ZCS Azzurro 3000SP User manual

QUICK INSTALLATION GUIDE
- 3000SP STORAGE SYSTEM

1. INSTALLATION
Maximum inclination
permitted: 15°
Correct installation in
vertical position
Maximum
height from
ground
permitted:
180 cm
1. INSTALLATION AND DISTANCES
20 20
Distances for installing a single inverter
Distances for installing multiple inverters
Always wear protective
clothing and/or personal
protective equipment
Always consult the
manual
General notice -
Important Safety
Instructions

2.1 WIRING DIAGRAM FOR 3000SP SINGLE-PHASE STORAGE SYSTEM
2.2 WIRING DIAGRAM FOR 3000SP THREE-PHASE STORAGE SYSTEM
The wiring diagram for the 3000SP single-phase storage system is shown above.
For instructions on this installation mode, refer to all pages of this guide, except pages 16 to 22 (inclusive).
The wiring diagram for the 3000SP three-phase storage system is shown above.
For instructions on this installation mode, refer to all pages of this guide, except pages 10 to 15 (inclusive).
Note: If the 3000SP storage system is to be installed under different conditions from those
shown in the diagrams above, contact Technical Support to check whether it is feasible.
Photovoltaic
panels
Photovoltaic
inverter Production meter
CT pv sensor CT a sensor
Import/Export
meter
Grid connection
Utilities
Monitoring
Critical Loads
3000SP
Photovoltaic
panels Photovoltaic
inverter
CT pv current sensor
CT c current sensor
CT b current sensor
CT a current sensor
L3 Line loads
L1 Line loads
L2 Line loads
Batteries
Monitoring
3000SP
L1
L2
L3
Batteries

1
5
6
7
2
3
4
12
9
10
11
8
13
1. Menu/back
2. Up
3. Down
4. Enter/Forward
5. Discharge status
6. Charge status
7. Alarm status
8. System status
9. PV production
10. Grid power
11. Home consumption
12. Battery power
13. Date and time
14. Wi-Fi signal
14
Main menu
1. Settings
2. Event list
3. System Info
4. Software Update
5. Energy statistics
From the main screen, press
“Menu/Back” to enter the main
menu.
The main menu contains five
different options:
3. LIGHTS AND BUTTONS
4. MAIN MENU
1.Settings
1.Battery Parameters
9.EPS Mode
2.Delete Energy Data
10.DRMs0 Control
3.Clear events
11.Self-test
4.Set Country
12.Working Mode
5.Commun.Address Select.
13.CTpv Scale Factor
6.Enable Country Change
14.CT Direction
7.Language
13.Set parameters Safety
8.Date and time
2. Event list
1. List of current events
2. List of historical events
5.Energy Statistics
Today
Week
Month
Year
Life Cycle
PV prod.
PV prod.
PV prod.
PV prod.
PV prod.
AutoCon
AutoCon
AutoCon
AutoCon
AutoCon
Export
Export
Export
Export
Export
Consumption
Consumption
Consumption
Consumption
Consumption
AutoCon
AutoCon
AutoCon
AutoCon
AutoCon
Amount
Amount
Amount
Amount
Amount
3. System Info
System info (1)
Battery Parameters (1)
System info (2)
Battery Parameters (2)
System info (3)
Battery Parameters (2)
4. SW Update
Start Update ...
PWD: 0715
Operating status
Green charging light
Green charging light
Red alarm light
Discharge
Steady
Discharging control
Intermittent
Charge
Steady
Charging control
Intermittent
Standby
Intermittent
Intermittent
EPS status
Steady
Steady
Alarm
Steady
Charge

