ZIGBEE ROB-200-040-0 User manual

Zigbee Heating ThermostatROB_200-040-0Function introductionImportant: Read All Instructions Prior to InstallationFront side1. Product DataFTIME/SHIFT button, to set time schedule of the device quickly and move the cursorFunction button, to confirm, save settingMode button, to switch operation modes and quitMove up and move down buttonsLED Display59 mm80 mm
59 mm80 mm
10 mm10 mm31 mmBack sideNTCL L N NAC Power inputFloor temp sensorOutputHome InterfaceSR-ZG9092ARadio FrequencyInput VoltageOutput VoltageMax LoadMax CurrentPower ConsumptionAmbient TemperatureSet Temperature RangeHysteresisFloor sensor typeControl TypeApprovals1. NTC/10K B(25/50℃)=3950 (default)2. NTC/15K B(25/50℃)=39503. NTC/50K B(25/50℃)=39504. NTC/100K B(25/50℃)=39505. NTC/12K B(25/50℃)=3950Control type means which temperature sensor the device refers to when it adjust temperature.Room sensor: adjust temperature refers to room temperature (factory default type).Floor sensor: adjust temperature refers to floor temperature.Room+Floor sensor: adjust temperature refers to both room temperature and floor temperature.CE,LVD: EN 60730-1:2016;A1, EN IEC 60730-2-9:2019;A1EMC & RF: EN IEC 61000-3-2:2019, EN 61000-3-3:2013+A1:2019,EN 60730-1:2016+A1:2019, EN 60730-2-19:2019+A1:2019+A2:2020, EN 50663:2017;ETSI EN 301 489-1V2.2.3, ETSI EN301 489-3V2.1.1ETSI EN300 220-1 v3.1.1., ETSI EN300 220-2 V3.2.1RED certificate: 2014/53/EU• The Zigbee HVAC controller is a wireless thermostat for heating system, which complies to Zigbee 3.0 wireless protocol standards. The thermostat has 4 operation modes which can be controlled manually and locally or through remote controlled through Zigbee gateway controller.• All setup is performed via supported IEEE 802.15.4-based control platforms and other Zigbee3.0 compatible control systems. Appropriate gateway control software allows for adjustment of control mode, control type, schedule etc.• Sensors: Air temperature• THERMOSTAT MODE: OFF, HEAT, ENERGY HEAT, AWAY, DRY• Measurement range: –10°C to +60°C• Accuracy: ±0.1°C • WARNING: Electrical power must be switched off during installation2.4GHzEU: AC200-240V, 50/60HzEU: AC200-240V3680W @ 230V (resistive load)16A<2W0°C to 40°C (during operation)0°C to 40°C0.5°C to 2°C (default 0.5°C)Control ModeOFF, HEAT, ENERGY HEAT, AWAY, DRYWiring RequirementCurrent ≤ 13A - 1.5mm² wireCurrent > 13A to 16A - 2.5mm² wire
IP RatingControl Pollution Degree (Method D)Rated Impulse Voltage (Method D)Relative HumidityDimensionsIP218% to 80%4kV80x80x52mmpollution degree 2Revised 11.08.2021

by the gateway alone.Away (Away Mode): this mode means there is no person at home, to keep a certain indoor temperature, the user can set the deadline of away, it also can be considered as anti-freezing function, the recommended setting temperature is 4-10 degrees. The mode and temperature can be configured by Zigbee gateway.Drying (Drying Mode): The device will judge the set temperature for heating within a short period of time, or the mode and temperature can be configured by Zigbee gateway.4.2 System Setting InterfaceUnder Home interface, meanwhile the device is at OFF mode , press and hold move up and move down buttons at the same time for over 5 seconds to enter into System Setting Interface as follows:Quit: on System Setting Interface short press button to go back to Home interface.Enter into set interface of each setting item: short press move up or move down button to select a setting item, then short press button to enter into set interface of the selected item. F4.3 Preview of Device InformationOn System Setting Interface, user can enter into PREVIEW interface, the interface will display some basic configurations, energy consumption, date, floor temperature etc.4.4 Auto Mode ScheduleWhen Auto Mode Schedule is valid, the device will control according to the set temperature of the schedule.For instance, if user would like to keep room temperature at 18 degree Celsius during 18:00-23:00 on every Monday, and keep room temperature at 20 degree Celsius after 22:30 on every Monday, then user can set schedule by himself.Schedule setting method 1: user can enters into schedule on System Setting Interface, the schedule interface is as follows:Short press button to select “Auto Schedule”, then short press button to enter into Auto Mode Schedule weekly setting interface.F2.3 Standby InterfaceIf there is no operation within 2 minutes, the device will go to this standby interface.Once the device goes to standby interface, if there is no operation within 1 minute, the display will go off automatically.