RStoONresetsthevalve
adjustmentsettingsandcausesthe
indication“V.RS”toblink.
OFF
(V.L)
Fully-closedvalveposi-
tionsetting
PressingtheSET/ENTERkeywithvalve
positionsettothefully-closedposition
byDownarrowkeycausestheadjusted
valuetobestored.WhenV.Ladjustment
iscompleted,V.Lstopsblinking.
-
(V.H)
Fully-openedvalveposi-
tionsetting
PressingtheSET/ENTERkeywith
valvepositionsettothefully-opened
positionbyUparrowkeycausesthe
adjustedvaluetobestored.WhenV.H
adjustmentiscompleted,V.Hstops
blinking
-
(TR.T) Valvetravelingtime 5to300s 60s
STD
(V.MOD) Valveadjustingmode
0:Valvepositionfeedbacktype
1:
Valvepositionfeedbacktype(moves
totheestimatingtypeifafeedback
inputerrororbreakoccurs.)
2:Valvepositionestimatingtype
0
(RTS)
Retransmissionoutput
typeofRET
OFF:Disable
PV1:PV
SP1: SP
OUT1:
OUT(Valveopening:0to100%
inPositionproportionalcontrol)
LPS:15VDClooppowersupply
PV2:Loop-2PV
SP2:Loop-2SP
OUT2:Loop-2OUT
TSP1:TargetSP
HOUT1:Heating-sideOUT
COUT1:Cooling-sideOUT
MV1:Positionproportionaloutput
(internalcomputedvalue)
TSP2:Loop-2targetSP
HOUT2:Loop-2heating-sideOUT
COUT2:Loop-2cooling-sideOUT
MV2:Loop-2positionproportional
output(internalcomputedvalue)
PV:PVterminalsanaloginput
RSP:RSPterminalsanaloginput
AIN2:AIN2terminalsanaloginput
AIN4:AIN4terminalsanaloginput
*Loop-2settingvaluesare
unavailable
inSingle-loopcontrol.
PV1 EASY
(RTH)
Maximumvalueof
retransmission output
scaleofRET
WhenRTS=PV1,SP1,PV2,SP2,
TSP1,TSP2,PV,RSP,AIN2,or
AIN4,
RTL+1digitto30000
-19999toRTH-1digit
Decimalpointposition:
WhenRTS=PV1,SP1,orTSP1,
decimal point position is same as
thatofPVinput.
WhenRTS=PV2,SP2,orTSP2,
decimal point position is same as
thatofRSPinput.
WhenRTS=PV,decimalpointposition
issameasthatofPVinputscale.
WhenRTS=RSP,decimalpointposition
issameasthatofRSPinputscale.
WhenRTS=AIN2,decimalpointposi-
tionissameasthatofAIN2scale.
WhenRTS=AIN4,decimalpointposi-
tionissameasthatofAIN4scale.
100%
ofPV
input
range
STD
(RTL)
Minimumvalueof
retransmission output
scaleofRET
0%
ofPV
input
range
(O1RS)
Retransmissionoutput
typeofOUTcurrent
output
SameasRTS
OFF
STD
(O1RH)
Maximumvalueof
retransmission output
scaleofOUTcurrent
output
WhenO1RS=PV1,SP1,PV2,SP2,
TSP1,TSP2,PV,RSP,AIN2,orAIN4,
O1RL+1digitto30000
-19999toO1RH-1digit
Decimalpointposition:
WhenO1RS=PV1,SP1,orTSP1,
decimal point position is same as
thatofPVinput.
WhenO1RS=PV2,SP2,orTSP2,
decimal point position is same as
thatofRSPinput.
WhenO1RS=PV,decimalpointposi-
tionissameasthatofPVinput
scale.
WhenO1RS=RSP,decimalpoint
positionissameasthatofRSP
input scale.
WhenO1RS=AIN2,decimalpoint
positionissameasthatofAIN2
scale.
