York TVHC09-18DSAAAR User manual

Read this manual before installation and operation
Make sure that it is well kept for later reference
Read this manual before installation and operation
Make sure that it is well kept for later reference
Mini-Split Air Conditioner
TVHC09-18DSAAAR
INSTALLATION MANUAL

CONTENTS
Safety precautions ..................................................................................3
Part names.................................................................................................4
Manual operation....................................................................................5
How the air conditioner works...........................................................6
Optimal operation...................................................................................6
Adjusting air ow direction................................................................7
Preparation before installation...........................................................8
Installation procedure..........................................................................10
Maintenance.............................................................................................18
Operation tips..........................................................................................19
Troubleshooting guide..........................................................................20
Please read this installation
manual carefully before starting
the installation. It will tell you
necessary information.
Quality POLICY
We will continuously strive to satisfy
our customers with consistent reli-
abilityinproduct,service andsupport
through superior quality, service
culture and distinctive technology.
J440-EN.indd 2 2/14/08 1:26:32 PM
Wiring Diagram........................................................................................14
Air Purging.................................................................................................16

EN
3
ENGLISH
EXTENDED PARTS
1. Refrigerant Pipe
2. Pipeinsulationmaterial(Polyethylenefoam9mm thick)
3. Vinyl tape
4. Putty
REQUIRED TOOLS
1. Screw driver 9. Manifold gauge
2. Hexagonal wrench 10. Gas leak detector
3. Torque wrench 11. Vacuum pump
4. Spanner 12. Pipe clamp
5. Reamer 13. Pipe cutter
6. Hole core drill 14. Flare tool set
7. Tape measure 15. Electrical circuit tester
8. Thermometer
• Please read this installation manual carefully before starting installation of the unit.
• This air conditioning system contains refrigerant under pressure, rotating parts and electrical connection which may
be dangerous and can cause injury. Installation and maintenance of this air conditioning system should only be car-
ried out by trained and qualied personnel.
• After unpacking, please check the unit carefully for possible damage.
• Before undertaking any work on the unit, make sure that the power supply has been disconnected.
WARNING & CAUTION
Do not store or unpack the unit in a wet area or
expose to rain or water.
Do not install in a place where ammable gas
may leak.
Do not conduct installation in wet area or in the rain.
This system is designed for domestic or residential
use only.
It may cause the unit to short circuit and may result electric
shocks or re.
It may cause re.
It is a high risk to cause the electrical shocks. If used in certain environments, such as a manufacturing
workplace, the equipment may not function ef ciently.
INSTALLATION
SAFETY PRECAUTIONS
J440-EN.indd 3 2/14/08 1:26:32 PM
Models
Liguid size
Gas size
6.35 Ø 6.35 Ø 6.35Ø
Ø Ø 12.7 Ø 12.7
9.53
12 18
09

4ENGLISH
4
3
5
2
6
1
8
10
11
9
7
1
auto
2 3 45
PART NAMES
INDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
1. Front panel
2. Air inlet
3. Air lter
4. Air outlet
5. Horizontal air ow grille
6. Vertical air ow louver
7. Display panel
8. Remote controller
OUTDOOR UNIT
9. Connecting pipe, drain hose
10. Air inlet (side and rear)
11. Air outlet
NOTE:
All the pictures in this manual are for explanation
purpose only. Your air conditioner may be slightly
dierent.
The actual shape shall prevail.
Signal receptor
Indicator Lights on Display panel
The display panel on the indoor unit would look like one
of the following:
For cooling only models ( f21000Btu/h unit), 2indicator
light is FAN ONLY.
1AUTO indicator:
This indicator illuminates when the air conditioner is in
AUTO operation.
2DEFROST Indicator
(For cooling & heating model only):
This indicator illuminates when the air conditioner starts
defrosting automatically or when the warm air control
feature is activated in heating operation.
3DIGITAL DISPLAY:
Displays the current setting temperature when the air
conditioner is in operation.
4OPERATION indicator:
The indicator ashes once every second after power is
on and illuminates when the air conditioner is in operation.
5TIMER indicator:
The indicator illuminates when TIMER is set ON/OFF.
J440-EN.indd 4 2/14/08 1:26:33 PM