• DO NOT install with power applied to device.• DO NOT expose the device to moisture.3.Safety & Warnings4. Basic Function Introduction4.1 Switch Operation modesShort press button on Home interface to switch operation modes: the icons of Away, Manual (Comfort), Automatic (Energy Save), Drying, OFF modes will be displayed alternatively for 3 seconds and last displayed mode will be selected, or just short press button to select a desired mode when the modes’ icon displayed alternatively.Press and hold button on Home interface for over 3 seconds to select Away mode directly, then press and hold button for 3 seconds to quit Away mode. OFF Mode: this mode means that the device is under idle status. Manual (Comfort Mode): the device will control the heating system according to current set temperature. The temperature can be set by move up and move down button on the Home interface, or the mode and temperature can be configured by Zigbee gateway.Automatic (Energy Save Mode): the device will control the heating system according to the configured time schedule, or the mode can be configured by Zigbee gateway but the temperature can not be modified and sent F: TIME/SHIFT button, to set time schedule of the device quickly and move down the cursor: Function button, to confirm, save setting: Mode button, to switch operation modes and quit: Move up and move down buttons2.Home InterfaceAlready added to a Zigbee network: Child Lock enabled: Week display: MON, TUE, WED, THU, FRI, SAT, SUNThe set temperature: Set 28.5℃Room temperature: 25.5℃Floor temperature:Operation modes: ( AWAY), (Automatic), (Manual), (Drying) , (OFF)Heating status: (Heating), (Locked: heating forbidden), (Door is opened, heating forbidden)2.2 Button DescriptionF2.1 Home InterfaceFOn Auto Day Schedule interface, short press button to select the time or temperature that you would like to modify, then short press move up and move down buttons to modify value, then short press button to save and quit, short pressing button only quits without saving.FFor each schedule, the latter time should be later than the former time, otherwise saving will fail with the error remind “Time setting error!!!”. The default time schedules are as follows:Monday ~ FridaySchedule setting method 2: on System Setting Interface, meanwhile the device is under Auto Mode , short press button to enter into Auto Mode Schedule weekly setting interface quickly:On Auto Mode Schedule weekly setting interface, use buttons and to enter into schedule setting of a certain week as follows:

4.7 MONITOR SETThe function of monitor set is real time monitor of over current, over heat and freezing, on Home interface, short press MONITOR SET to enter into monitor set interface as follows: For configuration method and modification, please refer to Automatic Mode (Energy Save Mode) Schedule:After Mode: set the mode after the drying mode ends, can be configured through the proprietary attribute ModeAfterDry (0x1007) of Thermostat Cluster (0x0201).Duration: set how long the dry mode lasts, can be configured through the proprietary attribute DryTime (0x1006) of Thermostat Cluster (0x0201), the configurable range is 5-100 minutes. For example, in order to quickly dry the water on the floor of the bathroom, the device can be set to quickly heat in a short time to dry the floor. Enter the configuration interface as follows:4.6 Dry Mode ScheduleRemain: shows the remaining time of the drying modeTo enter into the setting interface and setting method, please refer to the 1.4 Auto Mode (Energy Save Mode) Schedule.Start and end mean away time.D means date, M means month, Y means year (2019-2099).2.If away mode has already been activated, the values of end time for away mode are set as 0, the device will always execute current set temperature with no time limitation. The device will consider the mode as anti-freeze mode, the recommended temperature setting is 4-10℃, and factory default setting is 6℃.4.5 Away Mode ScheduleUser can set time to leave home and time to go home according to the requirements of themselves, and set how the device will control the temperature during this period.1.If away mode has already been activated, the end time for away mode is valid, the device will execute Away Mode Temperature Schedule before the end time.Hysterersis (0.5°C by default)To prevent the undulation of sensor temperature when the sensor temperature is approaching the set