WhenO1RS=AIN4,decimalpoint
positionissameasthatofAIN4
scale
-
(O1RL)
Minimumvalueof
retransmission output
scaleofOUTcurrent
output
-
(O2RS)
Retransmissionoutput
typeofOUT2current
output
SameasRTS
OFF
STD
(O2RH)
Maximumvalueof
retransmission output
scaleofOUT2current
output
WhenO2RS=PV1,SP1,PV2,SP2,
TSP1,TSP2,PV,RSP,AIN2,orAIN4,
O2RL+1digitto30000
-19999toO2RH-1digit
Decimalpointposition:
WhenO2RS=PV1,SP1,orTSP1,
decimal point position is same as
thatofPVinput.
WhenO2RS=PV2,SP2,orTSP2,
decimal point position is same as
thatofRSPinput.
WhenO2RS=PV,decimalpointposi-
tionissameasthatofPVinput
scale.
WhenO2RS=RSP,decimalpoint
positionissameasthatofRSP
input scale.
WhenO2RS=AIN2,decimalpoint
positionissameasthatofAIN2
scale.
WhenO2RS=AIN4,decimalpoint
positionissameasthatofAIN4
scale.
-
(O2RL)
Minimumvalueof
retransmission output
scaleofOUT2current
output
-
(OU.A)
OUTcurrentoutput
range
4-20:4to20mA
0-20:0to20mA
20-4:20to4mA
20-0:20to0mA
4-20
(OU2.A)
OUT2currentoutput
range 4-20
(RET.A)
RETcurrentoutput
range 4-20
nHeater Break Alarm Setting Parameter
Menusymbol: (HBA)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(HB1.S)
Heaterbreakalarm-1
function selection 0:Heatercurrentmeasurement
1:Heaterbreakalarm
1
EASY
(HB2.S)
Heaterbreakalarm-2
function selection 1
(HB1)
Heaterbreakalarm-1
current setpoint
OFF,0.1to300.0Arms
OFF
(HB2)
Heaterbreakalarm-2
current setpoint OFF
(CT1.T)
CT1
coilwindingnumberratio
1to3300
800
(CT2.T)
CT2
coilwindingnumberratio 800
(HDN1)
Heaterbreakalarm-1
On-delaytimer
0.00to99.59(m.s)
0.00
STD
(HDN2)
Heaterbreakalarm-2
On-delaytimer 0.00
IncaseswherethecurrenttransformersmanufacturedbyU.R.D.Co.,Ltdareused,setthefollowingvaluefor
thecoilwindingnumberratio.
CTL-6-S-H:800,CTL-12L-30:3000
n
RS-485 Communication Setting Parameter (E1/E3/E4-terminal Area)
Menusymbol: (R485)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(PSL) Protocol selection
PCL:PClinkcommunication
PCLSM:PClinkcommunication(with
checksum)
LADR:Laddercommunication
CO-M:Coordinatedmasterstation
MBASC:Modbus(ASCII)
MBRTU:Modbus(RTU)
CO-M2:Coordinatedmasterstation
(2-loopmode)
P-P:Peer-to-peercommunication
MBRTU
EASY
(BPS) Baud rate
600:600bps,1200:1200bps,
2400:2400bps,4800:4800bps,
9600:9600bps,19200:19.2kbps,
38400:38.4kbps
*ThebaudrateforRS-485isupto
19.2kbpsinE4-terminalarea.
19200
(PRI) Parity NONE:None,EVEN:Even,
ODD:Odd EVEN
(STP) Stopbit 1:1bit,2:2bits 1
(DLN) Datalength 7:7bits,8:8bits 8
(ADR) Address 1to99 1
■
Ethernet Communication Setting Parameter (E3-terminal Area)
Menusymbol: (ETHR)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(HSR)
High-speedresponse
mode OFF,1to8 1
EASY
(BPS) Baud rate 9600:9600bps,19200:19.2kbps,
38400:38.4kbps 38400
(PRI) Parity NONE:None,EVEN:Even,
ODD:Odd EVEN
to
(IP1toIP4) IP address 1 to 4
0to255
Initialvalue:(IP1).(IP2).(IP3).(IP4)=
(192).(168).(1).(1)
See left Table
below
to
(SM1toSM4) Subnetmask1to4
0to255
Initialvalue:(SM1).(SM2).(SM3).