EN
5
ENGLISH
AUTO/COOL
Manual operation can be used temporarily in case you cannot nd the remote controller or its batteries are exhausted.
1Open and lift the front panel up to an angle until it
remains xed with a clicking sound.
2One press of the manual control button will lead to the
forced AUTO operation.
3Close the panel rmly to its original position.
CAUTION
• Once you push the manual button, the operation mode
is shifted in an order as: AUTO, COOL, OFF.
• Push the button twice, the unit will operate in forced
COOL mode. This is used for testing purposes only.
• Third press will stop the operation and turn o the air
conditioner operation.
• To restore the remote controller operation, use the
remote controller directly.
CAUTION
1. If air conditioner is used outside of the above conditions, certain safety protection features may come into operation
and cause the unit to function abnormally.
2. Room relative humidity less than 80%. If the air conditioner operates in excess of this gure, the surface of the air
conditioner may attract condensation. Please sets the vertical air ow louver to its maximum angle (vertically to the
oor), and set HIGH fan mode.
3. Optimum performance will be achieved within these operating temperature.
OPERATING TEMPERATURE
MANUAL OPERATION
Manual control button
Panel
Mode
Temperature Cooling operation Heating operation Drying operation
Room temperature 17ºC 30ºC 10ºC
Outdoor temperature
18ºC ~ 50ºC
-15ºC ~ 34ºC 10ºC ~ 50ºC
(-15ºC 50ºC: For the models
with low temperature
cooling system)
J440-EN.indd 5 2/14/08 1:26:35 PM
>
/
>
/
>
/

6ENGLISH
Cooling Cooling
Time
Room
temperature
set temperature
Cooling
Fan only
Fan only
1
1
1 hour
1 hour
Set
Temperature
Cooling
Press Sleep button
Press Sleep button
1
1
1 hour 1 hour
Set
Temperature
Heating
To achieve optimal performance, please note the following:
• Adjust the air flow direction correctly so that it is not directed on people.
• Adjust the temperature to achieve the highest comfort level. Do not adjust the unit to excessive temperature levels.
• Close doors and windows on COOL or HEAT modes, or performance may be reduced.
• Use TIMER ON button on the remote controller to select a time you want to start your air conditioner.
• Do not put any object near air inlet or air outlet, as the efficiency of the air conditioner may be reduced and the air
conditioner may stop running.
• Clean the air filter periodically, otherwise cooling or heating performance may be reduced.
• Do not operate unit with horizontal louver in closed position.
nAUTOMATIC OPERATION
• When you set the air conditioner in AUTO mode, it will
automatically select cooling, heating (cooling/heating models
only), or fan only operation depending on what temperature
you have selected and the room temperature.
•
The air conditioner will control room temperature automatically
round the temperature point set by you.
• If the AUTO mode is uncomfortable, you can select desired
conditions manually.
nDRYING OPERATION
• The dry mode will automatically select the drying operation
based on the difference between the set temperature and
the actual room temperature.
•
The temperature is regulated while dehumidifying by repeating
turning on and off of the cooling operation or fan only.
The fan speed is LOW.
HOW THE AIR CONDITIONER WORKS
OPTIMAL OPERATION
nECONOMIC OPERATION
• When you push SLEEP button during cooling, heating
(cooling/heating models only)
, or AUTO operation, the air
conditioner will automatically increase (cooling) or decrease
(heating) 1°C per hour.
The set temperature will be steady 2 hours later.
• The fan speed will be automatically controlled.
DRYING operation
J440-EN.indd 6J440-EN.indd 6 2/14/08 1:26:37 PM2/14/08 1:26:37 PM

EN
7
ENGLISH
• Adjust the air flow direction properly, otherwise it might cause
discomfort or cause uneven room temperatures.
•
Adjust the horizontal louver using the remote controller.
• Adjust the vertical louver manually.
Adjusting the Vertical Air Flow Direction (up - down)
The air conditioner automatically adjusts the vertical air flow direction in
accordance with the operating mode.
To set the vertical air flow direction
Perform this function while the unit is in operation.
Keep pressing the AIR DIRECTION button on the remote controller to
move the louver to the desired direction.
• Adjust the vertical air flow direction to the desired direction.
• In subsequent operations, the vertical air flow is automatically set in
the direction to which you adjusted the louver by pressing the AIR
DIRECTION button.
To set the horizontal air flow direction (left - right)
Adjust the vertical louver manually using the lever on the left or right
side of the vertical louver arm (depending on model). Take care not to
catch fingers on the fan, horizontal louver or to damage vertical louvers.
When the air conditioner is in operation and the horizontal louver is in
a specific position, move the lever at left (or right, depending on model)
end of the air outlet to the desired position.
To automatically swing the air flow direction (up - down)
Perform this function while the air conditioner is in operation.
• Press the SWING button on the remote controller.
• To stop the function, press the SWING button again.
Press AIR DIRECTION button to lock louver in desired position.
ADJUSTING AIR FLOW DIRECTION
Lever
J440-EN.indd 7J440-EN.indd 7 2/14/08 1:26:38 PM2/14/08 1:26:38 PM