temperature, which will cause that the controller may keep switching on/off the relay. Here hysterersis enables the controller to control the relay only when the sensor temperature is a little bit lower than the set temperature, this value can be set. For instance, when hysterersis is set as 0.5 degree, then only when current sensor temperature is 0.5 degree lower than the set temperature, will the controller heat, if the sensor temperature >= set temperature, the controller will not heat.This value can also be configured through the proprietary attribute Hysterersis (0x100A) of Thermostat Cluster (0x0201).Note: This hysterersis only valid when the control type is single sensor, please refer to the part Control Type.reported to the associated devices, meanwhile the buzzer or vibrator will beep 3 times every 10 seconds. The over heat alarm function can be disabled, which can be set directly through the device. Or can be configured through the attribute AlarmAirTempOverValue (0x2001) of Thermostat Cluster (0x0201), when this value is set as 0, this function is disabled.Over heat alarm interface is as follow:Note: to cancel over current alarm or over heat alarm, just press and hold button for over 3 seconds or reset power of the device. After cancel manually, the relay will show heating forbidden icon within 120 seconds, but other operations are allowed.Max Current (16A by default)If current is over the set value, the relay will be forced to off by the device, and the state will be reported to the gateway. The over current alarm function can be disabled, which can be set directly through the device. Or can be configured through the ACAlarmsMask and ACCurrentOverload of Electrical Measurement (0X0B04), for details please refer to the configuration value . RoomTemp alarm (by default)45°C If room temperature is over the set value, the relay will be forced to off by the device, and over heat alarm will be Short press button to select the item would like to modify, then short press move up and move down buttons to modify value of selected item, then short press button to save and quit, short pressing button only quits without saving.FWindow Open Detect (disabled by default)Once the device is powered on and stable, referring to the room temperature sensor, if the temperature decreases to the threshold of this setting, the window open mark will be enabled, the relay will be forced to turn off to save energy, then the icon will appear.After window open mark is enabled, if the temperature increases to the threshold of this setting in 3 minutes, the window open mark will be disabled.Once the window open mark is enabled, it will be disabled after 10 minutes, and the device will keep current working mode.This value can also be configured through the proprietary attribute WindowOpenCheck (0x1009) of Thermostat Cluster (0x0201), 0 means this function is disabled.Note: this function will work better when the device is installed beside the window or door.7:30,24℃ ~ 12:00,20℃ 18:00,16℃ ~ 22:30,18℃ Saturday~Sunday7:30,24℃ ~ 12:00,20℃ 18:00,18℃ ~ 22:30,18℃Short press button to select the item would like to modify, then short press move up and move down buttons to modify value of selected item, then short press button to save and quit, short pressing button only quits without saving.4.9 OTHER SETSelect OTHER SET on Home Interface to enter into OTHER SET interface as follow:FShort press button to select the item would like to modify, then short press move up and move down buttons to modify value of selected item, then short press button to save and quit, short pressing button only quits without saving.F4.8 TIME/DATE SETSelect TIME/DATE on Home Interface to enter into TIME/DATE SET interface as follow:The device Time Cluster is client, if the bound device supports local time of Time Cluster, the device will acquire local time from the bound device spontaneously under 3 situations: acquire after this device is added to a network, acquire when the device already added to a network and power is reset, acquire every 24 hours .

