manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ziton
  6. •
  7. Horn
  8. •
  9. Ziton ZP755HAV-2 Series Assembly instructions

Ziton ZP755HAV-2 Series Assembly instructions

© 2014 UTC Fire & Security. All rights reserved. 1 / 4 P/N 501-1780ZE-1-10 • REV 10 • ISS 16APR14
ZP755HAV-2 Addressable Horn Sounder/Visual
Indicator Installation Sheet
Description
The ZP755HAV-2 is an addressable horn sounder/visual
indicator designed for use in Ziton analogue addressable fire
detection and alarm systems.
Note: The visual indicator of this product does not comply with
EN 54-23 and must not be used in fire alarm installations
where fire notification beacons are required.
The device includes a volume control, an address-setting
switch, programmable tone settings, and a pair of jumpers to
select the operating power — from the analogue addressable
loop or an external supply. The device plugs into a base that is
purchased separately. See Table 1 for a list of model numbers.
Table 1: Models
Number Description
Sounder:
ZP755HAV-2R
ZP755HAV-2P
Horn sounder, red
Horn sounder, polar white
Base:
SPB-2R
SPB-2P
Base, red
Base, polar white
Installation
To install the device;
1. Wire the base
2. Set the operating power
3. Set the address
4. Set the mode of operation
5. Set the tone
6. Set the volume
7. Mount the sounder/visual indicator onto the base
The details of each step are given below.
Wiring the base
Connect the loop wiring for the plug-in base as shown in
Figure 1. There is no wiring between the sounder and base.
The base is supplied separately.
Figure 1: Loop wiring for the base
1. Ext. 24 VDC+ IN/OUT
2. Ext. 24 VDC ground IN/OUT
5. Loop+ IN/OUT
6. Loop − IN/OUT
7. Shield
Setting the operating power
The sounder includes a pair of power selection jumpers, J1
and J2. To select the source of the sounder operating power,
position the jumpers as shown in Figure 2.
Figure 2: Power selection jumper configuration
1. Loop powered 2. External 24 VDC
Note: When using an external power supply, use only one that
is CE and EN 54-4 compliant to power all the sounders on the
same loop.
6
2
5
1
J1 J1J2 J2
21
2 / 4 P/N 501-1780ZE-1-10 • REV 10 • ISS 16APR14
Setting the address
The sounder includes a seven-segment DIP switch (SW1) for
assigning device addresses. Each switch segment has a
decimal value as shown in Figure 3. The address is the sum of
all the switch segments in the ON position. The switch may be
set to represent any address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Figure 3: Address switch setting
Mode and tone settings
The sounder includes a seven-segment DIP switch (SW2) to
select operating mode, device mode, and tone. See Figure 4.
Figure 4: Mode of operation switch settings
1. Power selection jumpers
2. SW2 configuration switch
3. Tone
4. Device mode
5. Operating mode
Setting the operating mode
The device operates as a dedicated (stand-alone) sounder with
its own unique loop address when SW2-7 is set to ON.
To configure operation as a stand-alone sounder:
1. Set SW2-7 to ON.
2. Navigate to the following menu to tag the sounders as
SAB:
ZP3 Panel Menu/Setup/Sounders/SAB/Add SAB
The Planner can also be used.
3. To map an alert-to-evac function, make the first input type
a fast flash input.
The sounder will sound the alert tone in response to a fast
flash input or an evac tone when the input configured as
steady is triggered, overriding the alert tone.
Setting the device mode
SW2-6 selects whether the loop sounder operates in ZP755
mode or in ZP754 emulation mode as described in Table 2.
Table 2: SW2-6 mode selection switch
Mode SW2-6 Output Signal Requirement
ZP755 OFF User-selectable two-
tone operation and full
monitoring
ZP3 software v
1.18 or
later
ZP754
emulation ON Two fixed tones ZP5 panels or ZP3
panels with legacy
software
Setting the tone
Two different tones can be programmed to operate from the
panel. In ZP755 mode these tones are selected using SW2-1,
SW2-2, and SW2-3. Refer to Table 3.
Note: In the ZP panel I/O mapping menu, outputs are
programmed as "steady" or "flashing." The link to the table
below is as follows:
• Tone A = Panel setting "fast flash/slow flash.”
• Tone B = Panel setting "steady.”
1
2
34
5
P/N 501-1780ZE-1-10 • REV 10 • ISS 16APR14 3 / 4
Table 3: Tone settings
SW2-6 device mode
switch setting Device mode SW2 switch setting
-1 -2 -3 Mapping input type
Fast flash Steady
Tone type
Tone A primary/alert Tone B secondary/evac