8ENGLISH
PREPARATION BEFORE INSTALLATION
• Before doing any work, check the interior power supply cord and the main breaker capacity are sucient and the
installation area is sucient and complies with the requirements.
• Check that the power supply available agrees with nameplate voltage.
•
Electrical work, wiring and cables must be performed in compliance with national and local wiring codes and standard.
• Do not use the extension cables. In the case extended cables are needed, use the terminal block.
SELECTION OF THE LOCATION
• Select a place which provides the space around the units as shown in the diagram below.
INDOOR UNIT OUTDOOR UNIT
CAUTION
• Do not install in a place that cannot bear the weight of the unit.
INDOOR UNIT PICTURES
TVHC09-18
Dimension
Models W H D
09 - 12 790 275 190
18 940 275 198
J440-EN.indd 8 2/14/08 1:26:39 PM
Models 09
A12 cm
B230 cm
C12 cm
D15 cm
12 18
12 cm
230 cm
12 cm
15 cm
12 cm
230 cm
12 cm
15 cm
Models 09
A
B
C
D
12 18
30 cm
200 cm
60 cm
30 cm
30 cm
200 cm
60 cm
30 cm
30 cm
200 cm
60 cm
30 cm

EN
9
ENGLISH
OUTDOOR UNIT PICTURES
TVHC09-18
Models W H D L1 L2 L3
07-09 685 430 276 460 300 445
12 700 522 250 458 275 537
18 780 530 275 549 290 545
J440-EN.indd 9 2/14/08 1:26:40 PM

10 ENGLISH
ø 65 mm
PARTS INSTALLATION
Mounting screw B
ST3.9x10-C-H
Remote controller
holder
Loop the
connective
cable.
8
9
Remote Controller
7
C
B
A
60 cm or more
30 cm or more
60 cm r
oe
r
o
m
200 cm or more
6
2
3
1
12cm or
more
12cm o r
more
Air Filter
15cm or more
Air Outlet
300 cm ormore
On/O
Sleep
Fan
Swing
AirDi rect ion
Timer On
Timer O
Mode
Hr.
ON TIMER
Hr.
O TIMER
SET TEMP
Auto
INDOOR UNIT
INSTALLATION PROCEDURE
Fixing
• Place the installation guide pattern on the designated
installation place and mark the hole position.
• Drill a hole and mount installation plate.
MODEL 09-18
•
Make 6 mm 4-6 holes, in the wall at the four corners of mount-
ing
plate (bracket) then insert appropriate mounting devices.
• Install the mounting plate using 4-6 pieces of mounting screw
securely at four corners and tighten the screw completely.
Do not over tighten the screws and deform the back plate.
• Ensure that the space around the left and right of the
indoor unit is more than 12cm.
The indoor unit should be installed allowing a minimum
clearance of 15cm from the ceiling.
•
Use a stud nder to locate studs to prevent unnecessary
damage to the wall.
• Aminimum pipe run of 3 metres is required to minimise
vibration & excessive noise.
Theindoorunitshouldbeinstalledonthe wallata height
of 1.7 metres or more from the oor but less than 2.3
metres from the oor.
•
Directions A, B and C should be free from obstructions.
• This illustration is for explanation purposes only.
• Copper lines must be insulated independently.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
• After determining the pipe
hole position. Drill the hole
at a slight downward slant
towards the outdoor side.
Outdoor
Indoor
Note: When installing
the refrigerant pipes from
others side. A hole must
be place to allow fall
towards the outdoor unit.
Except the above parts provided, the other parts needed
during installation you must purchase.
NOTES
CAUTIONS
Number
Name of Accessories
11
82
38
14
15
6
Connecting
pipe
Assembly
Liquid side ø 6.35 (7000-18000 Btu/h)
Parts you
must
purchase
Gas side
ø 9.53 (7000-9000 Btu/h)
ø 12.7 (12000-18000 Btu/h)
17
19
NOTES
65
70 70
45
0
7
2
Indoor unit outline Installation plate
A:780 (<16000Btu/h model), 920 ( f16000Btu/h model)
120 mm or
more to wall
120 mm or
more to wall
Left refrigerant
pipe hole Ø65
Right refrigerant
pipe hole Ø65
150 mm or more to ceiling
J440-EN.indd 10 2/14/08 1:26:41 PM
2
Q’ty
Installation plate
Clip anchor
Self-tapping screw AST3.9X25
Seal
Drain joint
Remote contoroller
Self-tapping screw B ST3.9X10
8
Remote Controller holder