Floor Sensor (NTC 10K by default)If external sensor is broken, the user can buy NTC sensor by themselves, the available sensor types are as follows:NTC 100K/25 (3m,NTC,R25=100KΩ±1%@25℃, B25/50=3950K±1%)NTC 50K/25 (3m,NTC,R25=50KΩ±1%@25℃, B25/50=3950K±1%)NTC 15K/25 (3m,NTC,R25=15KΩ±1%@25℃, B25/50=3950K±1%)NTC 10K/25 (3m,NTC,R25=10KΩ±1%@25℃, B25/50=3950K±1%)NTC 12K/25 (3m,NTC,R25=12KΩ±1%@25℃, B25/50=3950K±1%)This sensor type can also be configured through the proprietary attribute FloorSensorType (0x1002) of Thermostat Cluster (0x0201).Key vibration level (OFF by default)Set the level of vibration sensor under the buttons or buzzer level.OFF: vibration or buzzer offLow Level, High Level: low vibration or buzzer level, high vibration or buzzer levelThis level can also be configured through the proprietary attribute ButtonVibrationLevel (0x1001) of Thermostat Cluster (0x0201).Control type (Room sensor by default)Control type means which temperature sensor the device refers to when it adjust temperature.Room sensor: adjust temperature refers to room temperature (factory default type)Floor sensor: adjust temperature refers to floor temperatureRoom+Floor sensor: adjust temperature refers to both room temperature and floor temperature. Turn on heat valve under other circumstances. This mode is to prevent the device from continuous heating that caused by malfunction of either sensor. When the floor sensor temperature is >= the set temperature minus 1 or when the room sensor is >= the set temperature, either of the conditions is achieved, the controller will stop heat, otherwise the controller will heat. This control type can also be configured through the proprietary attribute ControlType (0x1003) of Thermostat Cluster (0x0201).Temp compensation (0 by default)The displayed temperature may has big tolerance caused by the sensor or other factors, so it is necessary to do temp compensation to room sensor and floor sensor.Compensation range is -5 ~ +5, stepping is 0.5.℃℃This value can also be configured through the attribute LocalTemperatureCalibration (0x0010) of Thermostat Cluster (0x0201), and through the proprietary attribute FloorSensorCalibration (0x1005) of Thermostat Cluster (0x0201).RePower status(last status by default)Device state after reset power of the device.If set as “last status”, device will go to the status before power failure after power on again.If set as “default”, device will go to default mode after power on again.This status can also be configured through the proprietary attribute PowerUpStatus (0x1004) of Thermostat Cluster (0x0201).Display Temp type (Home Temp by default)This parameter defines which sensor temperature will be displayed on Home page.Floor Temp: floor temperature (external sensor).Home Temp: indoor air temperature.This status can also be configured through the proprietary attribute TemperatureDisplay (0x1008) of Thermostat Cluster (0x0201).Operate Brightness (Mid Level by default)The OLED display brightness when operate the device.Adding to a Zigbee NetworkOperate your Zigbee gateway to add device, select “Add”, then short press button , the device will search network and try to join, “Status” will show “Inclusion...”. If there is no response from a gateway, or adding failed, “Status” will show “Fail”. If added successfully, “Status” will show “Inclusion OK” and device ID.Removing from a Zigbee Network Operate your Zigbee gateway to remove device, Select “Remove”, then short press button , the device will send out removing request, “Status” will show “Exclusion...”. If there is no response from a gateway, or removing failed, “Status” will show “Fail”. If removed successfully, “Status” will show “Exclusion OK” and device ID will be showed as 0.The device will be removed from the network and all parameters will be restored to factory default setting, all bindings will be cleared.FFSelect Network Set on Home Interface to enter into Zigbee network management interface as follow:4.10 Zigbee Configuration IntroductionInternal Over Heat ProtectionTo ensure the safety of the device, if the internal temperature of the device (not displayed on the interface) is over a certain value during heating process, the device will execute a short temporary action to turn off the relay, and the icon will appear on the interface , after the temperature decreases to a certain value, the device will recover to work.Factory Reset (Reset)Factory resetting will remove the device from Zigbee network and all parameters will be restored to factory default setting, all bindings will be cleared.Select “Reset”, then short press button , the device will start reset, “Status” will show “Reset...”. If exclusion failed, “Status” will show “Fail”. If reset successfully, “Status” will show “Reset OK”.FConfigure Device Operation Mode through ZigbeeSince Zigbee does not have away mode, the attribute Occupancy (occupied or unoccupied) of Thermostat
(0x0201) and attribute Occupancy of received OccupancySensing (0x0406) are required to judge whether
it is away mode.1) if the device receives other devices’ or the gateway’s report: the Bit 0 of the value of attribute
Occupancy (0x0000) of OccupancySensing Cluster (0x0406) is 1, which means occupied, then the operation mode of the thermostat, the attribute SystemMode(0x001c)=0x04(heat) of Thermostat (0x0201), High Level, Mid Level, Low Level.This brightness can also be configured through the proprietary attribute OperateDisplayLcdBrightness (0x1000) of Thermostat Cluster (0x0201).Display Auto Off (60S by factory setting)By factory setting, once the device goes to standby interface, if there is no operation within 1 minute, the display will go off automatically.Child LockOn the Home Interface, press and hold both and buttons for over 10S, the Child Lock can be enabled or disabled, when the Child Lock is enabled, the icon will appear at the upper right corner, otherwise the icon will not appear.