The 3000SP will remain in Standby until:
•the difference between the photovoltaic
production and the power required by the load is
less than 100W
•the battery is fully charged and the photovoltaic
production is higher than the consumption (with
tolerance of 100W)
•the battery is flat and the photovoltaic production
is lower than the consumption (with tolerance of
100W)
When the power produced from the photovoltaic
system is greater than the energy required by the
loads, the 3000SP system will charge the battery with
the excess energy.
When the battery is fully charged, or when the
charging power is limited (to preserve the integrity of
the battery), the excess energy will be exported to
the grid.
Charge
When the power of the photovoltaic system is once
again less than the power required by the loads, the
system will use the energy stored in the battery to
power the domestic utilities.
Discharge
When the sum of the power produced by the
photovoltaic system and supplied by the battery is
less than that required by the loads, the missing
energy will be taken from the grid.
Standby
Standby
Press the “↓” key once from the
main menu to access the
instantaneous information on how
to operate the 3000SP.
Press the “↓” key a second time to
display the power flows on the CTs.
CTA 0.30kW IMPORT
CTB 0.00kW IMPORT
CTC 0.00kW IMPORT
CTPV 1.04kW EXPORT
PF 99%
PF 0%
PF 0%
PF 99%
6. OPERATING STATES IN AUTOMATIC MODE
5. QUICK INFO ON SYSTEM STATUS
Charge
Charge
Discharge
Discharge

3.1 Battery connection
3.3 Grid Connections
In case of a single battery, two power cables (positive and negative) and a communication cable will be connected.
This connection is shown in the figures below:
Note: The DIP switch positions must be set according to the factory settings (if
modified accidentally, contact technical support)
CONNECTING THE POWER CABLES:
1) Unscrew the 4 screws (A) with a screwdriver.
2) Remove the cover (B), loosen the cable gland (C),
and then remove the stopper (G).
3) Feed the battery cables (F) through the cable gland,
then connect them to the positive and negative
terminals of the inverter (E).
4) Replace the cover on the inverter and secure it with
the four screws; then tighten the cable glands.
CONNECTING THE COMMUNICATION CABLES:
1) Unscrew the 4 screws (A) with a screwdriver.
2) Remove the cover (B), loosen the cable gland (C),
and then remove the stopper (G).
3) Feed the communication cable (inverter side)
through the cable gland on the left side of the
cover, then insert the connector into the CAN port
on the inverter's communication board.
4) Replace the cover on the inverter and secure it with
the four screws; then tighten the cable glands.
Note: The communication cable is located inside the
kit in the inverter box.
Communication cable pinout between Pylontech
battery & 3000SP system, left to right
PIN 1: White orange
PIN 2: orange
PIN 3: white blue
PIN 4: blue
PIN 1: not used
PIN 2: not used
PIN 3: not used
PIN 4: White orange
PIN 5: orange
PIN 6: not used
PIN 7: white blue
PIN 8: blue
1 … 4
3000SP
Pylontech 1 … 8
The communication
cable must be
connected to the
battery's CAN port
If the storage system has to be switched off, make sure to disconnect the AC voltage first by opening the
dedicated switch.
NEVER turn off the batteries while the storage system is connected to the AC mains.
Do not extend the DC cables, and only used those supplied.
Do not use DC circuit breakers.
Note: Maximum DoD
Programmable 80%
8.1 SINGLE PYLONTECH BATTERY
7. BATTERY CONNECTION

Master
Slave 1
Slave n
…
When connecting multiple batteries in parallel, connect the communication cable previously connected to the
inverter's CAN port to the CAN port of one of the batteries. This will be referred to as the MASTER battery.
A communication cable will go from the port 1 link of the MASTER battery to the second battery called SLAVE 1,
entering the port 0 link.
In case of additional batteries, the communication cable will be connected as indicated above for the connection of
the MASTER battery to SLAVE 1.
The last battery will only
have the port 0 link connected.
The batteries must be connected in a “loop” as shown in the side
photo, and explained below:
The power cable connected to the inverter’s negative pole must be
connected to the MASTER battery, while the cable connected to
the inverter’s positive pole must be connected to the last “SLAVE
N” battery.
Inverter
negative
Inverter
positive
3.1 Battery connection
Communication cable pinout between Weco
battery and 3000SP system, from left to right
PIN 1: White orange
PIN 2: orange
PIN 3: white green
PIN 4: blue
PIN 1: White orange
PIN 2: orange
PIN 3: white green
PIN 4: blue
PIN 5: not used
PIN 6: not used
PIN 7: not used
PIN 8: not used
1 … 4
3000SP
WeCo 1 … 8
Note: To connect multiple batteries in parallel, use the appropriate cables (power and
connection) contained in the kit.
Note: The communication cables are located inside the
kit in the WeCo battery box
Note: Maximum DoD programmable 90%
8.3 SINGLE WECO BATTERY
8.2 PYLONTECH BATTERIES IN PARALLEL
Note: The DIP switch positions must be set according to the factory settings (if
modified accidentally, contact technical support)