EN
11
ENGLISH
Wiring
• This indoor unit is ready for connection to the outdoor unit.
CAUTION
•
Nevermodifythe unitby removing anyof thesafetyguards
or by passing any of the safety interlock switches.
•
Connect the interconnecting cable correctly and connect
the connecting cable to terminal as identied with their
respective marking.
•
Do not damage the conductor core or inner insulation of power
supply cables and do not deform or crush the cables.
Piping
The auxiliary piping can be connected in the directions
shown the above diagram. To connect in the D,Eand
Fdirection, pipes will need to be extended.
CAUTION
• Bend pipes carefully to avoid attening or obstructing
them if the pipes are bent incorrectly, the indoor unit
may be unstable on the wall.
• Carefully arrange pipes so that pipes do not stick out
of the rear plate of the indoor unit.
Drain hose
• Drain hose is exible and can be routed to suit various
piping arrangements. The drain line must include elbow
trap (U bend). Connect a plastic condensate pipe with
an internal diameter of 12 mm.
• The drain hose can be connected to the left or the right side.
Verication of condensate water drainage:
Fill the drain pan with water and observe evacuation.
Note: Do not put the drain hose end into water.
For left and left rear piping (Factory standard)
Drain hose
Drain cap
For right connection
Drain hose
Drain cap
ARight
BRight
CRight DRight
FLeft
ERear Bottom
J440-EN.indd 11 2/14/08 1:26:44 PM

12 ENGLISH
Indoor Unit Fixing
• Thread the indoor unit piping and cable through the hole.
• Hang the top of the unit onto the upper ridge of them in mounting plate.
• Make sure that the unit is correctly hung in place by sliding it to the left, then to the right.
• Press the bottom left and bottom right hand corners of the unit against the mounting plate until the xing prongs click
into place in the retainers provided to that eect.
Drainage line
Interconnection cable
Note: The condensate evacuation line should be taped to the
refrigerant lines with vinyl tape.
a) Access plate for the
condensate drainage
pump detection
(condensate pump is
available as an
accessory).
Condensate
drainage line Vinyl tape
a
OUTDOOR UNIT
Fixing and Piping
• Piping must be performed by qualied personnel
according to good refrigeration systems practices.
• Piping materials and insulation materials must be of
refrigerant quality.
• Select the pipe diameters according to the size of unit
and cut the pipe to design length by using pipe cutter.
• Install the are nuts and are the end of the pipes.
• Check that no foreign bodies are inside the piping.
• Align the central of the connecting pipes and tighten
the are nut.
•
Fix piping with pipe clamps and check that any pipe
vibrations cannot be transmitted to the building structure.
NOTES
• Connect the pipe correctly.
• Do not apply the excessive torque.
• Use an appropriate bending tool to form curves and
avoid over-tightening the refrigerant tubes.
• To prevent heat loss, the two lines must be insulated
separately.
Maximum Piping Length
The suction line must have a 2% gradient up to the
compressor on horizontal sections.
Where piping lengths are unusually long and include a
large number of oil traps, it may be necessary to adjust
to compressor charge.
Refrigerant piping connections
(FLARE connections)
To avoid alteration of unit capacities, check that piping
lengths and changes in elevation are kept to a strict
minimum.
Before connecting the refrigerant lines, follow the
procedures below (if pre-charged connection lines are
not supplied):
• Select copper pipe diameters according to the size of
unit to be installed.
• Install the refrigeration lines, checking that no foreign
bodies get inside the piping.
• Install the are connectors and are the ends of the
pipes.
•
Evacuate the piping. This operation, which should last
at least 15 minutes if there are large piping lengths and
changes in elevation, should be followed by a leak test.
Refrigerant charge to be added per extra meter
of piping length when more than 7 meters.
Note: Where the dierence in elevation between the indoor
unit and the outdoor unit is greater than 5 meters, install
an oil trap every 5 meters.
J440-EN.indd 12 2/18/08 2:50:03 PM
Max. refrigerant
pipe length
Max. dierence
in level
Unit size
m
m
09 12 18
25
10
20 20
88
Unit size MODELS
g/m
09 12 18
30 30 30