(SM4)=(255).(255).(255).(0)
See left Table
below
to
(DG1toDG4) Defaultgateway1to4
0to255
Initialvalue:(DG1).(DG2).(DG3).
(DG4)=(0).(0).(0).(0)
See left Table
below
(PRT) Portnumber 502,1024to65535 502
(IPAR) IP access restriction OFF:Disable,ON:Enable OFF
to
,
to
(1.IP1to1.IP4,
2.IP1to2.IP4)
Permitted IP address
1-1to1-4
Permitted IP address
2-1to2-4
0to255
Initialvalue:
(1.IP1).(1.IP2).(1.IP3).(1.IP4)=
(255).(255).(255).(255)
(2.IP1).(2.IP2).(2.IP3).(2.IP4)=
(255).(255).(255).(255)
See left Table
below
(ESW) Ethernetsettingswitch
Settingthisparameterto“ON”en-
ablestheEthernetcommunication
parametersettings.
OFF,ON
OFF
UsethefollowingtabletorecordEthernetcommunicationsettingvalue.
Parameter n=1 n=2 n=3 n=4
IPn
SMn
DGn
1.IPn
2.IPn
n
PROFIBUS-DP Communication Setting Parameter (E3-terminal Area)
Menusymbol: (PROF)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(BR) Baud rate
9.6K:9.6kbps
19.2K:19.2kbps
93.75K:93.75kbps
187.5K:187.5kbps
0.5M:0.5Mbps
1.5M:1.5Mbps
3M:3Mbps
6M:6Mbps
12M:12Mbps
AUTO
45.45K:45.45kbps
AUTO
EASY
(ADR) Address 0to125 3
(BPS) Baud rate
9600:9600bps
19200:19.2kbps
38400:38.4kbps
38400
(FILE) Prolenumber 0,11to15 0
SetupParameters(Continuedfrompage12)
nPV Input Setting Parameter (Continued)

IM 05P02C41-15EN page 14/14
n
DeviceNet Communication Setting Parameter (E3-terminal Area)
Menusymbol: (DNET)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(BR) Baud rate
125K:125kbps
250K:250kbps
500K:500kbps
125K
EASY
(ADR) Address 0to63 63
(BPS) Baud rate
9600:9600bps
19200:19.2kbps
38400:38.4kbps
38400
(FILE) Prolenumber 0,11to15 0
n
CC-Link Communication Setting Parameter (E3-terminal Area)
Menusymbol: (CC-L)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(BR) Baud rate
156K:156kbps
625K:625kbps
2.5K:2.5kbps
5M:5Mbps
10M:10Mbps
10M
EASY
(ADR) Address 1 to 64 1
(BPS) Baud rate
9600:9600bps
19200:19.2kbps
38400:38.4kbps
38400
(FILE) Prolenumber 0,11to15
(0,11:Ver.1.10)(12to15:Ver.2.00) 0
■DisplayFunctionSettingParameter
Menusymbol: (DISP)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(PCMD)
ActivecolorPVdisplay
switch
0:Fixedinwhite
1:Fixedinred
2:Linktoalarm1(AlarmOFF:white,
AlarmON:red)
3:Linktoalarm1(AlarmOFF:red,
AlarmON:white)
4:Linktoalarm1or2(AlarmOFF:
white,AlarmON:red)
5:Linktoalarm1or2(AlarmOFF:
red,AlarmON:white)
6:PVlimit(Withinrange:white,Out
ofrange:red)
7:PVlimit(Withinrange:red,Outof
range:white)
8:SPdeviation(Withindeviation:
white,Outofdeviation:red)
9:SPdeviation(Withindeviation:red,
Outofdeviation:white)
10:LinktoDI(ON:red,OFF:white)
0
EASY
(PCH)
PVcolorchangehigh
limit
SetadisplayvaluewheninPVlimit
orSPdeviation.
-19999to30000(Setavaluewithin
theinputrange.)
Decimalpointpositiondependson
the input type.
