4eco immerSUN User manual

Water heating for your PV system
Installation and user guide
v1.3

2

Contents
1 Overview 4
2 Te hni al Spe ifi ations 5
3 Installation 6
3.1 Mounting 6
3.2 Ele tri al Conne tions 7
3.3 Clamp Installation 8
3.4 Wiring Diagrams 9
3.5 Using the immerSUN with a dual-rate ele tri al supply 13
4 Installer Settings 14
4.1 DIP Swit h Settings 14
4.2 Installation Setup 15
4.3 Installer Menu 16
5 User Operation 18
5.1 Controls and Display 18
5.2 Changing Values 18
5.3 Normal Operation Display 19
5.4 Main Menu 20
5.5 Timed & Manual Hot Water Boost 21
5.6 Error Messages 22
6 Troubleshooting 23
7 Legionella and General Advi e 24
7.1 Legionella 24
7.2 Getting the most from your immerSUN 24
8 Warranty 25
9 Conforman e 26
10 Commissioning Sheet 27
3

1. Overview
Thank you for hoosing immerSUN. This intelligent devi e is a sensible and pra ti al addition to your PV
or Wind mi rogeneration system.
Water is heated via your existing immersion heater, using surplus power that would otherwise have been
exported to the grid.
Please read and follow this guide to ensure many years of trouble-free operation and savings!
Key features
•Heats water from your PV system or Wind Turbine
•Effe tively adjusts power levels to the immersion heater, keeping the exported
power at virtually zero
•The onsumer no longer needs to be at home to use the free ele tri ity,
whatever the weather
•No need to hange the immersion heater
•Suitable for all ele tri al mi rogeneration systems
•Built-in hot water boost timer
•Manual hot water boost fun tion
•Ba k-lit LCD display shows energy saved, output power and operating mode
•Dual immersion heater ontrol option
•Internal multi-fun tion relay in-addition to the modulated power output
•Up to 4 devi es an be daisy- hained for master / slave operation
•MODBUS RS485 interfa e for system expansion and external data logging
•Internal thermal prote tion
•3 year produ t warranty
4

2. Te hni al Spe ifi ations
Electrical Specifications
Description Minimum Nominal Maximum
Supply Voltage (VAC) 198 230 264
Supply Frequen y (Hz) - 50Hz -
Load Current (A) - 13 16
Load Size (W) 250 3000 3200
Relay Conta t Voltage (VAC) - - 250
Relay Conta t Current (A) - - 16
Clamp Current (A) - - 100
Re ommend PV System Size (kW) 2 - 15
Dimensions and weight
Width (mm) 150 Depth (mm) 64
Height (mm) 140 Weight (g) 935
5

3. Installation
3.1 Mounting
Often, the most suitable lo ation for the immerSUN is near to the onsumer unit. Usually all the
onne tions required are available here.
The following should be onsidered when de iding upon the most suitable lo ation:
•Close to the main in oming mains ele tri al supply of the property
•A ess to immersion heater supply able (this is usually at the onsumer unit)
•A ess to suitable supply via 16A MCB or 13A fused outlet
•User a ess to immerSUN ontrols and visibility of LCD s reen
•Adequate ventilation – keeps vents lear and provide airflow around the unit
•Cable a ess point – through the rear or bottom of the unit
Use the 3 s rews and wall plugs provided to mount the immerSUN at the hosen lo ation.
Remove LCD protective cover after mounting the unit
DO NOT BLOCK VENTS! The en losure may get hot, always keep vents lear of obstru tion and allow
suffi ient learan e from walls, eilings and other obje ts. Observe minimum learan es as shown below.
6
50mm
100mm
100mm
0mm

