5. Configure the A-1019
1) Turn the back switch to Init mode and power on the A-1019. Over the USB or RS-485 to
link A-1019 and PC.
2) Open the YottaUtility software.
3) Click the Refresh button to refresh the COM port.
4) Click the related COM port. And then
click Search for modules button the to search module.
5) Can setup the communication parameter from below figure 1. When finish the setup,
must click the update button.
6) Can setup the Analog input mode from
below figure 2. When finish the setup,
mustclicktheUpdatebutton.
7) When complete above step 6) Analog
Input mode modify and click the
Update button, can click ”?” button to
refer Analog Input mode specification
table.
8) Can setup the temperature
compensation when chose the
Thermocouple mode. When finish the
setup, must click the update button.
9) The A-1019 can support multiple
Analog Input mode. When complete
above PC software setup, unscrew the
device housing screws and remove the internal
circuit board to setup the Analog Input Jumper
Wire. Each Analog Input channel had its Jumper Pin. The initial setup is for 0/4-20mA. The
jumper indication is as below.
0/4-20mA: Pin A short. Thermistor: Pin B short. Thermocouple: Empty Pin A & B.
10) When complete above Jumper Wire setup, place the circuit board back into the device
housing and lock it. Turn the device back switch to Normal mode and power on.
11) Done.
Note: If the Analog Input mode PC software setup and Jumper Wire not synchronized,
the data will be mistake.
Figure 1
Figure 2