0
(PCL) PVcolorchangelowlimit 0
(PTSL)
Programdisplaypattern
selection
PTN:Patterndisplay
SK.RP:Rampandsoakdisplay PTN
STD
(BAR1)
Upperbar-graphdisplay
registration
0:Disable
1:
OUT,Heating-sideOUT,Internalvalue
in Position proportional control
2:Cooling-sideOUT
3:PV
4: SP
5:Deviation
6:
Loop-2OUT,Loop-2heating-sideOUT
7:Loop-2cooling-sideOUT
8:Loop-2PV
9:Loop-2SP
10:Loop-2deviation
11to16:Disable
17:Feedbackinput(valveopening)
18:PVterminalsanaloginput
19:RSPterminalsanaloginput
20:AIN2terminalsanaloginput
21:AIN4terminalsanaloginput
22:Segmentprogress
23:Timeeventandalarmstatus
23
(BAR2)
Lowerbar-graphdisplay
registration
0
(BDV)
Bar-graphdeviation
displayband
0.0to100.0%ofPVinputrangespan
(EUS)
10.0%
ofPV
input
range
span
STD
(GUID) GuidedisplayON/OFF OFF:Nondisplay,ON:Display ON
(ECO) Economymode
OFF:Disable
1:EconomymodeON(Allindications
exceptPVdisplayOFF)
2:EconomymodeON(Allindications
OFF)
3:Brightness10%(wholeindication)
OFF
(BRI) Brightness (Dark)1to5(Bright) 3EASY
(MLSD)
Leastsignicantdigital
maskofPVdisplay
OFF:Withleastsignicantdigit
ON:Withoutleastsignicantdigit OFF STD
■SELECTDisplaySettingParameter
Menusymbol: (CSEL)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
to
(CS1toCS5)
SELECTDisplay-1to-5
registration
Registertheoperationparameter
(excepttheOperationMode)thatis
frequentlymodiedtodisplayitinthe
OperationDisplay.
OFF,2201to5000
Forthesettingrange,seeUser's
Manual.
OFF STD
UsethefollowingtabletorecordSELECTDisplaysettingvalue.
Parameter n=1 n=2 n=3 n=4 n=5
CSn
■KeyLockSettingParameter
Menusymbol: (KLOC)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(COM.W)
Communicationwrite
enable/disable OFF:Enable,ON:Disable OFF
STD
(DATA)
Front panel parameter
data(▼,▲)keylock
OFF:Unlock,ON:Lock
OFF
(RUN)
FrontpanelRUNkey
lock OFF
(RST) FrontpanelRSTkeylock OFF
(PTN) FrontpanelPTNkeylock OFF
(MODE)
FrontpanelMODEkey
lock OFF
■DIFunctionRegistrationParameter
Menusymbol: (DI.SL)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(PRG)
SwitchtoPROG(Start
ofprogramoperation)
SetanIrelaynumberofcontact
input.
Set“OFF”todisablethefunction.
Standard terminals
DI1:5025,DI2:5026,DI3:5027
E1-terminalarea
DI11:5041,DI12:5042,DI13:5043,
DI14:5044,DI15:5045,DI16:5046
E2-terminalarea
DI21:5057,DI22:5058,DI23:5059,
DI24:5060,DI25:5061,DI26:5062
E3-terminalarea
DI31:5073,DI32:5074,DI33:5075,
DI34:5076,DI35:5077
E4-terminalarea
DI41:5089,DI42:5090,DI43:5091,
DI44:5092,DI45:5093,DI46:5094
5025
STD
(RST)
SwitchtoRESET(Stop
ofprogramoperation) 5026
(LOC)
SwitchtoLOCAL(LSP)
(Startoflocal-mode
operation)
5027
(REM) SwitchtoREMOTE 5046
(P/R) PROG/RESETSwitch OFF
(P/H) PROG/HOLDSwitch OFF
(P/L)
PROG/LOCAL(LSP)
Switch OFF
(HOLD)
SwitchtoHOLD(Start
ofhold-modeoperation) OFF
(ADV) Advanceofsegment OFF
(WAIT) WaitON/OFFswitch OFF
(A/M) AUTO/MANswitch OFF
(AT)
Auto-tuningSTART/STOP
switch
OFF
(LAT) Latchrelease OFF
(LCD)
LCDbacklightON/OFF
switch
OFF
(PVRW)
PVred/whiteswitch
OFF
■DIFunctionNumberingParameter
Menusymbol: (DI.NU)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(PT.B0)
Bit-0ofprogrampattern
number
Seenexttable.