3.2 Ele tri al Conne tions
Electrical connections should be made only by a competent person Do not attempt to install this
unit if you are not a qualified or an experienced electrician Installation may involve alterations to
fixed wiring and opening the consumer unit, there is risk of death by electrocution
Choose the most suitable able entry points (rear or bottom) and make the ele tri al onne tions to the
unit a ording to the appropriate wiring diagram (see se tion 3.4). Use the blanking plugs provided for
unused able entry points.
Alternative loads
In some ases it may be desired to ontrol the power to a load other than an immersion heater. The load
MUST be a simple resistive load, e.g. an ele tri towel radiator, storage heater et .
The load must not ex eed 3.2kW and must not in lude digital or analogue timers, as they may be
damaged by the proportional output ontrol of the immerSUN.
IMPORTANT!
Be sure to fully tighten terminals, he king the ables are se urely lamped by the terminals and the ord
grips. Failure to ensure good onne tion ould result in fire or permanent damage to the unit.
NOTE: The s rew terminals are 'rising lamp' type.
TERMINALS
MAINS
L LIVE FEED 240V supply input, should be from 16A MCB or 13A fused outlet
LH LIVE OUTPUT Live output to immersion heater, maximum load 13A or 3kW
N NEUTRAL (x2) Mains Neutral terminals (All Neutral terminals are internally onne ted)
E EARTH (x2) Mains Earth terminals (All Earth terminals are internally onne ted)
IMPORTANT! Earth MUST be onne ted
RELAY (used for some additional fun tions, see wiring diagrams in se tion 3.4)
NO NORMALLY OPEN Volt-free normally open relay onta t (max. urrent 13A)
C COMMON Volt-free ommon relay onta t (max. urrent 13A)
NC NORMALLY CLOSED Volt-free normally losed relay onta t (max. urrent 13A)
CLAMP
CT CURRENT TRANSFORMER AC urrent transformer lamp terminals
COMMUNICATIONS
A RS485 A RS485 ommuni ation terminal A (D+)
B RS485 B RS485 ommuni ation terminal B (D-)
GD DIGITAL GND Ground onne tion for future use
5V 5V OUTPUT 5-volt output onne tion for future use
7

3.3 Clamp Installation
Corre t positioning of the urrent sensor lamp is vital to the operation and effi ien y of the immerSUN.
In orre t installation may result in in reased ele tri al osts to the user.
The lamp should be lo ated at the main incoming grid supply to the building. This will be the supply
from the main ele tri meter (NOT the PV generation meter). Close the lamp around one of the ables
(Live or Neutral) from the meter, this an be at the meter lo ation or inside the onsumer unit.
IMPORTANT! Ensure the lamp is se urely losed around the able.
Conne t the lamp wire to the CT terminals inside the immerSUN. Don't worry about polarity as the
immerSUN will figure it out during setup.
PV connected via Henley Block
If the PV system is onne ted via a 'Henley Blo k' then the lamp should be installed on the grid side of
the blo k, i.e. between the meter and Henley blo k.
More than one consumer unit
Where there is more than one onsumer unit, the lamp should be installed at the primary in oming
supply (i.e. before it splits).
Three phase supply
One immerSUN will only work on one of the phases, the lamp MUST be installed on the SAME PHASE
that is wired to the immerSUN, the inverter MUST be on the SAME PHASE also.
If the inverter is 3-phase, then the immerSUN will only 'see' the import/export on that phase, therefore not
all of the export power an be utilised.
Extending the clamp cable
The lamp wire an be extended if required, however due to the small signal from the lamp, twisted-pair
able should be used to help eliminate possible interferen e. The maximum able length is 50m. Most
types of twisted-pair able an be used, e.g. Beldon able, Cat.5, telephone able et .
8

