.1
Technical data ………………………………………
Type - Plate
Order number
Supply voltage Us/ frequency
Power consumption
………………………………………
Tolerance voltage Us AC 0.9 ... 1.1 Us
Tolerance frequency Us 48 ... 62 Hz
Sensor connection
Sensor thermocouple (see type plate)
Limit value
Adjustment accuracy approx. 1 % of span
Repeat accuracy approx. 0,2 % of span
Hysteresis ≤2 % of span
Switching state standard: closed - circuit current principle
option: operating current principle
Relay standard true > set value = relay released
LED Display relay released = LED off
Relay output 1 relay,1 x CO-contact
Switching voltage max. AC 415 V
Switching current max. 6 A
Switching power consumption max. 1100 VA
Rated operational current 2,5 A 400 VAC 15
4 A 250 V AC 15
3 A 24 V DC 13
Testing conditions VDE 0660 / VDE 0160
Rated insulation voltage Ui
according to VDE 0110 AC 415 V
Isolation VDE 110 / Gr. C
Transformer VDE 0550
Test voltage between supply voltage,
relay output and sensor side 2.5 kV
On period 100 %
max. ambient temperature -20 ... +55 °C
Climatic category F (according to DIN 40 040)
Housing: design S-12, plug-in housing
Dimensions (H x W x D) 82 x 42 x 121 mm
Line connection 12-pole, max. 2 x 1.5 mm2each
Protection Housing IP 30
Protection contacts IP 20
Panel inclination any
Mounting snapable on 35 mm standard rail according to DIN
or assembly with screws M 4