OFF ZP755 0 Intermittent Continuous
OFF ZP755 1 Continuous Intermittent
OFF ZP755 2 Continuous Two-tone
OFF ZP755 3 Two-tone Continuous
OFF ZP755 4 Two-tone Intermittent
OFF ZP755 5 Intermittent Two-tone
OFF ZP755 6 Not used
ON ZP754 7 Intermittent Continuous
Setting the volume
The sounder has a volume control potentiometer to adjust
the volume. Refer to Figure 5.
WARNING: To conform to EN 54 Part 3 sound output levels,
the volume control must be set to the full clockwise position.
If the volume is adjusted for any reason, it must be returned
to the full clockwise position.
Figure 5: Volume control
1. Tone select
2. SW2-6 on 3. SW2-6 off
4. Volume control
Mounting the sounder onto the base
Refer to Figure 6. Align the addressable sounder to the
base. Push up (A), and then turn the sounder until it clicks
into place (B). Push the sounder up once more to engage
(C).
Reverse the above procedure to remove the sounder from
the base.
Figure 6: Mounting
1. Plug-in base
2. Release/lock catch
3. Release aid (3X)
4. Addressable sounder
Sounders per loop
The sounder can be powered directly from the loop of a ZP3
or ZP5 panel. Use Table 4, in conjunction with Figure 7, to
determine the quantity of detectors and sounders that can be
connected to a two-core shielded loop.
1
2
3
123
4
4
3
2
1
A
B
C
4 / 4 P/N 501-1780ZE-1-10 • REV 10 • ISS 16APR14
Figure 7: Detector/sounders per loop
A. Cable length panel to first sounder
B. Cable length first to last sounder
C. Cable length last sounder to panel
1. Detectors and Sounders
Table 4: Maximum detectors and sounders per loop
A B C Quantity allowed [1]
10 m 980 m 10 m 80 detectors and 20 sounders
100 detectors and 15 sounders
100 m 800 m 100 m 80 detectors and 20 sounders
100 detectors and 15 sounders
200 m 600 m 200 m 60 detectors and 20 sounders
100 detectors and 15 sounders
300 m 400 m 300 m 40 detectors and 20 sounders
110 detectors and 15 sounders
[1] Using a two-core shielded loop of 1000 meters cable size
1.5 mm²
Specifications
Operating voltage
External supply
Loop supply, ZP protocol
18 to 30 VDC
19.5 to 20.5 V pulsed, max. 4 V line
loss
Current (line powered)
Quiescent (RMS)
Alarm (RMS)
Alarm (excluding device
address)
Alarm (at device address)
820 μA
9.6 mA
19.6 mA max.
26 mA max.
Current (externally powered)
Quiescent (RMS)
Alarm (RMS)
Maximum number
470 μA
500 μA
20 per 1 km loop (subject to cable
size and sounder spacing)
Sound output
Tone 1
Tone 2
Tone 3
90 dBA (all around)
Continuous 980 Hz.
Intermittent 980 Hz. (0.5 sec on/off)
Two-tone warble 980 Hz./670 Hz.
Sound distribution Wide
Light output Equivalent to 1J xenon element
Strobe frequency Flash rate 1.3 seconds
CNPP anechoic sound levels See Figure 8
Monitoring
ZP loop
Sound output level
Open and short circuit fault
Self test facility
Compatibility Ziton analogue addressable
systems
Addressing method 7-segment DIP switch
Mounting Surface with plug-in base
Wiring Two-core shielded loop
Construction
Material
Colour
Weight
Dimensions (Ø × D)
Moulded thermoplastic
Red or polar white
305 g
127 × 113 mm
Operating environment
Temperature
Relative humidity
−10 to +60°C
10 to 95%, noncondensing
Storage temperature −20 to +70°C
Figure 8: CNPP anechoic sound levels
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information refer to the product Declaration of Performance.
Certification
Certification body 0370
Declaration of
Performance number 360-5201-0499
Year of first CE marking 14
Product Identification ZP755HAV-2
Intended use See DoP point 3
Essential characteristics See DoP point 9
Manufacturer Gulf Security Technology Co.,Ltd
80, Changjiang East Road,
QETDZ, Qinhuangdao,
Hebei Province, China 066004
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
European Union
directives 1999/5/EC (R&TTE directive): Hereby, UTC
Fire & Security declares that this device is in
compliance with the essential requirements
and other relevant provisions of Directive
1999/5/EC.
2002/96/EC (WEEE directive): Products
marked with this symbol cannot be disposed
of as unsorted municipal waste in the
European Union. For proper recycling, return
this product to your local supplier upon the
purchase of equivalent new equipment, or
dispose of it at designated collection points.
For more information see:
www.recyclethis.info.
Contact information
For contact information, see www.utcfssecurityproducts.eu.
165
O
105
O
75
O
45
O
15
O
135
O
dBA 70 75 80 857075808590 90