3.4 Wiring Diagrams
Single heater wiring
Most installations will be a single immerSUN onne ted to a single heater. This is shown in the diagram
below.
Alternative wiring method
If the immerSUN is lo ated lose to the onsumer unit, it may be simpler to use the alternative wiring
option using 4- ore able or singles. As the Earth and Neutral terminals are ea h ommon, the alternative
option shows that the heater earth and neutral need not be dire tly onne ted the the immerSUN. The
alternative wiring method an also be used for all of the additional wiring options.
Using the multifunction relay
When wiring one of the options involving the relay onta ts, the relay fun tion must be sele ted. This is
done via the Relay Fun tion option in the Installer Menu. See se tion 4.3. The relay an be set to perform
only one of the fun tions.
Linking several immerSUN units (Cascading)
Up to four immerSUN units an be linked together. This allows up to 12kW (3kW for ea h immerSUN) of
surplus power to be utilised on one phase. This is known as Cas ading as the first immerSUN will
onsume the first available 3kW, the se ond unit in the hain will then onsume the next available 3kW
and so on. When using as ade mode, ea h immerSUN must have its own 3kW (maximum) load.
The immerSUNs should be linked in a 'daisy- hain' fashion with twisted-pair signal able using the
COMMS terminals A and B. Cas ade mode needs to be sele ted in the Installer Menu. See se tion 4.3
For simple single heater ontrol, relay onne tions not required, omms onne tions (A&B) are used only when several immerSUN
devi es are to be linked. (Also see Alternative Mains Wiring diagram).
9
240V AC MAINS SUPPLY
From 16A MCB or
13A fused outlet
IMMERSION HEATER
Max. Load 3kW
CLAMP
Install onto incoming mains
Live ca le to uilding
Single Immersion Heater
COMMS LINK
For linking several
ImmerSUN devices
ISOLATOR
Must e dou le-pole
5V GD AB CT CT
COMMS
RELAY MAINS
NOCNC E
EN LN LH
CLAMPPWR

As an alternative to using two flex ables, one 4- ore able may be used for the mains wiring.
Two heaters an be ontrolled by using the multi-fun tion relay. The heaters need not be in the same ylinder. Heater no. 1 has
priority.
10
CONSUMER UNIT
With 16A MCB
IMMERSION HEATER
Max. Load 3kW
Alternative Mains Wiring
ISOLATOR
Must e dou le-pole
4-Core
16A
E N
RELAY MAINS
NOCNC E
EN LN LH
IMMERSION HEATERS
Max. Load 3kW each
(Other loads can e used)
CLAMP
Install onto incoming mains
Live or Neutral ca le to uilding
Two Heaters
1
2
ISOLATORS
Must e dou le-pole
240V AC MAINS SUPPLY
From 16A MCB or
13A fused outlet
COMMS LINK
For linking several
ImmerSUN devices
5V GD AB CT CT
COMMS
RELAY MAINS
NOCNC E
EN LN LH
CLAMPPWR

Rather than using the immersion heater to boost hot water, an external heat sour e e.g. a boiler an be used by making use of the
multi-fun tion relay wired to the boiler hot water ontrols.
I
t may be desirable to use a de-stratifi ation pump to mix the ooler water at the bottom of the ylinder with the hotter water at the
top, this allows a top mounted immersion heater to heat all of the water in the ylinder.
11
Boiler Hot Water Boost
BOILER HW CALL
Volt-free contact
Connect to oiler wiring
240V AC MAINS SUPPLY
From 16A MCB or
13A fused outlet
IMMERSION HEATER
Max. Load 3kW
CLAMP
Install onto incoming mains
Live ca le to uilding
COMMS LINK
For linking several
ImmerSUN devices
ISOLATOR
Must e dou le-pole
5V GD AB CT CT
COMMS
RELAY MAINS
NOCNC E
EN LN LH
CLAMPPWR
De-strat Pump
CLAMP
Install onto incoming mains
Live or Neutral ca le to uilding
240V AC MAINS SUPPLY
From 16A MCB or
13A fused outlet
COMMS LINK
For linking several
ImmerSUN devices
5V GD AB CT CT
COMMS
RELAY MAINS
NOCNC E
EN LN LH
CLAMPPWR
IMMERSION HEATER
Max. Load 3kW
DE-STRAT PUMP
With 3A fused isolator
ISOLATOR
Must e dou le-pole