EN
13
ENGLISH
To this effect, when the piping has been evacuated, close the pressure gauge tap, note the value on the gauge, then
wait for 15 minutes. If the needle moves, there is a leak in the system. Make the necessary adjustments or repairs and
repeat this procedure until the needle no longer moves.
• Open the service valves and top up the refrigerant charge if necessary.
Insulation
Minimum thickness 6 mm
Heat pump
Liquid
Cooling
Heat pump
(discharge)
Cooling
(suction)
Heat pump
(discharge)
Heat pump
This unit is shipped complete with a charge of R-22 / R407C / R410A
refrigerant that will be sufficient for an interconnecting piping length
of 7 meters.
Liquid
Cooling
GAS
Cooling
(suction)
Low pressure High pressure
Manifold
Gas valve
Liquid valve
Pressure tap
Outdoor unit Indoor unit
Gas line
Liquid line
R-22 / R407C / R410A
• Outdoor heat pump unit : install the unit at least 10 cm above ground level to facilitate drainage of defrost water and
prevent accumulation of ice. In effect, defrost water can cause accumulation of ice under the unit during subfreezing
outdoor temperatures.
• In areas with heavy snowfall it is best to install the unit on wall supports.
• In some regions, it is necessary to heat the bottom of the condensate drainage pan and the condensate drainage piping
to avoid ice formation, and resulting ice build-up in the fan compartment (heater strip must be at least 25 W/m).
COLD AREA RECOMMENDATION
OK
J440-EN.indd 13J440-EN.indd 13 2/14/08 1:26:48 PM2/14/08 1:26:48 PM

14 ENGLISH
Wiring
Prepare the power source for exclusive with the air conditioner.
The supply voltage must comply with the rated voltage of the air conditioner: The plug socket shall be accessible after installation.
Remark: All the wiring must be based on the wiring nameplate which is shown on the model.
CAUTIONS
•Perform the wiring with sucient capacity. Installation places legally require a short circuit isolator to be attached to
prevent electrical shock.
•Do not extend the power cable code by cutting.
•Power voltage should be in the range of 90%~110% of rated voltage.
•Theplugof theair conditionertakesa groundingleg,andclientsshoulduse agroundingsocketsothatthe airconditioner
can be grounded eciently.
•If the power cord is damaged, replacement should be conducted by qualied technician or a serviceman.
NOTE Remark per EMC Directive 89/336/EEC
To prevent icker impressions during the start of the compressor (technical process), following installation conditions do apply.
1.The power connection for the air conditioner has to be done at the main power distribution.
The distribution has to be of a low impedance, normally the required impedance reaches at a 32 A fusing point.
2.No other equipment has to be connected with this power line.
3.For detailed installation acceptance, please refer to your contract with the power supplier if restrictions do apply for
products like washing machines, air conditioner or electrical ovens.
4.For power details of the air conditioner, refer to the rating plate of the product.
5.For any question, contact your local dealer.
CAUTIONS
• Never modify the unit by removing any of the safety guards or by bypassing any of the safety interlock switches.
•
Connect the connecting cable correctly and connect the connecting cable to terminal as identied with their respective marks.
• Do not scratch the conductive core & inner insulator of power supply cables and do not deform or smash on the surface
of cables.
Electrical Connections
All electrical wiring and connections must comply with local codes and standards. Power supply cord and interconnection
cord used must not be lighter than Polychloroprene sheethed cord (245 IEC 57 or H05RN-F).
Disconnecting device must have a contact separation of at least 3 mm.
Indoor Unit : TVHC09DSAAAR
J440-EN.indd 14 2/14/08 1:26:49 PM
Outdoor Unit : TVHC09DSAAAR
4
P_1
OPTIONAL:
OPTIONAL:
335
24
CHOOSE ONE BY THE
TRANSFORMER. ~
~
~
~
+ +
--
3
11
ORANGE
OR A N G E
CAP ACITOR
3
4
3
FILTER
HL1
HL2
HN1
HN2
S
N
L
2