In case of multiple batteries connected in parallel or when adding new batteries to a system with batteries already
installed and working, make sure that the difference between the voltages of all the batteries is less than 1 Volt.
Each battery must be measured individually, therefore make sure the batteries are not connected to each other.
(If the value is higher than 1 Volt, contact Technical Support)
Note: Turn off the batteries each time the position of the
DIP switches is changed.
To access the battery connection, remove the cover by unscrewing the crosshead screws.
In the event of MULTIPLE BATTERIES, connect the communication cable from the CAN port of the inverter to the
CAN-BMS port of the MASTER battery after defining the correct positioning of the DIP Switches:
The MASTER battery must be connected to the communication cable inside the battery box starting from the RS485-B
port and arriving at the RS485-A communication port of the Slave 1 battery. (Attention: do not connect the RS485-A
port to the Master battery).
In case of additional batteries, the communication cable will be connected as indicated above for the connection of
the MASTER battery to SLAVE 1.
The last battery will only have the RS485-A port connected.
As for the power connections, all the batteries must be connected in parallel using the power cables supplied, making
sure that the cable does not exceed a length of 2.5 m.
The “NEGATIVE” power cable coming out from the inverter must be connected to the MASTER battery on the
NEGATIVE terminal, while the “POSITIVE” cable must be connected to the last SLAVE N battery on the POSITIVE
terminal.
8.4 WECO BATTERIES IN PARALLEL
In case of a SINGLE BATTERY:
1. Connect the BMS-CAN input
2. Set the DIP switches as shown
in the photo
3. The power connections must
be made by attaching the
appropriate B+ and B-
connectors to the corresponding
input (as shown in the figure).
4. Connect the ground cable to
the battery through the
threaded hole
Inv-Batt communication cable
Positive power cable
Negative power cable
Ground cable (PE)
INCORRECT CONNECTION
CORRECT CONNECTION

MASTER SLAVE 2
SLAVE 1
MASTER SLAVE
MASTER SLAVE 2
SLAVE 1 SLAVE 3
MASTER SLAVE 2SLAVE 1 SLAVE 3 SLAVE 4
Connecting 5
batteries
Connecting 4
batteries
Connecting 3
batteries
Connecting 2
batteries

OK
Correctly position the current sensors (CT):
Note: The direction of the CTpv is independent of the
installation.
•CTpv (measures the photovoltaic production).
Must be positioned on the phase cable coming out from
the photovoltaic inverter (AC side) on the same phase
where the storage was installed.
Unscrew the 4 screws (A) with a screwdriver.
Remove the cover (B), loosen the cable gland (C), and then remove
the stopper (G).
Route the CT cables through the cable glands on the right side of the
cover, connect the positive and negative cables to the counterpart
contained in the inverter kit, then insert the counterpart into the
corresponding ports on the inverter board.
For the extension cable, it is recommended to use a category five 8-pole mains
cable, or a 2x0.5 mm² cable. In the first case, four conductors will be connected to
one pole of the sensor and the other four will be connected to the other pole.
To prevent the conductor wires from breaking, it is recommended to use a cable
with flexible and non-rigid conductors.
•CTa (measures the current exchanged with the grid).
Position the CTa sensor on the phase where the storage system is
installed, at the output of the import/export meter so that all the power
flows entering and leaving the meter can be read.
Replace the cover and secure it with the four screws; then
tighten the cable glands.
INSTALLATION OF
SINGLE-PHASE SYSTEM
9. CURRENT SENSOR CONNECTION
PV Inverter
Panels 3000SP
Batteries
Utilities
Meter
Current sensor
CTpv CTa