The multi-fun tion relay an be used to swit h any load on for a set duration, on e an export threshold has been rea hed. The
maximum relay urrent should not be ex eeded (an additional onta tor may be used for larger loads).
If a fault signal for a BMS system is required, the multi-fun tion relay an be set to de-a tivated when a fault o urs.
12
Threshold Switch
APPLIANCE LIVE SWITCH
Volt-free contact
Can e used to switch live
feed to appliance.
NOTE: If load exceeds 13A,
a separate contactor
must e used.
240V AC MAINS SUPPLY
From 16A MCB or
13A fused outlet
IMMERSION HEATER
Max. Load 3kW
CLAMP
Install onto incoming mains
Live ca le to uilding
COMMS LINK
For linking several
ImmerSUN devices
ISOLATOR
Must e dou le-pole
5V GD AB CT CT
COMMS
RELAY MAINS
NOCNC E
EN LN LH
CLAMPPWR
Fault Signal
TO BMS SYSTEM
Volt-free contact
Contact is closed when
unit Is powered.
Contact opens if fault
occurs.
240V AC MAINS SUPPLY
From 16A MCB or
13A fused outlet
IMMERSION HEATER
Max. Load 3kW
CLAMP
Install onto incoming mains
Live ca le to uilding
COMMS LINK
For linking several
ImmerSUN devices
ISOLATOR
Must e dou le-pole
5V GD AB CT CT
COMMS
RELAY MAINS
NOCNC E
EN LN LH
CLAMPPWR

3.5 Using the immerSUN with a dual-rate ele tri al supply
There are 2 ommon ways that a dual-rate ele tri al supply an be onfigured...
1 A single dual-rate meter feeding the whole house
This is the most ommon onfiguration.
•The immerSUN should be wired as normal. See wiring diagrams in se tion 3.4
•The immerSUN's Timed Boost should be set to operate at off-peak times.
•Remove any timers that are installed on the immersion heater ir uit.
2 Two meters supplying two consumer units
With this onfiguration there is a separate timed off-peak supply.
•Wire the immerSUN as shown in the diagram below.
•Set the Relay Fun tion to Water Boost and then set the Timed Boost to operate at off-peak
times.
•Remove any timers that are installed on the immersion heater ir uit.
•Label the immersion heater with a “Dual Supply” warning label.
•Please Note: It will not be possible to Boost outside of off-peak times.
13
Dual Rate Supply (with two meters)
IMMERSION HEATER
Max. Load 3kW
(Other loads can e used)
CLAMP
Install onto incoming mains
Live or Neutral ca le to uilding ISOLATOR
Must e dou le-pole
240V AC 24hr SUPPLY
From 16A MCB or
13A fused outlet
COMMS LINK
For linking several
ImmerSUN devices
5V GD AB CT CT
COMMS
RELAY MAINS
NOCNC E
EN LN LH
CLAMPPWR
240V AC TIMED SUPPLY
From 16A MCB or
13A fused outlet

4. Installer Settings
On e the unit is mounted and wired, the installer will need to set parameters as required for the parti ular
installation. Before applying power to the unit the DIP swit hes will need to be set.
4.1 DIP Swit h Settings
The default position of the DIP swit hes, is all four set to ON. For the majority of installations this will be
the orre t setting. However if several immerSUN devi es are being as aded, then the DIP swit hes will
need to be set a ordingly, see table below.
Default settings show in Italics
S1 S2 Cascade Position Select Notes
OFF OFF 1
st
Slave Clamp not used, ontrol is via master
OFF ON 2
nd
Slave Clamp not used, ontrol is via master
ON OFF 3
rd
Slave Clamp not used, ontrol is via master
ON ON Master Unit Clamp is required
S3 Termination Resistor Select
ON RS485 termination resistor ENABLED Set to ON if this is at the end of the ommuni ation hain. If
the unit is in the middle of the hain, set to OFF. Where
there are only two devi es onne ted, set both to ON.
OFF RS485 termination resistor DISABLED
S4 Clamp Burden Resistor Select
ON Internal burden resistor ENABLED
OFF Internal burden resistor DISABLED Use external resistor (for supporting alternative lamps)
14