5. Zigbee InterfaceThe thermostat provides 3 zigbee application endpoints:EndpointProfileApplication0(0x00)1(0x01)2(0x02)242(0xF2)0x0000(ZDP)0x0104(HA)0x0104(HA)0xA1E0(GP)ZigBee Device Object (ZDO) – standard management featuresDevice ID is 0x0301(Thermostat ).Device ID is 0x0007(OTA).Device ID is 0x0021(GreenPower).5.1 Application Endpoint #0 –ZigBee Device Object • Application profile Id 0x0000• Application device Id 0x0000• Supports all mandatory clusters5.2 Application Endpoint #1 –Thermostatmeanwhile the value of attribute Occupancy (0x0002) of Thermostat (0x0201) is 0. It means the Away Mode is activated, and the thermostat UI will display .2) if the gateway send command to modify the attribute SystemMode(0x001c) of Thermostat (0x0201), the thermostat will quit Away Mode. Meanwhile the value of attribute Occupancy (0x0002) of Thermostat
(0x0201) is 1.3) The proprietary attribute 0x2002(Manufacturer Code=0x1224) of the cluster 0x0201 can be modified to configure whether it is away mode or at home.Note: Away Mode uses attribute UnOccupiedHeatingSetpoint to set temperature.Other modes uses attribute OccupiedHeatingSetpoint to set temperature.ClustersupportedDescription0x0000serverBasicProvides basic information about the device, such as the manufacturer ID, vendor and model name, stack profile, ZCL version, production date, hardware revision etc. Allows a factory reset of attributes, without the device leaving the network.0x0003serverIdentifyAllows to put the endpoint into identify mode. Useful for identifying/locating devices and required for Finding & Binding.0x0004serverGroupsAllows adding this endpoint to one or more groups. Afterwards the endpoint can be addressed using the group address. This is also a prerequisite for scenes. You may also query group membership and delete group associations.0x0005serverScenesAllows storing one or more scenes per group, where each scene consists of a pre-set on/off state value. You may either store the current values as a scene, or provide scene settings when adding a scene, or delete scenes.0x0201serverThermostat0x0702serverSimple Meter0x0b04serverElectrical Measurement Measuring power, voltage, current0x0009serverAlarmDevice related alarm0x0406clientOccupancy Sensing5.2.1 Basic -0x0000 (Server)Attributes supported:0x0002INT8U ,read-onlyStackVersion0x0003INT8U ,read-onlyHWVersionHardware version 10x0004string,read-onlyManufacturerName“Sunricher”0x0005string,read-onlyModelIdentifier“Zg9092”0x0006string,read-onlyDateCodeNULL0x0007ENUM8,read-onlyPowerSource Device power supply, fixed value 0x01 Mains (single phase)0x0008ENUM8,read-onlyGenericDevice-Class0XFF0x0009ENUM8,read-onlyGenericDevice-Type0XFF0x000Aoctstrread-onlyProductCode000x000Bstring,read-onlyProductURLNULL0x4000string,read-onlySw build id6.9.1.0_r4Command supported:CommandDescription0x00Reset to Factory Defaults CommandOn receipt of this command, the device resets all the attributes of all its clusters to their factory defaults. Note that networking functionality, bindings, groups, or other persistent data are not affected by this command.5.2.2 Scenes 0x0005 (Server)Attributes supported:AttributeTypeDescription0x0000int8u,read-onlySceneCountHolds the total number of scenes (across all groups) currently stored on the device. 0x0001int8u,read-onlyCurrentSceneIf the SceneValid attribute is true, this attribute, together with the CurrentGroup attribute,indicates the currently active scene. 0x0002int16u,read-onlyCurrentGroupIf the SceneValid attribute is true, this attribute, together with the CurrentScene attribute,indicates the currently active scene. 0x000aclientTime0x0001INT8U ,read-onlyApplicationVersionThis is the firmware version number of the applicationAttributeTypeDescription0x0000INT8U,read-onlyZCLVersion0x03