The sensor must include all phase cables
entering or leaving the meter.
NO!!!!
Do not read the
consumption but the
exchanges with the grid!!!
INSTALLATION OF SINGLE-PHASE SYSTEM
PV Inverter
Panels 3000SP
Batteries
Utilities
Meter
Current sensor
CTpv
CTa
PV Inverter
Panels 3000SP
Batteries
Utilities
Meter
Current sensor
CTpv CTa

Make sure that the AC circuit breaker
of the 3000SP system is open and that
no AC voltage is present at the ends of
the 3000SP. OFF
3000SP storage system GRID
8888
> 200W
Make sure the PV system is not producing any power on
the phase where the 3000SP system is connected, then
open the AC circuit breaker dedicated to the photovoltaic
inverter to verify that no power is being produced.
OFF
Make sure that there is a domestic load of at least 200 W. To make certain,
use a current clamp to measure the current present on the phase under the
import/export meter.
The current will enter from the grid to the utility.
Current flow
Loads
Import/Export meter
In case of WeCo batteries, press the POWER button of
each battery for 1 second, the RUN LED will turn on and
the internal contactor will close automatically.
Turn on the batteries:
To turn on Pylontech
batteries: bring the switch
on the front of all the
batteries to the ON
position.
Press the red SW button of a
single battery for one second,
the internal contactor will
close automatically.
1) Unscrew the 4 screws (A) of the cover.
2) Remove the cover (B), loosen the cable gland (C), and then remove the stopper (G).
3) Pass the AC cable through the cable gland (C), and connect the phase, neutral and ground
cables to the GRID terminal block.
INSTALLATION OF SINGLE-PHASE SYSTEM
11.1 INITIAL SET UP PROCEDURE OF THE 3000SP STORAGE SYSTEM
10. CONNECTING THE AC - GRID POWER CABLES

Close the AC circuit breaker of the 3000SP
system so that it is supplied with AC voltage.
The inverter will turn on.
The procedure for freezing the current sensors is available from firmware version 2.00
of the Service Code onwards; in the event of lower Service Codes, contact technical
support to receive the updated firmware.
Enter Pwd!
0001
Back
Increase
number
Decrease
number
Forward or
confirm
1.Settings
13.CT Direction
“Password 0001”
Power read by CTa
Direction of power flow:
•IMPORT → from grid to utility
•EXPORT → from utility to grid
Phase shift between the voltage (V) and current (I)
expressed as a percentage → P/ (V x I) = cosϕ
CTa info
Indicates the status of the current sensors:
•UNFREEZE → direction not blocked (at each system start, the direction depends on the direction of the first current flow).
•FREEZE → direction blocked (sensors keep the same direction at each start up).
NOTE: Info for writing the password
3000SP System GRID
ON
To perform the freezing operation, follow the instructions below:
ON
Close the AC circuit breaker
of the 3000SP system so
that it is supplied with AC
voltage.
INSTALLATION OF SINGLE-PHASE SYSTEM
11.2 INITIAL SET UP PROCEDURE OF 3000SP SYSTEM - FREEZING OF CURRENT SENSORS
11.3 INITIAL SET-UP PROCEDURE OF THE 3000SP SYSTEM - PHOTOVOLTAIC START UP
After checking for the presence of a power flow towards the utility (IMPORT), freeze the CTs by pressing the
arrow so that the word FREEZE appears at the bottom and then confirm with the fourth button
To unfreeze, press the third button to display the UNFREEZE message and then confirm . By
switching the system off and on in this way, the sensor can once again the directed.