5089
EASY
(PT.B1)
Bit-1ofprogrampattern
number 5090
(PT.B2)
Bit-2ofprogrampattern
number 5091
(PT.B3)
Bit-3ofprogrampattern
number 5092
(PT.B4)
Bit-4ofprogrampattern
number 5093
(PT.B5)
Bit-5ofprogrampattern
number SetanIrelaynumberofcontactinput.
Set“OFF”todisablethefunction.
Standard terminals
DI1:5025,DI2:5026,DI3:5027
E1-terminalarea
DI11:5041,DI12:5042,DI13:5043,
DI14:5044,DI15:5045,DI16:5046
E2-terminalarea
DI21:5057,DI22:5058,DI23:5059,
DI24:5060,DI25:5061,DI26:5062
E3-terminalarea
DI31:5073,DI32:5074,DI33:5075,
DI34:5076,DI35:5077
E4-terminalarea
DI41:5089,DI42:5090,DI43:5091,
DI44:5092,DI45:5093,DI46:5094
OFF
STD
(PN.B0) Bit-0ofPIDnumber OFF
(PN.B1) Bit-1ofPIDnumber OFF
(PN.B2) Bit-2ofPIDnumber OFF
(PN.B3) Bit-3ofPIDnumber OFF
(MP.B0)
Bit-0ofmanualpreset
outputnumber OFF
(MP.B1)
Bit-1ofmanualpreset
outputnumber OFF
(MP.B2)
Bit-2ofmanualpreset
outputnumber OFF
■AL1-AL3FunctionRegistrationParameter
Menusymbol: (ALM)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(AL1.S) AL1functionselection
SetanIrelaynumber.Fortheitems
otherthanbelow,seeUser'sManual.
Ex.)Setthenumber4353forAL1.S
to use the alarm 1.
Set“OFF”todisablethefunction.
Settingrange:4001to6304
Nofunction:OFF,
PVevent1:4801,PVevent2:4802,
PVevent3:4803,PVevent4:4805,
PVevent5:4806,PVevent6:4807,
PVevent7:4809,PVevent8:4810,
Timeevent1:4817,Timeevent2:4818,
Timeevent3:4819,Timeevent4:4821,
Timeevent5:4822,Timeevent6:4823,
Timeevent7:4825,Timeevent8:4826,
Timeevent9:4833,Timeevent10:4834,
Timeevent11:4835,Timeevent12:4837,
Timeevent13:4838,Timeevent14:4839,
Timeevent15:4841,Timeevent16:4842,
Alarm1:4353,Alarm2:4354,
Alarm3:4355,Alarm4:4357
Alarm5:4358,Alarm6:4359,
Alarm7:4361,Alarm8:4362
AUTO(ON)/MAN(OFF)status:4177
ProgramRESETstatus:4181
ProgramRUNstatus:4182
Localoperationstatus:4183
Remoteoperationstatus:4185
HOLDmodestatus:4189
Programadvancestatus:4187
Patternendsignal(1second):4265
Patternendsignal(3seconds):4266
Patternendsignal(5seconds):4267
Waitendsignal(1second):4257
Waitendsignal(3seconds):4258
Waitendsignal(5seconds):4259
Outputtracking(ON)switchingsignal:4186
FAIL(NormallyON)output:4256
4801
STD
(AL2.S) AL2functionselection 4802
(AL3.S) AL3functionselection 4803
(OR.S)
OUTrelayfunction
selection OFF
(OR2.S)
OUT2relayfunction
selection OFF
■DOSettingParameter(E1/E2/E3/E4-terminalArea)
Menusymbol: (DO)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(DO1.S)
DO11/DO21/DO31/DO41
function selection SameasAL1.S
Set“OFF”todisablethefunction.