Command supported:CommandDescription0x00Add SceneAdds a scene with or without a scene field set 0x01View SceneReturns the scene field set, name and transition times for a scene. 0x02Remove SceneRemoves a scene from the scene table. 0x04Store SceneStores the device’s current state as a scene or updates a previously stored scene accordingly 0x03Remove All ScenesRemoves all scenes that belong to a particular group. 0x05Recall SceneReverts the device’s current state using the values from the previously stored field set. 5.2.3 Groups-0x0004 (Server)Attributes supported:AttributeTypeDescription0x0000bitmap8,read-onlyNameSupport0, not supportedCommand supported:CommandDescription0x00Add Group Adds the endpoint to a group. 0x01View Group Determines whether the device belongs to a group and returns the group name, if supported 0x03Remove GroupRemoves this endpoint from the specified group. Also removes all scenes that refer to this group. 0x04Remove All GroupsRemoves this endpoint from all groups. Also removes all scenes that refer to any of the existing groups. 0x05Add Group if IdentifyingAdds this endpoint to the group, if the endpoint is identifying. 5.2.4 Thermostat-0x0201(Server)Attributes supported:AttributeTypeDescription0x0000int16S ,read-onlyreportable LocalTemperature AttributeThis is room temperature, the maximum resolution this format allows is 0.01 ºC. 0x0002bitmap8 ,read-onlyOccupancy When this flag is set as 1, it means occupied, OccupiedHeatingSetpoint will be used, otherwise UnoccupiedHeatingSetpoint will be used.0x0010Int8S ,reportableLocalTemperatureCalibrationRoom temperature calibration, range is -30-30, the maximum resolution this format allows 0.1°C. Default value: 00x0011int16S ,reportable OccupiedCoolingSetpointThis system is not invalid.0x0012int16S ,reportable OccupiedHeatingSetpoint Range is 0-4000,the maximum resolution this format allows is 0.01 ºC. Default is 0xbb8(30.00ºC)0x0014int16S ,reportableUnoccupiedHeatingSetpointRange is 0-4000,the maximum resolution this format allows is 0.01 ºC. Default is 0x258(6.00ºC)0x001BEnum8,reportableControlSequenceOfOperationSet device supported operation type, here only supports Heating Only(0x02)0x0029Map16,read-only,reportable HVAC relay state/ ThermostatRunningStateIndicates the relay on/off status, here only supports bit0( Heat State) Proprietary Attributes:AttributeTypeDescription0x1000ENUM8,reportable OperateDisplayLcdBrightnesssOLED brightness when operate the buttons:Value=0 : Low LevelValue=1 : Mid Level(default)Value=2 : High LevelManufacturercode0x12240x1001ENUM8reportable ButtonVibrationLevelKey beep volume & vibration level:Value=0 : off(default)Value=1 : Low LevelValue=2 : High Level0x12240x1002ENUM8reportable FloorSenserTypeSelect external (Floor) sensor type:Value=5 : NTC 12K/25Value=4 : NTC 100K/25Value=3 : NTC 50K/25 Value=2 : NTC 15K/25 Value=1 : NTC 10K/25 (Default)0x12240x1003ENUM8reportable ControlTypeThe referring sensor for heat control:Value=0 : Room sensor(Default)Value=1 : floor sensorValue=2 : Room+floor sensor 0x12240x1004ENUM8reportable PowerUpStatusThe mode after reset power of the device:Value=0 : default modeValue=1 : last status before power off (Default)0x12240x0003bool,read-onlySceneValidIf true, the scene identified by CurrentGroup and CurrentScene is currently active, i.e. all device attribute values match the values in the scene field set. 0x0004bitmap8 ,read-onlyNameSupport0x0001int16S ,read-onlyreportable OutdoorTemperatureThis is floor temperature, the maximum resolution this format allows is 0.01 ºC.