•CTa, CTb, CTc (measures the current exchanged with the grid).
a) Position the CTa sensor on the same phase where the storage inverter is installed.
b) Position the CTb and CTc sensors on the other two phases.
c) Each sensor must be positioned at the output of the import/export meter so that all the
incoming and outgoing power flows can be read.
Same phase
Correctly position the current sensors (CT):
Note: The direction of the CTpv is independent of the
installation.
•CTpv (measures the photovoltaic production).
It must be positioned on the phase cable coming out from
the photovoltaic inverter (AC side) on the same phase
where the storage was installed.
Unscrew the 4 screws (A) with a screwdriver.
Remove the cover (B), loosen the cable gland (C), and then remove
the stopper (G).
Route the CT cables through the cable glands on the right side of the
cover, connect the positive and negative cables to the counterpart
contained in the inverter kit, then insert the counterpart into the
corresponding ports on the inverter board.
For the extension cable, it is recommended to use a category five 8-pole mains
cable, or a 2x0.5 mm² cable. In the first case, four conductors will be connected to
one pole of the sensor and the other four will be connected to the other pole.
To prevent the conductor wires from breaking, it is recommended to use a cable
with flexible and non-rigid conductors.
Replace the cover and secure it with the four screws; then
tighten the cable glands.
INSTALLATION OF
THREE-PHASE SYSTEM
12. CURRENT SENSOR CONNECTION

CTa
OK
The direction of the CTa is independent of the installation, and is recognised by the system during the first
start-up.
S T
R N
CTb
CTc
CTa
OK
S T
R N
CTb
CTc
CTa
NO
S T
R N
CTb
CTc
Each sensor must include all phase cables entering or exiting from the meter.
Replace the waterproof cover and secure it with the four screws; then tighten the cable glands.
ok ok ok
INSTALLATION OF THREE-PHASE SYSTEM
Photovoltaicpanels Photovoltaicinverter
CTpv current sensor CTc current sensor
CTb current sensor
CTa current sensor
Batteries
L2 Line loads
L1 Line loads
L3 Line loads
Meter
L1
L2
L3
Photovoltaicpanels Photovoltaicinverter
CTpv current sensor CTc current sensor
CTb current sensor
CTa current sensor
Batteries
L2 Line loads
L1 Line loads
L3 Line loads
Meter
L1
L2
L3

OFF
3000SP System GRID
L1
L2
L3
L2 Line loads
L1 Line loads
L3 Line loads
8888
> 200W
> 200W > 200W
Make sure the PV system is not producing power on
any phase where the PV system is connected, then
open the AC circuit breaker dedicated to the PV
inverter to verify that no power is being produced.
OFF
Make sure there is a load of at least 200 W on all three phases by using a
current clamp to measure each phase one at a time under the
import/export meter.
Current flow
Make sure that the AC circuit breaker of the 3000SP
system is open and that no AC voltage is present at the
ends of the 3000SP.
1) Unscrew the 4 screws (A) of the cover.
2) Remove the cover (B), loosen the cable gland (C), and then remove the stopper (G).
3) Pass the AC cable through the cable gland (C), and connect the phase, neutral and ground cables to the
GRID terminal block.
INSTALLATION OF THREE-PHASE SYSTEM
14.1 INITIAL SET UP PROCEDURE OF THE 3000SP SYSTEM
13. CONNECTING THE AC - GRID POWER CABLES

In case of WeCo batteries, press the POWER button of
each battery for 1 second, the RUN LED will turn on and
the internal contactor will close automatically.
Turn on the batteries:
Close the AC circuit breaker of the 3000SP
system so that it is supplied with AC voltage.
The inverter will turn on.
To turn on Pylontech
batteries: bring the
switch on the front of all
the batteries to the ON
position.
Press the red SW button of
a single battery for one
second, the internal
contactor will close
automatically.
The procedure for freezing the current sensors is available from firmware version 2.00 of
the Service Code onwards; in the event of lower Service Codes, contact technical support
to receive the updated firmware.
Enter Pwd!
0001
Back
Increase
number
Decrease
number
Forward or
confirm
1.Settings
13.CT Direction
“Password 0001”
Power read by CTa
Direction of power flow:
•IMPORT → from grid to utility
•EXPORT → from utility to grid
Phase shift between voltage and current
CTa info
CTb info
CTc info Indicates the status of the current sensors:
•UNFREEZE → direction not blocked (at each
system start, the direction depends on the
direction of the first current flow).
•FREEZE → direction blocked (sensors keep the
same direction at each start up).
NOTE: Info for writing the password
3000SP System GRID
ON
To perform the freezing operation, follow the instructions below:
INSTALLATION OF THREE-PHASE SYSTEM
14.2 INITIAL SET UP PROCEDURE OF 3000SP SYSTEM - FREEZING OF CURRENT SENSORS

