Conventional Wireless Dual IO Unit Installation Guide
General
The Ziton conventional wireless dual IO (CWIO) unit is
available under the following part number:
PART NO VARIANT TYPE
ZCR452 Ziton conventional wireless dual IO unit
Introduction
The address of the unit is set when programming the
device to the Ziton conventional wireless communicator
(see programming manual for details). The installation
must conform to BS5839:Part 1 (or applicable local
codes). The Ziton CWIO unit is suitable for indoor use only.
Ensure that all Ziton CWIO units are sited in accordance
with the survey and design details.
© 2018 EMS Ltd. All rights reserved 1 / 44 / 4 TSD145 Iss3 17/10/2018 AJM© 2018 EMS Ltd. All rights reserved TSD145 Iss3 17/10/2018 AJM
Prepare the back box
Remove the four front plate retaining screws. Retain
these for re-assembly when installation is complete.
Remove the front plate.
Drill required cable entry points for the CWIO units cable
connections. Recommended cable entry points are
shown in Figure 2.
SOUNDER
START/STOP
PANEL
SILENCE
SUPPLY FAULT FIRE ALARM
SUPPLYFAULT
EARTHFAULT
OUTOF SERVICE
SYSTEMFAULT
SOUNDERFAULT/
DISABLE/TEST
SOUNDER
DELAY
NETWORK FAULT
EXPANS.I/O FLT/DIS
DISABLE
TEST
12
4
3
POWER
FAU LT
CONVENTIONALWIRELESS COMMUNICATOR
ZCR452
WIRELESSZONE INTERFACE MODULE
0.6m 0.6m 2m
Figure 1
LOGON ANTENNA
KEEP CABLES AWAY FROM THIS AREA
LR6 AA
LR6 AA
LR6 AA
LR6 AA
LR6 AA
LR6 AA
JP9
LED
ENABLE
F-SAFE
1
2
4
8
16
32
64
CLOSED
FA U LT
EXPAN 1
3VDC SET RST N/O COM N/C
OUTPUT 1
INPUT 1
RELAY ON
IP- IP+
INPUT 1
POWER
ADDRESS0=ON
C NO NC
TAMPER
Cable
entry points
Cable
entry points
Figure 2
Specication
Operating
temperature -10 to +70°C (ambient)
Operating
temperature 0 to +35°C
Humidity Up to 95% non-condensing
Supply 6x AA Alkaline (Panasonic LR6AD
Powerline / Varta 4006 Industrial)
IP rating IP65
Output rating 2A @ 24V DC
Operating
frequencies 868 MHz
Output transmitter
power Variable 0-14 dBm
Dimensions 120mm (H) 240mm (W) 50mm (D)
Weight 0.60kg
Regulatory information
Year of
manufacture See serial number label inside unit
Certication
Certication body
CPR certicate 0359-CPR-00437
DOP
Approved to EN54-18
EN54-25
Application Type A. Indoor use only
European Union
directives
EMS declares that the radio
equipment type Ziton Conventional
Wireless Dual IO Unit is in
compliance with Directive
2014/53/EU. The full text of the EU
declaration of conformity is
available at the following internet
address:
www.utcfssecurityproducts.eu/dop/
2012/19/EU (WEEE directive):
Products marked with this symbol
cannot be disposed of as unsorted
municipal waste in the European
Union. For proper recycling, return
this product to your local supplier
upon purchase of equivalent new
equipment, or dispose of it at
designated collection points. For
more information see
www.recyclethis.info
Fit the back box to the wall
Position the Ziton CWIO unit in the required location and
mark the four xing positions. These are shown in Figure
2.
Using suitable screws and xings attach the device
securely to the wall.
2m
0359
14
Mounting location guidelines
To ensure the optimum range performance of the CWIO
unit is achieved, the following should be considered:
Ensure the CWIO and CWC are seperated by a minimum
of 0.6m.
Ensure that the CWIO is not installed within 2m of the
Control Panel or any other wireless or electrical
equipment. See Figure 1.
Fixing
position 1
Fixing
position 2
Fixing
position 3
Fixing
position 4