4.2 Installation Setup
At first swit h on, the immerSUN will run through the installation setup pro ess, follow the instru tions on
the display.
Step 1
INSTALLATION
SETUP – PRESS >
Press
►
to start the installation setup pro ess as
instru ted. Otherwise press
◄
to an el.
Step 2
SELECT CLAMP
<RADIO< >WIRED>
Step 3
TURN ON HEATER
THEN PRESS >
Ensure that the heater isolator is ON and that the
thermostat is losed (i.e. the water in the ylinder is old)
ERROR! HEATER
NOT DETECTED
An error will o ur if no load is dete ted, the immersion
heater may be swit hed off at the isolator, or the
thermostat open be ause the water is hot already.
Press
◄
to go ba k to step 1
CHECKING
HEATER...
The immerSUN will then perform a test to he k the
output and the heater.
Step 4
(master only)
TURN INVERTER
OFF THEN PRESS >
You will be asked to swit h off the inverter, this is so the
immerSUN an dete t import/export dire tion.
Use the AC isolator of the PV system.
Step 5
(master only)
SETTING UP
PLEASE WAIT...
Setting up will take several se onds.
CLAMP CURRENT
TOO LOW!
If the import power is too small, this ould be be ause
the inverter is still swit hed on, the heater thermostat is
open ir uit, or the lamp is at the wrong lo ation.
Press
◄
to go ba k to step 1
Step 6
INSTALLATION
SETUP COMPLETE!
On e setup has finished this message will be displayed.
Step 7
Swit h inverter ba k on again. Wait for inverter to start
working, this usually takes 3 minutes.
If export is high enough the immerSUN will start heating
water, otherwise you will see the waiting s reen.
15

4.3 Installer Menu
Installer Menu Options
(Press and hold
▼
AND
▲
for 5 seconds for installer menu)
Des ription Menu S reen Sub Menus
Installer Menu
INSTALLER MENU
PRESS >
Press and hold
▼
AND
▲
for 5 seconds for installer
menu, you will then see this s reen, press
►
to
ontinue to installer menu.
View Readings
INSTALLER MENU
View Readi gs
View Readi gs
AC Volts: 245V
AC Volts
Shows AC mains voltage at present.
The display will update approximately every 2 se onds.
View Readi gs
Grid I: 12.5A
Grid I
Shows AC mains urrent at lamp.
The display will update approximately every 2 se onds.
View Readi gs
Load I: 8.2A
Load I
Shows AC mains urrent applied to load.
The display will update approximately every 2 se onds.
View Readi gs
Temperature: 38C
Temperature
Shows internal temperature on the immerSUN.
The display will update approximately every 2 se onds.
Clamp
INSTALLER MENU
Clamp (Wired)
Clamp Type
The lamp type is shown, the lamp type an only be
hanged by resetting the unit.
Cascade
INSTALLER MENU
Cascade (Off)
Cascade Mode
When as ading several immerSUN's to ontrol several
loads, Cas ade should be set to ON
Set Load
The output an be set
to a given per entage
for testing purposes
INSTALLER MENU
Set Load (Auto)
SET LOAD
>Auto<
Auto (Normal mode)
Set output to automati ally tra k exported power.
SET LOAD
>100%<
Manual
Manually set output power for testing purposes only.
Rela Function
The internal multi-
fun tion relay an be
set to operate as one
of 8 different fun tions.
(The urrently enabled
option is shown in
bra kets).
See appropriate wiring
diagram for chosen
relay function
INSTALLER MENU
Relay (OFF)
RELAY FUNCTION
>Whe Heati g<
When Heating
Relay is on when output is heating water.
RELAY FUNCTION
>Two Heaters<
Two Heaters (2 Heater)
Use relay to swit h load output between two heaters.
Heater no.1 output takes priority (see wiring diagram).
Heater no.2 output only heats when no.1 is fully heated.
NB: When heating no.2, the output is swit hed ba k to
heater no.1 every 15mins to he k if more heat is
required.
RELAY FUNCTION
>Water Boost<
Water Boost (Boost)
Relay ontrols boiler to heat water when in water boost
mode, rather than using the immersion heater.
RELAY FUNCTION
>De-strat Pump<
De-stratification Pump (De-strat)
Relay ontrols ylinder de-stratifi ation pump.
Pump is a tivated when immersion thermostat opens
and runs until thermostat loses again.
(The immersion thermostat is he ked only on e a
minute so there may be a delay before the pump stops).
16