Block the CTs by pressing the arrow so that the word FREEZE appears at the bottom and then confirm
with the fourth button
Checks to be carried out:
Make sure that the power consumption is greater than
800W on the CTA, CTB and CTC phases by checking the
values on the display; also make sure that IMPORT is
present on each of the three phases.
NOTE: If not, increase the consumption until the required
condition is met.
If each sensor has been correctly positioned on its
reference phase, the PF value (phase shift between
voltage and current) will be greater than 90% on all three
phases.
Otherwise, the value will be around 50% and an alarm will
be signalled < ! >
The sensors or the terminals inserted in the inverter's
terminal board will need to be moved until the value of
the Power Factor takes on the correct values.
ON
Turn on the photovoltaic system
OK
OK
OK
OK
OK
OK
NO
OK
NO
1.Settings
14.CTpv Scale Factor
“Password 0001”
Scale Factor:
1.00 → Single-phase configuration
3.00 → Three-phase configuration
NOTE: The CTpv scale factor is the multiplying coefficient of the
power value read by the CTpv sensor on the phase in which it is
installed.
This value is set to 1 by default and can be modified to multiply
the power value read by the sensor.
If the required conditions cannot be checked, please contact
technical support for assistance
INSTALLATION OF THREE-PHASE SYSTEM
14.3 INITIAL SET-UP PROCEDURE OF THE 3000SP - CTpv SETTINGS AND PHOTOVOLTAIC START UP

To carry out the check, it is necessary to:
1) Switch off the photovoltaic system.
2) Lower the switch of the circuit breaker, the 3000SP system will remain on but will go into error due to
no AC power supply
(or in EPS mode, if previously enabled).
4) Power up the 3000SP by flicking the AC switch up.
6) Check that the PV generation value shown on the
screen is equal to zero.
5) Check that the display shows a withdrawn power value equal to the absorbed power value which can be
measured by placing a current clamp under the import/export meter.
15. CHECKING FOR CORRECT OPERATION
OFF
ON
OFF
Waiting time 300 s
Error

Check that the value of the consumption remains constant*
as the power supplied by the battery increases during
discharge.
8) The power taken from the
grid should decrease by an
amount equal to the power
supplied by the battery.
The photovoltaic system
remains at zero.
9) Once the photovoltaic system has been activated, check that:
The value of consumption remains constant as the photovoltaic
power increases.
Depending on the photovoltaic production, the
system will work according to the
modes described in Chapter 6.
Note: if the four conditions above are not met,
check the positioning of the CTs
7) Once the countdown is over, the batteries will start to
deliver power according to the availability towards the utility,
trying to reset the consumption from the grid.
*Check that the power of the loads in use does not change:
•Heat pump or pump → load variable over time
•Light or Hairdryer → load constant over time
10) Compare the value of the photovoltaic power shown on the storage inverter's display with that indicated
by the photovoltaic inverter, making sure that they are almost equal.
Waiting time
300 s
Discharg
e
Discharge
Charge
Normal
Other manuals for Azzurro 3000SP
1
Table of contents
Popular Storage manuals by other brands

HP
HP VS80 - StorageWorks DLT VS 80 Tape Drive Getting started guide

Grizzly
Grizzly H8140 parts list

Seagate
Seagate ST9100822A installation guide

Western Digital
Western Digital WD10EFRX Product specifications

Seagate
Seagate ST31500341AS - Barracuda 1.5 TB Hard Drive specification

Glyph
Glyph PGFW8004B-500 quick start