This manual suits for next models

2

Popular Horn manuals by other brands

Vixen Horns VXO8115/3311B installation guide

Vixen Horns

Vixen Horns VXO8115/3311B installation guide

Vixen Horns VXO8580/3418B installation guide

Vixen Horns

Vixen Horns VXO8580/3418B installation guide

Vixen Horns VXO8330B/1164B installation guide

Vixen Horns

Vixen Horns VXO8330B/1164B installation guide

Anchor LBH-30 Specifications

Anchor

Anchor LBH-30 Specifications

Electro-Voice MH640C Specification sheet

Electro-Voice

Electro-Voice MH640C Specification sheet

Vixen Horns VXO8560/3318B installation guide

Vixen Horns

Vixen Horns VXO8560/3318B installation guide

Vixen Horns VXO8115/3311 installation guide

Vixen Horns

Vixen Horns VXO8115/3311 installation guide

Cooper Wheelock WH1T-115-NS specification

Cooper Wheelock

Cooper Wheelock WH1T-115-NS specification

Wheelock TBH-104 installation instructions

Wheelock

Wheelock TBH-104 installation instructions

Vixen Horns VXO8330APRO/3418C installation guide

Vixen Horns

Vixen Horns VXO8330APRO/3418C installation guide

Vixen Horns VXO8210/3318 installation guide

Vixen Horns

Vixen Horns VXO8210/3318 installation guide

Vixen Horns VXO8805/4114 installation guide

Vixen Horns

Vixen Horns VXO8805/4114 installation guide

Vixen Horns VXO8350/4318 installation guide

Vixen Horns

Vixen Horns VXO8350/4318 installation guide

Altec 815A LF SPEAKER CABINET manual

Altec

Altec 815A LF SPEAKER CABINET manual

Vixen Horns VXO8580 installation guide

Vixen Horns

Vixen Horns VXO8580 installation guide

Electro-Voice Constant-Directivity Horn HP420 specification

Electro-Voice

Electro-Voice Constant-Directivity Horn HP420 specification

Monacor IT-250TW installation instructions

Monacor

Monacor IT-250TW installation instructions

Vixen Horns VXO8210/3311C installation guide

Vixen Horns

Vixen Horns VXO8210/3311C installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.