EN
15
ENGLISH
J440-EN.indd 15 2/14/08 1:26:50 PM
Indoor Unit : TVHC12DSAAAR Outdoor Unit : TVHC12DSAAAR
Indoor Unit : TVHC18DSAAAR Outdoor Unit : TVHC18DSAAAR
4
P_1
OPTIONAL:
OPTIONAL:
335
24
CHOOSE ONE BY THE
TRANSFORMER.
~
~
~
~
+ +
--
3
11
ORANGE
OR A NG E
CAP ACITOR
3
4
3
FILTER
HL1
HL2
HN1
HN2
S
N
L
2
4
P_1
OPTIONAL:
OPTIONAL:
335
24
CHOOSE ONE BY THE
TRANSFORMER.
R
S
C
BLUE
U
V
W
RY3
4
CN6
CN7
CN28
CN26
CN10
N-B
RED
YELLOW
ORANGE RED
YELLOW
ORANGE
CN3
CN2
CN1
CN15 CN14
CN16
L2
N-A
YELLOW
ORANGE
Y/G
RED
BLUE
BLACK
GRAY
RED
BROWN
BLUE
YELLOW
Y/G
CN5
CN4
RED
RED
L N S GND
CN31 CN33
CN34
CN32
5
BLACK
BLACK
RED RED
B
A
Y/G
R1815E

16 ENGLISH
After the conrmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specically for the air conditioner.As for the method of wiring, be guided
by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical ttings are liable to come loose from vibrations to which
the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened.
(If they are loose, it could cause burn-out of the wires.)
3) Specication of power source.
4) Conrm that electrical capacity is sucient.
5)
See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the nameplate.
6) Conrm that the cable thickness is as specied in the power source specication.
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function
of the overload.
9) The means for disconnection from a power supply shall be incorporated in the xed wiring and have an air gap contact
separation of at least 3 mm in each active (phase) conductors.
CAUTIONS
Air and moisture in the refrigerant system have undesirable eects as indicated below:
• Pressure in the system rises.
• Operating current rises.
• Cooling or heating eciency drops.
• Moisture in the refrigerant circuit may freeze and block capillary tubing.
• Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove
any noncondensables and moisture from the system.
Air purging with vacuum pump
Preparation
Check that each tube (both liquid and gas side tubes) between the indoor and outdoor units have been properly
connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and
the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are
kept closed at this stage.
•When relocate the unit to another place, perform evacuation using vacuum pump.
•Make sure the refrigerant added into the air conditioner is liquid form in any case.
AIR PURGING
Connective pipe length Air purging method Additional amount of refrigerant to be charged
Less than 7 m Use vacuum pump.
5~10 m Use vacuum pump. Liquid side: ø6.35 (Pipe length-7) x 30 g
Pipe length and refrigerant amount:
J440-EN.indd 22 2/14/08 1:26:59 PM

EN
17
ENGLISH
Defrosting operation (Available for heating only)
1. Condition to start defrosting: Units will switch to defrosting
mode when either of the following conditions is met.
a. Unit has been running under T3<0 oC for 40 minutes
and T3<-3 oC for 3 minutes.
b. Unit has been running at high temperature protection
mode* for 90 minutes. (*High temperature protection
mode: when coil temperature of indoor unit reaches
55°C, outdoor unit will turn o external unit fan but still
keep compressor running).
2.
Condition to stop defrosting: Units will switch back to heating
mode when either of the following conditions is met.
a. Unit has been running at defrosting mode for 10
minutes.
b. T3>20 oC
Remark: T3 is coil temperature of outdoor units.
T3 (°C)
3 min
40 min
Time
Elapsed
(min)
Starting Defrosting Mode under condition a.
NOTE: The supply voltage cannot be less than the rate voltage of the air conditioner.
ylppusrewoPledoM Input Rated Amp
(Switch/Fuse) Power Cord Size
a12000Btu/h 10A/15A f1.0/1.5mm
220-230V ~ 60Hz
f12000Btu/h 220-240V ~ 50Hz 16A f1.5mm
Electrical Work
Heating mode Defrosting mode
J440-EN.indd 23 2/14/08 1:27:00 PM