RELAY FUNCTION
>Threshold<
Threshold (Threshld)
Relay operates when an export threshold is rea hed,
relay remains a tivated for set period of time, even if
export drops. Export threshold level and relay on
duration an be set as shown below:
THRESHOLD SET
Export: 500W
THRESHOLD SET
Duratio : 1h30m
RELAY FUNCTION
>Fault Sig al<
Fault Signal (Fault)
Relay is dea tivated if a fault ondition o urs.
RELAY FUNCTION
>Always O <
Always On (ON)
Relay is operated ontinuously.
(This is for testing purposes only).
RELAY FUNCTION
>Always Off<
Always Off (OFF)
Relay is disabled. (This is the default relay fun tion).
Nominal Voltage
INSTALLER MENU
Nom Voltage 240V
NOMINAL VOLTAGE
>240< Volts
Nominal Voltage
The nominal mains operation voltage should be set.
Default is 240V.
Reset Settings
INSTALLER MENU
Reset Setti gs
RESET SETTINGS
CONFIRM Press >
Reset Settings
Use to setup immerSUN after installation.
(See se tion 4.2).
Serial Number &
Firmware
Version
INSTALLER MENU
S/N:123456 V1.10
Serial Number & Firmware Version
The serial number and firmware version are displayed.
17

5. User Operation
5.1 Controls and Display
Button Operation Alt Operation Description
◄BACK SCREEN CHANGE Exit menu or hange s reen when not in menus
▼
DOWN MENU Go down through list or de rease value
Enter Main Menu
▲
UP MENU Go up through list or in rease value
Enter Main Menu
►
SET BOOST Set value or hold to boost hot water
5.2 Changing Values
To hange values, navigate to value you wish to hange and press ►
Arrows either side of the value to hange will then be shown. Use the ▼and▲buttons to hange the
value. Press
► again to store the new value. Pressing ◄ will exit edit mode, without hanging the
value.
Non-Edit Mode
SET TIME
16:01
Press ► to edit value.
Edit Mode
SET TIME
16>01<
Value to be edited is indi ated by > < symbols.
18
LCD DISPLAY
STATUS LED
BACK
DOWN UP
SET / BOOST