0x1007ENUM8reportableModeAfterDryThe mode after Dry Mode:Value=0 : OFFValue=1 : Manual modeValue=2 : Auto mode –schedule (default)Value=3 : Away mode0x12240x1008ENUM8reportableTemperatureDisplay : Value=0 : Room Temp (Default)Value=1 : Floor Temp0x12240x1009INT8UreportableWindowOpenCheckThe threshold to detect open window, range is 0.3-8, unit is 0.5ºC,0 means disabled, default is 00x12240x100AINT8UreportableHysterersisHysterersis setting, range is 5-20, unit is 0.1ºC, default value is 50x12240x2001INT8U,reportableAlarmAirTempOverValueRoom temp alarm threshold, range is 0.20-60, unit is 1ºC,0 means disabled, default is 450x1224Command supported:CommandDescription0x0000Setpoint Raise/LowerIncrease or decrease the set temperature according to current mode, unit is 0.1ºC5.2.5 Simple Meter-0x0702 (Server)Attributes supported:AttributeTypeDescription0x0000unsigned48 ,read-only,reportable CurrentSummationDelivered Indicates the current amount of electrical energy delivered to the load.0x0200bitmap8 ,read-onlyStatusFlags indicating current device status, always is 0x000x0300enum8 ,read-onlyUnitOfMeasureThe unit of metering data, this is always kWh(0x00)0x0303map8 ,read-onlySummationFormattingThe decimal point on the left and right sides of the data, this is always 0x000x0306bitmap8,read-onlyMeteringDeviceTypeMetering data type, this is always Electric Metering (0x00)5.2.6 Electrical Measurement-0x0b04(Server)Attributes supported:AttributeTypeDescription0x0000bitmap32 ,read-onlyMeasurementType Indicates the physical entities that this devices is able to measure. Supports only bit0: Active measurement (AC) 0x0505int16U ,read-only,reportable RMSVoltageSingle phase valid voltage, unit is V0x0508int16U ,reportable,read-onlyRMSCurrentSingle phase valid current, unit is A0x050Bint16S ,reportableread-onlyActivePower Single phase valid power, unit is W0x0600int16U,read-onlyACVoltageMultiplier0x0601int16U,read-onlyACVoltageDivisorUsed together with above attributes, the real displayed voltage = RMSVoltage* ACVoltageMultiplier/ ACVoltageDivisor0x0602int16U,read-onlyACCurrentMultiplier0x0603int16U,read-onlyACCurrentDivisorUsed together with above attributes, the real displayed current = RMSCurrent * ACCurrentMultiplier/ ACCurrentDivisor0x0800int16U,ACAlarmsMaskSpecifies which configurable alarms may be generated, onlyBit1: Current Overload is set, if set=0, then ACCurrentOverload=0, over current will not be detected0x0802int16S ,reportableread-onlyACCurrentOverloadAlarms when the current is over a certain value, 0, 10-16, unit is AProprietary Attributes:Attribute0x0000TypeInt8u,reportableManufacturer code0x1224DescriptionOverCurrent Over current value set by the user, range is 0, 10-16, ACCurrentOverload will change spontaneously if this value is modified. 5.2.7 Alarm-0x0009(Server)Please set a valid value for ACAlarmsMask of Electrical Measurement.The Alarm Server cluster can generate the following commandsCmdIDDescription0x00Alarm:The alarm code of Electrical Measurement is 0, Proprietary command, Manufacturer code=0x1224CmdIDDescription0x00Room air temperature over heat, not alarm code0x2002ENUM8reportableAway Mode Set:Value=0: not away (default)Value=1: away0x12240x1006INT8Ureportable DryTimeThe duration of Dry Mode, range is 5-100, unit is min.Default value is 5.0x12240x1005INT8S,reportableFloorSenserCalibrationThe temp compensation for the external (floor) sensor, range is -30-30, unit is 0.1°C. default value 00x1224