Initialvalue:
DO11=4805,DO12=4806
DO13=4807,DO14=4809,
DO15=4810,DO21=4817,
DO22=4818,DO23=4819
DO24=4821,DO25=4822,
DO31=4823,DO32=4825,
DO33=4826,DO34=4833,
DO35=4834,
DO41toDO45=OFF
See left
Table
below STD
(DO2.S)
DO12/DO22/DO32/DO42
function selection See left
(DO3.S)
DO13/DO23/DO33/DO43
function selection See left
(DO4.S)
DO14/DO24/DO34/DO44
function selection See left
(DO5.S)
DO15/DO25/DO35/DO45
function selection See left
UsethefollowingtabletorecordDOsettingvalue.
Parameter E1-terminalArea E2-terminalArea E3-terminalArea E4-terminalArea
DO1.S
DO2.S
DO3.S
DO4.S
DO5.S
■SystemSettingParameter
Menusymbol: (SYS)
Parameter
symbol Name of Parameter Setting Range Initial value User
setting
Display
level
(R.MD) Restartmode
Sethowthecontrollershouldrecoverfrom
a power failure of 5 seconds or more.
CONT:Continueactionsetbefore
power failure.
MAN:StartfromMAN.
RESET:StartfromAUTOandRESET.
Outputsthepresetoutputvalue.
CONT
STD
(R.TM) Restarttimer
Settimebetweenpoweronandthe
instant where controller starts compu-
tation.0to10s
0
(EPO)
Input error preset
output
Setpresetoutputvaluewhentheinputburnout
orADCerroroccurs.Manualoutputispriori-
tizedwhentheinputburnoutoccursinMAN.
0:Presetoutput
1:0%output
2:100%output
0 STD
(FREQ) Powerfrequency AUTO,60:60Hz,50:50Hz AUTO
EASY
(QSM) Quicksettingmode OFF:Disable
ON:Enable ON
(LANG)
Guidedisplay
language
ENG:English
FRA:French
GER:German
SPA:Spanish
Dependson
the model
andsufx
codes
(PASS) Passwordsetting 0(Nopassword)to65535 0
■
ErrorandVersionConrmationParameter(fordisplayonly)
Menusymbol: (VER)
Parameter
symbol Name of Parameter Status record
Display
level
(PA.ER) Parameter error status
EASY
(OP.ER) Optionerrorstatus
(AD1.E) A/Dconvertererrorstatus1
(AD2.E) A/Dconvertererrorstatus2
(PV1.E) Loop-1PVinputerrorstatus
(PV2.E) Loop-2PVinputerrorstatus
(LA.ER) Laddererrorstatus
(MCU) MCUversion
(DCU) DCUversion
(ECU1) ECU-1version(E1-terminalarea)
(ECU2) ECU-2version(E2-terminalarea)
(ECU3) ECU-3version(E3-terminalarea)
(ECU4) ECU-4version(E4-terminalarea)
(PARA) Parameterversion
(H.VER) Productversion
(SER1)Serialnumber1
(SER2) Serialnumber2
(MAC1) MACaddress1(E3-terminalarea)
(MAC2) MACaddress2(E3-terminalarea)
(MAC3) MACaddress3(E3-terminalarea)
*TheparametersforLoop-2areunavailableinSingle-loopcontrol.
■ParameterDisplayLevelParameter
Menusymbol: (LVL)
Parameter
symbol Name of Parameter Setting Range Initial
value
User
setting
Display
level
(LEVL) Parameterdisplaylevel
EASY:Easysettingmode
STD:Standardsettingmode
PRO:Professionalsettingmode
STD EASY
*ForProfessionalsettingmode,seeUser’sManual.
Trademarks
● Our product names or brand names mentioned in this manual are
the trademarks or registered trademarks of Yokogawa Electric Corporation.
● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks
of Adobe Systems Incorporated.
● Ethernet is a registered trademark of XEROX Corporation in the United States.
● Modbus is a registered trademark of Schneider Electric.
● PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.
● DeviceNet is a registered trademark of Open DeviceNet Vendor Association.
● CC-Link is a registered trademark of CC-Link Partner Association.
● We do not use the TM or ® mark to indicate these trademarks or
registered trademarks in this manual.
● All other product names mentioned in this manual are trademarks
or registered trademarks of their respective companies.