18 ENGLISH
MAINTENANCE
nCleaning the air filter
A clogged air filter reduces the cooling efficiency of this unit. Please clean
the filter once every 2 weeks.
1.
Lift the indoor unit panel up to an angle until it stops with a clicking sound.
2. Take hold of the handle of the AIR FILTER and lift it up slightly to take it
out from the filter holder, then pull it downwards.
3. Remove the AIR FILTER from the indoor unit.
• Clean the AIR FILTER once two weeks.
• Clean the AIR FILTER with a vacuum cleaner or water, then dry it up
in cool place.
4. Remove the air freshening filter from its support frame (The installation
and removing method of the air freshening filter is different depending on
the models, see the pictures marked 1and 2on the left).
• Clean the air freshening filter at least once a month, and replace it
every 4-5 months.
• Clean it with vacuum cleaner, then dry it in cool place.
5. Install the AIR FILTER back into position.
6. Insert the upper portion of the AIR FILTER back into the unit taking care that
the left and right edges line up correctly and place filter into position.
nMaintenance
If you plan to idle the unit for a long time, perform the following:
(1) Operate the fan for about half a day to dry the inside of the unit.
(2) Stop the air conditioner and disconnect power.
Remove the batteries from the remote controller.
(3) The outdoor unit requires periodic maintenance and cleaning. Do not
attempt to do this yourself.
Contact your dealer or servicer.
nChecks before operation
• Check that the wiring is not broken off or disconnected.
• Check that the air filter is installed.
• Check if the air outlet or inlet is blocked after the air conditioner has not
been used for a long time.
It is necessary to stop the air conditioner and disconnect the power supply
before cleaning.
WARNING
nCleaning the indoor unit and remote controller
• Use a dry cloth to wipe the indoor unit and remote controller.
• A cloth dampened with cold water may be used on the indoor unit if it
is very dirty.
•
The front panel of the indoor unit can be removed and cleaned with water.
Then wipe it with a dry cloth.
• Do not use a chemically treated cloth or duster to clean the unit.
• Do not use benzine, thinner, polishing powder, or similar solvents for
cleaning. These may cause the plastic surface to crack or deform.
CAUTIONS
CAUTIONS
1
2
Air freshening filter
Filter Handle
Air freshening filter
Household
Drain
Cleaner
No
Thinner
• Do not touch the metal parts of the unit when removing the filter. Injuries
can occur when handling sharp metal edges.
• Do not use water to clean inside the air conditioner.
Exposure to water can destroy the insulation, leading to possible electric shock.
• When cleaning the unit, first make sure that the power and circuit breaker
are turned off.
J440-EN.indd 24J440-EN.indd 24 2/14/08 1:27:01 PM2/14/08 1:27:01 PM

EN
19
ENGLISH
OPERATION TIPS
The following events may occur during normal operation.
1. Protection of the air conditioner.
Compressor protection
• The compressor cannot restart for 3 minutes after it stops.
Anti-cold air (Cooling and heating models only)
•
The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in one of the following
three situations and the set temperature has not been reached.
A) When heating has just starting.
B) Defrosting.
C) Low temperature heating.
• The indoor or outdoor fan stop running when defrosting (Cooling and heating models only).
Defrosting (Cooling and heating models only)
• Frost may be generated on the outdoor unit during heat cycle when outdoor temperature is low and humidity is
high resulting in lower heating efficiency of the air conditioner.
• During this condition air conditioner will stop heating operation and start defrosting automatically.
• The time to defrost may vary from 4 to 10 minutes according to the outdoor temperature and the amount of frost
buildup on the outdoor unit.
2. A white mist coming out from the indoor unit.
• A white mist may generate due to a large temperature difference between air inlet and air outlet on COOL mode
in an indoor environment that has a high relative humidity.
• A white mist may generate due to moisture generated from defrosting process when the air conditioner restarts
in HEAT mode operation after defrosting.
3. Low noise of the air conditioner.
• You may hear a low hissing sound when the compressor is running or has just stopped running.
This sound is the sound of the refrigerant flowing or coming to a stop.
• You can also hear a low “squeak” sound when the compressor is running or has just stopped running. This is
caused by heat expansion and cold contraction of the plastic parts in the unit when the temperature is changing.
• A noise may be heard due to louver restoring to its original position when power is first turned on.
4. Dust in blown out from the indoor unit.
This is a normal condition when the air conditioner has not been used for a long time or during first use of the unit.
5. A peculiar smell come out from the indoor unit.
This is caused by the indoor unit giving off smells permeated from building material, from furniture, or smoke.
6.
The air conditioner turns to FAN only mode from COOL or HEAT (for cooling and heating models only) mode.
When indoor temperature reaches the temperature setting on air conditioner, the compressor will stop automatically,
and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises
on COOL mode or falls on HEAT mode (For cooling and heating models only) to the set point.
7. Dripping water may generate on the surface of the indoor unit when cooling in a high relatively humidity (relative humidity
higher than 80%). Adjust the horizontal louver to the maximum air outlet position and select HIGH fan speed.
8. Heating mode (for cooling and heating models only)
The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit during heating operation.
When the outdoor temperature falls, heat drawn in by the air conditioner decreases accordingly. At the same time,
heat loading of the air conditioner increases due to larger difference between indoor and outdoor temperature. If a
comfortable temperature cannot be achieved by the air conditioner, we suggest you use a supplementary heating
device.
9. Auto-restart function
Power failure during operation will stop the unit completely.
For the unit without Auto-restart feature, when the power restores, the OPERATION indicator on the indoor unit starts
flashing. To restart the operation, push the ON/OFF button on the remote controller. For the unit with Auto-restart
feature, when the power restores, the unit restarts automatically with all the previous settings preserved by the memory
function.
10.
Lightning or a car wireless telephone operating nearby may cause the unit to malfunction.
Disconnect the unit with power and then re-connect the unit with power again. Push the ON/OFF button on the remote
controller to restart operation.
J440-EN.indd 25J440-EN.indd 25 2/14/08 1:27:02 PM2/14/08 1:27:02 PM