5.3 Normal Operation Display
The table below summarises the operation of the immerSUN. There are four main modes of operation:
Heating Water; Water Hot; Waiting and Hot Water Boost. The mode is shown on the LCD display, the
LED allows the mode to be determined from a distan e.
The display hanges every two se onds, showing the mode with additional information, the time and
date, and the savings in kWh.
Normal Operation
Mode & LED status Mode Information Time & Date Savings Des ription
Waiting...
●
Waiti g...
4eco immerSUN
Waiti g...
10:52 16/02/12
Today: 12.562kWh
Total: 5651kWh
Waiting for suffi ient exported
power to start heating water.
Heating Water
●○
Heati g Water
Output: 2925W
Heati g Water
10:52 16/02/12
Today: 12.562kWh
Total: 5651kWh
Heating water with power from
PV system, no Grid power is
being used.
The urrent output power applied
to load is shown.
Heating Water
(Dual Heater Mode)
●○
Heati g Water(2)
Output: 2925W
Heati g Water(2)
10:52 16/02/12
Today: 12.562kWh
Total: 5651kWh
Heating water with power from
PV system, no Grid power is
being used. Current heater is
show in bra kets.
Water Hot
●
Water Hot
Water Hot
10:52 16/02/12
Today: 12.562kWh
Total: 5651kWh
The water is fully heated, the
immersion thermostat is open.
Hot Water Boost
●○
Timed Boost
for: 1h 15m 25s
Timed Boost
10:52 16/02/12
Today: 12.562kWh
Total: 5651kWh
Heating water at full power,
regardless of available export
power.
Hot Water Boost
(Dual Heater Mode)
●○
Timed Boost (2A)
for: 1h 15m 25s
Timed Boost (2A)
10:52 16/02/12
Today: 12.562kWh
Total: 5651kWh
Heating water at full power,
regardless of available export
power. Current heater is show in
bra kets.
Cascade Mode
Slave Devices
Status Screen
Status of Slaves
HEAT WAIT ----
When Cas ade Mode this s reen will be
shown giving the status of all the slave
immerSUN devi es in the system.
Status Abbreviations
HEAT : Heating Water
HOT : Water Hot
WAIT : Waiting for suffi ient
export power
BOOS : Timed Boost
---- : No devi e dete ted
19

5.4 Main Menu
Main Menu Options
(Press
▼
OR
▲
for main menu)
Des ription Menu S reen Sub Menus
View Savings
The immerSUN
measures and re ords
energy applied to
immersion heater. As
only the renewable
energy is ounted this
is effe tively saved
energy.
MAIN MENU
View Savi gs
Savi gs
Today: 12.563kWh
Today
Show savings made today in kWh.
Savi gs
Mo th: 224kWh
Month (current month)
Show savings made this month in kWh.
Savi gs
MAR: 224kWh
Month (each month)
Show savings made in the indi ated month in kWh.
Savings are stored for ea h month of the year.
Savi gs
Year: 1791kWh
Year
Show savings made this year in kWh.
Savi gs
Total: 3215kWh
Total
Shows total energy saved to date in kWh.
View Event Log
MAIN MENU
View Eve t Log
Power O
14:53 12/06/12
Code: 7
Value: 0
Log Details
Every normal operation event is
logged along with the time and
date of the event.
Code is the event ode number.
Value is the value asso iated
with the event.
View Fault Log
MAIN MENU
View Fault Log
POWER FAILED
14:53 12/06/12
Code: 105
Value: 0
Log Details
Every hange of status and any
faults are re ording in the log
along with the time and date of
the event.
Code is the fault ode number.
Value is the value asso iated
with the fault.
Settings
MAIN MENU
Setti gs
SETTINGS
Set Time
SET TIME
16:01
Set Time
Time is used for Hot Water Boost
and the event log. Time is
maintained during power
outages for at least 48 hours.
SETTINGS
Set Date
SET DATE
12/06/12
Set Date
The date is used for the event
log.
Date is maintained during power
outages for at least 48 hours.
SETTINGS
Set Co trast
SET CONTRAST
>20%<
Set Display Contrast
The display ontrast an be
adjusted if required.
cont...
20
Table of contents
Popular Water System manuals by other brands

Billi
Billi B-4000 user guide

meibes
meibes KE KELIT Fully Instructions for installation, operation, maintenance

Pivot Stove & Heating
Pivot Stove & Heating Hydronic installation guide

Rain Soft
Rain Soft TC Series owner's manual

Pelican
Pelican Calcite Cartridge System owner's manual

Kinetico
Kinetico Drinking Water System Plus Deluxe owner's manual

flamco
flamco Flexcon instruction manual

UNIPRODO
UNIPRODO UNI WATER 06 user manual

Watts
Watts FEBCO 765 INSTRUCTION, INSTALLATION, MAINTENANCE AND REPAIR MANUAL

Albion
Albion ART 26 Installation & operating manual

Zip
Zip HydroTap G4 Installation and operating instructions

Sonnenkraft
Sonnenkraft PRO CLEAN SOTF500 manual