5.2.9 OccupancySensing-0x0406(client) The attributes that can be received:AttributeTypeDescription0x0000bitmap8 , OccupancyBit 0 specifies the sensed occupancy as follows: 1 = occupied, 0 = unoccupied. This flag bit will affect the Occupancy attribute of HVAC cluster, and the operation mode.5.3 Application Endpoint #2–OTAClustersupportedDescription0x0000serverBasic0x0003serverIdentify0x0019ClientOTA Upgrade Pull-oriented firmware upgrade. Searches the network for mating servers and allows the server to control all stages of the upgrade process, including which image to download, when to download, at what rate and when to install the downloaded image. Ota complies to standard Zigbee protocol.5.4 Application Endpoint #242 –GreenPower2. Remove the display unit and backplate of the device from the packaging.3. FIRST ENSURE THE POWER IS OFF at the main circuit breaker, and then test the wires with a probe or multimeter to verify. This device should be installed by a licensed electrician in a manner that conforms to local regulations and building codes. Provide these instructions to the licensed electrician who is installing the device.WARNING: Electrical power must be switched off during installation. 1. Placement of the device is of utmost importance for proper operation and must be away from sunlight and sources of direct heat. We recommend installing the device approximately 1.5 meters above the floor.Troubleshooting:1. External (floor) sensor temperature tolerance is too high Possible reason: the selected sensor type is not correct2. The gateway can not set temperature when energy save mode is selected The temperature schedule of auto mode (energy save mode) is not configured correctly3. Current temperature is not executed when away mode is selected Check whether away mode time is set as 0 or within valid time range4. Over heat alarm when power on the device Possible reason: the set sensor type is not correct or sensor type after factory reset is not correct5. Device time is not the same as the gateway controller after added to the network Set the device time and time zone manually after added to the gateway network6. The tolerance of the indoor temperature sensor is high after powered on Possible reason: due to temperature effect, we need to wait for a while6.Wiring diagramInsert the power and heater wires to the correct device terminals by inserting a small Phillips-head screwdriver in the slot beneath each terminal to open. Follow the connection diagram and instructions below:• Power wires: connect Line & Neutral wires to L & N terminals labeled “IN”• Heater wires: connect Line & Neutral wires to L & N terminals labeled with “heating element” graphicWARNING: The wire size shall be in compliance with regulations, using wire with insufficient size for big load will cause severe temperature rising. NTCL L N NSR-ZG9092AFloor tempsensorL NConnection diagram 1NTCL L N NL NFloor tempsensorConnection diagram 2SR-ZG9092A1) Release front cover by inserting a flat screw-driver into side crack3) Mount back part into junction box, then screw the thermostat in2)Release the frame4) Re-install the frame and the front part in sequences7. Installation5.2.8 Time-0x000A(client) The Time cluster is a general cluster for time it is based on a UTC time in seconds since 0 hrs 0 mins 0 sec on 1st January 2000. Refer to [Z2] for ZigBee specification of the time cluster.The metering device will use this clusters as a client – provided that a suitable Time Server is available on the network (most likely on the Gateway/concentrator)If the device has bound TIME cluster, then the device will acquire the value of Local Time (0x0007) spontaneously.
Table of contents
Other ZIGBEE Thermostat manuals
Popular Thermostat manuals by other brands

Heatmiser
Heatmiser SLIMLINE user manual

Home Automation
Home Automation O M N I S T A T RC-90BZ installation instructions

proSmart
proSmart BBoil instruction manual

Lauda
Lauda Ecoline RE 320 operating instructions

NOBOCOOL
NOBOCOOL R80-UDF User instruction

ensto
ensto ECO500 Installation and operating instructions