20 ENGLISH
TROUBLESHOOTING GUIDE
ydemeResuacelbaborPmelborP
A. The air conditioner does not
run.
1. Power failure.
2. Fuse blown or circuit breaker
open.
3. Voltage is too low.
4. Faulty contactor or relay.
5. Electrical connections loose.
6. Thermostat adjustment too low
(in heating mode) or too high (in
cooling mode).
7. Faulty capacitor.
8. Incorrect wiring, terminal loose.
9. Pressure switch tripped.
1. Wait for power resume.
2. Replace the fuse or reset the
breaker.
3. Find the cause and ?x it.
4. Replace the faulty component.
5. Retighten the connection.
6. Check thermostat setting.
7. Find the cause then replace
capacitor.
8. Check and retighten.
9. Find the cause before reset.
B. The outdoor fan runs but the
compressor will not start.
1. Motor winding cut or grounded.
2. Faulty capacitor.
1. Check the wiring and the
compressor winding resistance.
2. Find the cause then replace
capacitor.
C. There is insuf ?cient heating or
cooling.
1. There is a gas leak.
2. Liquid and gas line insulated
together.
3. The room was probably very hot
(cool) when you started the
system.
1. Remove charge, repair,
evacuate and recharge.
2. Insulate them separately.
3. Wait while unit has enough time
to cool the room.
D. The compressor runs
continuously.
1. Thermostat adjustment too low
(in heating mode) or too high
(in cooling mode).
2. Faulty fan.
3. Refrigerant charge too low, leak.
4. Air or incondensables in refriger-
ant circuit.
1. Check thermostat setting.
2. Check condenser air circulation.
3. Find leak, repair and recharge.
4. Remove charge, evacuate and
recharge.
E. The compressor starts but shuts
down quickly.
1. Too much or too little refrigerant.
2. Faulty compressor.
3. Air or incondensables in
refrigerant circuit.
4. Changeover valve damaged or
blocked open (heat pump unit).
1. Remove charge, evacuate and
recharge.
2. Determine the cause and
replace compressor.
3. Remove charge, evacuate and
recharge.
4. Replace it.
F. Clicking sound is heard from the
air conditioner.
In heating or cooling operation any
plastic parts may expand or shrink
due to a sudden temperature change
in this event, a clicking sound may
occur.
In heating or cooling operation any
plastic parts may expand or shrink
due to a sudden temperature change
in this event, a clicking sound may
occur.
J440-EN.indd 26 2/14/08 1:27:04 PM
According to REACH Regulation 1907/2006/ EC article 33 products contain DEHP in quantities above 0.1% W/W are :
Table of contents
Other York Air Conditioner manuals

York
York R-410A User manual

York
York YH9FXH12BAH FX Series User manual

York
York UC18A3XC1 Quick start guide

York
York PREDATOR MagnaDRY DR120 User manual

York
York IDH072B21S Series Manual

York
York GCGA SERIES User manual

York
York ZV Series User manual

York
York YJU3YH019BARRA-X User manual

York
York Sunline 2000 User manual

York
York HA300 Quick start guide

York
York LX series Quick start guide

York
York D3HH 024 Quick start guide

York
York PREDATOR DM 090 User manual

York
York GCGA36 THRU 76 Quick start guide

York
York DH 180 Quick start guide

York
York D1CE User manual

York
York D3CG090 User manual

York
York PREDATOR DM 090 User manual

York
York EVHC 09 DSAAAR User manual

York
York YH9FYC09BAH-A-X User manual